Johnson Controls MS-IOM1710-0, IOM4710 Installation Instructions Manual

IOM1710 Input/Output Module
Installation Instructions
MS-IOM1710-0
Part No. 24-10144-9, Rev. G
Release 5.0
Issued January 4, 2010
Supersedes October 6, 2008

Applications

The Input/Output Module (IOM) 1710 is a member of the Metasys® system Field Equipment Controller (FEC) family. The IOM controller provides increased capacity to larger FEC applications when used on the Sensor Actuator (SA) Bus. The IOM controller can also be used on the Field Controller (FC) Bus to connect additional physical points to the system.
IMPORTANT: In Metasys system smoke control applications, use only the IOM1710 models that are UL Listed, UUKL 864 Listed, Smoke Control Equipment. See Repair Information UUKL 864 Listed IOM1710 models. For Metasys system smoke control applications, you must refer to the Metasys System UL 864 UUKL Ninth Edition
Smoke Control System Technical Bulletin (LIT-12011252) for detailed requirements and
procedures for installing and operating UUKL 864 Listed Metasys system devices. Failure to meet the requirements or follow the procedures in the
Metasys System UL 864 UUKL Ninth Edition Smoke Control System Technical Bulletin (LIT-12011252)
can void the UUKL 864 listing for Smoke Control Equipment.
on page 6 for

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Observe the following guidelines when installing the IOM controller:
Transport the IOM controller in the original container to minimize vibration and shock damage to the IOM.
Do not drop the IOM controller or subject it to physical shock.

Materials and Special Tools Needed

Y ou need either of the following items to install the IOM controller:
three fasteners appropriate for the mounting surface (#8 screws or M4 screws)
one 20.3 cm (8 in.) or longer piece of DIN rail and appropriate hardware for mounting the DIN rail

Mounting

Follow these guidelines when mounting an IOM controller:
Ensure that the mounting surface can support the IOM controller and any user-supplied enclosure.
Mount the IOM controller in the proper orientation. See the Wall Mount Applications Mount Applications section.
Mount the IOM controller on an even surface whenever possible.
Use shims or washers to mount the unit securely on the mounting surface.
Mount the IOM controller in areas free of corrosive vapors and observe the environmental limitations listed in the Technical Specifications
and DIN Rail
section.
IOM1710 Input/Output Module Installation Instructions 1
Do not mount the IOM controller on surfaces that
Figure 1: IOM1710 Controller Physical Features
and Wiring Terminal Blocks
FAULT
POWER
A
ON
IN 1
ICOM 1
IN 2
ICOM 2
IN 3
ICOM 3
IN 4
ICOM 4
BINARY INPUTS
COM
+
SHLD
+
COM
PWR
A
O N
Binary Inputs
Clip
EOL
Switch
DIP Switches
SA BUS FC BUS
Mounting
Clip
Status
LEDs
Port
FIG:IOM17 10_frnt
54
(2.13 )
54
(2.13)
108
(4-1/4 )
F
I
G
:
I
O
M
1
7
1
0
_
b
c
k
Hooks
Mounting Clip
(Shown Extended )
143
(5 - 5/8)
Figure 2: IOM1710 Controller Mounting Features,
mm (in.)
IN 1
ICOM 1
IN 2
ICOM 2
IN 3
ICOM 3
IN 4
ICOM 4
B I
N A R Y I N P U T S
COM
+ –
SHLD
R
ET SY
FAULT
POWER
ADDRESS
ON
I
N
1
I
C
O
M
1
I
N
2
I
C
O
M
2
I
N
3
I
C
O
M
3
I
N
4
I
C
O
M
4
BINARY INPUTS
C
O
M
+
S
H
L
D
+
C
O
M
P
W
R
ADDRESS Ø = ALL OFF
EOL
O N
Figure 3: Required Orientation for Wall Mount
Applications
are prone to vibration, such as duct work, or in areas where electromagnetic emissions from other devices or wiring can interfere with IOM controller communication.
Allow sufficient space for cable and wire connections (minimum of 51 mm [2 in.] in each direction).
On panel or enclosure mount applications, observe these guidelines:
Do not install the IOM controller in an airtight enclosure.
Mount the IOM controller so that the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing.
24 VAC
Power Terminal
HOT
COM
DIN Rail
DDRESS
DDRESS Ø = ALL OFF
EOL
Mounting

Wall Mount Applications

Use the holes in the mounting clips for wall mount applications.
To mount the IOM controller on a wall or other vertical surface:
1. Ensure that the bottom mounting clip(s) are pulled outward and snapped firmly into the extended position and that the top clip is securely installed (Figure 2).
IOM1710 Input/Output Module Installation Instructions2
SA/FC Bus
Device Address
2. Mark the location of the wall mount holes using the dimensions in Figure 2, or hold the IOM controller up to the wall as a template and mark the locations.
Note: Mount the IOM controller horizontally for proper airflow.
T
M
O
O
H
C
A D D R E S S Ø = A L L O F F
O
N
E O L
A D
O N
D R E S S
+
COM PWR
P
F
O
A
W
U L
E
T
R
E T
S Y
R
COM
HOT
l
l w
_
t
n
r
o
: G
I F
3. Drill holes in the wall at the locations marked in Step 2 and insert wall anchors (if necessary).
4. Position the IOM controller and insert the screws through the holes in the mounting clips, and carefully tighten all the screws.
IMPORTANT: Do not overtighten the mounting screws. Overtightening the screws may damage the mounting clips or IOM housing.

DIN Rail Mount Applications

Figure 4: Required Orientation for DIN Rail
Mount Applications
R
ET SY
FAULT
POWER
A
ON
I
N
1
I
C
O
M
1
I
N
2
I
C
O
M
2
I
N
3
I
C
O
M
3
I
N
4
I
C
O
M
4
BINARY INPUTS
C
O
M
+
S
H
L
D
+
C
O
M
P
W
R
A
O N
F
I
G
:
I
O
M
1
7
1
0
_
o
r
n
t
_
D
I
N
Figure 5: FC Bus Terminal Block Wiring
Isolated Shield
Connection
Terminal
the FC Bus
Segment
FC Bus
Terminal
FIG: fc_bus_term
+
_
COM
SHLD
Terminating Device
on FC Bus Segment
To Next
Device on
the FC Bus
Segment
Daisy Chained Device
on FC Bus Segment
(One twist ed pair is the and leads.
The second pair is COM and SA PWR.)
+ -
Cable Shield
Connection
To Next
Device on
the SA Bus
FIG:sa_bus_terms
SA Bus
Terminal
Block Plugs
Terminating Device
on SA Bus
on SA Bus
To Next
Device on
the SA Bus
+
CO
SA
Figure 6: SA Bus Terminal Block Wiring
To mount the IOM controller on a DIN rail:
1. Securely mount the section of DIN rail horizontally and centered in the required space.
2. Carefully pull down (outward) the bottom mounting clip(s) until they lock in place (Figure 2).
Note: The top mounting clip is not used on DIN rail applications. You may remove the clip.
To wire the IOM controller:
1. Terminate wiring per engineering drawings.
2. If the IOM is connected to the FC Bus of a Network Automation Engine (NAE) or Network Control Engine (NCE), wire the FC Bus in a daisy chain (Figure 5).
s
3. Hang the IOM controller on the DIN rails using the DIN rail hooks on the back of the IOM controller.
4. Secure the IOM controller on the DIN rail by pressing the bottom mounting clips up until they snap into place.
To remove the IOM controller from the DIN rail, snap the bottom DIN clips to the outboard position and carefully lift the IOM controller off the DIN rail.
EOL
DDRESS Ø = ALL OFF

Wiring

IMPORTANT: Do not connect 24 VAC supply
power to the IOM controller before finishing wiring and checking all wiring connections. Short circuits or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: User copper conductors only. Make all wiring in accordance with local, national, and regional regulations. The IOM controller is a low-voltage (<30 VAC) device. Do not exceed the IOM controller electrical ratings.
to the IOM controller. Static elec tric discharge can damage the IOM controller and void any warranties.
Refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034) for more information on Master-Slave/Token-Passing (MS/TP) devices.
IMPORTANT: Prevent any static electric discharge
T
M
O
O
H
C
DDRESS
_
+
COM
SHLD
Block Plugs
To Next
Device on
Stranded 3-Wire Tw isted Shiel ded Cable
3. If the IOM is connected to the SA Bus of an NCE or FEC, wire the SA Bus in a daisy chain (Figure 6).
Daisy Chained Device
M
PWR
+
COM
SA PWR
Stranded, 4- Wire (2 Twisted Pair) Shielded Cable
Note: The SA/FC Bus Port (RJ-12, 6-pin, modular connector) provides 15 VDC on two of its pins, which is used to power the MS-BTCVT (Figure 7).
Note: If the IOM controller is at one end of the SA Bus daisy chain, set the End-of-Line (EOL) switch to ON.
4. Connect power to the IOM controller.
5. Download and commission the IOM controller . See the Commissioning
section.
IOM1710 Input/Output Module Installation Instructions 3
Loading...
+ 5 hidden pages