The FEU16x0 Controlleris a member of the Metasys® system Field Equipment Controller (FEC) family. The
controller is designed exclusively for use in a Metasys Re lease 8.1 smo ke con trol a pplica tion tha t is UL 86 4 UUKL/
UUKLC 10th Edition Smoke Control Listed. For Metasys system smoke control applications, you must refer to the
Metasys® System UL 864 10th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System (LIT-12012487) for
detailed requirements and procedures for installing, commissioning, and operating UL 864 UUKL/UUKLC Listed
Metasys system devices. For example, the MS-FEU1610-0U can only be used with the Firefighters Smoke Control
Station (FSCS) panel manufactured by Automation Displays, Inc. (ADI). The UL 864 UUKL/UUKLC listing for
Smoke Control Equipment is voided if (1) you do not use the required software to ols at the required version s; or (2)
you do not meet the requirements or do not follow the procedures as documented in the Metasys® System UL 864 10th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System Technical Bulletin (LIT-12012487).
North American Emissions Compliance
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Part No. 24-10143-535, Rev. B
Release 8.1
Issued March 2018
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not inst alled an d used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference, in which case the user will be required to correct the interference at his/her
own expense.
Installation
Observe these guidelines when installing the FEU controller:
•Transport the controller in the original container to minimize vibration and shock damage to the controller.
•Verify that all parts shipped with the controller.
•Do not drop the controller or subject it to physical shock.
Parts Included
•one MS-FEU1610-0U Controller with removable Terminal Plugs
•one Installation Instructions sheet
Materials and Special Tools Needed
•three fasteners appropriate for the mounting surface (#8 screws or M4 screws)
FEU16x0 Field Equipment Controller Installation Instructions
1
Page 2
•one 15.2 cm (6 in.) or longer piece of DIN rail and appropriate hardware for mou nting the DIN rail
Figure 1: FEU16 ControllerPhysical Features and Wiring Terminals
S
t
a
t
u
s
L
E
D
s
D
e
v
i
c
e
A
d
d
r
e
s
s
D
I
P
S
w
i
t
c
h
B
l
o
c
k
F
C
T
e
B
i
n
a
r
y
O
u
t
p
u
t
s
T
y
p
i
c
a
l
l
y
2
4
V
A
C
T
r
i
a
c
o
u
t
p
u
t
s
V
o
l
t
a
g
e
A
n
a
l
o
g
O
u
t
p
u
t
B
i
n
a
r
y
O
u
t
p
u
t
(
0
-
1
0
V
D
C
)
(
2
4
V
A
C
T
r
i
a
c
)
U
n
i
v
e
r
s
a
l
I
n
p
u
t
s
V
o
l
t
a
g
e
A
n
a
l
o
g
I
n
p
u
t
C
u
r
r
e
n
t
A
n
a
l
o
g
I
n
p
u
t
R
e
s
i
s
t
i
v
e
A
n
a
l
o
g
I
n
p
u
t
s
:
D
r
y
C
o
n
t
a
c
t
B
i
n
a
r
y
I
n
p
u
t
c
a
n
b
e
d
e
f
i
n
e
d
a
s
:
(
0
-
1
0
V
D
C
)
(
4
-
2
0
m
A
)
0
-
2
k
o
h
m
R
T
D
:
1
k
N
i
c
k
e
l
,
1
k
P
l
a
t
i
n
u
m
,
o
r
A
9
9
B
S
I
N
T
C
:
1
0
k
T
y
p
e
L
o
r
2
.
2
2
5
k
T
y
p
e
2
B
i
n
a
r
y
I
n
p
u
t
s
D
r
y
C
o
n
t
a
c
t
M
a
i
n
t
a
i
n
e
d
P
u
l
s
e
C
o
u
n
t
e
r
M
o
d
e
c
a
n
b
e
d
e
f
i
n
e
d
a
s
:
(
1
0
0
H
z
h
i
g
h
-
s
p
e
e
d
)
F
I
G
:
F
E
C
1
6
1
0
_
t
e
r
m
O
N
A
D
D
R
E
S
S
Ø
=
C
O
M
+
–
S
H
L
D
C
O
M
+
–
S
A
P
W
R
O
U
T
2
O
C
O
M
2
O
U
T
1
O
C
O
M
1
O
U
T
3
O
C
O
M
3
B
I
N
A
R
Y
I
N
3
I
C
O
M
3
U
N
I
V
E
R
S
A
L
+
1
5
V
I
N
1
I
C
O
M
1
I
N
2
I
C
O
M
2
S
A
B
U
S
F
A
U
L
T
P
O
W
E
R
T
h
e
B
i
n
a
r
y
O
u
t
p
u
t
’
s
I
N
T
/
E
X
T
p
o
w
e
r
s
o
u
r
c
e
j
u
m
p
e
r
s
a
r
e
l
o
c
a
t
e
d
u
n
d
e
r
t
h
e
N
o
t
e
:
•small straight blade screwdriver for securing communication wires in the terminal blocks
•one phone jack splitter (optional)
d
2
k
r
c
e
s
o
s
w
l
a
o
l
B
P
l
C
a
,
y
l
n
C
i
p
A
p
m
V
r
u
e
4
S
T
2
T
O
H
M
O
C
7
M
O
C
O
T
7
U
O
6
M
O
C
O
U
O
6
T
5
M
O
C
O
5
T
U
O
4
M
O
C
O
T
U
O
4
:
s
a
d
e
n
i
f
e
d
e
b
n
a
c
s
t
u
p
t
u
O
e
l
b
a
r
u
g
i
f
n
o
C
FEU16x0 Field Equipment Controller Installation Instructions
w
e
r
c
S
r
e
v
o
C
C
F
2
e
h
n
c
i
t
i
L
-
w
f
S
o
n
d
o
n
i
t
E
a
s
n
i
u
B
m
r
L
O
E
N
O
S
U
B
A
S
S
R
S
O
E
S
R
N
D
E
D
S
A
F
F
O
L
L
A
n
a
k
s
c
l
o
a
l
n
i
B
l
m
d
a
r
n
n
e
i
a
T
s
u
B
C
F
k
m
s
c
l
r
o
a
e
l
n
T
i
B
l
m
a
r
n
e
i
T
m
s
r
u
e
T
B
A
S
)
k
c
a
J
r
a
t
l
r
u
o
d
P
o
r
M
o
s
n
i
n
e
P
-
S
6
2
1
J
R
(
.
d
r
a
o
b
n
o
i
t
a
n
i
m
r
e
t
e
h
t
n
o
r
e
v
o
c
C
E
F
Page 3
Mounting
Figure 2: Required Orientation for DIN Rail Mount Applications
FIG:DINril
ON
ADDRESS
ADDRESS Ø = ALL OFF
C
COM
+
–
SA
PWR
OUT 4
OCOM 4
OUT 5
OCOM 5
OUT 6
OCOM 6
OUT 7
OCOM 7
BINA RY
IN3
ICOM
3
UNIVERSAL
+15V
IN1
ICOM1IN2
ICOM
2
EOL
SAB
FLT
PWR
R
ET SY
Observe these guidelines when mounting a field controller:
•Ensure the mounting surface can support the controller, DIN rail,
and any user-supplied enclosure.
•Mount the controller horizontally on 35 mm DIN rail whenever possible.
•Mount the controller in the proper orientation. If wall mount applications are not allowed for the FEU1610-0U,
then proper mounting position will only be as shown in Figure 2.
•Mount the controller on a hard, even surface whenever possible in wall mount applications.
•Use shims or washers to mount the unit securely and evenly on the mounting surface.
•Mount the controller
listed in the Technical Specifications
in an area free of corrosive vapors and observe the Ambient Conditions requirements
section.
•Provide for sufficient space around the controller for calbe and wire connections for easy cover removal and
good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
•Do not mount the controller
on surfaces prone to vibration, such as duct work.
•Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can
interfere with controller
communication.
Observe these additional guidelines when mounting a controller in a panel or enclosure:
•Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the
controller.
•Mount the controller so that the power transformer and other devices do not radiate excessive heat to the
controller.
•Do not install the controller
in an airtight enclosure.
Wall Mount Applications
The FEU16 controller must be installed inside an FSCS panel; therefore, a wall mount application is not
acceptable.
DIN Rail Mount Applications
To mount the controlleron a DIN rail inside the FSCS panel:
1. Securely mount a 20.3 cm (8 in.) or longer section of DIN ra il horizont ally and cen tered in the desir ed sp ace so
that the controller mounts in the horizontal position shown in Figure 2.
HOT
OUT 2
OUT 1
OUT 3
OCOM 1
OCOM 2
OCOM 3
SENSOR
2. Ensure that the bottom two mounting clips are pulled outward and snapped firmly into the extended position.
COM
esc
FC
O
N
SA BUS
OM
+
–
SHLD
FEU16x0 Field Equipment Controller Installation Instructions
3
Page 4
3. Hand the controller by the hooks at the top of the DIN rail channel on the back of the controller, and position the
controller snugly against the DIN rail.
4. Push the bottom mounting clips inward (up) to secure the controller
To remove the controller from the DIN rail, pull the bottom mounting clip s out to the extended position and car efully
lift the controller
off the DIN rail.
on the DIN rail tracks.
Wiring
Risk of Electric Shock: Disconnect the power supply before making electrical connections to avoid electric
shock.
Mise En Garde: Risque de décharge électrique: Débrancher l'aliment ation avant de réaliser to ut raccordement
électrique afin d'éviter tout risque de décharge électrique.
Risk of Property Damage: Do not apply power to the system before checking all wiring connections. Short
circuited or improperly connected wires may result in permanent damage to the equipment.
Mise En Garde: Risque de dégâts matériels: Ne pas mettre le système sous tension avant d'avoir vérifié tous
les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent
d'endommager irrémédiablement l'équipement.
IMPORTANT: Do not exceed the controller electrical ratings. Exceeding controller electrical ratings can result
in permanent damage to the controller and void any warranty.
IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional
regulations.
IMPORTANT: Electrostatic discharge can damage controller components. Use proper electrostatic discharge
precautions during installation, setup, and servicing to avoid damaging the controller.
For detailed information on configuring and wiring an MS/TP Bus, FC Bus, and SA Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
Hard-Wired Installation
To install an FEU16 for hard-wired operation, perform the steps tha t follow . See Figure 1 for jack and terminal block
locations.
Input/Output Terminals
Terminate input/output point wiring at the controller per engineering drawings.
SA Bus Terminal Block and Sensor Port
Wire Network Sensors and other devices to the Sensor Actuator (SA) Bus terminal block (Figure 3) or Sen sor p ort
(RJ-12 modular jack) for sensors.
Note: The FEU16 controller should be at one end of the SA Bus daisy chain. If multiple Input/Output Modules
(IOMs) are used, set the End-of-Line (EOL) switch on the last IOM.
FEU16x0 Field Equipment Controller Installation Instructions
4
Page 5
FC Bus Terminal Block
Figure 3: SA Bus Terminal Block Wiring
Figure 4: FC Bus Terminal Block Wiring
Wire the Field Controller (FC) Bus in a daisy chain to other devices on the FC Bus and the supervisory controller
(Figure 4).
Note: The Shield terminal (SHLD) on the FC Bus terminal block is isolated and can be used as a convenient
terminal for connecting the bus cable shield (Figure 4).
Sensor Port
The Sensor Bus port on the bottom-right of the IOM is an RJ-12, 6-position modular jack that provides a connection
for an NS sensor. See Table 1 for more information. The Sensors Port pin assignment is shown in (Figure 5).
Device Address DIP Switches
Ensure the device address DIP switches are set to the approp riate address (in the r ange of 4-127). En sure that DIP
switch 128 is set to Off, which disables wireless mode. For more details on setting the DIP switches, see the
Setting the FC Bus Address
on page 11.
FEU16x0 Field Equipment Controller Installation Instructions
5
Page 6
Figure 5: Pin Number Assignments for Sensor, SA Bus, and FC Bus Ports on FEC,
IOM, and VMA16
(15 VDC)
SA or FC Bus +
SA or FC Bus
-
Power
(15 VDC)
Sensor, SA Bus, or FC Bus Port
(RJ-12 Mod ul ar Jack)
FIG:RJ_pinout
2
3
4
5
6
1
Figure 6: 24 VAC Supply Power Terminal Block Wiring
FEC
Supply Power
Terminal Bloc k
Plug
Wires from
Johnson C ont r ols
24 VAC, Class 2
Power T rans f orme r
(COM)
(24 VA C)
FIG:FEC_Pwer_Prt
24V~
COM
HOT
Bus and Power Common
Bus and Power Common
Power
Supply Power Terminal Block
The 24 VAC supply power terminal block is a gray, removable, 3-terminal plug that fits into a board-mounted jack
on the top right of the controller. Connect the 24 VAC supply power wires from the transformer to the HOT and
COM terminals on the plug as shown in Figure 6. The middle terminal on the supply power block is not used..
IMPORTANT: The 24 VAC power should be connected to all network devices so transformer phasing is
uniform across the devices. Powering devices with uniform 24 VAC supply power phasing reduces noise,
interference, and ground loop problems. The FEC does not require an earth ground connection.
Supply Power
Terminal Block
Brown W ire
Orange Wire
FEU16x0 Field Equipment Controller Installation Instructions
6
FEC
Page 7
Wire Gauges and Lengths
See Table 1 for the field controller platform wiring list and Table 2 for alternative wire gauges and lengths.
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 1 of 3)
Terminal
Block
Universal IN+15 VProvides 15 VDC power for active devices connected to
(10k Type L, 2.252k Type 2)
Binary Input, Dry Contact Maintained Mode
1 second minimum pulse width (0.5 Hz at 50% duty cycle)
Internal 12 V, 15k ohm Pullup
ICOM nThe signal common for all Universal IN terminals;
ICOM nThe signal common for Binary IN terminals; isolated from
isolated from all other terminal commons
0.01 second min. pulse width (50 Hz at 50% duty cycle)
Internal 8 V, 3.3k ohm Pullup
Binary Input, Pulse Counter Mode
0.01 second min. pulse width (50 Hz at 50% duty cycle)
Internal 8 V, 3.3k ohm Pullup
all other terminal commons, excluding Configurable
Output (CO) terminal commons that are configured as
Analog Outputs (AOs).
and Length
0.6 mm (22 AWG) stranded, 3-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Same as IN. See IN n cable type.
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable
(See Row B in
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Same as IN. See IN n cable type.
Note: Use 3-wire cable for active
devices that connect to the +15 V
terminal also.
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
1
Table 2.)
Table 2.)
Table 2.)
Table 2.)
Table 2.)
FEU16x0 Field Equipment Controller Installation Instructions
7
Page 8
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)
Terminal
Block
Binary OUT
(Jumper set
to External)
Binary OUT
(Jumper Set
to Internal)
Configurable
OUT
Sensor
SA Bus
FC Bus
Terminal
Block
2,3
2,3
3
Terminal
Labels
OUT nBinary Output, 24 VAC Triac
OCOM nThe signal common for Binary OUT terminals; isolated
OUT nSources 24 VAC Power (Hot)0.6 mm (22 A WG) stranded, 2-wire
OCOM nBinary Output, 24 VAC Triac
OUT nAnalog Output, Voltage Mode
OCOM nAnalog Output: The signal common for all analog CO
SensorProvides SA Bus communication network.
+
COMProvides reference for network communication bus and
SA PWRSources 15 VDC power for devices on the SA Bus
+
COM
SHLDProvides an optional shield connection.
Function and Electrical Ratings/RequirementsRecommended Cable Type
and Length
0.6 mm (22 AWG) stranded, 2-wire
Connects OUT to OCOM when activated
30 VAC maximu m output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
from all other terminal commons, including Binary Output
terminal commons
Connects OCOM to 24 VAC Power (Com) when activated
(low side switching).
30 VAC maximu m output voltage
0.5 A maximum output current
40 mA minimum load current
Sources 0-10 VDC
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current
Binary Output, 24 VAC Triac mode
Connects OUT to OCOM when activated.
30 VAC maximu m output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
terminals; isolated from all other terminal commons,
excluding BI terminal commons
Binary Output: The signal common for binary-configured
CO terminals; isolated from all other terminal commons,
including other CO terminal common s
RJ-12 6-position modular connector
Provides SA Bus communication network.0.6 mm (22 AWG) stranded, 4-wire
15 VDC source power.
Provides FC Bus communication network.0.6 mm (22 AWG) stranded, 3-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row C in
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row C in
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row C in
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Same as OUT. See OUT cable
type.)
24 AWG 3-pair CAT 3 Cable
<30.5 m (100 ft)
twisted, shielded cable
recommended
twisted, shielded cable
recommended
1
Table 2.)
Table 2.)
Table 2.)
Table 2.)
FEU16x0 Field Equipment Controller Installation Instructions
8
Page 9
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 3 of 3)
Terminal
Block
24~ PowerHotAC Supply Input
Terminal
Function and Electrical Ratings/RequirementsRecommended Cable Type
Labels
Supply 20-30 VAC (Nominal 24 VAC)
SHLDProvides an optional shield connection.
and Length
0.8 mm to 1.0 mm
(20 to 18 AWG) 2-wire
1
1.See
2.The SA Bus terminals and the RJ-style modular Sensor Port are connected internally.
3.The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k baud. For more
Table 2 for alternative wire gauges and lengths.
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-1201 1034).
Table 2: Wire Gauge and Length Guidelines
GuidelineCable Size Maximum
Assumptions
Length
A1.0 mm (18 AWG)457.2 m (1,500 ft)100 mV maximum voltage drop
0.8 mm
0.6 mm
0.5 mm (24 AWG)106.7 m (350 ft)
B1.0 mm (18 AWG)228.6 m (750 ft)100 mV maximum voltage drop
0.8 mm
0.6 mm
0.5 mm (24 AWG)61 m (200 ft)
C
See
(20 AWG)
(22 AWG)
(20 AWG)
(22 AWG)
Figure 7.See Figure 7.
297.2 m (975 ft)
182.9 m (600 ft)
137.1 m (450 ft)
91.4 m (300 ft)
N/A
FEU16x0 Field Equipment Controller Installation Instructions
9
Page 10
Wiring Requirements
Figure 7: Maximum Wire Length by Current and Wire Size
50
0
0 m (0 ft)
15.2 m (50 ft)
30.5 m (100 ft)
45.7 m (150 ft)
61 m (200 ft )
76.2 m (250 ft)
91.4 m (300 ft)
106.7 m (350 ft)
121.9 m (400 ft)
137.2 m (450 ft)
Load Current (mA)
FIG:wir_lngth
1.0 mm (18 AWG)
0.8 mm (20 AWG)
0.6 mm(22 AWG)
0.5 mm (24 AWG )
Use Figure 7 to determine the maximum wire length allowable when alternative wire gauges are required.
Length
100
200150
250
300
350
400
450
500
Setup and Adjustments
Determining the FC Bus Address
The FC Bus address switch sets a unique address for this controller on the FC Bus. You must set the FEC’s device
address for your field bus application.
Set consecutive device addresses 4 through 127 for Field Equipment Controllers and other master devices on the
FC Bus. Use sequential addressing with no gaps in the device address range to ensure best FC Bus performance.
Note: Switch 128 on the device address DIP switch block should be set to Off.
Table 3 shows and describes the valid FC Bus and SA Bus devices addresses for FECs and IOMs on Johnson
Controls® MS/TP communications bus applications.
Table 3: FC Bus Device Address Descriptions
Device
Description
Address
0Reserved for FC Bus supervisory controller.
1-3Reserved for peripheral devices.
4-127Available for FECs on the FC bus and IOMs
128Unused and should be set to Off.
129-255Are not valid addresses for FEC or IOM
on the SA or FC Bus.
controllers on the SA or FC Bus.
FEU16x0 Field Equipment Controller Installation Instructions
10
Page 11
Setting the FC Bus Address
Figure 8: Device Address Switches Set to 21
ON
Note:
Switch 12 8 i s
used to enable or
disable an FEC for
wireless oper ation.
Figure 9: EOL Switch Positions
FIG:E
O
N
Figure 10: Binary Output (BO) Jumper Positions
Jumper
on top two pi ns
INT
EXT (Default)
FIG:Bin_Jmpr
Set the address of the FEU16 using the DIP switches on the face of the FEU16. The addr ess equals the sum of the
numbers set to ON. For example, if the first (1), the third (4), and the fifth (16) DIP switches are set to ON, the
device address is 21 (1 + 4 + 16 = 21). See Figure 8.
128
64
32
16
8
1
2
4
FIG:fec_dip_swtch
FC Bus End-of-Line Switch
The FC Bus End-of-Line termination switch allows you to designate the FE U16 as the end of the FC Bus. The
default position is OFF. If the FEU16 is at the end of a daisy chain of devices on the FC Bus, set the EOL switch to
the ON position. See Figure 9.
O
N
OL_Swtch
EOL ON PositionEOL Off Position
Setting the Binary Output INT/EXT Jumpers
The Binary Output jumpers (OUT1 through OUT3) are located on the circuit board in the mounting base near the
binary outputs. These jumpers select whether the ou tp ut provides internal power to the load (INT) or requires
external power (EXT). See Figure 10.
IMPORTANT: Do not set the Binary Output jumpers to INT when an external transfor mer is wired to th e Binary
Output terminals. Failure to follow this precaution may cause damage to the cont ro ller.
When set to the INT position, the FEU16
be wired directly to the OUTx and COMx terminals.
Setting the jumper to the EXT position isolates the Binary Outputs, and power must come from one or more
external sources. Do not wire the load directly to the OUTx and COMx terminals. Wire one side of the load to the
source and the other side of the load to the OUTx terminal. Wire the other side of the external power source to the
COMx terminal.
FEU16x0 Field Equipment Controller Installation Instructions
Jumper positioned
Jumper positioned
Pins
on bottom tw o pins
isthepower source for the Binary Output and both sides of the load can
11
Page 12
Commissioning
Figure 11: Location of Removable Fuse
of
Fuse
FIG:fse_rmv
Controller Mounting Base
Commission the controller with the Controller Configuration Tool (CCT), either through the BTCVT or in
passthrough mode when connected via a Network Application Engine (NAE) or Network Control Engine (NCE).
Refer to CCT Help.
Troubleshooting
Use Table 4 to troubleshoot the controller.
Table 4: Status LEDs
NameColorNormalDescriptions
Power/PWRGreenOn SteadyOff Steady = No Power
On Steady = Power is supplied by Primary Voltage.
Fault/FLTRedOff SteadyBlink - 2 Hz = Download or Startup in progres s, not ready for normal operation
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download required, if
controller is in Boot mode.
SA Bus/SABGreenBlink - 2 HzBlink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
FC Bus/FCBGreenBlink - 2 HzBlink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (auto baud in progress)
On Steady = Communication lost, waiting to join communication ring
Replacing the Fuse
If you connect power to the controller but it does not fu nction, the fuse may need to be replaced. Use the following
procedure to replace the fuse.
1. Remove power from the controller.
2. Loosen the cover screw and remove the cover.
3. Remove the fuse. See Figure 11.
4. Install a new replacement fuse (MS-FUSE01-1).
5. Replace the cover.
6. Reconnect power to the controller.
Location
Removable
F1
FEU16x0 Field Equipment Controller Installation Instructions
12
Page 13
Repair Information
If you need to replace the MS-FEU1611-0U controller, contact the Johnson Controls Repair Center in Louisville,
Kentucky, at 1-502-671-7312. This model has special restrictions because it is UL 864 10th Edition UUKL/ORDC100-13 UUKLC listed for smoke control.
Accessories
Use Table 5 to order accessories.
Table 5: FEU16 Accessories Ordering Information
Product Code NumberDescription
PAN-PWRSP-UTransformer , 120/24 VAC, 96 VA, with circuit breaker and 120 VAC outlet, approved for Smoke
MS-FUSE01-1Replacement fuse (Bulk Pack of 10)
Control
Technical Specifications
FEU1610 Controller
Product Code NumbersMS-FEU1610-0U Field Equipment Controller
Supply Voltage20 - 30 VAC at 50 or 60 Hz, Class 2
Power Consumption10 VA typical, 14 VA maximum, plus all BO and CO loads
Ambient ConditionsOperating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage: -40 to 70°C (-40 to 158°F); 10 to 90% RH noncondensing
TerminationsScrew Terminals and Screw Terminal Pluggable Blocks
Controller AddressingDIP switch set (4-127). Addresses 0-3, 128-255 are reserved.
Communications BusBACnet® MS/TP; 3-wire FC Bus between the NAE and other devices. 4-wire SA Bus
MountingOn flat surface with screws on three mounting clips or a single 35 mm DIN rail
HousingPlastic housing
Analog Input/Analog
Output Resolution and
Accuracy
Dimensions
(Height x Width x Depth)
Weight0.5 kg (1.10 lb)
ComplianceUnited States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
between network sensors and other devices.
Plastic material: ABS and polycarbonate UL94 5VB
Analog Input Points: 15-bit resolution
Analog Output Points: 16-bit resolution, +
144 x 127 x 58 mm (5.68 x 5 x 2.25 in.)
Minimum space for mounting:
Equipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A
UL Listed, File S4977, UL 864 UUKL/UUKLC 10th Edition Listed, Smoke Control Units and
Accessories for Fire Alarm Systems Equipment
Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal
Equipment; Industry Canada Compliant, ICES-003
UL Listed, File S4977, UL 864 UUKL/ORD-C100-13 10th Edition Listed, Smoke Control Units
and Accessories for Fire Alarm Systems
Europe: CE Mark, EMC Directive, in accordance with EN 61000-6-3 and EN 61000-6-2, and
the Low Voltage Directive in accordance with EN 60730.
174 x 350 x 110 mm (6.8 x 13.8 x 4.3 in.)
200 mV accuracy
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant.
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
FEU16x0 Field Equipment Controller Installation Instructions
13
Page 14
Published in U.S.A.
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.