Johnson Controls JC-VSD FP Series II Drives Catalog Page

Code No. LIT-1900957
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
1
Issued July 1, 2015
JC-VSD FP Series
II Drives
Description
The Johnson Controls® VSD FP Series II provides the advanced technology and features of the Johnson Controls VSD Series II with a Disconnect or Bypass in a factory mount option. Either option is available in NEMA 1 galvanized steel or NEMA 3R painted product. The FP Series II IntelliDisconnect comes with an enclosed disconnect (fused or non-fused) and door mounted operator. The FP Series II IntelliPass offers a fused or non-fused disconnect switch, a two contactor bypass design, and door mounted controls.
Refer to the JC-VSD FP Series II Drives Product Bulletin (LIT-12012081) for important product information.
Features
Network Connectivity for Drive and Bypass (BACnet®, SA Bus, N2, and LON) — allows for compatibility with current and future Johnson Controls network architecture
Software parameters that utilize engineering units common to the HVAC industry — allow for quick and easy startup using the onboard startup wizard with engineering units transmitted over a communications bus
Johnson Controls Support That Includes Ordering, Estimating, and Project Management Tools: Advanced Order Management System (AOMS), Advanced Installation Management (AIM) Tools ­QuickLIT, Catalog, PRESTO, and STORE— allows users to easily identify and order products
Closed-Loop Control Programmed with Engineering Units for Specific HVAC Applications: pump— provides software parameters using engineering units common to the HVAC industry
Standard TYPE 12 Keypad on all Drives with Copy and Paste Function; Capable of Monitoring Three Parameters Simultaneously — allows easy transfer of parameter settings from one drive to another drive
Drive Programming Capability Using Auxiliary — allows variable speed drive programming (including network communication validation) prior to wiring 3-phase power to the drive
Standard, PID, or multi-
24 V Power
Supply
(VS-AUX24V)
Additional FP Series II Features
NEMA 1 or NEMA 3R designs
Temperature range of -10°C to 40°C (14°
to 104°F)
OSHPD Certified
Plenum rated
Fused or Non-fused disconnect designs
with handle lockable in Off position
EMI/RFI Filters standard on all drives
I/O and communication cards provide
plug-and-play functionality
Active Energy Control on-board all drives to minimize energy losses and provide industry leading efficiency
Real Time Clock supporting calendaring and PLC functionality
Thin metal capacitor design for efficient drive operation and extended life
Standard DC link choke wit h MOVs for enhanced transient and harmonic distortion protection
Top and bottom conduit entry for ease of installation
Copy and paste keypad function that allows you to transfer parameter settings from one drive to another
Keypad that displays up to nine monitored parameters simultaneously
Standard TYPE12 keypad on all drives
Simplified operating menu allows for
quick programming changes
Anti-trip DC bus regulation
Onboard RS-485 Communications
(BACnet, N2, Modbus®)
Onboard Ethernet-based communications (BACnet/IP, Modbus/TCP)
SA bus communication factory installed option
Standard I/O: 6DI, 2AI, 1 AO , 1 Form C RO (NO/NC),
Short circuit withstand rating of 100kAIC (additional fuses required for non-fused disconnect designs)
Input surge protection against voltage spikes (varistor input)
Hard-wired external/damper interlock
Accommodates a wide variety of
expander boards and adapter boards
Control logic can be powered from an external auxiliary control panel
Robust steel enclosure for simple installation
FP Series II Drive with
IntelliPass and
IntelliDisconnect
Additional FP Series II IntelliPass Only Features
HAND/OFF/AUTO and DRIVE/OFF/BYPASS sel ect or on keypad that simplifies control
2 contactor bypass with drive isolation switch
Control power transformer with primary and secondary fusing
Bypass can be controlled mechanically, electronically, and via SA Bus
Repair Information
If the FP Series II Drive fails to operate within its specifications, contact the nearest Johnson Controls representative.
Code No. LIT-1900957
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
2
460V 3-Phase (YK pr o d uct )
208V, 230V 3-Phase (YK product )
200-240V 3-Phase (YM product)
380-480V 3-Phase (YM product)
1 = 208V (YK only) 6 = 200-240V (YM only)
Base Product
Amps, kW, Hp
Voltage
Enclosure Style
Separator
Options
1 = NEMA Type 1
1 = Non-fused Intell iDi sco nnect 3 = IntelliPass w/ Fused Disconnect
1 = 230V 3-phase Int ell iP ass only
B = Rev 2 (Americas)
00000 = No options
YK = VSD Series II Base Drive
Catalog Number
Y
K 4 D
8 4 1
1
B
0
0
0
0
0
-
JC-VSD FP Series II Drives (Continued)
Catalog Number Selection
Issued July 1, 2015
YM = VSM Drive
4D8 = 4.8 Amp, 0.75kW (1 Hp) 8D0 = 8.0 Amp, 1.5 kW (2 Hp) 011 = 11 Amp, 2.2 kW (3 Hp) 016 = 16 Amp, 4.0 kW (5 Hp) 018 = 18 Amp, 4.0 kW (5 Hp) 024 = 24 Amp, 5.5 kW (7.5 Hp) 025 = 25 Amp, 5.5 kW (7.5 Hp) 031 = 31 Amp, 7.5 kW (10 Hp) 048 = 48 Amp, 11 kW (15 Hp) 062 = 62 Amp, 15 kW (20 Hp) 070 = 70 Amp, 18.5 kW (25 Hp) 075 = 75 Amp, 18.5 kW (25 Hp) 088 = 88 Amp, 22 kW (30 Hp) 115 = 115 Amp, 37 kW (40 Hp) 140 = 140 Amp, 37 kW (40 Hp) 150 = 150 Amp, 45 kW (50 Hp) 170 = 170 Amp, 45 kW (50 Hp)
2D8 = 2.8 Amp, 0.37 kW (0.5 Hp) 3D7 = 3.7 Amp, 0.55 kW (0.75 Hp) 4D8 = 4.8 Amp, 0.75 kW (1 Hp) 7D0 = 7.0 Amp, 1.1 kW (1.5 Hp)
1
1
1
1
1
2D4 = 2.4 Amp, 1.1 kW (1 Hp) 3D4 = 3.4 Amp, 1.1 kW (1 Hp) 4D0 = 4.0 Amp, 1.5 kW (2 Hp) 4D8 = 4.8 Amp, 1.5 kW (2 Hp) 5D6 = 5.6 Amp, 2.2 kW (3 Hp) 9D0 = 9.0 Amp, 4.0 kW (5 Hp) 9D6 = 9.6 Amp, 4.0 kW (5 Hp) 012 = 12 Amp, 5.5 kW (7.5 Hp) 016 = 16 Amp, 7.5 kW (10 Hp) 023 = 23 Amp, 11 kW (15 Hp) 031 = 31 Amp, 15 kW (20 Hp) 038 = 38 Amp, 18.5 kW (25 Hp) 046 = 46 Amp, 22 kW (30 Hp) 061 = 61 Amp, 30 kW (40 Hp) 070 = 70 Amp, 30 kW (50 Hp) 072 = 72 Amp, 37 kW (50 Hp) 080 = 80 Amp, 45 kW (60 Hp) 087 = 87 Amp, 45 kW (60 Hp) 105 = 105 Amp, 55 kW (75 Hp) 140 = 140 Amp, 75 kW (100 Hp) 170 = 170 Amp, 90 kW (125 Hp)
1D3 = 1.3 Amp, 0.37 kW (0.5 Hp) 1D9 = 1.9 Amp, 0.55 kW (0.75 Hp) 2D4 = 2.4 Amp, 0.75 kW (1 Hp) 3D3 = 3.3 Amp, 1.1 kW (1.5 Hp) 4D3 = 4.3 Amp, 1.5 kW (2 Hp)
2
2
2
2
2
2
2 = 230V (YK only) 7 = 380-480V (YM only) 4 = 460V (YK only)
2 = NEMA Type 3R (YK only)
2 = Fused IntelliDisconnect3 4 = IntelliPass w/ Non-fused Disconnect
2 = 460V 3-phase Int ell iP ass only 3 = Fused Disconnect is only option for YM product
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
3
FP Series II Drives (Part 2 of 2)
Analog Output
0 to 10 V, 0 (4) to 20 mA; RL max. 500 Ohms;
Relay Outputs
3 Programmable, 2 Form C, 1 Form A Relay
Hard-Wired Jumper
Between Terminal 6 and 10 (Factory Default)
DIP Switch Setting
RS485 = Off, AO1 = Current, AI2 = Current
Overcurrent Protection
Yes
Overvoltage Protection
Yes
Undervoltage Protection
Yes
DC Bus Regulation
Yes (Accelerates or Decelerates the Load)
Earth Fault Protection
Yes, in case of earth fault in motor or motor cable,
Input Phase Supervision
Yes, trips if any of the input phases are missing
Motor Phase
Yes, trips if any of the output phases are missing
Overtemperature
Yes
Motor Overload
Yes
Motor Stall Protection
Yes
Motor Underload
Yes
Short Circuit Protection
Yes
Surge Protection
Yes (Varistor Input)
Conformed Coated
Yes (Prevents Corrosion)
OHSPD Special Seismic
Yes
Compliance
UL Listed File No 508C, cUL Listed
Safety – EN 61800-5-1
Warranty
30 Months Standard Terms;
Reliability
500,000 hours Mean Time Between Failures
Weight
Depends on configuration and horsepower. Refer
Horsepower/Amps/kW
208V: 1-50 Hp, 4.8-170 A, 0.75 to 45 kW
230V: 1-50 Hp, 4.8- 170 A, 0.75 – 45 kW
200-240V: 0.5-1.5 Hp, 2.8-7 A, 0.37-1.1 kW
380-480V: 0.5-2 Hp, 1.3-4.3 A, 0.37-1.5 kW
460V: 1-125 Hp, 3.4-170 A, 1.1-90 kW
FP Series II Drives (Part 1 of 2)
Input Voltage (Vin)
208, 230, 460 VAC -10%/+10%
Input Frequency (fin)
50/60 Hz (Variation Up to 47-66 Hz)
Connection to Power
Once Per Minute or Less (Typical Operation)
Current Withstand
15k AIC
Output Voltage
0 to V
Line Voltage In
Continuous Output
Ambient Temperature Maximum 104°F (40°C),
Overload Current
110% (1 min./10 min.)
Initial Output Current
150% for 2 Seconds
Output Frequency
-320 to 320 Hz
Frequency Resolution
0.01 Hz
Control Method
Frequency Control (V/f) Open Loop Sensorless
Switching Frequency
1.5 to 10 kHz; default = 6 kHz
Frequency Reference
Analog Input: Resolution 0.1% (10 bit),
Field Weakening Point
8 to 320 Hz
Acceleration Time
0.1 to 3,000 s
Deceleration Time
0.1 to 3,000 s
Braking Torque
DC Brake: 30% x Tn (without Brake Option)
Ambient Operating
14 (No Frost) to 104°F (-10 to 40°C)
Storage Temperature
-40 to 158°F (-40 to 70°C)
Relative Humidity
0 to 95% RH, Noncondensing, Noncorrosive,
Air Quality
Chemical Vapors: IEC 60721-3-3, Unit In
Altitude
100% Load Capacity (No Derating) Up to 3,280 ft
Vibration
EN 61800-5-1, EN 60068-2-6; 5 to 150 Hz,
Shock
EN 61800-5-1, EN 6068-2-27 United Parcel
Enclosure Class
NEMA Type 1 or NEMA Type 3R
EMC (at default settings)
Immunity: Fulfills all Electromagnetic
C2)
Emissions
EMC Level Dependent: +EMC 2: EN 61800-3
Analog Input Voltage
0 to 10 V, R = 200 kOhms Differential Resolution
Analog Input Current
0 (4) to 20 mA; Ri - 250 Ohms Differential
Digital Inputs (6)
Positive or Negative Logic; 18 to 30 VDC
Auxiliary Voltage
24 V ±10%, Maximum 100 mA
Output Reference
10 V +3%, Maximum Load 10 mA
JC-VSD FP Series II Drives(Conti nu ed)
Technical Specifications
Rating
Current
Temperature
in
Overload 1.1 x IL (1 min./10 min.)
Vector Control
Accuracy +/-1% Panel Reference: Resolution 0.01 Hz
De-rating to operate at 122°F (50°C)
No Dripping Water
Operation, Class 3C2; Mechanical Particles: IEC 60721-3-3, Unit In Operation, Class 3S2
Default
Anti-trip
Supervision
Protection
Protection
Protection
(Varnished) Board
Certification Pre-Approval
Resolution 10 bit; Accuracy ± 2%, Dip Switch Selection (Voltage/Current)
Outputs Switching Capacity: 24 VDC/8 A, 250 VAC/8 A, 125 VDC/0.4 A
AI1 = Voltage
only the frequency converter is protected.
Voltage
(1,000 m); 1% Derating for Each 328 ft (100 m) Above 3,280 ft (1,000 m); Maximum 9,842 ft (3,000 m)
Displacement Amplitude 1 mm (Peak) at 5 to 15.8 Hz, Max. Acceleration Amplitude 1 G at 15.8 to 150 Hz, OSHPD Seismic Certi fi e d
Service® (UPS) Drop Test (for Applicable UPS Weights) Storage and Shipping: max. 15 G, 11 ms(in package)
Compatibility (EMC) Immunity Requirements; Emissions: EN 61800-3 (2004), LEVEL H (EMC
(2004) Category C2, Delivered with Class C2 EMC filtering as Default
0.1%; Accuracy ±1%, Dip Switch Selection (Voltage/Current)
39 Months with Certified Startup
(MTBF)
to JCI FP Series Drives Product Bulletin (LIT-
12012081) for more information.