IOM1711 and IOM2711 Input/Output Module Installation
Instructions
MS-IOM1711-0U, MS-IOM2711-0U
Part No. 24-10144-246, Rev. A
Software Release 8.1
Issued March 2018
Application
The IOM1711 and IOM2711 input/output expansion
modules are part of the Metasys® system Field
Equipment Controller family. Input/Output Module (IOM)
expansion modules expand the number of points
connected to a Network Automation Engine (NAE), Field
Equipment Controller (FEC), VAV Modular Assembly
(VMA), or Advanced Application Field Equipment
Controller (FAC) to monitor and control a wide variety of
HVAC equipment.
IOM field controllers operate on an RS-485 BACnet®
MS/TP Bus and integrate into Johnson Controls® and
third-party BACnet systems.
Important: The MS-IOM171x-0U and MS-IOM271x-0U
models are used in Metasys Release 8.1
smoke control applications and are UL 864
UUKL/UUKLC 10th Edition Smoke Control
Listed. You must refer to the Metasys®
System UL 864 10th Edition
UUKL/ORD-C100-13 UUKLC Smoke
Control System Technical Bulletin
(LIT-12012487) for detailed requirements
and procedures for installing,
commissioning, and operating UL 864
UUKL/UUKLC Listed Metasys system
devices. The UL 864 UUKL/UUKLC listing
for Smoke Control Equipment is voided if
(1) you do not use the required software
tools at the required versions; or (2) you do
not meet the requirements or do not follow
the procedures as documented in the
Metasys® System UL 864 10th Edition
UUKL/ORD-C100-13 UUKLC Smoke
Control System Technical Bulletin
(LIT-12012487).
Note: With CCT Release 10.3 and Release Module (RM)
10.2, a new capability allows VMAs, FECs, and
FACs to communicate by using either the BACnet
or the N2 field bus networking protocol. The
operation of the IOM Input/Output Module is not
affected by the selection of the BACnet or the N2
protocol in the host controller when the IOM is
connected to the host controller using the SA bus.
Only the BACnet protocol is supported when the
IOM is connected directly to the trunk using the
FC bus.
North American Emissions
Compliance
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes
les exigences du Règlement sur le matériel brouilleur
du Canada.
United States
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction
manual, may cause harmful interference to radio
communications. Operation of this equipment in a
residential area may cause harmful interference, in which
case the users will be required to correct the interference
at their own expense.
1IOM1711 and IOM2711 Input/Output Module Installation Instructions
Installation
Observe these guidelines when installing a field controller:
•Transport the controller in the original container to
minimize vibration and shock damage.
•Verify that all parts shipped with the controller.
•Do not drop the controller or subject it to physical
shock.
Parts Included
•one controller with removable terminal blocks (Power
and SA/FC bus are removable)
•one installation instructions sheet
Materials and Special Tools Needed
•three fasteners appropriate for the mounting surface
(M4 screws or #8 screws)
•one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
•small straight-blade screwdriver for securing wires in
the terminal blocks
Observe these additional guidelines when mounting a
field controller in a panel or enclosure:
•Mount the controller so that the enclosure walls do
not obstruct cover removal or ventilation through the
controller.
•Mount the controller so that the power transformer
and other devices do not radiate excessive heat to
the controller.
•Do not install the controller in an airtight enclosure.
Figure 1: Controller Mounting Positions
Mounting
Observe these guidelines when mounting a field
controller:
•Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.
•Mount the controller horizontally on 35 mm DIN rail
whenever possible.
•Mount the controller in the proper mounting position
(see Figure 1).
•Mount the controller on a hard, even surface
whenever possible in wall-mount applications.
•Use shims or washers to mount the controller securely
and evenly on the mounting surface.
•Mount the controller in an area free of corrosive
vapors and observe the Ambient Conditions
requirements in Technical Specifications.
•Provide for sufficient space around the controller for
cable and wire connections for easy cover removal
and good ventilation through the controller (50 mm
[2 in.] minimum on the top, bottom, and front of the
controller).
•Do not mount the controller on surfaces prone to
vibration, such as duct work.
•Do not mount the controller in areas where
electromagnetic emissions from other devices or
wiring can interfere with controller communication.
DIN Rail Mount Applications
Mounting the controller horizontal on 35 mm DIN rail is
the preferred mounting method.
To mount a field controller on 35 mm DIN rail:
1. Securely mount a 20 cm (8 in.) or longer section of
35 mm DIN rail horizontal and centered in the desired
space so that the controller mounts in the horizontal
position shown in Figure 1.
2. Pull the bottom mounting clip outward from the
controller to the extended position as shown in Figure
2.
3. Hang the controller on the DIN rail by the hooks at
the top of the (DIN rail) channel on the back of the
controller (Figure 2), and position the controller snugly
against the DIN rail.
4. Push the bottom mounting clip inward (up) to secure
the controller on the DIN rail.
To remove the controller from the DIN rail, pull the
bottom mounting clip out to the extended position and
carefully lift the controller off the DIN rail.
Wall Mount Applications
To mount a field controller directly on a wall or other flat
vertical surface:
2IOM1711 and IOM2711 Input/Output Module Installation Instructions
1. Pull the bottom mounting clip outward and ensure it
is locked in the extended position as shown in Figure
2.
2. Position the controller in a proper mounting position
shown in and mark the mounting hole locations on
the wall or surface using the dimensions shown in
Figure 2. Or, hold the controller up to the wall or
surface in a proper mounting position and mark the
hole locations through the mounting clips.
3. Drill holes in the wall or surface at the marked
locations, and insert appropriate wall anchors in the
holes (if necessary).
4. Hold the controller in place, and insert the screws
through the mounting clips and into the holes (or wall
anchors). Carefully tighten all of the screws.
Important: Do not overtighten the mounting screws.
Overtightening the screws may damage
the mounting clips.
Figure 2: Back of IOM17 or IOM27 Controller Showing
Extended Mounting Clips, DIN Rail Channel, and
Mounting Dimensions, mm (in.)
3IOM1711 and IOM2711 Input/Output Module Installation Instructions
Figure 3: IOM1711 and IOM2711 Physical Features
Table 1: IOM17 and IOM27 Physical Features
Physical Feature: Description and ReferencesCallout
1
3
4
5
6
7
8
9
10
11
12
Device Address DIP Switch Block. See Setting the Device Addresses for more information.
Mounting Clip2
24 VAC, Class 2 Supply Power Terminal Block. See Table 5 for more information.
Cover Lift Tab. See Removing the Controller Cover for more information.
Sensor Actuator (SA) Bus / Field Controller (FC) Bus Terminal Block. See Table 5 for more information.
Binary Inputs (BIs) Terminal Block (IOM17 only). See Table 3 for more information.
End-of-Line (EOL) Switch. See Setting the End-of-Line (EOL) Switch for more information.
Note: The EOL Switch is located under the controller cover. You must remove the cover to change the EOL
switch position.
Sensor Actuator (SA) Bus or Field Controller (FC) Bus Port (RJ-12 6-pin Modular Jack). See Table 5 for more
information.
Light-Emitting Diode (LED) Status Indicators. See Table 7 for more information.
Universal Outputs (UO) Terminal Blocks (IOM27 only). See Table 3 for more information.
Universal Inputs (UI) Terminal Blocks (IOM27 only). See Table 3 for more information.
Relay Output Terminal Blocks (IOM27 only). See Table 3 for more information.
4IOM1711 and IOM2711 Input/Output Module Installation Instructions
Wiring
Risk of Electric Shock: Disconnect or isolate all power
supplies before making electrical connections. More than
one disconnection or isolation may be required to
completely de-energize equipment. Contact with
components carrying hazardous voltage can cause
electric shock and may result in severe personal injury
or death.
Avertissement: Risque de décharge électrique:
Débrancher ou isoler toute alimentation avant de réaliser
un branchement électrique. Plusieurs isolations et
débranchements sont peut-être nécessaires pour
-couper entièrement l'alimentation de l'équipement. Tout
contact avec des composants conducteurs de tensions
dangereuses risque d'entraîner une décharge électrique
et de provoquer des blessures graves, voire mortelles.
Risk of Property Damage: Do not apply power to the
system before checking all wiring connections. Short
circuited or improperly connected wires may result in
permanent damage to the equipment.
Terminal Blocks and Bus Ports
See Figure 3 for terminal block and bus port locations on
the controller. Observe the following guidelines when
wiring a controller.
Input and Output Terminal Blocks
Most of the input terminal blocks are mounted on the
bottom of the controller and the output terminal blocks
are mounted on the top of the controller. See Table 3 for
more information about I/O terminal functions,
requirements, and ratings.
SA/FC Bus Terminal Block
An IOM can be connected to a Sensor/Actuator (SA) bus
or a Field Controller (FC) bus, but not to both buses
simultaneously. The SA/FC bus terminal block is a
removable, 4-terminal plug that fits into a board-mounted
jack.
When connecting the IOM to an FC bus, wire the bus
terminal block plugs on the controller and the other
controllers in a daisy-chain configuration using 3-wire
twisted, shielded cable as shown in the FC Bus Terminal
Block wiring figure below. See Table 5 for more
information.
Figure 4: FC Bus Terminal Block Wiring
Mise En Garde: Risque de dégâts matériels: Ne pas
mettre le système sous tension avant d'avoir vérifié tous
les raccords de câblage. Des fils formant un court-circuit
ou connectés de façon incorrecte risquent
d'endommager irrémédiablement l'équipement.
Important: Do not exceed the controller electrical
ratings. Exceeding controller electrical
ratings can result in permanent damage to
the controller and void any warranty.
Important: Use copper conductors only. Make all wiring
in accordance with local, national, and
regional regulations.
Important: Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
For detailed information on configuring and wiring an
MS/TP Bus, FC bus, and SA bus, refer to the MS/TPCommunications Bus Technical Bulletin (LIT-12011034).
When connecting the IOM to an SA bus, wire the bus
terminal block plugs on the controller and other SA bus
devices in a daisy-chain configuration using 4-wire
twisted, shielded cable as shown in Figure 5. See Input
and Output Wiring Guidelines for more information.
5IOM1711 and IOM2711 Input/Output Module Installation Instructions
Figure 5: SA Bus Terminal Block Wiring
Note: The SA PWR/SHLD terminal does not supply 15
VDC. The SA PWR/SHLD terminal is isolated and
can be used to connect (daisy chain) the 15 VDC
power leads on the SA bus (Figure 5) or the cable
shields on the FC bus (Figure 4). The SA bus
supervisor (FAC, FEC, or VMA) supplies 15 VDC
to devices on the SA Bus requiring power.
Supply Power Terminal Block
The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a board-mounted
jack on the top right of the controller.
Wire the 24 VAC supply power wires from the transformer
to the HOT and COM terminals on the terminal plug as
shown in the following figure. The middle terminal on the
supply power terminal block is not used. See Table 5 for
more information about the Supply Terminal Block.
Figure 7: 24 VAC Supply Power Terminal Block Wiring
SA/FC Bus Port
The SA/FC bus port on the front of the controller is an
RJ-12, 6-position modular jack that provides a connection
for devices on the SA bus.
The SA/FC bus port is connected internally to the SA/FC
bus terminal block. See Table 5 for more information.
The SA/FC Bus Port pin assignment is shown in the Pin
Number Assignments figure below.
Figure 6: Pin Number Assignments for Sensor, SA
Bus and FC Bus Ports on Controllers
Important: Connect 24 VAC supply power to the
controller and all other network devices so
that transformer phasing is uniform across
the network devices. Powering network
devices with uniform 24 VAC supply power
phasing reduces noise, interference, and
ground loop problems. The controller does
not require an earth ground connection.
Wireless Network Applications
Important: Wireless operation is not approved for
smoke control applications. Refer to the
Metasys® System UL 864 10th Edition
UUKL/ORD-C100-13 UUKLC Smoke
Control System Technical Bulletin
(LIT-12012487) for detailed requirements
and procedures for installing,
commissioning, and operating UL 864
UUKL/UUKLC Listed Metasys system
devices.
6IOM1711 and IOM2711 Input/Output Module Installation Instructions
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.