The FAC4911 Advanced Application Field Equipment
Controller is part of the Metasys® system Field
EquipmentController family. The FAC4911
equipment controllers run pre-engineered and userprogrammed applications, and provide the inputs
and outputs required to monitor and control a wide
variety of HVAC equipment.
FAC4911 controllers operate on BACnet®/IP
networks and integrate into Johnson Controls
and third-party systems. The controllers include
an integral real-time clock, which enables the
controllers to monitor and control schedules,
calendars, and trends, and operate for extended
periods of time as stand-alone controllers when
offline from the Metasys system network.
The Metasys system FAC family controllers and
network sensors communicate using the BACnet
protocol. The BACnet protocol is a standard for
ANSI, ASHRAE, and the International Standards
Organization (ISO) for building controls. FAC
equipment controllers are BTL-listed and certified as
BACnet Advanced Application Controllers (B-AACs).
®
Controller Installation Guide
Part No. 24-10143-1086 Rev. C
2019-10-18
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Observe the following guidelines when installing a
field controller:
• To minimize vibration and shock damage,
transport the controller in the original container.
• Verify that all parts shipped with the controller.
• Do not drop the controller or subject it to physical
shock.
Parts included
• One field Controller. (Power and SA bus terminal
blocks are removable)
• One installation instructions sheet.
Materials and special tools needed
North American emissions
compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment
is operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area
may cause harmful interference, in which case the
users will be required to correct the interference at
their own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
• Three fasteners appropriate for the mounting
surface (M4 screws or #8 screws)
• One 23 cm (9.125 in.) or longer piece of 35 mm
DIN rail and appropriate hardware for DIN rail
mount (only)
• Small straight-blade screwdriver for securing
wires in the terminal blocks
*24101431086C*
(barcode for factory use only)
MS-FAC4911-0
FAC4911 physical features
The following figure displays the physical features
of FAC4911, and the accompanying table provides a
Figure 1: Physical Features
description of the physical features and a reference
to further information where required.
Table 1: Physical features
Physical feature: description and references
Controller Number Rotary Switches: can be numbered
1
from 000 to 999 (see Setting the Controller Number)
Binary Outputs (BO) Terminal Block: 24 VAC Triac (see I/
Analog Output, Voltage Mode, 0–10 VDC
Analog Current Mode, 4–20 mA
Analog Output, Voltage Mode, 0–10 VDC
Binary Output Mode, 24 VAC Triac
6-Pin SA Bus with four communicating
sensors
10
6
4
4
Mounting
Observe the following guidelines when mounting a
field controller:
• Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied
enclosure.
• Mount the controller horizontally on 35 mm DIN
rail whenever possible.
• Mount the controller in the correct mounting
position (Figure 2).
• Whenever possible in wall-mount applications,
mount the controller on a hard, even surface.
• Use shims or washers to mount the controller
securely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive
vapors and observe the ambient conditions
requirements in Technical specifications.
• Provide sufficient space around the controller for
cable and wire connections, easy cover removal,
and good ventilation through the controller (50
mm [2 in.] minimum on the top, bottom, and
front of the controller).
• Do not mount the controller on surfaces prone to
vibration, such as ductwork.
• Do not mount the controller in areas where
electromagnetic emissions from other
devices or wiring can interfere with controller
communication.
Observe these additional guidelines when mounting
a field controller in a panel or enclosure:
• Mount the controller so that the enclosure walls
do not obstruct cover removal or ventilation
through the controller.
• Mount the controller so that the power
transformer and other devices do not radiate
excessive heat to the controller.
• Do not install the controller in an airtight
enclosure.
FAC4911 Advanced Application Field Equipment Controller Installation Guide3
Figure 2: Controller Mounting Positions
2.Pull the two bottom mounting clips outward
from the controller to the extended position
(Figure 3).
3.Hang the controller on the DIN rail by the hooks
at the top of the (DIN rail) channel on the back
of the controller (Figure 3), and position the
controller snugly against the DIN rail.
4.Push the bottom mounting clips inward (up) to
secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the
bottom mounting clips out to the extended position
and carefully lift the controller off the DIN rail.
Mounting Features and Dimensions
See Figure 3 for mounting dimensions in millimeters
and inches. Inches are listed in parenthesis. Figure
3 also illustrates the DIN rail channel and the
mounting clips in an extended position.
Figure 3: Back of Controller
Wall mount applications
To mount a field controller directly on a wall or
other flat vertical surface, complete the following
steps:
1.Pull the two bottom mounting clips outward
and ensure they are locked in the extended
position.
2.Mark the mounting hole locations on the wall
in either the horizontal or vertical mounting
position. Or hold the controller up to the wall or
surface in a proper mount position and msark
the hole locations through the mounting clips.
3.Drill holes in the wall or surface at the marked
locations, and insert appropriate wall anchors
in the holes (if necessary).
4.Hold the controller in place, and insert the
screws through the mounting clips and into the
holes (or anchors). Carefully tighten all of the
screws.
DIN Rail mount applications
Mounting the field controller horizontally on 35 mm
DIN rail is the preferred mounting method.
To mount a field controller on 35 mm DIN rail,
complete the following steps:
1.Securely mount a 23 cm (9.125 in.) or longer
section of 35 mm DIN rail, horizontally and
centered in the desired space, so that the
controller mounts in the position shown in
Figure 2.
FAC4911 Advanced Application Field Equipment Controller Installation Guide4
Important: Do not overtighten the mounting
screws. Overtightening the screws may
damage the mounting clips.
Wiring
CAUTION
Important: Electrostatic discharge can
damage controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
Risk of Electric Shock:
Disconnect the power supply before making electrical
connections to avoid electric shock
ATTENTION
Mise En Garde: Risque de décharge électrique
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de
décharge électrique.
CAUTION
Risk of Property Damage:
Do not apply power to the system before checking all
wiring connections. Short circuited or improperly connected wires may result in permanent damage to the
equipment.
ATTENTION
Mise En Garde: Risque de dégâts matériels
Ne pas mettre le système sous tension avant d'avoir
vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement
l'équipement.
For detailed information about configuring and
wiring an MS/TP bus, FC bus and SA bus, refer to
the MS/TP Communications Bus Technical Bulletin(LIT-12011034).
Network topology
FAC4911 controllers may be connected to a building
automation network in multiple ways: as daisychained devices, as part of a star (also called home
run) network, or as part of a ring network.
To daisy-chain FAC4911 controllers, connect the
controllers to the bus supervisor in a chain with
the Ethernet cable connecting to the FAC4911
at the ETH1 or ETH2 port and connecting to the
next device from the other port. Benefits of daisychained networks are that they require less physical
wiring and new devices can be added easily to the
network.
In a star network, each FAC4911 controller is
connected directly back to a main switch. This
configuration reduces the possibility of network
failure but requires more wiring to install.
A ring network is a chain of controllers virtually
closed by a software component in an Ethernet
switch. Not all switches support the ring topology.
The dual-port controller from Johnson Controls
supports Media Redundancy Protocol (MRP). MRP
allows a chain of Ethernet devices to overcome any
single communication failure, with a recovery time
faster than in a BACnet system.
For more information about network topologies
for the BACnet/IP Controllers, refer to the Metasys
IP Networks for BACnet/IP Controllers Configuration
Guide Technical Bulletin (LIT-12012458).
Important: Do not exceed the controller
electrical ratings. Exceeding controller electrical
ratings can result in permanent damage to the
controller and void any warranty.
Important: Use copper conductors only. Make
all wiring in accordance with local, national, and
regional regulations.
FAC4911 Advanced Application Field Equipment Controller Installation Guide5
Terminal blocks and bus ports
See for terminal block and bus port locations on the
controller. Observe the following guidelines when
wiring a controller.
Input and Output terminal blocks
The fixed input terminal blocks are located on the
bottom of the controller, and the output terminal
blocks are located on the top of the controller. See
Table for more information about I/O terminal
functions, requirements, and ratings.
SA bus terminal block
The SA Bus terminal block is a brown, removable, 4terminal plug that fits into a board-mounted jack.
Wire the removable SA Bus terminal block plugs on
the controller, and other SA bus devices in a daisychain configuration using 4-wire twisted, shielded
cable as shown in Figure 4. For more information
about the SA Bus terminal function, requirements,
and ratings, see .
Figure 4: SA bus terminal block wiring
Wire the 24 VAC supply power wires from the
transformer to the HOT and COM terminals on the
terminal plug as shown in Figure 5. Do not use the
middle terminal on the supply power terminal block.
See for more information about the Supply Power
Terminal Block.
Figure 5: 24 VAC supply power terminal block
wiring
Note: The SA PWR terminal supplies 15 VDC.
The SA PWR terminal can be used to connect
(daisy chain) the 15 VDC power leads on the SA
bus.
SA Bus Port
The Sensor (SA Bus) port on the bottom of the
controller is an RJ-12, 6-position modular jack
that provides a connection for the Wireless
Commissioning Converter, the VAV Balancing Tool,
specified network sensors, or other SA Bus devices
with RJ-12 plugs. When the FEC is configured for N2
network communication, the SA Bus port must be
used to download and commission the controller.
A DIS1710 Local Controller Display also can be
connected to the SA Bus port.
The Sensor port is connected internally to the SA
bus terminal block.
Supply power terminal block
The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a boardmounted jack on the top right of the controller.
Note: The supply power wire colors may
be different on transformers from other
manufacturers. Refer to the transformer
manufacturer’s instructions and the project
installation drawings for wiring details.
Important: Connect 24 VAC supply power
to the field controller and all other network
devices so that transformer phasing is uniform
across the network devices. Powering network
devices with uniform 24 VAC supply power
phasing reduces noise, interference, and
ground loop problems. The field controller
does not require an earth ground connection.
Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements
Input and output wiring guidelines
The following table provides information and
guidelines about the functions, ratings, and
requirements for the controller input and
output terminals; and references guidelines for
determining proper wire sizes and cable lengths.
FAC4911 Advanced Application Field Equipment Controller Installation Guide6
In addition to the wiring guidelines in the following
table, observe these guidelines when wiring
controller inputs and outputs:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All input and output cables, regardless of wire
size or number of wires, should consist of
stranded, insulated, and twisted copper wires.
• Shielded cable is not required for input or output
cables.
• Shielded cable is required for input and output
cables that are exposed to high electromagnetic
or radio frequency noise.
• Inputs or outputs with cables less than 30 m
(100 ft) typically do not require an offset in the
software setup. Cable runs over 30 m (100 ft) may
require an offset in the input/output software
setup.
FAC4911 Advanced Application Field Equipment Controller Installation Guide7
I/O terminal blocks, ratings, and
requirements
Table 3: I/O terminal blocks, functions, ratings, requirements, and cables
[ Johnson Controls sensor], 1k Platinum, and A99B Silicon
Temperature Sensor) Negative Temperature Coefficient
(NTC) Sensor
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V. 15kΩ pull-up
Universal Input Common for all Universal Input
terminals
Note: All Universal ICOMn terminals share a
common, which is isolated from all other commons,
except the SA bus common. One common screw
terminal point is provided for every two input screw
terminal points.
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width
Internal 18 V. 3k Ω pull-up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V. 3kΩ pull-up
Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons.
Determine wire size and
maximum cable length
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power
from the +15V terminal.
See Guideline A in Table .
See Guideline B in Table .
See Guideline A in Table .
See Guideline A in Table .
Same as (Universal) INn
See Guideline A in Table .
FAC4911 Advanced Application Field Equipment Controller Installation Guide8
Table 3: I/O terminal blocks, functions, ratings, requirements, and cables
10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1,000 Ω or more.
Note: The Analog Output (AO) operates in the
O
ANALOG
(Outputs)
OCOMn
OUTn
BINARY
(Output)
OCOMn
OUTn
CONFIGURABLE
(Output)
OCOMn
Voltage Mode when connected may not operate as
intended for Voltage Mode applications.
.
Note: The Analog Output (AO) operates in the
Current Mode when connected to devices with
impedances less than 300 Ω. Devices that exceed
below 300 Ω may not operate as intended for
Current Mode applications.
Analog Output Signal Common for all Analog OUT
terminals.
Note: All Analog Output Common terminals
(OCOMn) share a common, which is isolated from
all other commons. One common screw terminal
point is provided for every two output screw
terminal points.
Binary Output - 24 VAC Triac Class 2, 24 V, 500 mA
(External Power Source)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Binary Output Common (for OUTn terminal)
Note: Each Binary Output Common terminal
(OCOMn) is isolated from all other commons,
including other Binary Output Common terminals.
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
or more.
Binary Output - 24 VAC Triac (External Power Source
only)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Analog and Binary Output Signal Common All
Configurable Outputs (COs) defined as Binary Outputs
are isolated from all other commons, including other CO
commons.
Determine wire size and
maximum cable length
See Guideline C in Table .
See Guideline C in Table .
See Guideline A in Table
See Guideline C in Table
Same as (Configurable) OUTn
FAC4911 Advanced Application Field Equipment Controller Installation Guide9
Cable and wire length guidelines
The following table defines cable length guidelines
for the various wire sizes that may be used for
wiring low-voltage (<30 V) input and outputs.
Note: The required wire sizes and lengths
for high-voltage (>30 V) Relay Outputs are
determined by the load connected to the relay,
and local, national, or regional electrical codes.
Table 4: Cable length guidelines for recommended wire sizes for low-voltage (<30 V) Inputs and
Outputs
Wire size/Gauge and type
1.0 mm (18 AWG) stranded copper457 m (1,500 ft) twisted wire
0.8 mm (20 AWG) stranded copper297 m (975 ft) twisted wire
A
B
C
0.6 mm (22 AWG) stranded copper183 m (600 ft) twisted wire
0.5 mm (24 AWG) stranded copper107 m (350 ft) twisted wire
1.0 mm (18 AWG) stranded copper229 m (750 ft) twisted wire
0.8 mm (20 AWG) stranded copper137 m (450 ft) twisted wire
0.6 mm (22 AWG) stranded copper91 m (300 ft) twisted wire
0.5 mm (24 AWG) stranded copper61 m (200 ft) twisted wire
See Figure 6 to select wire size/gauge. Use
stranded copper wire
Maximum cable length and
type
See Figure 6 to determine cable
length. Use twisted wire cable.
Assumptions
100 mV maximum voltage drop
Depending on cable and the
connected input or output device, you
may have to define an offset in the
setup software for the input or output
point.
100 mV maximum voltage drop
Depending on cable and the
connected input or output device, you
may have to define an offset in the
setup software for the input or output
point.
N/A
Maximum cable length versus load
current
Use Figure 6 to estimate the maximum cable length
relative to the wire size and the load current (in mA)
when wiring inputs and outputs.
Note: Figure 6 applies to low-voltage (<30 V)
inputs and outputs only.
Figure 6: Maximum wire length for low-voltage
(<30 V) Inputs and Outputs by current and wire
size
Communications bus and supply
power wiring guidelines
The provides information about the functions,
ratings, and requirements for the communication
bus and supply power terminals. The table also
provides guidelines for wire sizes, cable types, and
cable lengths for when you wire the controller's
communication buses and supply power.
In addition, observe these guidelines when you wire
an SA or FC bus and the 24 VAC supply power:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All SA and FC bus cables, regardless of wire size,
should be twisted, insulated, stranded copper
wire.
• Shielded cable is strongly recommended for all SA
and FC bus cables.
• Refer to the MS/TP Communications BusTechnical Bulletin (LIT-12011034) for detailed
information regarding wire size and cable length
requirements for SA and FC buses.
FAC4911 Advanced Application Field Equipment Controller Installation Guide10
Communications Bus and supply power terminal blocks, ratings, and
requirements
Table 5: Communications Bus and supply power terminal blocks, functions, ratings, requirements, and
cables
Terminal
block/Port
label
SA BUS
Sensor
(Port)
Ethernet
(Ports)
24~
Terminal labels
+
-
COM
SA PWR
Sensor
ETH1
ETH2
HOT
COM
Function, electrical ratings/
requirements
SA Bus Communications
SA Bus Signal Reference and 15 VDC
Common
15 VDC Supply Power for Devices on
the SA Bus
(Maximum total current draw for SA
Bus is 240 mA.)
RJ-12 6-Position Modular Connector
provides:
SA Bus Communications
SA Bus Signal Reference and 15 VDC
Common
15 VDC Power for devices on the SA
bus and BTCVT
Connect to BACnet IP Network
24 VAC Power Supply - Hot
Supply 20–30 VAC (Nominal 24 VAC)
24 VAC Power Supply Common
(Isolated from all other Common
terminals on controller)
Incremental
Control to
Actuator (Switch
High, Externally
Sourced)
Type of Input/
Output
BO
BO
Termination diagrams
Network Stat with
Phone Jack (Fixed
Address = 199)
Network Stat
with Terminals
Addressable
SA Bus
Note: The bottom jack (J2) on the TE-700 and TE-6x00 Series Sensors is not usable as a zone
bus or an SAB connection.
SA Bus
FAC4911 Advanced Application Field Equipment Controller Installation Guide16
Table 6: Termination details
Type of field
device
Network Stat with
Terminals (Fixed
Address = 199)
Type of Input/
Output
SA Bus
Termination diagrams
Setup and Adjustments
Setting the Controller Number
Each controller on a network must have a unique
number on the subnet where it resides in order to
identify it in the Controller Configuration Tool (CCT)
for uploading, downloading, and commissioning.
The controller number is set using three rotary
switches (Figure 7) and may be numbered from 000
to 999. The numbers are ordered from left to right,
most significant bit (MSB) to least significant bit
(LSB) when the controller is oriented as shown in
FAC4911 physical features.
In the following figure the switches are set to
4 2 5, designating this controller as controller
number 425. The controller number must match
the controller number defined in CCT under DefineHardware > Network Settings. The number of
the controller can be written in the white squares
provided so the controller number can be easily
seen from a distance.
Figure 7: Rotary Switch for Setting Controller
Numbers
Note: The BACnet device ID is calculated
using the value of controller number added
to 2000000 . The device ID configured in this
manner does not require any configuration
from CCT.
FAC4911 Advanced Application Field Equipment Controller Installation Guide17
Removing the Controller cover
Important: Electrostatic discharge can
damage controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
Important: Disconnect all power sources to
the controller before you remove the cover and
change the position of any jumper or the EOL
switch on the controller. Failure to disconnect
power before changing a jumper or EOL switch
position can result in damage to the controller
and void any warranties.
ATTENTION
Risque de décharge électrique
Débrancher l'alimentation de l'controller avant tout
réglage du Binary Output Source Power Selection
Jumpers. Le non-respect de cette précaution risque
de provoquer une décharge électrique.
UI current loop jumpers
The UI current loop fail-safe jumper pins are located
on the circuit board under the controller cover near
the UI terminals.
The controller cover is held in place by four
plastic latches that extend from the base and
snap into slots on the inside of the housing
cover.
To remove the controller cover, complete the
following steps:
1.Place your fingertips under the two cover lift
tabs on the sides of the housing cover and
gently pry the top of the cover away from the
base to release the cover from the two upper
latches.
2.Pivot the top of the cover further to release it
from the lower two latches.
3.Replace the cover by placing it squarely over
the base, and then gently and evenly push the
cover on to the latches until they snap into the
latched position.
Setting the Input Jumpers
Figure 8: Current loop jumper positions
Set the current loop jumper to the Enabled position
(Figure 8) to connect an internal 100 ohms resistor
across the UI terminals, which maintains the 4–20
mA current loop circuit even when power to the
controller is interrupted or off.
Important: Current loop jumpers must be in
the Disabled (default) position for all UIs that
are not set up to operate as 4–20 mA analog
inputs.
The following table identifies the current loop
switches associated with each UI on the controller.
Table 7: UI Inputs and Jumper Labels
CAUTION
Risk of Electric Shock:
Disconnect supply power to the field controller before
attempting to adjust the Binary Output Source Power
Selection Jumpers. Failure to disconnect the supply
power may result in electric shock.
FAC4911 Advanced Application Field Equipment Controller Installation Guide18
The FAC4911 controllers ship with a default state
that can assist in validating the wiring of the input
and output terminals prior to download of an
application file. When the controller is powered on
in this state, the Fault LED will flash in a pattern of
two quick blinks and then a long pause (see Table
8).
To make use of this feature, ensure the rotary
switches are set to the desired controller number
and wire the input and output terminals. Apply
power to the FAC controller and connect to the
device with either a MAP Gateway or MS-DIS1710-0
Local Display to view the points in the controller.
The FAC controller will report an Operational status
even though there is no true application loaded.
CCT will not be able to commission or upload
the device as a result until a true application is
downloaded. The application name displayed will be
the controller number followed by the model of the
controller and “Default State”.
For example, a FAC4911 controller whose rotary
switches are set to 8 would have the default state
application name of “8-FAC4911 Default State”.
The default state creates I/O points for all
connections on the input and output terminals.
It assumes all Universal Inputs (UIs) are Nickel
temperature sensors. All Configurable Outputs
(COs) are treated as Binary Outputs (BOs) with an
initial value of 0. The default state also takes input
from a Network Sensor at address 199. If there is
no connected Network Sensor, the startup of this
default state will be delayed by 30 seconds as the
controller attempts to establish connection with the
sensor.
You commission controllers with the CCT software,
either via a Bluetooth® Wireless Commissioning
Converter, a ZFR wireless dongle, MAP 4.2+/ BACnet
Router (Mobile Access Portal (MAP) Gateway at
version 4.2 or above), or in passthrough mode when
connected to an NAE or NCE. Refer to ControllerTool Help (LIT-12011147) for detailed information on
commissioning field controllers.
Note: The MAP Gateway serves as a
replacement for the BTCVT, which is no longer
available for purchase, but continues to be
supported.
Firmware Package File
The MS-FCP-0 equipment controller firmware
package files are required for CCT to configure and
commission the controllers. The firmware package
files also allow you to upgrade an existing controller
to the latest firmware release available for that
controller.
Beginning at CCT Release 13, the firmware package
files are orderable separately; they are not included
with CCT. They are obtained from the Metasys
software licensing portal, and are loaded and
licensed on the computer/server that is running
CCT.
For additional information about the firmware
package files, refer to the CCT Installation Instructions(LIT-12011259).
Troubleshooting Field Controllers
Observe the Status LEDs on the front of the field
controller and see the table below to troubleshoot
the controller. To troubleshoot an integral or
local controller display, refer to the DIS1710 LocalController Display Technical Bulletin (LIT-12011270).
LED status and description table
Table 8: Status LEDs and descriptions of LED States
LED labelLED colorNormal LED state Description of LED states
Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse is
POWERGreenOn Steady
FAULTRedOff Steady
open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download required,
if controller is in Boot mode, or a firmware mismatch exists between the FAC and
the ZFR1811 Wireless Field Bus Router.
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
Rapid blink = SA Bus communications issue
FAC4911 Advanced Application Field Equipment Controller Installation Guide19
Table 8: Status LEDs and descriptions of LED States
LED labelLED colorNormal LED state Description of LED states
Blink - 2 Hz = Data Transmission (normal communication)
SA BUSGreenBlink - 2 Hz
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
Repair information
If a field controller fails to operate within its
specifications, replace the controller. For a
replacement controller, contact your Johnson
Controls representative.
FAC4911 Advanced Application Field Equipment Controller Installation Guide20
Accessories ordering information
Table 9: Accessories Ordering Information
Product Code Number Description
IOM Series Controllers
Mobile Access Portal
(MAP) Gateway
TL-CCT-0Metasys Controller Configuration Tool (CCT) Software
MS-FCP-0Metasys Equipment Controller Firmware Package Files for CCT
MS-DIS1710-0Local Controller Display
NS Series Network
Sensors
TP-2420Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
Y65T31-0
AS-XFR050-0
AS-CBLTSTAT-0Cable adapter for connecting to 8-pin TE-6700 Series sensors
AP-TBK4SA-0Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10
AP-TBK4FC-0Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10
AP-TBK3PW-0Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack of 10
Refer to the Metasys® System Field Equipment Controllers and Related Products Product Bulletin (LIT-12011042)
for a complete list of available IOM Series Controllers.
Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the appropriate product for
your region.
Note: The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for
purchase, but continues to be supported.
Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specific sensor model descriptions.
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in. Primary Leads and
Secondary Screw Terminals, Class 2
Note: Additional Y6x-x Series transformers are also available. Refer to the Series Y63, Y64, Y65, Y66, and
Y69 Transformers Product Bulletin (LIT-125755)
for more information.Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure for more
information.
FAC4911 Advanced Application Field Equipment Controller Installation Guide21
Technical specifications
Table 10: FAC4911 Advanced Application Field Equipment Controller for BACnet IP Networks
Product Code NumbersMS-FAC4911-0 Advanced Application Field Equipment Controller for BACnet/IP Networks
Analog Input/Analog Output Resolution
and Accuracy
Terminations
Mounting
Housing
Dimensions (Height x Width x Depth)
Weight0.5 kg (1.1 lb)
Compliance
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
14 VA maximum
Note: The VA rating does not include any power supplied to the peripheral devices
connected to binary outputs (BOs) or configurable outputs (COs), which can
consume up to 12 VA for each BO or CO; for a possible total consumption of an
additional 72 VA (maximum).
+15 VDC power source terminals provide 100 mA total current. Quantity 3 located in
Universal IN terminals - for active (3-wire) input devices.
Operating: 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing
Storage: -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing
Super capacitor maintains power to the onboard real-time clock for a minimum of 72
hours when supply power to the controller is disconnected.
10 - Universal Inputs: Defined as 0-10 VDC, 4-20 mA, 0-600k ohms, or Binary Dry Contact
6 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator
Mode
4 - Binary Outputs: Defined as 24 VAC Triac (external power source only)
4 - Analog Outputs: Defined as 0-10 VDC or 4-20 mA
4 - Configurable Outputs: Defined as 0-10 VDC or 4-20 mA
150 mm x 220 mm x 57.5 mm (5-7/8 in. x 8-3/4 in. x 2-3/8 in.) including terminals and
mounting clips
Note: Mounting space requires an additional 50 mm (2 in.) space on top,
bottom, and front face of controller for easy cover removal, ventilation, and wire
terminations.
United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment
Industry Canada Compliant, ICES-003
Europe: Johnson Controls, Inc. declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
BACnet Testing Laboratories™ (BTL) Protocol Revision 15 Listed and Certified BACnet
Advanced Application Controller (B-AAC), based on the ANSI/ASHRAE 135-2016
The performance specifications are nominal and
conform to acceptable industry standard. For
application at conditions beyond these specifications,
consult the local Johnson Controls office. Johnson
FAC4911 Advanced Application Field Equipment Controller Installation Guide22
Controls shall not be liable for damages resulting from
misapplication or misuse of its products.
Product warranty
This product is covered by a limited
warranty, details of which can be found at
www.johnsoncontrols.com/buildingswarranty.
Single point of contact
APACEuropeNA/SA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 32 CHANGJIJANG RD NEW
DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
For more contact information, refer to
www.johnsoncontrols.com/locations.
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
FAC4911 Advanced Application Field Equipment Controller Installation Guide23