Johnson Controls MAP Series, MAP 1810 Installation Instructions Manual

Mobile Access Portal Gateway Installation Instructions
Part No. 24-10737-8, Rev. F
Software Release 4.0
Issued April 2016
Refer to the QuickLIT website for the most up-to-date version of this document.

Applications

The Mobile Access Portal (MAP) Gateway is an alternate local display solution or a temporary portable commissioning device that enables users to leverage the power of mobility using smart phones, tablets, or laptop computers to interact with building automation equipment controls. The MAP Gateway serves up web pages through a built-in Wi-Fi access point or tethered Ethernet connection, which allows users to view and edit equipment controller configuration parameters, setpoints, schedules, and alarms through a browser. A mobile application is not required to use the MAP Gateway with your mobile device.
The MAP Gateway can be used to see field bus devices
on Metasys® systems, Facility Explorer systems, and
Smart Equipment rooftop units (RTUs) with unit control boards (UCBs). The MAP Gateway supports
Johnson Controls® branded Field Controllers, including
FEC, FAC, VMA, PCA, PCG, and PCV Series devices. MAP Gateway also supports the TEC3000 Series Thermostats.
The wireless connection on the MAP Gateway allows users of a supported mobile device to be up to 30 m (100 ft, line of sight) away indoors and up to 91 m (300 ft, line of sight) away outdoors. Power may be supplied via the SAB (sensor/actuator bus), the FCB (field controller bus), a supplied external power supply, or a micro USB port.
The MAP Gateway comes in two configurations: a portable configuration and a stationary configuration. Configuration is chosen at purchase, and the accessories shipped with the MAP Gateway depend on the configuration chosen.
When used as a portable device, the MAP Gateway can be attached to a lanyard. In this configuration, the MAP Gateway can be carried from site to site, depending on the needs and workflow of field personnel.
When used as a stationary device, the MAP Gateway can be permanently mounted directly to a wall or DIN rail using the supplied MAP Gateway mounting cradle.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.
RF Transmitters: Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
RF Exposure (OET Bulletin 65)
To comply with FCC RF exposure requirements for mobile transmitting devices, this transmitter should only be used or installed at locations where there is at least 20 cm separation distance between the antenna and all persons.
1Mobile Access Portal Gateway Installation Instructions

Canada

Industry Canada Statement The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industry Canada.

Installation

Observe the following guidelines:
Verify that all parts shipped with the MAP Gateway.
Keep the unit encased in the protective shell. If not protected by the enclosure in which it ships, the MAP Gateway may be subject to physical damage.

Parts Included (Portable Model)

MAP Gateway
Protective shell
6-pin RJ-12 connector cable
Lanyard
Installation Instructions
Mobile Access Portal Gateway Quick Start Guide (Part No. 24-10737-16)

Parts Included (Stationary Model)

MAP Gateway
Field bus adapter
Mounting bracket (with locking screw)
Installation Instructions
Mobile Access Portal Gateway Quick Start Guide (Part No. 24-10737-16)

Special Tools Needed

To use the MAP Gateway, you need a mobile device (tablet or smart phone) or computer (laptop or desktop) that supports Wi-Fi.
If the unit is permanently mounted to a vertical surface without a DIN rail, you need screws to mount the unit. The specific screw types depend upon the surface to which the unit is mounted. The screw holes on the MAP Gateway can accommodate M3.5 and #6 screws.

Portable Use

When used as a portable unit, the MAP Gateway should be housed in the supplied shell. During use, the unit can be temporarily hung on nearby equipment using the supplied lanyard.
Risk of Personal Injury. Do not wear or hold the MAP Gateway during use, and only use or install the MAP Gateway at locations where there is at least 20 cm between the built-in antenna and all persons. Failure to do so may result in minor or moderate personal injury.
MISE EN GARDE:
Risque de blessure. Ne pas porter ou soutenir l'MAP
Gateway durant son utilisation et utiliser ou installer l'MAP Gateway uniquement à un emplacement offrant une distance minimum de 20 cm entre l'antenne intégrée et toute personne. Le non-respect de cette précaution risque de provoquer des blessures légères ou de gravité modérée.
Observe the following guidelines when using a portable MAP Gateway:
Do not use the RJ-12 cable to support the weight of the MAP Gateway. Use the lanyard to support it.
Keep the MAP Gateway in the protective shell with which it ships. To insert the MAP Gateway into the shell, stretch the shell edges and slide the MAP Gateway unit into place (Figure 1). This shell protects the unit from drops up to 1.22 m (4 ft).
The MAP Gateway has not been designed for prolonged outdoor use. Leaving it in outdoor environments (such as inside rooftop units) may result in damage.
Objects (including ductwork, cabinets, doors, and glass) can impede the wireless signal. Minimize the number of objects between the connected computer or mobile device and the MAP Gateway. Use line of sight, if possible.
Metal objects (such as cabinet doors, enclosures, and pipes) and concrete objects (such as pillars, walls, and ceilings) may limit Wi-Fi service. To accommodate potential structural obstacles on site, the MAP Gateway can be mounted flat or on the side.
Use of the mounting bracket locking screw requires a T15 Torx driver.
2Mobile Access Portal Gateway Installation Instructions
Risk of Property Damage. Do not use the RJ-12 cable or any other field bus cable or electrical cable to support the weight of the MAP Gateway. Hanging the MAP Gateway from anything other than the supplied lanyard may result in damage to the product or peripheral equipment.
MISE EN GARDE:
Risque de dégâts matériels. Ne pas utiliser le câble
RJ-12 ou tout autre câble de bus de terrain ou câble électrique pour soutenir le poids de l'MAP Gateway. La suspension de l'MAP Gateway à tout autre élément que la longe fournie risque d'endommager le produit ou les équipements périphériques.
Figure 1: Portable MAP Gateway and Protective Shell

Location Considerations

Observe the following guidelines when mounting a MAP Gateway:
Mount the MAP Gateway in areas free of corrosive vapors and observe the environmental limitations listed in the Technical Specifications section of this document.
Objects (including ductwork, cabinets, doors, and glass) can impede the wireless signal. Minimize the number of objects between the connected computer or mobile device computer and the MAP Gateway. Use line of sight, if possible.
Metal objects (such as cabinet doors, enclosures, and pipes) and concrete objects (such as pillars, walls, and ceilings) may limit Wi-Fi service. To accommodate potential structural obstacles on site, the MAP Gateway can be mounted flush against the wall or perpendicular to it.
The MAP Gateway is not rated for outdoor mounting.

Locking Screw (Stationary Unit Only)

Regardless of which mounting configuration is used, a locking screw can be used to secure the unit into the mounting bracket. Do not overtighten the locking screw.

Mounting

Permanent

When used in a stationary configuration, the MAP Gateway is permanently mounted using a bracket which is provided with the stationary MAP Gateway. We recommend the following three ways to mount the unit: vertically (upright and flush), horizontally (sideways and flush), or perpendicularly (perpendicular to the wall). This flexibility allows the unit to be mounted in a way that minimizes spacial constraints and maximizes placement options for optimal wireless signal strength.
The unit should be mounted in such a way that labels can be read if they are visible. (For example, do not mount the unit upside down, which puts the labels upside down.)
Figure 2: Stationary Mounting with Locking Screw

Permanent Mounting Locations

The mounting bracket can be attached to a 35 mm (1-1/8 in.) DIN rail or a flat, vertical surface. Mounting the unit on a ceiling or in a way that positions the front of the unit facing down is not recommended.
3Mobile Access Portal Gateway Installation Instructions
Although the bracket has two mounting clips, only the bottom clip snaps inward. The top clip is permanently locked in the outward position, and it can be used as an additional hole for screwing the bracket into place. If not utilized for DIN rail or surface mounting, the top and bottom clips may be removed from the mounting bracket.
DIN Rail Mounting
To mount the bracket on a DIN rail:
1. Securely mount a 7.5 cm (3 in.) or longer section of 35 mm (1-1/8 in.) DIN rail in the required space.
2. On the bracket, pull the bottom mounting clip outward to the extended position.
Figure 3: Positioning the Bracket on a DIN Rail
Figure 4: Sample Permanent Mounting, Back-side
Screws
Figure 5: Sample Permanent Mounting, Side Screws
3. Hang the bracket on the DIN rail by the hooks at the top of the DIN rail channel (on the back of the bracket), and position the bracket snugly against the DIN rail.
4. Push the bottom mounting clip inward to secure the mounting bracket on the DIN rail.
5. Place the MAP Gateway unit in the bracket and secure it with the locking screw.
Wall Mounting
The bracket may be mounted using screw holes on the back of the bracket (so that the unit is flat on its back), using the screw holes on the side of the bracket, or using the holes in the DIN rail clips. This orientation helps accommodate on-site constraints. Screw hole locations are illustrated in Figure 7, Figure 8, and Figure 9.
The screw types needed to mount the unit depend upon the surface to which the unit is mounted. The screw holes on the MAP Gateway can accommodate M3.5 and #6 screws.
For information on location considerations for maximizing signal strength, see the Mounting section.
Figure 6: Sample Permanent Mounting, DIN Rail
Screw Holes
4Mobile Access Portal Gateway Installation Instructions
To mount the bracket on a flat surface (such as a wall):
1. Pull the bottom mounting clip outward to the extended position.
2. Mark mounting hole locations on the wall using the dimensions shown in Figure 7, Figure 8, or Figure 9; or hold the bracket against the wall and mark the hole locations through the mounting clips. Note: The position of the location holes depends on
whether the bracket is mounted horizontally or vertically.
Figure 7: Mounting Holes, Flat Mounting
Figure 8: Mounting Holes, Side Mounting
Note: The screw holes on the MAP Gateway can
accommodate M3.5 and #6 screws.
Note: The screw holes on the MAP Gateway can
accommodate M3.5 and #6 screws.
5Mobile Access Portal Gateway Installation Instructions
Loading...
+ 9 hidden pages