Johnson Controls JC-VSD FP Series II Drives Data Sheet

JC-VSD FP Series II Drives
Features
Benefits
Network Connectivity for Drive and Bypass
Allows for compatibility with current and future Johnson Controls
Software Parameters That Utilize Engineering
Allow for quick and easy startup using the onboard startup wizard with
Johnson Controls Support That Includes
Allows users to easily identify and order products.
Closed-Loop Control Programmed with
Provides software parameters using engineering units common to the
Standard TYPE 12 Keypad on all Drives with
Allows easy transfer of parameter settings from one drive to another Drive Programming Capability Using Auxiliary
Allows variable speed drive programm ing (including network
Product Bulletin
The Johnson Controls® VSD FP Series II provides the advanced technology and features of the Johnson Controls VSD Series II with a Disconnect or Bypass in a factory mount option. Either opt ion is available in NEMA 1 galvanized steel or NEMA 3R painted product. The FP Series II IntelliDisconnect comes with an enclosed disconnect (fused or non­fused) and door mounted operator. The FP Series II IntelliPass offers a fused or non-fused disconnect switch, a two contactor bypass design, and door mounted controls.
Table 1: Features and Benefits
Refer to the QuickLIT website for the most up-to-date version of this document.
Code No. LIT-12012081
Issued July 1,
Figure 1: FP Series II Drives
2015
(BACnet®, SA Bus, N2, and LON)
Units Common to the HVAC Industry
Ordering, Estimating, and Project Management Tools: Advanced Order Management System (AOMS), Advanced Installation Management (AIM) Tools - QuickLIT, Catalog, PRESTO, and STORE
Engineering Units for Specific HVAC Applications: Standard, PID, or multi-pump
Copy and Paste Function; Capable of Monitoring Three Parameters Simultaneously
24 V Power Supply (VS-AUX24V)
network architecture.
engineering units transmitted over a communications bus.
HVAC industry.
drive.
communication validation) prior to wiring 3-phase power to the drive.
JC-VSD FP Series II Drives Product Bulletin 1
2
VSD FP Series II Drives Product Bulletin
Additional FP Series II Features
IMPORTANT: Use this FP Series II Drive only
NEMA 1 or NEMA 3R designs
Temperature range of -10°C to 40°C (14° to 104°F)
OSHPD Certified
Plenum rated
Fused or Non-fused disconnect designs with handle lockable in Off position
EMI/RFI Filters standard on all drives
I/O and communication cards provide plug-and-play functionality
Active Energy Control on-board all drives to minimize energy losses and provide industry leading efficiency
Real Time Clock supporting calendaring and PLC functionality
Thin metal capacitor design for efficient drive operation and extended life
Standard DC link choke and MOVs for enhanced transient and harmonic distortion protection
Top and bottom conduit entry for ease of installation
Copy and paste keypad function that allows you to transfer parameter settings from one drive to another
Keypad that displays up to nine monitored parameters simultaneously
Standard TYPE12 keypad on all drives
Simplified operating menu allows for quick programming changes
Anti-trip DC bus regulation
Onboard RS-485 Communications (BACnet, N2, Modbus®)
Onboard Ethernet-based communications (BACnet/IP, Modbus/TCP)
SA Bus factory installed communications option
Standard I/O: 6DI, 2AI, 1AO, 1 Form C RO (NO/NC),
Short circuit withstand rating of 15kAIC (additional fuses required for non-fused disconnect designs)
Input surge protection against voltage spikes (varistor input)
Hard-wired external/damper interlock
Accommodates a wide variety of expander boards and adapter boards
Control logic can be powered from an external auxiliary control panel
Robust steel enclosure for simple installation
Additional FP Series II IntelliPass Only Features
• HAND/OFF/AUTO and DRIVE/OFF/BYPASS selector on keypad that simplifies control
• 2 contactor bypass with drive isolation switch
• Control power transformer with primary and secondary fusing
• Bypass can be controlled mechanically, electronically, and via SA Bus
as an operating control. Where failure or malfunction of the Series II open drive could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the Series II open drive.
VSD FP Series II Drives Product Bulletin
3
Catalog Number Selection
460V 3-Phase (YK pr o d uct )
208V, 230V 3-Phase (YK product )
200-240V 3-Phase (YM product)
380-480V 3-Phase (YM product)
1 = 208V (YK only) 6 = 200-240V (YM only) 4 = 460V (YK only)
Base Product
Amps, kW, Hp
Voltage
Enclosure Style
Separator
Options
1 = NEMA Type 1
1 = Non-fused Intell iDi sco nnect 3 = IntelliPass w/ Fused Disconnect
1 = 230V 3-phase Bypass only
B = Rev 2 (Americas)
00000 = No options
YK = VSD Series II Base Drive YM = VSM Drive
Catalog Number
Y
K 4 D
8
4
1
1
B
0
0
0
0
VSD Series II Enclosed Drives Selection Chart
4D8 = 4.8 Amp, 0.75kW (1 Hp) 8D0 = 8.0 Amp, 1.5 kW (2 Hp) 011 = 11 Amp, 2.2 kW (3 Hp) 016 = 16 Amp, 4.0 kW (5 Hp) 018 = 18 Amp, 4.0 kW (5 Hp) 024 = 24 Amp, 5.5 kW (7.5 Hp) 025 = 25 Amp, 5.5 kW (7.5 Hp) 031 = 31 Amp, 7.5 kW (10 Hp) 048 = 48 Amp, 11 kW (15 Hp) 062 = 62 Amp, 15 kW (20 Hp) 070 = 70 Amp, 18.5 kW (25 Hp) 075 = 75 Amp, 18.5 kW (25 Hp) 088 = 88 Amp, 22 kW (30 Hp) 115 = 115 Amp, 37 kW (40 Hp) 140 = 140 Amp, 37 kW (40 Hp) 150 = 150 Amp, 45 kW (50 Hp) 170 = 170 Amp, 45 kW (50 Hp)
2D8 = 2.8 Amp, 0.37 kW (0.5 Hp) 3D7 = 3.7 Amp, 0.55 kW (0.75 Hp) 4D8 = 4.8 Amp, 0.75 kW (1 Hp) 7D0 = 7.0 Amp, 1.1 kW (1.5 Hp)
2 = 230V (YK only) 7 = 380-480V (YM only)
1
1
1
1
1
2D4 = 2.4 Amp, 1.1 kW (1 Hp) 3D4 = 3.4 Amp, 1.1 kW (1 Hp) 4D0 = 4.0 Amp, 1.5 kW (2 Hp) 4D8 = 4.8 Amp, 1.5 kW (2 Hp) 5D6 = 5.6 Amp, 2.2 kW (3 Hp) 9D0 = 9.0 Amp, 4.0 kW (5 Hp) 9D6 = 9.6 Amp, 4.0 kW (5 Hp) 012 = 12 Amp, 5.5 kW (7.5 Hp) 016 = 16 Amp, 7.5 kW (10 Hp) 023 = 23 Amp, 11 kW (15 Hp) 031 = 31 Amp, 15 kW (20 Hp) 038 = 38 Amp, 18.5 kW (25 Hp) 046 = 46 Amp, 22 kW (30 Hp) 061 = 61 Amp, 30 kW (40 Hp) 070 = 70 Amp, 30 kW (50 Hp) 072 = 72 Amp, 37 kW (50 Hp) 080 = 80 Amp, 45 kW (60 Hp) 087 = 87 Amp, 45 kW (60 Hp) 105 = 105 Amp, 55 kW (75 Hp) 140 = 140 Amp, 75 kW (100 Hp) 170 = 170 Amp, 90 kW (125 Hp)
1D3 = 1.3 Amp, 0.37 kW (0.5 Hp) 1D9 = 1.9 Amp, 0.55 kW (0.75 Hp) 2D4 = 2.4 Amp, 0.75 kW (1 Hp) 3D3 = 3.3 Amp, 1.1 kW (1.5 Hp) 4D3 = 4.3 Amp, 1.5 kW (2 Hp)
2
2
2
2
2
2
Rating
2 = 460V 3-phase Bypass only 3 = Fused Disconnect is only option for YM product
2 = NEMA Type 2 (YK only)
2 = Fused IntelliDisconn ect3 4 = IntelliPass w/ Non-fused Disconnect
4
VSD FP Series II Drives Product Bulletin
FP Series II Micro Drives Product Selection
Current (A)
YM2D8612B-00000
0.5 hp
2.8
M1
NEMA Type 1
YM3D7612B-00000
0.75 hp
3.7
M1
NEMA Type 1
1 hp
4.8
M1
NEMA Type 1
YM7D0612B-00000
1.5 hp
7
M1
NEMA Type 1
Current (A)
YM1D3712B-00000
0.5 hp
1.3
M1
NEMA Type 1
YM1D9712B-00000
0.75 hp
1.9
M1
NEMA Type 1
YM2D4712B-00000
1 hp
2.4
M1
NEMA Type 1
YM3D3712B-00000
1.5 hp
3.3
M1
NEMA Type 1
YM4D3712B-00000
2 hp
4.3
M1
NEMA Type 1
Table 2: F P Series II Micro Drive with Fused Disconnect NEMA Type 1 – 200-240V
Code Number hp
1
Frame Enclosure Rating
YM4D8612B-00000
1. All horsepower and current ratings are Variable Torque (VT).
Table 3: FP Series II Micro Drive with Fused Disconnect NEMA Type 1 – 380-480V
Code Number hp
1. All horsepower and current ratings are Variable Torque (VT).
1
Frame Enclosure Rating
VSD FP Series II Drives Product Bulletin
5
FP Series II Drives Product Selection
Table 4: FP Series II IntelliDisconnect NEMA Type 1 - 208V Fused
Code Number
YK4D8112B-00000 1 hp (0.75 kW) 4.8 A1 NEMA Type 1 YK8D0112B-00000 2 hp (1.5 kW) 8 A1 NEMA Type 1 YK011112B-00000 3 hp (2.2 kW) 11 A1 NEMA Type 1 YK018112B-00000 5 hp (4 kW) 18 A1 NEMA Type 1 YK025112B-00000 7.5 hp (5.5 kW) 25 A2 NEMA Type 1 YK031112B-00000 10 hp (7.5 kW) 31 A2 NEMA Type 1 YK048112B-00000 15 hp (11 kW) 48 A3 NEMA Type 1 YK062112B-00000 20 hp (15 kW) 62 A3 NEMA Type 1 YK075112B-00000 25 hp (18.5 kW) 75 A4 NEMA Type 1 YK088112B-00000 30 hp (22 kW) 88 A4 NEMA Type 1 YK140112B-00000 40 hp (37 kW) 140 A4 NEMA Type 1 YK170112B-00000 50 hp (45 kW) 170 A6 NEMA Type 1
1. For non-fused disconnect, change the 8th digit to a 1.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
Table 5: FP Series II IntelliDisconnect NEMA Type 3R - 208V Fused
Code Number
YK4D8122B-00000 1 hp (0.75 kW) 4.8 C1 NEMA Type 3R YK8D0122B-00000 2 hp (1.5 kW) 8 C1 NEMA Type 3R YK011122B-00000 3 hp (2.2 kW) 11 C1 NEMA Type 3R YK018122B-00000 5 hp (4 kW) 18 C1 NEMA Type 3R YK025122B-00000 7.5 hp (5.5 kW) 25 C2 NEMA Type 3R YK031122B-00000 10 hp (7.5 kW) 31 C2 NEMA Type 3R YK048122B-00000 15 hp (11 kW) 48 C3 NEMA Type 3R YK062122B-00000 20 hp (15 kW) 62 C3 NEMA Type 3R YK075122B-00000 25 hp (18.5 kW) 75 C4 NEMA Type 3R YK088122B-00000 30 hp (22 kW) 88 C4 NEMA Type 3R YK140122B-00000 40 hp (37 kW) 140 C4 NEMA Type 3R YK170122B-00000 50 hp (45 kW) 170 C6 NEMA Type 3R
1. For non-fused disconnect, change the 8th digit to a 1.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
6
VSD FP Series II Drives Product Bulletin
Table 6: FP Series II IntelliDisconnect NEMA Type 1 - 230V Fused
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
NEMA Type 1
Code Number
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
YK4D8212B-00000 1 hp (0.75 kW) 4.8 A1 YK8D0212B-00000 2 hp (1.5 kW) 8 A1 YK011212B-00000 3 hp (2.2 kW) 11 A1 YK018212B-00000 5 hp (4 kW) 18 A1 YK025212B-00000 7.5 hp (5.5 kW) 25 A2 YK031212B-00000 10 hp (7.5 kW) 31 A2 YK048212B-00000 15 hp (11 kW) 48 A3 YK062212B-00000 20 hp (15 kW) 62 A3 YK075212B-00000 25 hp (18.5 kW) 75 A4 YK088212B-00000 30 hp (22 kW) 88 A4 YK140212B-00000 40 hp (37 kW) 140 A4 YK170212B-00000 50 hp (45 kW) 170 A6
1. For non-fused disconnect, change the 8th digit to a 1.
2. All horsepower and current ratings are Variable Torque (VT).
Table 7: FP Series II IntelliDisconnect NEMA Type 3R - 230V Fused
Code Number
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
YK4D8222B-00000 1 hp (0.75 kW) 4.8 C1 NEMA Type 3R YK8D0222B-00000 2 hp (1.5 kW) 8 C1 NEMA Type 3R YK011222B-00000 3 hp (2.2 kW) 11 C1 NEMA Type 3R YK018222B-00000 5 hp (4 kW) 18 C1 NEMA Type 3R YK025222B-00000 7.5 hp (5.5 kW) 25 C2 NEMA Type 3R YK031222B-00000 10 hp (7.5 kW) 31 C2 NEMA Type 3R YK048222B-00000 15 hp (11 kW) 48 C3 NEMA Type 3R YK062222B-00000 20 hp (15 kW) 62 C3 NEMA Type 3R YK075222B-00000 25 hp (18.5 kW) 75 C4 NEMA Type 3R YK088222B-00000 30 hp (22 kW) 88 C4 NEMA Type 3R YK140222B-00000 40 hp (37 kW) 140 C4 NEMA Type 3R YK170222B-00000 50 hp (45 kW) 170 C6 NEMA Type 3R
1. For non-fused disconnect, change the 8th digit to a 1.
2. All horsepower and current ratings are Variable Torque (VT).
VSD FP Series II Drives Product Bulletin
7
Table 8: FP Series II IntelliDisconnect NEMA Type 1 - 480V Fused
Code Number
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
YK3D4412B-00000 1 hp (1.1 kW) 3.4 A1 NEMA Type 1 YK4D8412B-00000 2 hp (1.5 kW) 4.8 A1 NEMA Type 1 YK5D6412B-00000 3 hp (2.2 kW) 5.6 A1 NEMA Type 1 YK9D6412B-00000 5 hp (4 kW) 9.6 A1 NEMA Type 1 YK012412B-00000 7.5 hp (5.5 kW) 12 A1 NEMA Type 1 YK016412B-00000 10 hp (7.5 kW) 16 A2 NEMA Type 1 YK023412B-00000 15 hp (11 kW) 23 A2 NEMA Type 1 YK031412B-00000 20 hp (15 kW) 31 A3 NEMA Type 1 YK038412B-00000 25 hp (18.5 kW) 38 A3 NEMA Type 1 YK046412B-00000 30 hp (22 kW) 46 A3 NEMA Type 1 YK061412B-00000 40 hp (30 kW) 61 A4 NEMA Type 1 YK072412B-00000 50 hp (37 kW) 72 A4 NEMA Type 1 YK087412B-00000 60 hp (45 kW) 87 A4 NEMA Type 1 YK105412B-00000 75 hp (55 kW) 105 A4 NEMA Type 1 YK140412B-00000 100 hp (75 kW) 140 A5 NEMA Type 1 YK170412B-00000 125 hp (90 kW) 170 A6 NEMA Type 1
1. For non-fused disconnect, change the 8th digit to a 1.
2. All horsepower and current ratings are Variable Torque (VT).
Table 9: FP Series II IntelliDisconnect NEMA Type 3R - 480V Fused
Code Number
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
YK3D4412B-00000 1 hp (1.1 kW) 3.4 C1 NEMA Type 3R YK4D8412B-00000 2 hp (1.5 kW) 4.8 C1 NEMA Type 3R YK5D6412B-00000 3 hp (2.2 kW) 5.6 C1 NEMA Type 3R YK9D6412B-00000 5 hp (4 kW) 9.6 C1 NEMA Type 3R YK012412B-00000 7.5 hp (5.5 kW) 12 C1 NEMA Type 3R YK016412B-00000 10 hp (7.5 kW) 16 C2 NEMA Type 3R YK023412B-00000 15 hp (11 kW) 23 C2 NEMA Type 3R YK031412B-00000 20 hp (15 kW) 31 C3 NEMA Type 3R YK038412B-00000 25 hp (18.5 kW) 38 C3 NEMA Type 3R YK046412B-00000 30 hp (22 kW) 46 C3 NEMA Type 3R YK061412B-00000 40 hp (30 kW) 61 C4 NEMA Type 3R YK072412B-00000 50 hp (37 kW) 72 C4 NEMA Type 3R YK087412B-00000 60 hp (45 kW) 87 C4 NEMA Type 3R YK105412B-00000 75 hp (55 kW) 105 C4 NEMA Type 3R YK140412B-00000 100 hp (75 kW) 140 C5 NEMA Type 3R YK170412B-00000 125 hp (90 kW) 170 C6 NEMA Type 3R
1. For non-fused disconnect, change the 8th digit to a 1.
2. All horsepower and current ratings are Variable Torque (VT).
8
VSD FP Series II Drives Product Bulletin
Table 10: F P Series II IntelliPass NEMA Type 1 - 208V Fused
Code Number
YK4D8113B-00000 1 hp (0.75 kW) 4.8 B1 NEMA Type 1 YK8D0113B-00000 2 hp (1.5 kW) 8 B1 NEMA Type 1 YK011113B-00000 3 hp (2.2 kW) 11 B1 NEMA Type 1 YK018113B-00000 5 hp (4 kW) 18 B1 NEMA Type 1 YK025113B-00000 7.5 hp (5.5 kW) 25 B2 NEMA Type 1 YK031113B-00000 10 hp (7.5 kW) 31 B2 NEMA Type 1 YK048113B-00000 15 hp (11 kW) 48 B3 NEMA Type 1 YK062113B-00000 20 hp (15 kW) 62 B3 NEMA Type 1 YK075113B-00000 25 hp (18.5 kW) 75 B4 NEMA Type 1 YK088113B-00000 30 hp (22 kW) 88 B4 NEMA Type 1 YK115113B-00000 40 hp (37 kW) 115 B4 NEMA Type 1 YK150113B-00000 50 hp (45 kW) 150 B6 NEMA Type 1
1. For non-fused disconnect, change the 8th digit to a 4.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
Table 11: FP Series II IntelliPass NEMA Type 3R - 208V Fused
Code Number
YK4D8123B-00000 1 hp (0.75 kW) 4.8 D1 NEMA Type 3R YK8D0123B-00000 2 hp (1.5 kW) 8 D1 NEMA Type 3R YK011123B-00000 3 hp (2.2 kW) 11 D1 NEMA Type 3R YK018123B-00000 5 hp (4 kW) 18 D1 NEMA Type 3R YK025123B-00000 7.5 hp (5.5 kW) 25 D2 NEMA Type 3R YK031123B-00000 10 hp (7.5 kW) 31 D2 NEMA Type 3R YK048123B-00000 15 hp (11 kW) 48 D3 NEMA Type 3R YK062123B-00000 20 hp (15 kW) 62 D3 NEMA Type 3R YK075123B-00000 25 hp (18.5 kW) 75 D4 NEMA Type 3R YK088123B-00000 30 hp (22 kW) 88 D4 NEMA Type 3R YK115123B-00000 40 hp (37 kW) 115 D4 NEMA Type 3R YK150123B-00000 50 hp (45 kW) 150 D6 NEMA Type 3R
1. For non-fused disconnect, change the 8th digit to a 4.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
VSD FP Series II Drives Product Bulletin
9
Table 12: F P Series II IntelliPass NEMA Type 1 - 230V Fused
Code Number
YK4D8213B-00000 1 hp (0.75 kW) 4.8 B1 NEMA Type 1 YK8D0213B-00000 2 hp (1.5 kW) 8 B1 NEMA Type 1 YK011213B-00000 3 hp (2.2 kW) 11 B1 NEMA Type 1 YK016213B-00000 5 hp (4 kW) 16 B1 NEMA Type 1 YK024213B-00000 7.5 hp (5.5 kW) 24 B2 NEMA Type 1 YK031213B-00000 10 hp (7.5 kW) 31 B2 NEMA Type 1 YK048213B-00000 15 hp (11 kW) 48 B3 NEMA Type 1 YK062213B-00000 20 hp (15 kW) 62 B3 NEMA Type 1 YK070213B-00000 25 hp (18.5 kW) 70 B4 NEMA Type 1 YK088213B-00000 30 hp (22 kW) 88 B4 NEMA Type 1 YK115213B-00000 40 hp (37 kW) 115 B4 NEMA Type 1 YK150213B-00000 50 hp (45 kW) 150 B6 NEMA Type 1
1. For non-fused disconnect, change the 8th digit to a 4.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
Table 13: F P Series II IntelliPass NEMA Type 3R - 230V Fused
Code Number
YK4D8223B-00000 1 hp (0.75 kW) 4.8 D1 NEMA Type 3R YK8D0223B-00000 2 hp (1.5 kW) 8 D1 NEMA Type 3R YK011223B-00000 3 hp (2.2 kW) 11 D1 NEMA Type 3R YK016223B-00000 5 hp (4 kW) 16 D1 NEMA Type 3R YK024223B-00000 7.5 hp (5.5 kW) 24 D2 NEMA Type 3R YK031223B-00000 10 hp (7.5 kW) 31 D2 NEMA Type 3R YK048223B-00000 15 hp (11 kW) 48 D3 NEMA Type 3R YK062223B-00000 20 hp (15 kW) 62 D3 NEMA Type 3R YK070223B-00000 25 hp (18.5 kW) 70 D4 NEMA Type 3R YK088223B-00000 30 hp (22 kW) 88 D4 NEMA Type 3R YK115223B-00000 40 hp (37 kW) 115 D4 NEMA Type 3R YK150223B-00000 50 hp (45 kW) 150 D6 NEMA Type 3R
1. For non-fused disconnect, change the 8th digit to a 4.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
10
VSD FP Series II Drives Product Bulletin
Table 14: F P Series II IntelliPass NEMA Type 1 - 480V Fused
Code Number
YK2D4413B-00000 1 hp (1.1 kW) 2.4 B1 NEMA Type 1 YK4D0413B-00000 2 hp (1.5 kW) 4 B1 NEMA Type 1 YK5D6413B-00000 3 hp (2.2 kW) 5.6 B1 NEMA Type 1 YK9D0413B-00000 5 hp (4 kW) 9 B1 NEMA Type 1 YK012413B-00000 7.5 hp (5.5 kW) 12 B1 NEMA Type 1 YK016413B-00000 10 hp (7.5 kW) 16 B2 NEMA Type 1 YK023413B-00000 15 hp (11 kW) 23 B2 NEMA Type 1 YK031413B-00000 20 hp (15 kW) 31 B3 NEMA Type 1 YK038413B-00000 25 hp (18.5 kW) 38 B3 NEMA Type 1 YK046413B-00000 30 hp (22 kW) 46 B3 NEMA Type 1 YK061413B-00000 40 hp (30 kW) 61 B4 NEMA Type 1 YK070413B-00000 50 hp (37 kW) 70 B4 NEMA Type 1 YK080413B-00000 60 hp (45 kW) 80 B4 NEMA Type 1 YK105413B-00000 75 hp (55 kW) 105 B4 NEMA Type 1 YK140413B-00000 100 hp (75 kW) 140 B5 NEMA Type 1 YK170413B-00000 125 hp (90 kW) 170 B6 NEMA Type 1
1. For non-fused disconnect, change the 8th digit to a 4.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
Table 15: F P Series II IntelliPass NEMA Type 3R - 480V Fused
Code Number
YK2D4423B-00000 1 hp (1.1 kW) 2.4 D1 NEMA Type 3R YK4D0423B-00000 2 hp (1.5 kW) 4 D1 NEMA Type 3R YK5D6423B-00000 3 hp (2.2 kW) 5.6 D1 NEMA Type 3R YK9D0423B-00000 5 hp (4 kW) 9 D1 NEMA Type 3R YK012423B-00000 7.5 hp (5.5 kW) 12 D1 NEMA Type 3R YK016423B-00000 10 hp (7.5 kW) 16 D2 NEMA Type 3R YK023423B-00000 15 hp (11 kW) 23 D2 NEMA Type 3R YK031423B-00000 20 hp (15 kW) 31 D3 NEMA Type 3R YK038423B-00000 25 hp (18.5 kW) 38 D3 NEMA Type 3R YK046423B-00000 30 hp (22 kW) 46 D3 NEMA Type 3R YK061423B-00000 40 hp (30 kW) 61 D4 NEMA Type 3R YK070423B-00000 50 hp (37 kW) 70 D4 NEMA Type 3R YK080423B-00000 60 hp (45 kW) 80 D4 NEMA Type 3R YK105423B-00000 75 hp (55 kW) 105 D4 NE MA Type 3R YK140423B-00000 100 hp (75 kW) 140 D5 NEMA Type 3R YK170423B-00000 125 hp (90 kW) 170 D6 NEMA Type 3R
1. For non-fused disconnect, change the 8th digit to a 4.
2. All horsepower and current ratings are Variable Torque (VT).
1
hp (kW)
2
Current (A)
Frame Enclosure Rating
VSD FP Series II Drives Product Bulletin
11
FP Series II Drives Options
Option Number
Description
-00000
N2 and BACnet Com
-S0000
N2 and BACnet Com, SA Bus Communication Card Installed
Code Number
Description
VS-RMT-KEYPAD2
Series II Remote Keypad Kit
VS-KEYPAD-SER2
Series II Graphic Bypass HOA (Hand-Off-Auto) Keypad
VS-REM-USB-LOAD
USB to RJ-45 Cable with Software Driver
VS-XMX-K9-FS4-5
Auxiliary Contacts - Quantity 2 (Frames 4 and 5 Bypass and Drive Output Contactors)
VS-XMX-K9-FS6-9
Auxiliary Contacts - Quantity 2 (Frames 6, 7, 8, and 9 Bypass and Drive Output Contactors)
Option Type
Description
Allowed Slot
Option Number
Extended I/O Cards
6 Digital Outputs (DI) or Digital Outputs (DO), 1 ext
D, E
VS-XMX-B1
1 Relay Output (RO) Normally Closed/Normally
D,E
VS-XMX-B2 1 AI (mA Isolated); 2 AO (mA Isolated)
D, E
VS-XMX-B4
Card - 3 Relay Dry Contact
D, E
VS-XMX-B5
1 RO (NO), 5 Digital Inputs (DI) 42 to 240V AC
D, E
VS-XMX-B9 Expander IO - 1*AO, 1*DO, 1*RO
D, E
VS-XMX-BF
Communication Cards Johnson Controls SA Bus Com
D, E
VS-XMX-CS
LONW
® Network
D, E
VS-XMX-C4
I/O Option Cards
3 Relay (Spare /Replacement Part Only - Not an
B
VS-XMX-F1
2 Relay and 1 Thermistor – Replaces standard
B
VS-XMX-F2
The following options are available for the FP Series II Drives when ordering from the factory.
Table 16: FP Series II Options
FP Series II Spare Parts and Options
The following spare parts and accessories are available for the FP Series II drives.
Note: These parts are ordered separately from the drive. Table 17: FP Series II Spare Parts & Accessories
The FP Series II drives can accommodate a wide selection of expander and adapter option boards to customize the drive for your application needs.
Table 18: FP Series II Option Cards
Locations
+24 V DC/EXT +24V DC Programmable
Open(NC/NO); 1 RO (NO); 1 Thermistor
Input
ORKS
Option with Standard VSD)
Relay board in Slot B
12
VSD FP Series II Drives Product Bulletin
Dimensions
HP
208-230V
380-480V
0.5
M1-1
M1-1
0.75
M1-2
M1-1
1
M1-2
M1-1
1.5
M1-2
M1-2
2 - M1-2
208 / 230V
460V
HP
Type 1
Disconnect
Type 1
Bypass
Type 1
Disconnect
Type 1
Bypass
1
A1-4
B1-4
A1-4
B1-4 2 A1-4
B1-4
A1-4
B1-4
3
A1-4
B1-4
A1-4
B1-4
5
A1-5
B1-5
A1-4
B1-4
7.5
A2-5
B2-5
A1-4
B1-4
10
A2-5
B2-5
A2-5
B2-5
15
A3-6
B3-6
A2-5
B2-5
20
A3-6
B3-6
A3-5
B3-5
25
A4-7
B4-7
A3-6
B3-6
30
A4-7
B4-7
A3-6
B3-6
40
A4-8
B4-8
A4-6
B4-6
50
A6-8
B6-8
A4-7
B4-7
60 - -
A4-7
B4-7
75 - -
A4-7
B4-7
100 - -
A5-8
B5-8
125 - -
A6-8
B6-8
See the table below and following pages for exterior dimensions of the FP Series II drives. Find the desired configuration based on hors epo wer, volta ge, and options. For sizing purposes, the drives are categorized by style and VSD frame size. For example, A1-4 is an A1 Enclosure Size and a Frame 4 VSD.
Table 19: FP Series II Micro Drives Selection Table
Table 20: FP Series II Drives Selection Table
VSD FP Series II Drives Product Bulletin
13
FP Series II Micro Drive with Disconnect NEMA Type 1 Dimensions
19.78 (502.4)
19.03 (483.4)
9.59 (243.6)
5.25 (133.4)
8.61 (218.7)
7.19 (182.6)
19.78 (502.4)
19.03 (483.4)
9.59 (243.6)
5.25 (133.4)
8.61 (218.7)
7.19 (182.6)
Figure 2: Micro Drive with Disconnect NEMA Type 1 Drawings Table 21: Micro Drive with Disconnect NEAM Type 1 Dimensions
Configuration
M1-1 M1-2
Dimensions, in. (mm), approximate H H1 W W1 D D1
Approximate Weights, lb (kg)
13.9 (6.3)
15.4 (7.0)
14
VSD FP Series II Drives Product Bulletin
FP Series II IntelliDisconnect NEMA Type 1
A1-4
20.61 (523.5)
19.75 (501.7)
8.65 (219.7)
6.75 (171.5)
10.4 (264.2)
8.96 (227.6)
A1-5
30 (762)
29 (736.6)
8.65 (219.7)
6.75 (171.5)
11.18 (284)
9.74 (247.4)
A2-5
30 (762)
29 (736.6)
8.65 (219.7)
6.75 (171.5)
11.18 (284)
9.74 (247.4)
A3-5
20.61 (523.5)
19.75 (501.7)
8.65 (219.7)
6.75 (171.5)
10.4 (264.2)
8.96 (227.6)
A3-6
32.5 (825.5)
31.5 (800.1)
10.4 (264.2)
7.5 (190.5)
11.41 (289.8)
9.97 (253.2)
A4-6
41.03 (1042.2)
39.5 (1003.3)
12.4 (315)
10.5 (266.7)
13.67 (347.2)
11.97 (304)
A4-7
41.55 (1055.4)
39.5 (1003.3)
12.4 (315)
10.5 (266.7)
13.94 (354.1)
12.25 (311.2)
A4-8
44.04 (1118.6)
39.5 (1003.3)
12 (304.8)
10.5 (266.7)
15.86 (402.8)
14.17 (359.9)
A5-8
44.05 (1118.9)
42.06 (1068.3)
12 (304.8)
10.5 (266.7)
15.86 (402.8)
14.17 (359.9)
A6-8
47.65 (1210.3)
46.5 (1181.1)
16 (406.4)
14.5 (368.3)
15.86 (402.8)
14.17 (359.9)
Figure 3: IntelliDisconnect NEMA Type 1 Drawings
Table 22: IntelliDisconnect NEMA Type 1 Dimensions
Configuration
Dimensions, in. (mm), approximate H H1 W W1 D D1
Approximate Weights, lb (kg)
34 (15.4) 54 (24.5) 54 (24.5) 54 (24.5) 101 (45.8) 113 (51.3) 200 (90.7) 363 (164.7) 363 (164.7) 363 (164.7)
VSD FP Series II Drives Product Bulletin
15
FP Series II Intellipass NEMA Type 1
23 (584.2)
21.75 (552.5)
16.28 (413.5)
14.75 (374.7)
15.7 (398.8)
14.26 (362.2)
23 (584.2)
21.75 (552.5)
16.28 (413.5)
14.75 (374.7)
15.7 (398.8)
14.26 (362.2)
30 (762)
29 (736.6)
16.28 (413.5)
14.75 (374.7)
15.7 (398.8)
14.26 (362.2)
31.5 (800.1)
30.5 (774.7)
19.13 (485.9)
17.75 (450.9)
15.7 (398.8)
14.26 (362.2)
31.5 (800.1)
30.5 (774.7)
19.13 (485.9)
17.75 (450.9)
15.7 (398.8)
14.26 (362.2)
39.5 (1003.3)
38.25 (971.6)
30.13 (765.3)
28.75 (730.3)
17.42 (442.5)
15.73 (399.5)
42.75 (1085.9)
38.25 (971.6)
30.13 (765.3)
28.75 (730.3)
17.42 (442.5)
15.73 (399.5)
42.9 (1089.7)
38.25 (971.6)
30.13 (765.3)
28.75 (730.3)
17.42 (442.5)
15.73 (399.5)
44 (1117.6)
42.75 (1085.9)
33.13 (841.5)
31.75 (806.5)
17.42 (442.5)
15.73 (399.5)
44 (1117.6)
42.75 (1085.9)
33.13 (841.5)
31.75 (806.5)
17.42 (442.5)
15.73 (399.5)
Figure 4: Intellipass NEMA Type 1 Drawings
Table 23: Intellipass NEMA Type 1 Dimensions
Dimensions, in. (mm), approximate
Configuration
H H1 W W1 D D1
B1-4
B1-5
B2-5 B3-5
B3-6
B4-6 B4-7
B4-8
B5-8
Approximate Weights, lb (kg)
64 (29.0) 88 (39.9) 88 (39.9) 88 (39.9) 145 (65.8) 158 (71.7) 262 (118.8) 455 (206.4) 455 (206.4)
B6-8
455 (206.4)
16
VSD FP Series II Drives Product Bulletin
Wiring
Figure 5: VSD FP Series II Base Drive Circuit
Diagram
VSD FP Series II Drives Product Bulletin
17
Technical Specifications
Input Voltage (Vin)
208, 230, 480 VAC, -10%/+10%
Input Frequency (fin)
50/60 Hz (Variation Up to 47-66 Hz)
Connection to Power
Once Per Minute or Less (Typical Operation)
Current Withstand Rating
15 kAIC
Output Voltage
0 to V
Line Voltage In
Continuous Output Current
Ambient Temperature Maximum 104°F (40°C), Overload 1.1 x I Overload Current
110% (1 min./10 min.)
Initial Output Current
150% for 2 Seconds
Output Frequency
-320 to 320 Hz
Frequency Resolution
0.01 Hz
Control Method
Frequency Control (V/f) Open Loop Sensorless Vector Control
Switching Frequency
1.5 to 10 kHz; default = 6 kHz
Frequency Reference
Analog Input: Resolution 0.1% (10 bit), Field Weakening Point
8 to 320 Hz
Acceleration Time
0.1 to 3,000 s
Deceleration Time
0.1 to 3,000 s
Braking Torque
DC Brake: 30% x Tn (without Brake Option)
Ambient Operating Temperature
14 (No Frost) to 104°F (-10 to 40°C), De-rating to operate at 122°F (50°C)
Storage Temperature
-40 to 158°F (-40 to 70°C)
Relative Humidity
0 to 95% RH, Noncondensing, Noncorrosive,
Air Quality
Chemical Vapors: IEC 60721-3-3, Unit In Operation, Class 3C2;
Altitude
100% Load Capacity (No Derating) Up to 3,280 ft (1,000 m);
Vibration
EN 61800-5-1, EN 60068-2-6; 5 to 150 Hz, Displacement
Shock
EN 61800-5-1,EN 60068-2-27 United Parcel Service® (UPS) Drop Test (for Enclosure Class
NEMA Type 1 or NEMA Type 3R
EMC (at default settings)
Immunity: Fulfills all Electromagnetic Compatibility (EMC) Immunity
Emissions
EMC Level Dependent: +EMC 2: EN 61800-3 (2004) Category C2, Delivered
Analog Input Voltage
0 to 10 V, R = 200 kOhms Differential Resolution 0.1%; Accuracy ±1%, Dip
JC-VSD FP Series II Drives (Part 1 of 2)
(1 min./10 min.)
Accuracy +/-1% Panel Reference: Resolution 0.01 Hz
in
L
No Dripping Water
Mechanical Particles: IEC 60721-3-3, Unit In Operation, Class 3S2
1% Derating for Each 328 ft (100 m) Above 3,280 ft (1,000 m); Maximum 9,842 ft (3,000 m)
Amplitude 1 mm (P eak) at 5 to 15.8 Hz, Max. Acceleration Amplitude 1 G at
15.8 to 150 Hz, OSHPD Seismic Certified
Applicable UPS Weights) Storage and Shipping: max. 15 G, 11 ms (in package)
Requirements; Emissions: EN 61800-3 (2004), LEVEL H (EMC C2)
with Class C2 EMC Filtering as Default
Switch Selection (Voltage/Current)
18
VSD FP Series II Drives Product Bulletin
Published in U.S.A.
www.johnsoncontrols.com
JC-VSD FP Series II Drives (Part 2 of 2)
Analog Input Current
0 (4) to 20 mA; Ri - 250 Ohms Differential
Digital Inputs (6)
Positive or Negative Logic; 18 to 30 VDC
Auxiliary Voltage
24 V ±10%, Maximum 100 mA
Output Reference Voltage
10 V +3%, Maximum Load 10 mA
Analog Output
0 to 10 V, 0 (4) to 20 mA; RL max. 500 Ohms; Resolution 10 bit; Accuracy
Relay Outputs
3 Programmable, 2 Form C, 1 Form A Relay Outputs, Hard-Wired Jumper
Between Terminal 6 and 10 (Factory Default)
Dip Switch Setting Default
RS485 = Off
Overcurrent Protection
Yes
Overvoltage Protection
Yes
DC Bus Regulation Anti-trip
Yes (Accelerates or Decelerates the Load)
Undervoltage Protection
Yes
Earth Fault Protection
Yes, in case of earth fault in motor or motor cable, only the frequency Input Phase Supervision
Yes, trips if any of the input phases are missing
Motor Phase Supervision
Yes, trips if any of the output phases are missing
Overtemperature Protection
Yes
Motor Overload Protection
Yes
Motor Stall Protection
Yes
Motor Underload Protection
Yes
Short Circuit Protection
Yes
Surge Protection
Yes (Varistor Input)
Conformed Coated (Varnished) Board
Yes (Prevents Corrosion)
OHSPD Special Seismic Certification
Yes
Compliance UL Listed File No 508C; cUL Listed
Safety – EN 61800-5-1 (2007)
Warranty
30 Months Standard Terms; Reliability
500,000 Hours Mean Time Between Failures (MTBF)
Weight
See dimensions section
Horsepower/Amperes/
208V
1 to 50 Hp, 4.8 to 170 Amps, 0.75 to 45 kW
230V
1 to 50 Hp, 4.8 to 170 Amps, 0.75 to 45 kW
200-240V
0.5 to 1.5 Hp, 2.8 to 7.0 Amps, 0.37 to 1.1 kW
380-480V
0.5 to 2 Hp, 1.3 to 4.3 Amps, 0.37 to 1.5 kW
460V
1 to 125 Hp, 3.4 to 170 Amps, 1.1 to 90 kW
± 2%, Dip Switch Selection (Voltage/Current)
Switching Capacity: 24 VDC/8 A, 250 VAC/8 A, 125 VDC/0.4 A
AO1 = Current AI2 = Current AI1 = Voltage
converter is protected.
Pre-Approval
39 Months with Certified Startup
Kilowatts
All other marks herein are the marks of their respective owners. © 2015 Johnson Controls, Inc.
Metasys® and Johnson Controls® are registered trademar k s of Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Loading...