The MS-IOM3733 input/output expansion module
is part of the Metasys® system Field Equipment
Controller family. Input/Output expansion modules
(IOMs) expand the number of input/output points
connected to either a Network Automation Engine
(NAE), Network Control Engine (NCE), Advanced
Application Field Equipment Controller (FAC), Field
Equipment Controller (FEC), or Variable Air Volume
Modular Assembly (VMA) to monitor and control a
wide variety of HVAC equipment.
Note: The IOM3733 model is only available
in certain regions. Contact your local Johnson
Controls representative for more information.
IOM expansion modules operate on an RS-485
BACnet® MS/TP bus and integrate into IOMs
communicate using the BACnet MS/TP protocol
when directly connected to the FC bus.
Note: With Release 10.1 and later of the
Controller Configuration Tool (CCT), VMAs, FECs,
and FACs can be configured to communicate
by using either the BACnet MS/TP or the N2
field bus networking protocol. The operation of
the IOM is not affected by the selection of the
BACnet MS/TP or the N2 protocol in the host
controller, when the IOM is connected to the
host controller using the SA bus.
North American emissions
compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment
is operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area
may cause harmful interference, in which case the
users will be required to correct the interference at
their own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Observe these guidelines when installing a
controller:
• Transport the controller in the original container
to minimize vibration and shock damage.
• Verify that all parts shipped with the controller.
• Do not drop the controller or subject it to physical
shock.
Parts included
• One controller with removable terminal blocks
• One installation instructions sheet
Materials and special tools needed
• Three fasteners appropriate for the mounting
surface (M4 screws or #8 screws)
• One 20 cm (8 in.) or longer piece of 35 mm DIN
rail and appropriate hardware for DIN rail mount
(only)
• Small straight-blade screwdriver for securing
wires in the terminal blocks
*24101431140D*
(barcode for factory use only)
MS-IOM3733
Physical features
The following figure displays the physical features
of the IOM, and the accompanying table provides a
Figure 1: IOM3733 physical features
description of the physical features and a reference
to further information where required.
Table 1: IOM3733 feature callouts and
descriptions
Callo
Physical feature: description and references
ut
1Binary Output (BO) Terminal Block (see Table 2)
2Mounting Clip (Three Total) (see Figure 1)
3Device Address DIP Switch Block (see )
24 VAC, Class 2 Supply Power Terminal Block (see Supply
4
Power Terminal Block)
Cover Lift Tab (One of Two) (see Removing the expansion
5
module cover)
Sensor Actuator (SA) Bus / Field Controller (FC) Bus
6
Terminal Block (see SA/FC bus terminal block)
End-of-Line (EOL) Termination Switch (see Setting the
7
End-of-Line (EOL) switch)
8Binary Input (BI) Terminal Block (see Table 2)
9LED Status Indicators
Mounting
Observe these guidelines when mounting a
controller.
• Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied
enclosure.
• Mount the controller in the proper mounting
position.
• Mount the controller on a hard, even surface
whenever possible in wall-mount applications.
• Use shims or washers to mount the controller
securely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive
vapors and observe the Ambient Conditions
requirements in Technical specifications.
• Provide for sufficient space around the controller
for cable and wire connections for easy cover
removal and good ventilation through the
controller (50 mm [2 in.] minimum on the top,
bottom, and front of the controller).
• Do not mount the controller on surfaces prone to
vibration, such as duct work.
• Do not mount the controller in areas where
electromagnetic emissions from other
devices or wiring can interfere with controller
communication.
• Mount the controller horizontally on 35 mm DIN
rail whenever possible.
IOM3733 Input/Output Module Installation Guide2
Observe these additional guidelines when mounting
a controller in a panel or enclosure:
• Mount the controller so that the enclosure walls
do not obstruct cover removal or ventilation
through the controller.
• Mount the controller so that the power
transformer and other devices do not radiate
excessive heat to the controller.
• Do not install the controller in an airtight
enclosure.
Figure 2: Controller mounting positions
DIN rail mount applications
Mounting the controller horizontal on 35 mm DIN
rail is the preferred mounting method. To mount a
controller on 35 mm DIN rail, complete the following
steps:
1.Securely mount a 20 cm (8 in.) or longer section
of 35 mm DIN rail horizontally and centered in
the desired space so that the controller mounts
in the horizontal position.
2.Pull the two bottom mounting clips outward
from the controller to the extended position.
3.Hang the controller on the DIN rail by the hooks
at the top of the (DIN rail) channel on the back
of the controller, and position the controller
snugly against the DIN rail.
4.Push the bottom mounting clips inward (up) to
secure the controller on the DIN rail. To remove
the controller from the DIN rail, pull the bottom
mounting clips out to the extended position
and carefully lift the controller off the DIN rail.
Mounting features and dimensions
Figure 3: Back of controller showing extended
mounting clips, DIN rail channel, and mounting
dimensions, mm (in.)
Wall-mount applications
To mount the controller directly on a wall or other
flat vertical surface, complete the following steps:
1.Pull the two bottom mounting clips outward
and ensure they are locked in the extended
position.
2.Mark the mounting hole locations on the wall
using the dimensions in Figure 3 and one of the
mount positions shown in Figure 2. Or hold the
controller up to the wall or surface in a proper
mount position and mark the hole locations
through the mounting clips.
3.Drill holes in the wall or surface at the marked
locations, and insert appropriate wall anchors
in the holes (if necessary).
4.Hold the controller in place, and insert the
screws through the mounting clips and into the
holes (or anchors). Carefully tighten all of the
screws.
Important: Do not overtighten the mounting
screws. Overtightening the screws may
damage the mounting clips.
IOM3733 Input/Output Module Installation Guide3
Wiring
Observe the following guidelines when wiring a
controller:
Important: Electrostatic discharge can
damage controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
CAUTION
Risk of Electric Shock
Disconnect the power supply before making electrical
connections to avoid electric shock.
ATTENTION
Mise En Garde: Risque de décharge électrique
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de
décharge électrique.
CAUTION
Risk of Property Damage
Do not apply power to the system before checking all
wiring connections. Short circuited or improperly connected wires may result in permanent damage to the
equipment.
ATTENTION
For detailed information on configuring and
wiring an MS/TP Bus, FC bus, and SA bus, refer to
the MS/TP Communications Bus Technical Bulletin(LIT-12011034).
Terminal blocks and bus ports
See Figure 1 for terminal block and bus port
locations on the expansion module. Observe the
following guidelines when wiring an expansion
module:
Input and output Terminal Blocks
Most of the input terminal blocks are mounted on
the bottom of the controller and the output terminal
blocks are mounted on the top of the controller.
See Table for more information about I/O terminal
functions, requirements, and ratings.
SA/FC bus terminal block
An IOM can be connected to an SA bus or an FC bus,
but not both buses simultaneously. The SA/FC bus
terminal block is a removable, 4-terminal plug that
fits into a board-mounted jack.
When connecting the IOM to an FC bus, wire the
bus terminal block plugs on the expansion module,
and the other controller and expansion modules
in a daisy-chain configuration using 3-wire twisted,
shielded cable as shown in Figure 4.
Figure 4: FC bus terminal block wiring
Mise En Garde: Risque de dégâts matériels:
Ne pas mettre le système sous tension avant d'avoir
vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement
l'équipement.
Important: Do not exceed the controller
electrical ratings. Exceeding controller electrical
ratings can result in permanent damage to the
controller and void any warranty.
Important: Use copper conductors only. Make
all wiring in accordance with local, national, and
regional regulations.
IOM3733 Input/Output Module Installation Guide4
When connecting the IOM to an SA bus, wire the bus
terminal block plugs on the expansion module and
other SA bus devices in a daisy-chain configuration
using 4-wire twisted, shielded cable as shown in
Figure 5.
Figure 5: SA bus terminal block wiring
Note: The SA PWR/SHLD terminal does not
supply 15 VDC. The SA PWR/SHLD terminal
is isolated and can be used to connect (daisy
chain) the 15 VDC power leads on the SA bus
(Figure 5) or the cable shields on the FC bus
(Figure 4). The SA bus supervisor (FAC, FEC, or
VMA) supplies 15 VDC to devices on the SA bus
requiring power.
Supply Power Terminal Block
The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a boardmounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the
transformer to the HOT and COM terminals on the
terminal plug as shown in the following figure:
Figure 6: 24 VAC Supply Power Terminal Block
Wiring
Note: The supply power wire colors may
be different on transformers from other
manufacturers. Refer to the transformer
manufacturer’s instructions and the project
installation drawings for wiring details.
Important: Connect 24 VAC supply power to
the controller and all other network devices so
that transformer phasing is uniform across the
network devices. Powering network devices
with uniform 24 VAC supply power phasing
reduces noise, interference, and ground loop
problems. The controller does not require an
earth ground connection.
Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements
Input and output wiring guidelines
The following table provides information and
guidelines about the functions, ratings, and
requirements for the controller input and
output terminals; and references guidelines for
determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in the following
table, observe these guidelines when wiring
controller inputs and outputs:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
IOM3733 Input/Output Module Installation Guide5
• All input and output cables, regardless of wire
size or number of wires, should consist of
stranded, insulated, and twisted copper wires.
• Shielded cable is not required for input or output
cables.
• Shielded cable is required for input and output
cables that are exposed to high electromagnetic
or radio frequency noise.
• Inputs or outputs with cables less than 30 m
(100 ft) typically do not require an offset in the
software setup. Cable runs over 30 m (100 ft) may
require an offset in the input/output software
setup.
IOM3733 Input/Output Module Installation Guide6
I/O terminal blocks, ratings, and
requirements table
Table 2: IOM3733 terminal blocks, functions, ratings, requirements, and cables
Terminal block label
BINARY INPUT
BINARY OUPUT
(External Power Source
Only)
Terminal
label
INn
ICOMnBinary Input Common for all Binary Input (IN) terminals
OUTn
OCOMnBinary Output Common (for OUTn terminal)
Function, ratings, requirements
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width
Internal 16V, 10K ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 16V, 10K ohm pull up
Binary Output - 24 VAC Triac (External Power)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Cable length guidelines for required wire
sizes
Determine wire size and
maximum cable length
See Guideline A in Table 3.
See Guideline C in Table 3.
The following table defines cable length guidelines
for the various wire sizes that may be used for
wiring low-voltage (<30 V) input and outputs
Table 3: Cable length guidelines for required wire sizes for low-voltage (<30 V) inputs and outputs
GuidelineWire size/Gauge and type
1.0 mm (18 AWG) stranded copper
A
B
C
0.8 mm (20 AWG) stranded copper297 m (975 ft) twisted wire
0.6 mm (22 AWG) stranded copper183 m (600 ft) twisted wire
0.5 mm (24 AWG) stranded copper107 m (350 ft) twisted wire
1.0 mm (18 AWG) stranded copper229 m (750 ft) twisted wire
0.8 mm (20 AWG) stranded copper137 m (450 ft) twisted wire
0.6 mm (22 AWG) stranded copper91 m (300 ft) twisted wire
0.5 mm (24 AWG) stranded copper61 m (200 ft) twisted wire
See Figure 7 to select wire size/gauge.
Use stranded copper wire
Maximum cable length
and type
457 m (1,500 ft) twisted
wire
See Figure 7 to determine
cable length. Use twisted
wire cable.
Assumptions
100 mV maximum voltage drop
Depending on cable and the connected input
or output device, you may have to define an
offset in the setup software for the input or
output point.
100 mV maximum voltage drop
Depending on cable and the connected input
or output device, you may have to define an
offset in the setup software for the input or
output point.
N/A
Maximum wire length by current and
wire size
Use the following figure to estimate the maximum
cable length relative to the wire size and the load
current (in mA) when wiring inputs and outputs.
This figure applies to low-voltage (<30 V) inputs and
outputs only.
IOM3733 Input/Output Module Installation Guide7
Figure 7: Maximum wire length for low-voltage
Inputs and Outputs by current and wire size
requirements for the communication bus and
supply power terminals; and guidelines for wire
sizes, cable types, and cable lengths when wiring
the controller's communication buses and 24 VAC
supply power.
In addition, observe these guidelines when wiring
an SA or FC bus and supply power:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All SA and FC bus cables, regardless of wire size,
should be twisted, insulated, stranded copper
wire.
Communication bus and supply power
FC bus cables.
wiring guidelines
• Refer to the MS/TP Communications Bus
• Shielded cable is strongly required for all SA and
Communications bus and supply power terminal
blocks, ratings, and requirements provides
information about the functions, ratings, and
Communications bus and supply power terminal blocks, ratings, and requirements
Table 4: Communications bus and supply power terminal blocks, functions, ratings, requirements, and
cables
Terminal block/Port
label
FC BUS
or
SA BUS
24~
Terminal labels Function, electrical ratings/Requirementsrequired cable type
+
-
COM
SHLD
or
SA PWR
HOT
COM24 VAC Power Supply - Common
FC or SA Bus Communications
Signal Reference (Common) for FC or SA Bus
communications
SHLD on FC Bus: Isolated terminal (optional
shield drain connection)
SA PWR on SA Bus: 15 VDC power lead
connection.
Note: The SA PWR terminal on an IOM
expansion module does not supply 15
VDC. The SA bus supervisor supplies 15
VDC to devices on the SA bus requiring
power.
24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24 VAC)
Technical Bulletin (LIT-12011034) for detailed
information regarding wire size and cable length
requirements for the SA and FC buses.
FC Bus: 0.6 mm (22 AWG) stranded, 3-wire
twisted, shielded cable required.
SA Bus: 0.6 mm (22 AWG) stranded, 4-wire
(2 twisted-pairs), shielded cable required.
Note: On the SA Bus, the + and - wire
are one twisted pair, and the COM
and SA PWR are the second twisted
pair of wires.
0.8 mm to 1.0 mm
(18 AWG) 2-wire
Note: See Maximum wire length by current
and wire size to determine wire size and cable
lengths for cables.
Note: The SA Bus and FC Bus wiring
recommendations in this table are for MS/
TP bus at 38,400 baud. For more information,
refer to the MS/TP Communications Bus TechnicalBulletin (LIT-12011034).
IOM3733 Input/Output Module Installation Guide8
Termination details
controllers. See the figures in this section for the
applicable termination diagrams.
A set of Johnson Controls termination diagrams
provides details for wiring inputs and outputs to the
Table 5: Termination details
Type of deviceType of Input/OutputTermination diagrams
Dry Contact (Binary Input) BI
Incremental Control to
Actuator (Switch Low,
Externally Sourced)
Incremental Control to
Actuator (Switch High,
Externally Sourced)
BO
BO
BO
IOM3733 Input/Output Module Installation Guide9
Setup and Adjustments
Setting the device address
Metasys expansion modules are master devices
on MS/TP (SA or FC) buses. Before operating an
expansion module on a bus, set a valid and unique
device address for each expansion module on
the bus. You set an expansion module's device
address by setting the positions of the switches on
the DIP switch block at the top of the expansion
module. Device addresses 4 through 127 are the
valid addresses for these expansion modules.
The following table describes the FC bus and SA
bus device addresses for Johnson Controls MS/TP
communications bus applications.
Table 6: SA/FC Bus Device Address Descriptions
Device
Address
0
(Switch 128
Off)
1-3
(Switch 128
Off)
4-127
(Switch 128
Off)
The DIP switch block has eight switches numbered
128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1
are device address switches. Switch 128 must be set
to OFF for all hard-wired SA and FC Bus applications.
Figure 8: Device address DIP switch Block set to
address 21
Use on Descriptions
Reserved for FC Bus Supervisory
Controller (not for use on
controllers or expansion modules).
Reserved for peripheral devices
(not for use on controllers or
expansion modules).
Used for MSTP master devices
(controllers and expansion
modules) that are hardwired to an
SA bus or FC bus.
Note: Metasys field controllers ship with switch
128 ON and the remaining address switches
off rendering the controllers wired subordinate
devices, which do not operate on MSTP buses,
but do not interfere with bus operation. Set
a valid and unique device address on the
expansion module before applying power to
the expansion module on the bus.
To set the device addresses on Metasys
expansion modules, complete the following
steps:
1.Set all of the switches on the address DIP
switch block (128 through 1) to OFF.
2.Set one or more of the seven address switches
(64 though 1) to ON, so that the sum of the
switch numbers set to ON equals the intended
device address, and ensure that switch 128
remains set to OFF.
Note: To do this, set the highest number switch
that is less than or equal to the intended device
address to ON. Then continue setting lower
numbered switches until the total equals the
intended address. For example, if the intended
device address is 21, set switches 16, 4, and 1 to
ON (16+4+1= 21) and all other switches to OFF.
3.Set a unique and sequential device address for
each of the expansion module connected on
the SA or FC bus, starting with device address 4.
Note: To ensure the best bus performance, set
sequential device addresses with no gaps in the
device address range (for example, 4, 5, 6, 7, 8,
9). The controllers/expansion modules do not
need to be physically connected on the bus in
their numerical device address order.
4.Write each expansion module's device address
on the white label below the DIP switch block
on the expansion module's cover.
Removing the expansion module
cover
Important: Electrostatic discharge can damage
expansion module components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the expansion module.
IOM3733 Input/Output Module Installation Guide10
Important: Disconnect all power sources to
the expansion module before removing the
cover and changing the position of any jumper
or the EOL switch on the expansion module.
Failure to disconnect power before changing
a jumper or EOL switch position can result in
damage to the expansion module and void any
warranties.
The expansion module cover is held in place by
four plastic latches that extend from the base
and snap into slots on the inside of the housing
cover.
Note: For detailed information regarding EOL
termination rules and EOL switch settings on
FC buses, refer to the MS/TP CommunicationsBus Technical Bulletin (LIT-12011034).
3.If the controller is a terminating device on
the FC bus, set the EOL switch to ON. If the
controller is not a terminating device on the
bus, set the EOL switch to Off.
When a controller is connected to power with its
EOL switch set to ON, the amber EOL LED on the
controller cover is lit.
To remove the expansion module cover,
complete the following steps:
1.Place your fingernails under the two cover
lift tabs (Figure 1) on the sides of the housing
cover and gently pry the top of the cover away
from the base to release the cover from the two
upper latches.
2.Pivot the top of the cover further to release it
from the lower two latches.
3.Replace the cover by placing it squarely over
the base, and then gently and evenly push the
cover onto the latches until they snap into the
latched position.
Setting the End-of-Line (EOL) switch
Each controller has an EOL switch, which, when set
to ON, sets the controller as a terminating device on
the bus. The default EOL switch position is OFF.
Figure 9: End-of-Line switch positions
Commissioning the Controllers
Commission BACnet MS/TP field controllers with the
controller (CCT) software, either via a Bluetooth
Wireless Commissioning Converter, a ZFR wireless
adapter (BACnet MS/TP only), or in BACnet routing
mode when connected to an NAE or NCE.
Note: N2-capable controllers do not support
Zone Bus or XT Bus. They do not support
wireless connections to the N2 Bus.
Refer to the Controller Tool Help (LIT-12011147)
for detailed information on commissioning field
controllers.
Firmware Package File
The MS-FCP-0 equipment controller firmware
package files are required for CCT to configure and
commission the controllers. The firmware package
files also allow you to upgrade an existing controller
to the latest firmware release available for that
controller.
Beginning at CCT Release 13, the firmware package
files are orderable separately; they are not included
with CCT. They are obtained from the Metasys
software licensing portal, and are loaded and
licensed on the computer/server that is running
CCT.
For additional information about the firmware
package files, refer to the CCT Installation Instructions(LIT-12011259).
®
To set the EOL switch on a field controller, complete
the following steps:
1.Determine the physical location of the field
controller on the FC bus.
2.Determine if the controller must be set as a
terminating device on the bus.
Troubleshooting
Observe the Status LEDs on the front of the
expansion module. Table 7 provides LED status
indicator information for troubleshooting the
expansion module.
LED status and states
IOM3733 Input/Output Module Installation Guide11
Table 7: Status LEDs and description of LED states
LED labelLED color
POWERGreenOn Steady
FAULTRedOff Steady
SA/FC BUSGreenBlink - 2 Hz
EOLAmber
Normal LED
state
Off (Except on
terminating
devices)
Description of LED states
Off Steady = No Supply Power. The expansion module’s
polyswitch/resettable fuse may be open. Check output wiring for
short circuits and cycle power to expansion module.
On Steady = Power Connected
Off Steady = No Faults
On Steady = Device Fault
Blink - 2 Hz = Download or Startup in progress: not ready for
normal operation
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not
supported)
On Steady = Communication lost; waiting to join communication
ring
On Steady = EOL switch in ON position
Off Steady = EOL switch in Off position
Repair information
If a controller fails to operate within its
specifications, replace the controller. For a
Table 8: Accessories Ordering Information
Product Code Number Description
Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the
Mobile Access Portal
(MAP) Gateway
TL-CCT-0Metasys Controller Configuration Tool (CCT) Software
MS-FCP-0Metasys Field Controller Firmware Package Files for CCT
TP-2420Transformer, 120 VAC Primary to 24 VAC Secondary, 20 VA, Wall Plug
Y65T31-0
AS-CBLTSTATCable adapter for connection to 8-pin TE-6700 Series sensors
AS-XFR050-0Power Transformer (Class 2, 24 VAC, 50 VA Maximum Output), no enclosure
AP-TBK4SA-0Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10
appropriate product for your region.
Note: The MAP Gateway serves as a replacement for the BTCVT, which is no
longer available for purchase, but continues to be supported.
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8
in. Primary Leads and Secondary Screw Terminals, Class 2
Note: Additional Y6x-x Series transformers are also available. Refer to the
Series Y63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755) for
more information.
replacement controller, contact your Johnson
Controls representative.
Accessories
IOM3733 Input/Output Module Installation Guide12
Table 8: Accessories Ordering Information
Product Code Number Description
AP-TBK4FC-0Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10
AP-TBK3PW-0Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack of 10
IOM3733 Input/Output Module Installation Guide13
Technical specifications
Table 9: IOM3733 technical specifications
MS-IOM3733-0 Input/Output Expansion Module
Product Code Number
Power Requirement
Power Consumption14 VA maximum
Ambient Conditions
Addressing
Communications Bus
ProcessorRX631 Renesas® 32-bit microcontroller
Memory4 MB external serial flash memory and 768 KB internal flash and 128 KB internal RAM
Input and Output Capabilities
Terminations
Mounting
Housing
Dimensions (Height x Width x Depth)
Weight0.5 kg (1.1 lb)
Compliance
Note: This model is only available in certain regions. Contact your local Johnson
Controls representative for more information.
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
Operating: 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing
Storage: -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing
DIP switch set; valid expansion module device addresses 4–127 (Device addresses 0–3 and
128–255 are reserved and not valid expansion module addresses.)
BACnet MS/TP, RS-485:
3-wire FC bus between the supervisory controller and expansion modules (for MS/TP bus
communications at 38,400 baud)
4-wire SA bus between expansion module, network sensors and other sensor/actuator
devices, includes a lead to source 15 VDC supply power (from controller or expansion
module) to bus devices (for MS/TP bus communications at 38,400 baud)
8 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator
Mode
8 - Binary Outputs: Defined as 24 VAC Triac (external source power only)
Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface
with three integral mounting clips on expansion module
150 mm x 164 mm x 53 mm (5-7/8 in. x 6-1/2 in. x 2-1/8 in.) including terminals and
mounting clips
Note: Mounting space requires an additional 50 mm (2 in.) space on top, bottom
and front face of the expansion module for easy cover removal, ventilation and wire
terminations.
United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada Compliant, ICES-003
Europe: Johnson Controls declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
BACnet International: BACnet Testing Laboratories (BTL) Protocol Revision 15 Listed and
Certified BACnet Smart Actuator (B-SA)
The performance specifications are nominal and
conform to acceptable industry standard. For
application at conditions beyond these specifications,
consult the local Johnson Controls® office. Johnson
IOM3733 Input/Output Module Installation Guide14
Controls shall not be liable for damages resulting from
misapplication or misuse of its products.
Product warranty
This product is covered by a limited
warranty, details of which can be found at
www.johnsoncontrols.com/buildingswarranty.
Single point of contact
APACEuropeNA/SA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 32 CHANGJIJANG RD NEW
DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
For more contact information, refer to
www.johnsoncontrols.com/locations.