Johnson Controls M9203-xxx-2(Z) Series Data Sheet

Page 1
M9203-xxx-2(Z) Series Electric
Spring-Return Actuator
Electric Damper Actuators
Code No. LIT-1900682
M9203-xxx-2(Z) Series Electric Spring-Return Actuators
Description
The M9203-xxx-2(Z) Series Electric Spring-Return Actuators provide control of dampers in HVAC systems. All actuators in this series provide 27 lb·in (3 N·m) rated torque. A mechanical spring-return system provides rated torque with and without power applied to the actuator. The series includes the following control options:
• On/Off, 24 V, 85 to 264 VAC power
• On/Off and Floating Point, 24 V power
• Proportional, 24 V power, for 0(2) to 10 VDC or 0(4) to 20 mA Control Signal
These actuators are configured for direct mounting and do not require a damper linkage. Actuators can be mounted directly to a damper shaft from 1/4 to 1/2 in. (6 to 12 mm) diameter with a universal clamp. An accessory crankarm and remote mounting kit are available for applications where the actuator cannot be direct-coupled to the damper shaft. An optional line voltage auxiliary switch indicates an end-stop position or performs switching functions within the selected rotation range.
Refer to the M9203-xxx-2(Z) Series Electric
Spring-Return Actuators Product Bulletin
(LIT-12011674) for important product
application information.
Accessories and Replacement Parts
Code Number Description
1
DMPR-KC003 M9000-200 Commissioning Tool that Provides a Control Signal to Drive 24 V On/Off, Floating, Proportional, and/or Resistive Electric Actuators
M9000-321 Weather Shield Kit for Damper Application of M9203 and M9208 Series Electric Spring-Return Actuators (Quantity 1) M9000-341 Weather Shield Kit for VG1000 Series Ball Valve Application of M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring-Return
M9000-400 Jackshaft Linkage Adapter Kit (Quantity 1) M9000-560 Ball Valve Linkage Ki t for Applying M9104, M9203, and M9208 Series Electric Actuators to VG1000 Series Valves (Quantity 1) M9000-561 Thermal Barrier Kit for M9000-560 Ball Valve Linkage. Extends M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring-Return
M9000-604 Replacement Anti-Rotation Bracket Kit for M9203, M9208, M9210, and M9220 Series Electric Spring-Return Actuators (Quantity 1) M9000-606 Position Indicator for Damper Applications (Quantity 5) M9000-607 Position Indicator for VG1000 Series Ball Valve Applications (Quantity 5) M9203-100 Remote Mounting Kit with Crankarm Kit (Quantity 1) M9203-110 Universal Mounting Kit without Crankarm Kit (Quantity 1) M9203-115 Universal Mounting Kit with Crankarm Kit (Quantity 1) M9203-150 Crankarm Kit (Quantity 1) M9203-250 Remote Mounting Kit with Crankarm Kit and Damper Linkage for D1300 Dampers (Quantity 1) M9203-601 Replacement Standard Couple r Kit (with Retainer) for Mounting M9203 Series Electric Spr i ng-Return Actuators (Quantity 1) M9203-602 Replacement Retainer for M9203 Series Electric Spring-Return Actuators (Quantity 5) M9203-603 Adjustable Stop Kit fo r M9203 Series Electric Spring-Return Actuators (Quantity 1)
1. Furnished with the damper and may be ordered separately
7 in. (178 mm) Blade Pin Extension (without Bracket) for Johnson Controls Direct-Mount Damper Applicat ions (Quantity 1)
(Quantity 1)
Actuators (Quantity 1)
Actuators Applications to Include Low-Pressure Steam (Quantity 1)
Features
• 27 lb·in (3 N·m) rated torque
• direct-coupled design
• reversible mounting
• electronic stall detection
• double-insulated construction
• microprocessor-controlled brushless DC motor (-AGx and -GGx types)
• external mode selection switch (-AGx and -GGx types)
• integral cables with colored and numbered conductors
• integral 1/2 in. (13 mm) threaded conduit connectors
• optional integrated auxiliary switch
• plenum rated models
• override control (proportional models only)
• Underwriters Laboratories Inc.® (UL), CE, and C-Tick compliance
• manufactured under International Standards Organization (ISO) 9001 quality control standards
• 5-year warranty
Electric Damper ActuatorsElectric Damper ActuatorsElectric Damper ActuatorsElectric Damper Actuators
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–37
Page 2
Electric Damper Actuators
M9203-xxx-2(Z) Series Electric Spring-Return Actuators (Continued)
Selection Chart
Code Number Rotation Time
Electric Damper Actuators
Electric Damper ActuatorsElectric Damper Actuators
M9203-AGA-2 150 < 25 6 4.7 (2.7) ■■ M9203-AGB-2 150 < 25 6 4.7 (2.7) ■■ M9203-AGA-2Z 90 < 25 6 5.1 (2.8) ■■ M9203-AGB-2Z 90 < 25 6 5.1 (2.8) ■■ M9203-BGA-2 < 75 < 25 6 5.0 (2.5) ■■ M9203-BGB-2 < 75 < 25 6 5.0 (2.5) ■■ M9203-BUA-2 < 75 < 25 0.06 (0.02) ■■ M9203-BUB-2 < 75 < 25 0.06 (0.02) ■■ M9203-BUA-2Z < 30 < 25 0.08 (0.02) ■■ M9203-BUB-2Z < 30 < 25 0.08 (0.02) ■■ M9203-GGA-2 15 0 < 25 6 4.7 (2.7) ■■ M9203-GGB-2 15 0 < 25 6 4.7 (2.7) ■■ ■■ ■ M9203-GGA-2Z 90 < 25 6 5.1 (2.8) ■■ M9203-GGB-2Z 90 < 25 6 5.1 (2.8) ■■ ■■ ■
(Seconds) for 90°
Power On — Running
Power Off — Spring Return
Power Requirements
24 VAC +/- 20%, VDC +/-10%
Electric Damper Actuators
Power Consumption Input Signal Position
85 to 264 VAC
VA Rating, Transformer Sizing
VA: Running (Holding)
Amperage: Running (Holding)
On/Off
On/Off and Floating Point
0(2) to 10 VDC
0(4) to 20 mA (with 500 Ohm Resistor)
Feedback
0(2) to 10 VDC
Auxiliary Switch
1 SPDT, 5.0 A (2.9 A Inductive) at 240 V
Electrical Connection
48 in. (1.2 m) 18 AWG Appliance Cable
120 in. (3.05 m) 19 AWG Plenum Cable
1/2 in. (13 mm) Conduit Connectors
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–38
Page 3
Electric Damper Actuators
M9203-xxx-2(Z) Series Electric Spring-Return Actuators (Continued)
Technical Specifications
M9203-GGx-2(Z) Series Proportional Electric Spring-Return Actuator (Part 1 of 2)
Power Requirements -GGx-2 Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV)
-GGx-2Z Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV)
Input Signal / Adjustments Factory Set at DC 0 to 10 V, CW Rotation with Signal Increase
Control Input Impedance Voltage Input: 100,000 Ohms
Feedback Signal DC 0 (2) to 10 V for Desired Rotation Range up to 95°
Auxiliary Switch Rating
Spring Return Direction is Selectable with Mounting Position of Actuator:
Rated Torque Power On (Running) 27 lb·in (3 N·m) All Operating Temperatures
Rotation Range Maximum Full Stroke: 95°
Rotation Time for 90 Degrees of Travel
-xxB Models One Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver Contacts:
Power Off (Spring Returning)
Power On (Running)
-GGx-2 Models
Power On (Running)
-GGx-2Z Models
(Europe), 4.7 VA Running, 2.7 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.8 W Running, 1 W Holding
Position Minimum Transformer Size: 6 VA per Actuator
(Europe), 5.1 VA Running, 2.8 VA Holding Position DC 24 V (DC 19.2 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.9 W Running, 1.1 W
Holding Position Minimum Transformer Size: 6 VA per Actuator
Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with Field Furnished 500 Ohm, 0.25 W Minimum Resistor Switch Selectable Direct or Reverse Action with Signal Increase
Current Input: 500 Ohms with Field Furnished 500 Ohm Resistor
Corresponds to Rotation Limits, 0.5 mA at 10 V Maximum
AC 24 V, 50 VA Pilot Duty AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Actuator Face Labeled A is away from Damper or Valve: CCW Spring Return Actuator Face Labeled B is away from Damper or Valve: CW Spring Return
27 lb·in (3 N·m) All Operating Temperatures
Adjustable Stop: 35° to 95° Maximum Position 150 Seconds Constant for 0 to 27 lb·in (3 N·m) Load, at All Operating Conditions
90 Seconds Constant for 0 to 27 lb·in (3 N·m) Load, at All Operating Conditions
Electric Damper ActuatorsElectric Damper ActuatorsElectric Damper ActuatorsElectric Damper Actuators
Power Off (Spring Returning)
Life Cycles 60,000 Full Stroke Cycles with 27 lb·in (3 N·m) Load
Audible Noise Rating Power On (Running)
Electrical Connections -GGA-2(Z) Models 120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG
Conduit Connections Integral 1/2 in. (13 mm) Threaded Conduit Connectors Mechanical
Connections
Enclosure Rating NEMA 2 (IP54) for All Mounting Orientations Ambient
Conditions
Dimensions 6.38 x 3.23 x 2.26 in. (162 x 82 x 57.5 mm)
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
-GGx-2 Models
Power On (Running)
-GGx-2Z Models
Power On (Holding) < 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off (Spring Returning)
Auxiliary Switch (-xxB Models)
Round Shafts Range of Sizes: 1/4 to 1/2 in. (6 to 12 mm) Square Shafts Range of Sizes: 1/4 to 5/16 in. (6 to 8 mm)
Standard Operating -22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing Storage -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
12 to 17 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature 16 Seconds Nominal at Full Rated Load 22 Seconds Maximum with 27 lb·in (3 N·m) Load, at -22°F (-30°C)
1,500,000 Repositions with 27 lb·in (3 N·m) Load < 28 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
< 37 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
< 56 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
(0.75 mm²) Conductors and 0.25 in. (6 mm) Ferrule Ends 48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG
(0.85 mm²) Conductors and 0.25 in. (6 mm) Ferrule Ends
V–39
Page 4
Electric Damper Actuators
M9203-xxx-2(Z) Series Electric Spring-Return Actuators (Continued)
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for
Electric Damper Actuators
Electric Damper ActuatorsElectric Damper Actuators
Shipping Weight -GGA Models: 2.0 lb (0.9 kg)
Power Requirements
Input Signal -AGx-2(Z) Models AC 19.2 to 28.8 V at 50/60 Hz or DC 24 V +20%/-10%
Control Input Impedance -AGx-2(Z) Models 4,700 Ohms Auxiliary Switch
Rating
Spring Return Direction is Selectable with Mounting Position of Actuator:
Rated Torque Power On (Running) 27 lb·in (3 N·m) All Operating Temperatures
Rotation Range Maximum Full Stroke: 95°
Rotation Time for 90 Degrees of Travel
Electric Damper Actuators
M9203-GGx-2(Z) Series Proportional Electric Spring-Return Actuator (Part 2 of 2)
Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric Actuators. (Models: All)
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
Europe CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
Australia and New Zealand
M9203-AGx-2(Z) Series On/Off and Floating Point Control Electric Spring-Return Actuator (Part 1 of 2)
-AGx-2 Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV)
-AGx-2Z Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV)
-xxB Models One Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver Contacts:
Power Off (Spring Returning)
Power On (Running)
-AGx-2 Models
Power On (Running)
-AGx-2Z Models
Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24- 93 Temperat ure Indicating and Regulating Equipment. (Models: All)
requirements and other relevant provisions of the EMCDirect ive 2004/108/ EC and Lo w Voltage Directive 2006/95/EC.
C-Tick Mark, Australia/NZ Emissions Compliant. (Models: All)
-GGB Models: 2.4 lb (1.1 kg)
(Europe), 4.7 VA Running, 2.7 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.8 W Running, 1 W Holding
Position Minimum Transformer Size: 6 VA per Actuator
(Europe), 5.1 VA Running, 2.8 VA Holding Position DC 24 V (DC 19.2 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.9 W Running, 1.1 W Holding Position
Minimum Transformer Size: 6 VA per Actuator
Class 2 (North America) or SELV (Europe) Minimum Pulse Width: 500 ms
AC 24 V, 50 VA Pilot Duty AC 120 V, 5.8 A Resistive, 1/4 hp, 275 V A Pilot Duty AC 240 V, 5.0 A Resistive, 1/4 hp, 275 V A Pilot Duty
Actuator Face Labeled A is away from Damper or Valve: CCW Spring Return Actuator Face Labeled B is away from Damper or Valve: CW Spring Return
27 lb·in (3 N·m) All Operating Temperatures
Adjustable Stop: 35 to 95° Maximum Position 150 Seconds Constant for 0 to 27 lb·in (3 N·m) Load, at All Operating Conditions
90 Seconds Constant for 0 to 27 lb·in (3 N·m) Load, at All Operating Conditions
Power Off (Spring Returning)
Life Cycles 60,000 Full Stroke Cycles with 27 lb·in (3 N·m) Load
Audible Noise Rating Power On (Running)
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
-AGx-2 Models
Power On (Running)
-AGx-2Z Models
Power On (Holding) < 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off (Spring Returning)
12 to 17 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature 16 Seconds Nominal at Full Rated Load 22 Seconds Maximum with 27 lb·in (3 N·m) Load at -22°F (-30°C)
1,500,000 Repositions with 27 lb·in (3 N·m) Load < 28 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
< 37 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
< 56 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
V–40
Page 5
Electric Damper Actuators
M9203-xxx-2(Z) Series Electric Spring-Return Actuators (Continued)
M9203-AGx-2(Z) Series On/Off and Floating Point Control Electric Spring-Return Actuator (Part 2 of 2)
Electrical Connections -AGA-2(Z) Models 120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG (0.75 mm²) Conductors and
Auxiliary Switch (-xxB Models)
Conduit Connections Integral 1/2 in. (13 mm) Threaded Conduit Connectors Mechanical
Connections
Enclosure Rating NEMA 2 (IP54) for All Mounting Orientations Ambient
Conditions
Dimensions 6.38 x 3.23 x 2.26 in. (162 x 82 x 57.5 mm) Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for
Round Shafts Range of Sizes: 1/4 to 1/2 in. (6 to 12 mm) Square Shafts Range of Sizes: 1/4 to 5/16 in. (6 to 8 mm)
Standard Operating -22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing Storage -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
Europe CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
Australia and New Zealand
0.25 in. (6 mm) Ferrule Ends 48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm²) Conductors and 0.25 in.
(6 mm) Ferrule Ends
Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric Actuators. (Models: All)
Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment (Models: All)
requirements and other relevant provisions of the EMCDirective 2004/108/ EC and Low Voltage Directive 2006/95/EC.
C-Tick Mark, Australia/NZ Emissions Compliant (Models: All)
Electric Damper ActuatorsElectric Damper ActuatorsElectric Damper ActuatorsElectric Damper Actuators
Shipping Weight -AGA Models: 2.0 lb (0.9 kg)
-AGB Models: 2.4 lb (1.1 kg)
M9203-Bxx-2(Z) Series On/Off Electric Spring-Return Actuators (Part 1 of 2)
Power Requirements -BGx-2 Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safet y Extra-Lo w Voltage (SELV)
-BUx-2 Models AC 100 to 240 V (AC 85 V to 264 V) at 50/60 Hz: 0.06 A Running, 0.02 A Holding Position
-BUx-2Z Models AC 100 to 240 V (AC 85 V to 264 V) at 50/60 Hz: 0.08 A Running, 0.02 A Holding Position
Auxiliary Switch Rating -xxB Models One Single-Pole, Double-Throw (SPDT), Double-I nsulated Switch with Silver Contacts:
Spring Return Direction is Selectable with Mounting Positi on of Actuator:
Rated Torque Power On (Running) 27 lb·in (3 N·m) All Operating Temperatures
Power Off (Spring Returning)
Rotation Range Maximum Full Stroke: 95°
Rotation Time for 90 Degrees of Travel
Life Cycles 60,000 Full-Stroke Cycles with 27 lb·in (3 N·m) Load
Power On (Running)
-Bxx-2 Models Power On (Running)
-BUx-2Z Models Power Off
(Spring Returning)
(Europe), 5 VA Running, 1.6 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe), 2.8 W Running, 0.8 W
Holding Position Minimum Transformer Size: 6 VA per Actuator
AC 24 V ,50VA Pilot Duty AC 120 V,5.8 A Resistive, 1/4 hp, 275 VAPilotDuty AC 240 V,5.0 A Resistive, 1/4 hp, 275 VAPilotDuty
Actuator Side A is away from Damper or Valve: CCWSpring Return Actuator Side B is away from Damper or Valve: CWSpring Return
27 lb·in (3 N·m) All Operating Temperatures
Adjustable Stop: 35to95° MaximumPosition 53 to 71 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature
60 Seconds Nominal at Full Rated Load (0.25 rpm) 24 to 28 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature
27 Seconds Nominal at Full Rated Load (0.5 rpm) 19 to 23 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature
22 Seconds Nominal at Full Rated Load 28 Seconds Maximum with 27 lb·in (3 N·m) Load at -22°F (-30°C)
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–41
Page 6
Electric Damper Actuators
M9203-xxx-2(Z) Series Electric Spring-Return Actuators (Continued)
Audible Noise Rating Power On (Running)
Electric Damper Actuators
Electric Damper ActuatorsElectric Damper Actuators
Electrical Connections Actuator (All Models) 48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm²) Conductors and 0.25in.
Conduit Connections Integral 1/2 in. (13 mm) Threaded Conduit Connectors Mechanical Connections Round Shafts Range of Sizes: 1/4 to 1/2 in. (6 to 12 mm)
Enclosure Rating NEMA 2 (IP54) for All Mounting Orientations Ambient Conditions Standard Operating -22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing
Dimensions 6.38 x 3.23 x 2.26 in. (162 x 82 x 57.5 mm) Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for
Electric Damper Actuators
M9203-Bxx-2(Z) Series On/Off Electric Spring-Return Actuators (Part 2 of 2)
-Bxx-2 Models
Power On (Running)
-BUx-2Z Models
Power On (Holding) < 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off (Spring Returning)
Auxiliary Switch (-xxB Models)
Square Shafts Range of Sizes: 1/4 to 5/16 in. (6 to 8 mm)
Storage -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
Europe CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
Australia and New Zealand
< 36 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
< 45 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
< 51 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
(6 mm) Ferrule Ends 48 in. (1.2 m) UL 758 TypeAWM Halogen-Free Cable with 18 AWG (0.85mm²) Condu ct ors and 0. 25in .
(6 mm) Ferrule Ends
Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric Actuators. (Models: All)
Electrical Controls for Household and Similar Use; and CSA C22.2 No.24-93 Temperature Indicating and Regulating Equipment (Models: All).
requirements and other relevant provisions of the EMCDirective 2004/108/EC and Low Voltage Directive 2006/95/EC.
C-Tick Mark, Australia/NZ Emissions Compliant (Models: All)
Shipping Weight -BxA Models: 2.0 lb (0.9 kg)
-BxB Models: 2.4lb(1.1kg)
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–42
Loading...