This chapter describes the purpose and contents of this
manual, the receiving inspection recommendations and
the variable frequency drive catalog numbering system.
How to Use this Manual
The purpose of this manual is to provide you with information
necessary to install, set and customize parameters, start up,
troubleshoot and maintain the
variable frequency drive (VFD).
To provide for safe installation and operation of the
equipment, read the safety guidelines at the beginning of this
manual and follow the procedures outlined in the following
chapters before connecting power to the VFD. Keep this
operating manual handy and distribute to all users,
technicians and maintenance personnel for reference.
Receiving and Inspection
The Variable Speed Drives Series III has met a stringent
series of factory quality requirements before shipment. It is
possible that packaging or equipment damage may have
occurred during shipment. After receiving your VFD, please
check for the following:
Check to make sure that the package includes the Instruction
Leaflet, Quick Start Guide, and accessory packet. The
accessory packet includes:
●
Rubber grommets
●
Control cable grounding clamps
●
Additional grounding screw
Inspect the unit to ensure it was not damaged during
shipment.
Make sure that the part number indicated on the nameplate
corresponds with the catalog number on your order.
If shipping damage has occurred, please contact and file a
claim with the carrier involved immediately.
If the delivery does not correspond to your order, please
contact your sales representative.
Note: Do not destroy the packing. The template printed on
the protective cardboard can be used for marking the
mounting points of the VFD on the wall or in a cabinet.
Real Time Clock Battery Activation
To activate the real time clock (RTC) functionality in the
VFD
, the RTC battery (already mounted in the drive) must
be connected to the control board.
Simply remove the primary drive cover, locate the RTC
battery directly below the keypad, and connect the white
2-wire connector to the receptacle on the control board.
Figure 1. RTC Battery Connection
Table 1. Common Abbreviations
AbbreviationDefinition
CTConstant torque with high overload rating (150%)
VTVariable torque with low overload rating (110%)
I
H
I
L
VFDVariable Frequency Drive
High Overload (150%)
Low Overload (110%)
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com1
Page 4
Step 1—Variable Speed Drives Series III Overview
Programmable
Soft Key 2
Change Control
Place to Auto
Move Cursor
Right
Start/Hand Button
Stop/Off Button
Back/Reset
Button
Increase
Value Scroll
Menu Up
Programmable
Soft Key 1
Decrease Value
Scroll Menu Down
Move Cursor
Left
Enter Menu
Conrm Selection
Rating Label
Figure 2. Rating Label
Keypad Overview
Figure 3. Keypad and Display
Carton Labels (U.S. and Europe)
Same as rating label shown above.
2Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 5
Step 2—Keypad Operation Overview
The keypad is the interface between the drive and the user.
It features an LCD display, 3 LED lights and 11 buttons. With
the control keypad, it is possible to control the speed of a
motor, to supervise the state of the equipment and to set the
frequency converter’s parameters. See Figure 3.
Keypad Buttons
Step 2—Keypad Operation Overview
Buttons Description
Table 2. Keypad Buttons
IconButtonDescription
Soft Key 1,
Soft Key 2
Back/ResetBack/Reset:
AutoAuto:
Soft Key 1, Soft Key 2:
The functions of these two buttons shall be the following:
Forward/Reverse, this shall change motor’s run direction.
Reset, this shall ask MCU to reset after some parameters are modified.
• Menu, this shall return to main menu.
• Details, this shall display the details of the fault.
• Bypass, this shall make drive go into bypass.
• Jog, this shall activate jog.
• Favorite, this shall add this parameter to the Favorite menu.
• Delete, this shall delete this parameter from the Favorite menu.
This button has three integrated functions. The button operates as backward button during
normal mode.
In edit mode, it is used as cancel operate. It is also used to reset faults when faults occur.
• Backs up one step.
• Cancels Modify in edit mode.
• Resets the active faults (all the active faults shall be reset by pressing this button
more than 2s in any page).
This button switches the drive into the auto control place.
Up
Down
Up and Down Arrows:
• Move either up or down a menu list to select the desired menu item.
• Editing a parameter bit by bit, while the active digit is scrolled.
• Increase/decrease the reference value of the selected parameter.
• In parameter comparison mode, scroll through the parameters of which current value
is different from comparison parameter value.
• In parameter page when in read mode, move to the previous or next brother
parameter of this parameter.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com3
Page 6
Step 2—Keypad Operation Over view
Table 2. Keypad Buttons, continued
IconButtonDescription
LeftLeft Arrow:
• Navigation button, movement to left when editing a parameter digit by digit.
• Backs up one step.
RightRight Arrow:
• Enter parameter group mode.
• Enter parameter mode from group mode.
• Enter parameter whole edit mode when this parameter can be written.
• Enter parameter bit by bit edit mode from whole edit mode.
• Navigation button, movement to right when editing a parameter bit by bit.
OKOK:
• To clear all the Fault History if pressed for more than 5s (including 5s) in any page.
• This button is used in the parameter edit mode to save the parameter setting.
• To confirm the start-up list at the end of the Start-Up Wizard.
• To confirm the comparison item in parameters comparison mode.
The following is the same with Right key:
• Enter parameter whole edit mode when this parameter can be written.
• Enter parameter group mode.
• Enter parameter mode from group mode.
Stop/OffStop/Off:
This button operates as the motor stop button for normal operation and places the drive in the
off control location. The Default is for this button to always be active. It can be changed in
Parameter P4.1.3 to only when “Keypad” is selected as the control source.
• Motor stop from the keypad.
• Transitions drive into an Off control location preventing start from any control source.
Start/HandStart/Hand:
This button operates as motor start button for normal operation when the “Keypad” is
selected as the active control source, as well as selects the Hand control place location.
• When Keypad is the reference place after hitting the start button, it will jump directly
to the Keypad Ref Screen.
• Places drive into Hand Control place. Hitting start again if keypad is in the control
location will start the Drive.
4Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 7
Step 2—Keypad Operation Overview
Drive Status
Direction Status
Control Place
Menu Location
Soft Key 2
Function Label
Soft Key 1
Function Label
Real Time Clock
(hh:mm)
Active
Selection
LED Lights
Table 3. LED State Indicators
IndicatorDescription
Run:
Indicates that the VFD is running and controlling the load in
Run
Drive or Bypass.
Blinks when a stop command has been given but the drive is
still ramping down.
Fault:
Turn on when there is one or more active drive fault(s).
Fault
Hand/OFF/Auto:
Hand: If the Hand or Off control place is selected,
Auto
turn off the light.
Auto: If the Auto control place is selected, turn on the light.
LCD Display
The keypad LCD indicates the status of the motor and the
drive and any faults in motor or drive functions. On the LCD,
the user sees information about the current location in the
menu structure and the item displayed.
Overview
Five lines shall be displayed in the screen. General view is as
following in Figure 4.
Figure 4. General View of LCD
The lines definition is as below:
The first line is State line, shows:
●
RUN / STP / NRD / FIM / TFM—If motor is running, the
run state shall display “RUN”, otherwise the state display
“STP”. “RUN” blinks when the stop command is sent but
the drive is decelerating. “NRD” is displayed if the drive is
not ready or does not have a signal. “FIM” is displayed to
indicate it is in Fire Mode and the drive is in a Run state.
“TFM” is displayed when in the Fire Mode Test Mode and
the drive is in a Run State.
●
FWD / REV / JOG—If the motor running the direction is
clockwise, it displays “FWD”, other wise displays “REV”
for counter clockwise. If “Jog” is displayed, it indicates
Jog mode is active.
●
KEY / I/O / BPS / RBP / BUS / OFF—If it is in bypass
currently, display “BPS”; when run command is given, it
will go to “RBP”; otherwise, if the current control source
is I/O terminal, display “I/O”. If it is keypad, then display
“KEY”; otherwise display “BUS.” When indicates “OFF”, it
indicates the drive will not accept a command from the
Hand or Auto Control place.
●
PAR / MON / FLT / OPE / QSW / FAV / TPM / BUx—
If the current page is parameter menu, display “PAR”;
If monitor menu, then display “MON”; If fault menu, then
display “FLT”; If operation menu, then display “OPE”;
If quick start wizard, then display “QSW”; If optional card
menu, then display “BOA”; If favorite menu, then display
“FAV”; If main menu, then display “TPM”. “BUx” indicates
the drive being a backup drive when in the redundant drive
system.
The second line is Code line, which shows the menu code.
The third line is Name line, which shows the menu name or
parameters name.
The fourth line is Value line, which shows the submenu
name or parameters value.
The fifth line is Soft key line, the functions of Soft key 1 and
Soft key 2 are changeable, and the real time is in the middle.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com5
Page 8
Step 3—Menu Navigation
Step 3—Menu Navigation
Menu Structure
Table 4. Keypad Menu
Item DescriptionItem Description
MonitorM1—BasicFaultF1—Active Fault
M2—IO StatusF2—History Fault
M3—Optional BoardsF3—Fault Log
M4—Energy savingsOption BoardsB1—Slot A
M5—FB Monitor MenuB2—Slot B
M6—PID MonitorFavorite
M7—Timer/Interval ControlOperate ModeO1—Output Frequency
M8—User Defined OutputO2—Freq Reference
M9—MWH MonitorO3—Motor Speed
M10—Multi-MonitoringO4—Motor Current
ParametersP1—Basic ParameterO5—Motor Torque
P2—InputsO6—Motor Power
P3—OutputsO7—Motor Voltage
P4—Drive ControlO8—DC-link Voltage
P5—Motor ControlO9—Unit Temperature
P6—ProtectionsO10—Motor Temperature
P7—PID Controller 1R11—Keypad Reference
P8—PID Controller 2R12—PID1 Keypad Set Point 1
P9—Fire ModeR13—PID1 Keypad Set Point 2
P10—BypassStartup WizardS—Startup Wizard
P11—Real Time Clock
P12—Communication
P13—System
Note: Will vary depending on application selected.
6Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 9
Menu Navigation
Back/left keyRight/OK key
UP key
Down key
M – Monitor
P – Parameters
F – Fault
B – Optional Boards
T – Favorite
O – Operate Mode
…
…
…
M1 – Basic
M10 – Multi-Monitoring
P1 – Basic Parameters
P13 – System
F1 – Active Fault
F2 – History Fault
P1.1 – Min Frequency
P1.16 – Auto 2 Reference
M1.1
S – Startup Wizard
F3 – Fault Log
Output Frequency
0.00 Hz
P1.1
Min Frequency
0.00 Hz
This section provides basic instruction on navigating each
section in the menu structure.
Figure 5. Main Menu Navigation
Step 3—Menu Navigation
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com7
Page 10
Step 4—Startup Wizard
Step 4—Startup Wizard
Startup Wizard
In the Startup Wizard, you will be prompted for essential
information needed by the drive so that it can start
controlling your process. In the Wizard, you will need
the following keypad buttons:
Up/Down buttons.
Use these to change value.
OK button.
Confirm selection with this button, and enter into
next question.
Back/Reset button.
If this button was pressed at the first question,
the Startup Wizard will be cancelled.
Once you have connected power to your frequency
converter, and the Startup Wizard is enabled, follow
these instructions to easily set up your drive.
Now the Startup Wizard is done. It won’t show again when
next power up. If you want to reset it, please set the Startup
Wizard (P13.1.17) or select it from the main menu screen to
enable and cycle the power to the drive.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com9
Page 12
Step 5—Standard Parameter List
Step 5—Standard Parameter List
Introduction
The Basic Application is designed for preloaded application
sets for use with HVAC specific terminology and functions.
It has the patent Active Energy Control algorithm that will
improve your efficiency as well as minimize losses in your
motor throughout the defined speed range. It provides the
ability for the user to define its Hand and Auto control and
reference signals with the standard Off condition as well.
In addition there is the ability to scale the analog input and
output signals to be read based off the desired motor
response. There are also 8 digital inputs, 3 relay outputs, and
1 digital output that can be programmed to allow for control
schemes that require the drive to have certain functions. It
provides full customization on the motor control sequence
with the ability to be in frequency or speed control mode, and
tuning of the V/Hz curve can be selected. Drive/Motor
protections can be customized to defined actions for added
user control. Below is a list of other features that are
available in the Basic Application.
Basic Application includes functions:
●
Bypass control
●
Fire mode
●
Pre heat/cold weather mode
●
Hand/Off/Auto in individual button for easy change of
control mode
●
Programmable protections
●
Programmable digital/analog input/output function
●
Programmable start/stop signal logic
●
Voltage and current limiters
●
Energy Savings Calculator
●
Two independent set of Acceleration/Deceleration ramps
●
Skip frequency
●
Start source (Local/Remote control function)
●
Reference source
●
Flying start
●
Volts per Hertz control programmable
●
Real time clock—RTC time display
●
Auto restart on fault to drive or bypass
●
Programmable switching frequency
●
Multi-preset speeds
●
Fan control
●
DC brake
I/O Controls
“Terminal To Function” (TTF) Programming
The design behind the programming of the digital inputs in
the DH1 drive is to use “Terminal To Function”
programming, which is composed of multiple functions that
get assigned a digital input to that function. The parameters
in the drive are set up with specific functions and by defining
the digital input and slot in some cases, depending on which
options are available. For use of the drives control board
inputs, they will be referred to as DigIN:1 through DigIN:8.
When additional option cards are used, they will be defined
as DigIN:X:IOY:Z. The X indicates the slot that the card is
being installed in, which will be either A or B. The IOY
determines the type of card it is, which would be IO1 or IO5.
The Z indicates which input is being used on that available
option card.
“Function To Terminal” (FTT) Programming
The design behind the programming of the relay outputs and
digital output in the DH1 drive is to use “Function To
Terminal” programming. It is composed of a terminal, be it a
relay output or a digital output, that is assigned a parameter.
Within that parameter, it has different functions that can be
set.
The parameters of the Standard Application are explained in
Appendix A of application manual.
The explanations are arranged according to the parameter
number. For the DI function, we use Terminal programming
method to function (TTF), where there is a fixed input that
gets programmed to a list of functions. This allows for
multiple inputs to be used for different functions. Connecting
a certain input with a certain parameter function is done by
give a parameter an appropriate value. The value is formed
by the location of the input, either being on the standard
control board or an external option board and the slot it is
located in.
10Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 13
Step 5—Standard Parameter List
Force Open/Force Close Selection
The Force Open Selection would make the selected function
always off. Essentially this is a virtual switch that is always
open. The Force Close Selection would make the selected
function always on. Essentially this is a virtual switch that is
always closed. These options are assigned to a function if we
want to force a state without using a hardware input.
The standard options are DigIn: Force Open—indication that
the parameter function is always going to be open, that being
said depending on the logic of the function this could mean
the function is always not active or always active. When the
selection of a function is DigIN: Force Closed—indication that
the parameter function is always going to be closed, that
being said again depending on the location of the function
this could mean the function is always active or not active.
Examples of these options would be ID190 Start Signal 1,
when set to “Force Open” and the drive is
looking at I/O terminals for control, in this case the drive
would never start since this Function is always Open. If this
function is set to “Force closed” the drive would always be
in a start mode when in that control location.
Example:
If we set Run Enable to Force Closed the drive is always
enabled. If we set the same function to Force Open the drive
would never be Enabled. If a Digital input is to be used to
activate this Run Enable the function should be assigned to
a hardware input (See below for DIGIN Selections).
DIGIN Selection
This allows Assignment of a hardware digital input to a
function, this is set in a format of DigIN:X where X is one
of the 8 Digital inputs on the Main control board.
Example:
If we set Run Enable to DigIN:6 the drive will be enabled
when digital input 6 (Terminal 8) is closed, and would not
be enabled when digital input 6 (Terminal 8) is open.
Option Board digIN Selection
This allows Assignment of a hardware digital input on an
option card to a function, this is set in a format of DigIN:
Y:IO1:X where Y is the slot the option card is inserted on the
Main control board and X is the Input on the Board and IO1 is
the type of option board used.
Example:
If we set Run Enable to DigIN:A:IO5:6 the drive will be
enabled when digital input 6 is closed on the IO5 option card
which is inserted in Slot A, and would not be enabled when
digital input 6 on the option card is open.
Timer Channel Selection
A Time Channel is a virtual path to link the digital output of a
timer function to a digital input function. To utilize this feature
a timer or interval would need to be assigned to a time
channel 1 through 3, and the input function to be controlled
would need to be assigned to the same time channel.
Example:
If we set Run Enable to DigIN:TimeChannel1 the drive will be
enabled when the timer assigned to Time Channel 1 is active
or High, and would not be enabled when the Time Channel is
inactive or Low.
Table 6. Drive Communication Ports
PortCommunication
RJ45 Keypad Port
Upload/Download Parameters USB to RJ45
Remote Mount Keypad Ethernet
Upgrade Drive Firmware USB to RJ45
RJ45 Ethernet Port
Upload/Download ParametersEthernet
BACnet/IP Communications Ethernet
Modbus TCP Communications Ethernet
RS-485 Serial Port
Upload/Download Parameters
Upgrade Drive FirmwareTwo-Wire Twisted Pair
Modbus RTU CommunicationsTwo-Wire Twisted Pair
BACnet MS/TP CommunicationsTwo-Wire Twisted Pair
SA BusTwo-Wire Twisted Pair
Note
1
Shielded wire recommended.
1
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com11
Page 14
Step 5—Standard Parameter List
Control I/O Configuration
●
Run 240 Vac and 24 Vdc control wiring in separate conduit
●
Communication wire to be shielded
Table 7. Analog Signals/Galaxy I/O Interface
External
Wiring
1
Signal
Pin
NameSignal
1+10VRef. Output Voltage—10 Vdc Supply Source
Res
2AI1+
2
Analog Input 10–10VVoltage Speed Reference (Programmable to 4 mA to 20 mA)
3AI1–Analog Input 1 Ground—Analog Input 1 Common (Ground)
4AI2+
i
5AI2–Analog Input 2 Ground—Analog Input 2 Common (Ground)
2
Analog Input 24 mA to 20 mACurrent Speed Reference (Programmable to 0–10V)
6GNDI/O Signal Ground—I/O Ground for Reference and Control
7DIN5Digital Input 5Preset Speed B0Sets frequency output to Preset Speed 1
8DIN6Digital Input 6Fire ModeEnables drive into Fire Mode
9DIN7Digital Input 7Bypass Start (TI–)Enables drive into Bypass mode waiting for drive start
10DIN8Digital Input 8Force Auto (TI+)Input forces drive into Auto Control place
11CMBDI5 to DI8 CommonGroundedAllows source input
12GNDI/O Signal Ground—I/O Ground for Reference and Control
1324V+24 Vdc Output—Control voltage output (100 mA max.)
14DO1Digital Output 1ReadyShows the drive is ready to run
1524Vo+24 Vdc Output—Control voltage output (100 mA max.)
16GNDI/O Signal Ground—I/O Ground for Reference and Control
17AO1+Analog Output 1Output FrequencyShows Output frequency to motor 0–60 Hz (4 mA to 20 mA)
18AO2+Analog Output 2Motor CurrentShows Motor current of motor 0–FLA (4 mA to 20 mA)
1924Vi+24 Vdc Input—External control voltage input
20DIN1Digital Input 1Run ForwardInput starts drive in forward direction (start enable)
21DIN2Digital Input 2Run ReverseInput starts drive in reverse direction (start enable)
22DIN3Digital Input 3External FaultInput causes drive to fault
23DIN4Digital Input 4Fault ResetInput resets active faults
24CMADI1 to DI4 CommonGroundedAllows source input
25A/+RS-485 Signal A—Fieldbus Communication (Modbus, BACnet, SA Bus)
26B/–RS-485 Signal B—Fieldbus Communication (Modbus, BACnet, SA Bus)
27R3NORelay 3 Normally OpenFaultRelay output 3 shows VFD is Faulted
28R1NCRelay 1 Normally ClosedBypass RunRelay output 1 shows VFD is in a bypass run state
29R1CMRelay 1 Common
30R1NORelay 1 Normally Open
31R3CMRelay 3 CommonFaultRelay output 3 shows VFD is Faulted
32R2NCRelay 2 Normally ClosedRun Relay output 2 shows VFD is in a drive run state
33R2CMRelay 2 Common
34R2NORelay 2 Normally Open
Notes
1
The above wiring demonstrates a SINK configuration. It is important that CMA and CMB are wired to ground (as shown by dashed line).
If a SOURCE configuration is desired, wire 24 V to CMA and CMB and close the inputs to ground. When using the +10 V for AI1, it is
important to wire AI1—ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered together.
2
AI1+ and AI2+ support 10K potentiometer.
Default
SettingDescription
12Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 15
Step 5—Standard Parameter List
Basic Application—Parameters List
On the next pages you will find the lists of parameters within the respective parameter
groups. The parameter descriptions are given in Appendix A of application manual. The
descriptions are arranged according to the parameter number.
Column explanations:
Code = Location indication on the keypad; shows the operator the present parameter number
Parameter = Name of parameter
Min = Minimum value of parameter
Max = Maximum value of parameter
Unit = Unit of parameter value; given if available
Default = Value preset by factory
ID = ID number of the parameter
Monitor
Table 8. Basic—M1
CodeParameterMin.Max.UnitDefaultIDNote
M1.1Output FrequencyHz1
M1.2Freq ReferenceHz24
M1.3Motor Speedrpm2
M1.4Motor CurrentA3
M1.5Motor Torque%4
M1.6Motor Power%5
M1.7Motor VoltageV6
M1.8DC-link VoltageV7
M1.9Unit Temperature°C8
M1.10Motor Temperature%9
M1.11Latest Fault Code28
M1.12Instant Motor PowerkW1686
M1.13RTC Battery Status5830 = Not Installed
1 = Installed
2 = Change Battery
3 = OverVoltage
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com13
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 16
Step 5—Standard Parameter List
Table 9. IO Status—M2
CodeParameterMin.Max.UnitDefaultIDNote
M2.1Analog Input 1Varies10
M2.2Analog Input 2Varies11
M2.3Analog Output 1Varies25
M2.4Analog Output 2Varies575
M2.5DI1, DI2, DI312
M2.6DI4, DI5, DI613
M2.7DI7, DI8576
M2.8DO1,Virtual RO1,Virtual RO214
M2.9RO1, RO2, RO3557
Table 10. Optional Boards—M3
CodeParameterMin.Max.UnitDefaultIDNote
M3.1PT100 Temperature°C1000.027
Table 11. Energy Savings—M4
CodeParameterMin.Max.UnitDefaultIDNote
2
M4.1
Energy SavingsVaries0.0002120
Table 12. FB Monitor Menu—M5
CodeParameterMin.Max.UnitDefaultIDNote
M5.1Control Board DIDO Status2209Bit 0 = DIN1 Status
Bit 1 = DIN2 Status
Bit 2 = DIN3 Status
Bit 3 = DIN4 Status
Bit 4 = DIN5 Status
Bit 5 = DIN6 Status
Bit 6 = DIN7 Status
Bit 7 = DIN8 Status
Bit 8 = DO1 Status
Bit 9 = RO1 Status
Bit 10 = RO2 Status
Bit 11 = RO3 Status
Bit 12 = Slot A with Board
Bit 13 = Slot B with Board
Bit 14–15 = Not used
3
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
14Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 17
Step 5—Standard Parameter List
Table 11. FB Monitor Menu—M5, continued
CodeParameterMin.Max.UnitDefaultIDNote
M5.2SlotA DIDO Status2210Bit 0 = IO1_DIN1 Status
M5.3SlotB DIDO Status2211Bit 0 = IO1_DIN1 Status
M5.4Application Status Word29Bit 0 = MC Ready
Bit 1 = IO1_DIN2 Status
Bit 2 = IO1_DIN3 Status
Bit 3 = IO1_DO1 Status
Bit 4 = IO1_DO2 Status
Bit 5 = IO1_DO3 Status
Bite 6 = IO3_RO1 Status
Bit 7 = IO3_RO2 Status
Bit 8 = IO3_RO3 Status
Bit 9 = IO5_AC1 Status
Bit 10 = IO5_AC2 Status
Bit 11 = IO5_AC3 Status
Bit 12 = IO5_AC4 Status
Bit 13 = IO5_AC5 Status
Bit 14 = IO5_AC6 Status
Bit 15 = Not Used
Bit 1 = IO1_DIN2 Status
Bit 2 = IO1_DIN3 Status
Bit 3 = IO1_DO1 Status
Bit 4 = IO1_DO2 Status
Bit 5 = IO1_DO3 Status
Bite 6 = IO3_RO1 Status
Bit 7 = IO3_RO2 Status
Bit 8 = IO3_RO3 Status
Bit 9 = IO5_AC1 Status
Bit 10 = IO5_AC2 Status
Bit 11 = IO5_AC3 Status
Bit 12 = IO5_AC4 Status
Bit 13 = IO5_AC5 Status
Bit 14 = IO5_AC6 Status
Bit 15 = Not Used
Bit 1 = MC_Run
Bit 2 = MC_Fault
Bit 3 = FB_Ref_Active
Bit 4 = MC_Stopping
Bit 5 = MC_Reverse
Bit 6 = MC_Warning/AR-Fault
Bit 7 = MC_ZeroSpeed
Bit 8 = I/O Control Indicate
Bit 9 = Panel Control Indicator
Bit 10 = Panel Fieldbus Indicator
Bit 11 = MC_DC_Brake
Bit 12 = RunEnable
Bit 13 = Run Bypass
Bit 14 = Ext Brake Control
Bit 15 = Bypass Mode
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com15
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 18
Step 5—Standard Parameter List
Table 11. FB Monitor Menu—M5, continued
CodeParameterMin.Max.UnitDefaultIDNote
M5.5Standard Status Word2414Bit 0 = See PAR ID 2415
Table 13. User Defined Output—M8
CodeParameterMin.Max.UnitDefaultIDNote
M8.1OutputVaries2445
M8.2ReferenceVaries2447
(default = Ready)
Bit 1 = See PAR ID 2416
(default = Run)
Bit 2 = See PAR ID 2417
(default = Fault)
Bit 3 = See PAR ID 2418
(default = Fault Invert)
Bit 4 = See PAR ID 2419
(default = Warning)
Bit 5 = See PAR ID 2420
(default = Reversed)
Bit 6 = See PAR ID 2421
(default = At Speed)
Bit 7 = See PAR ID 2422
(default = Zero Frequency)
Bit 8–15 = Not Used
Table 14. MWH Monitor—M9
CodeParameterMin.Max.UnitDefaultIDNote
M9.1Total MWh CountMwh601
M9.2Total Power Day Count603
M9.3Total Power Hr Count606
M9.4Trip MWh CountMwh604
M9.5Trip Power Day Count636
M9.6Trip Power Hr Count637
Table 15. Multi-Monitoring—M10
CodeParameterMin.Max.UnitDefaultIDNote
M10.1Multi-Monitoring0, 1, 230
3
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
16Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com21
Page 24
Step 5—Standard Parameter List
Table 22. Digital Output—P3.1, continued
CodeParameterMin.Max.UnitDefaultIDNote
2
P3.1.1
,
continued
P3.1.2
P3.1.3
P3.1.4
P3.1.5
P3.1.6
P3.1.7
P3.1.8
P3.1.9
P3.1.10
P3.1.11
P3.1.12
P3.1.13
DO1 Function115125 = Fire Mode
2
RO1 Function62152See Par ID 151
2
RO1 On Delay0.0320.0s0.02112
2
RO1 Off Delay0.0320.0s0.02113
2
RO2 Function2153See Par ID 151
2
RO2 On Delay0.0320.0s0.02114
2
RO2 Off Delay0.0320.0s0.02115
2
RO3 Function3538See Par ID 151
2
RO3 On Delay0.0320.0s0.02116
2
RO3 Off Delay0.0320.0s0.02117
2
RO3 Reverse021180 = No
2
Virtual RO1 Function02463See Par ID 151
2
Virtual RO2 Function02464See Par ID 151
26 = In Bypass Mode
27 = Ext Fault/Warning
28 = Auto Control
29 = Jog Speed Select
30 = Motor Therm Protection
31 = FB Digital Input 1
32 = FB Digital Input 2
33 = FB Digital Input 3
34 = FB Digital Input 4
40 = Power Limit Superv
41 = Temp Limit Superv
42 = Analog Input Superv
51 = Motor Current 1 Supv
52 = Motor Current 2 Supv
53 = Second AI Limit Supv
54 = DC Charge Switch Close
55 = Preheat Active
56 = Cold Weather Active
58 = 2th Stage Ramp Frequency
58 = Active
59 = STO Fault Output
60 = Run Bypass/Drive
61 = Bypass Overload
62 = Bypass Run
1 = Yes
Table 23. Supervisions—P3.2
CodeParameterMin.Max.UnitDefaultIDNote
2
P3.2.1
Freq Limit 1 Supv01540 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
2
P3.2.2
P3.2.3
P3.2.4
P3.2.5
P3.2.6
P3.2.7
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
22Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Freq Limit 1 Supv Val0.00See Par ID 102 Hz0.00155
2
Freq Limit 1 Supv Hyst0.101.00Hz0.102200
2
Freq Limit 2 Supv0157See Par ID 154
2
Freq Limit 2 Supv Val0.00See Par ID 102 Hz0.00158
2
Freq Limit 2 Supv Hyst0.101.00Hz0.102201
2
Torque Limit Supv0159See Par ID 154
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 25
Step 5—Standard Parameter List
Table 23. Supervisions—P3.2, continued
CodeParameterMin.Max.UnitDefaultIDNote
2
P3.2.8
P3.2.9
P3.2.10
P3.2.11
P3.2.12
P3.2.13
P3.2.14
P3.2.15
P3.2.16
P3.2.17
P3.2.18
P3.2.19
P3.2.20
P3.2.21
P3.2.22
P3.2.23
P3.2.24
P3.2.25
P3.2.26
P3.2.27
P3.2.28
P3.2.29
P3.2.30
P3.2.31
P3.2.32
Torque Limit Supv Val-1000.01000.0%100.0160
2
Torque Limit Supv Hyst1.05.0%1.02202
2
Ref Limit Supv0161See Par ID 154
2
Ref Limit Supv Val0.00See Par ID 102 Hz0.00162
2
Ref Limit Supv Hyst0.101.00Hz0.102203
2
Temp Limit Supv0165See Par ID 154
2
Temp Limit Supv Val-10.075.0°C40.0166
2
Temp Limit Supv Hyst1.010.0°C1.02204
2
Power Limit Supv0167See Par ID 154
2
Power Limit Supv Val-200.0200.0%0.0168
2
Power Limit Supv Hyst0.110.0%0.12205
2
AI Supv Select01700 = AI1
2
AI Limit Supv0171See Par ID 154
2
AI Limit Supv Val0.00100.00%0.00172
2
AI Supv Hyst1.0010.00%1.002198
2
Motor Current 1 Supv02189See Par ID 154
2
Motor Current 1 Supv Value 0.0DriveNomCurr
ADriveNomCurrCT2190
CT*2
2
Motor Current 1 Supv Hyst 0.11.0A0.12196
2
Motor Current 2 Supv02191See Par ID 154
2
Motor Current 2 Supv Value 0.0DriveNomCurr
ADriveNomCurrCT2192
CT*2
2
Motor Current 2 Supv Hyst 0.11.0A0.12197
2
Second AI Supv Select02193See Par ID 170
2
Second AI Limit Supv02194See Par ID 154
2
Second AI Limit Supv Val0.00100.00%0.002195
2
Second AI Supv Hyst1.0010.00%1.002199
1 = AI2
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com23
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 26
Step 5—Standard Parameter List
Table 24. Analog Output 1—P3.3
CodeParameterMin.Max.UnitDefaultIDNote
2
P3.3.1
P3.3.2
P3.3.3
P3.3.4
P3.3.5
P3.3.6
P3.3.7
AO1 Mode0227See Par ID 222
2
AO1 Function11460 = Not Used
2
AO1 Minimum11490 = 0 V / 0 mA
2
AO1 Filter Time0.0010.00s1.00147
2
AO1 Scale101000%100150
2
AO1 Inversion0148See Par ID 181
2
AO1 Offset-100.00100.00%0.00173
1 = Output Frequency
2 = Freq Reference
3 = Motor Speed (0–Nom)
4 = Motor Current (0–Nom)
5 = Motor Torque (0–Nom)
6 = Motor Power (0–Nom)
7 = Motor Voltage (0–Nom)
8 = DC-Bus Voltage
19 = AI1
20 = AI2
21 = Output Freq (-2-+2N)
22 = Motor Torque (-2-+2N)
23 = Motor Power (-2-+2N)
24 = PT100 Temperature
33 = SlotA PT100 Temp Channel 1
34 = SlotA PT100 Temp Channel 2
35 = SlotA PT100 Temp Channel 3
36 = SlotB PT100 Temp Channel 1
37 = SlotB PT100 Temp Channel 2
38 = SlotB PT100 Temp Channel 3
39 = User Defined Output
40 = Motor Current (-2-+2N)
1 = 2 V / 4 mA
Table 25. Analog Output 2—P3.4
CodeParameterMin.Max.UnitDefaultIDNote
2
P3.4.1
P3.4.2
P3.4.3
P3.4.4
P3.4.5
P3.4.6
P3.4.7
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
AO2 Mode0228See Par ID 222
2
AO2 Function4229See Par ID 146
2
AO2 Minimum1232See Par ID 149
2
AO2 Filter Time0.0010.00s1.00230
2
AO2 Scale101000%100233
2
AO2 Inversion0231See Par ID 181
2
AO2 Offset-100.00100.00%0.00234
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
24Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 27
Step 5—Standard Parameter List
Drive Control
Table 26. Basic Setting—P4.1
CodeParameterMin.Max.UnitDefaultIDNote
2
P4.1.1
P4.1.2
P4.1.3
P4.1.4
P4.1.5
P4.1.6Change PhaseSequence
P4.1.7
P4.1.9
P4.1.10
P4.1.11
P4.1.12
P4.1.13
P4.1.14
P4.1.15
P4.1.16
P4.1.17
P4.1.18
Keypad ReferenceSee Par ID 101 See Par ID 102 Hz0.00141
2
Keypad Direction01160 = Forward
1 = Reverse
2
Keypad Stop11140 = Enabled-Keypad Operation
1 = Always Enabled
2
Hand Key Enable017240 = Enabled
1 = Disabled
1
Reverse Enable016790 = Disabled
1 = Enabled
025150 = Change Disable
Motor
2
Power Up HOA Select016850 = Hold Last
1 = Change Enable
1 = Hand Control
2 = Auto control
3 = Off
2
Run Delay Time032500s02423
2
Start Mode02520 = Ramp
1 = Flying Start
2
Stop Mode02530 = Coasting
1 = Ramp
2
Ramp 1 Shape0.010.0s0.0247
2
Ramp 2 Shape0.010.0s0.0248
2
Accel Time 20.13000.0s10.0249
2
Decel Time 20.13000.0s10.0250
2
Power Loss Function0267See Par ID 1679
2
Power Loss Time0.35.0s2.0268
1 2
2nd Stage Ramp Frequency See Par ID 101 See Par ID 102 Hz30.002444
24 = Thermistor Fault Output
25 = Fire Mode
26 = In Bypass Mode
27 = Ext Fault/Warning
28 = Auto Control
29 = Jog Speed Select
30 = Motor Therm Protection
31 = FB Digital Input 1
32 = FB Digital Input 2
33 = FB Digital Input 3
34 = FB Digital Input 4
40 = Power Limit Superv
41 = Temp Limit Superv
42 = Analog Input Superv
51 = Motor Current 1 Supv
52 = Motor Current 2 Supv
53 = Second AI Limit Supv
54 = DC Charge Switch Close
55 = Preheat Active
56 = Cold Weather Active
58 = 2th Stage Ramp Frequency
58 = Active
59 = STO Fault Output
60 = Run Bypass/Drive
61 = Bypass Overload
62 = Bypass Run
22416See Par ID 2415
32417See Par ID 2415
42418See Par ID 2415
52419See Par ID 2415
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com33
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 36
Step 5—Standard Parameter List
Table 38. FB Process Data Output Sel—P12.2, continued
CodeParameterMin.Max.UnitDefaultIDNote
P12.2.14 2Standard Status Word Bit5
Function Select
2
P12.2.15
Standard Status Word Bit6
Function Select
2
P12.2.16
Standard Status Word Bit7
Function Select
RS-485 Bus
Table 39. Basic Setting—P12.3.1
CodeParameterMin.Max.UnitDefaultIDNote
1
P12.3.1.1
Table 40. Modbus RTU—P12.3.2
CodeParameterMin.Max.UnitDefaultIDNote
P12.3.2.1
P12.3.2.2
P12.3.2.3
P12.3.2.4Modbus RTU Protocol
P12.3.2.5Comm Timeout Modbus RTU 060000ms10000593
P12.3.2.6Modbus RTU Fault
RS485 Comm Set05860 = Modbus RTU
1
Slave Address12471587
1
Baud Rate15840 = 9600
1
Parity Type25850 = None
Status
Response
62420See Par ID 2415
72421See Par ID 2415
82422See Par ID 2415
1 = BACnet MS/TP
2 = SA Bus
1 = 19200
2 = 38400
3 = 57600
4 = 115200
1 = Odd
2 = Even
5880 = Initial
1 = Stopped
2 = Operational
3 = Faulted
025160 = in Fieldbus Control
1 = in all Control
Table 41. BACnet MS/TP—P12.3.3
CodeParameterMin.Max.UnitDefaultIDNote
1
P12.3.3.1
MSTP Baud Rate25940 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
1
P12.3.3.2
P12.3.3.3
MSTP Device Address01271595
1
MSTP Instance Number041943020596
P12.3.3.4MSTP Comm Timeout060000ms10000598
P12.3.3.5MSTP Protocol Status5990 = Stopped
1 = Operational
2 = Faulted
3
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
34Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 37
Step 5—Standard Parameter List
Table 41. BACnet MS/TP—P12.3.3, continued
CodeParameterMin.Max.UnitDefaultIDNote
P12.3.3.6MSTP Fault Code6000 = None
2
P12.3.3.7
P12.3.3.8
MSTP Fault Response02526See Par ID 2516
1
MSTP Max Master1271537
Table 42. SA Bus—P12.3.4
CodeParameterMin.Max.UnitDefaultIDNote
12
P12.3.4.1
P12.3.4.2
P12.3.4.3
P12.3.4.4
SA Bus Baud Rate21727See Par ID 584
12
SA Bus Device Address2042542041726
12
SA Bus Instance Number0419430201728
2
SA Bus Comm Timeout060000100001730
P12.3.4.5SA Bus Protocol Status1731See Par ID 599
2
P12.3.4.6
SA Bus Fault Response01732See Par ID 2516
1 = Sole Master
2 = Duplicate MAC ID
3 = Baud rate fault
EtherNet Bus
Table 43. Basic Setting—P12.4.1
CodeParameterMin.Max.UnitDefaultIDNote
1
P12.4.1.1
P12.4.1.2Active IP Address1507
P12.4.1.3Active Subnet Mask1509
P12.4.1.4Active Default Gateway1511
P12.4.1.5MAC Address1513
P12.4.1.6
P12.4.1.7
P12.4.1.8
P12.4.1.9
Table 44. Modbus TCP—P12.4.2
CodeParameterMin.Max.UnitDefaultIDNote
P12.4.2.1Connection Limit5609
P12.4.2.2Modbus TCP Unit ID1610
P12.4.2.3Comm Timeout Modbus TCP 060000ms10000611
P12.4.2.4Modbus TCP Protocol Status612See Par ID 599
P12.4.2.5Modbus TCP Fault Response02517See Par ID 2516
IP Address Mode115000 = Static IP
1 = DHCP with AutoIP
1
Static IP Address192.168.1.2541501
1
Static Subnet Mask255.255.255.01503
1
Static Default Gateway192.168.1.11505
1
Enable BACnetIP01725See Par ID 1679
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com35
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 38
Step 5—Standard Parameter List
Table 45. BACnet IP—P12.4.3
CodeParameterMin.Max.UnitDefaultIDNote
1 2
P12.4.3.1
P12.4.3.2
P12.4.3.3
P12.4.3.4
P12.4.3.5
P12.4.3.6
P12.4.3.7BACnet IP Protocol Status1740See Par ID 599
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
38Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 41
Step 5—Standard Parameter List
Table 47. Version Info—P13.2
CodeParameterMin.Max.UnitDefaultIDNote
P13.2.1Keypad Software Version640
P13.2.2Motor Control Software
Version
P13.2.3Application Software
Version
P13.2.4Software Bundle Version1714
Table 48. Application Info—P13.3
CodeParameterMin.Max.UnitDefaultIDNote
P13.3.1Brake Chopper646See Par ID 2118
P13.3.2Brake Resistor Status647See Par ID 2118
P13.3.3Serial Number648
Table 49. User Info—P13.4
CodeParameterMin.Max.UnitDefaultIDNote
P13.4.1Real Time Clock0.0.0.1:1:13566
P13.4.2Daylight Saving05820 = Off
P13.4.3Total MWh CountMwh601
P13.4.4Total Power Day Count603
P13.4.5Total Power Hr Count606
P13.4.6Trip MWh CountMwh604
P13.4.7Clear Trip MWh Count635See Par ID 2125
P13.4.8Trip Power Day Count636
P13.4.9Trip Power Hr Count637
P13.4.10Clear Trip Power Count639See Par ID 2125
642
644
1 = EU
2 = US
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com39
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Page 42
Appendix A—Fault and Warning Codes
Appendix A—Fault and Warning Codes
Under this menu, you can find Active faults, History faults and Fault codes.
Table 50. Active Faults
MenuFunctionNote
Active FaultsWhen a fault/faults appear(s), the display with the name and fault time of
the fault will be pop. Press DETAIL to see the fault data.
The Active Faults submenu shows the list of faults. Select the fault and
push DETAIL to see the fault data.
Table 51. History Faults
MenuFunctionNote
History Faults10 latest faults are stored in the Fault history, Select the fault and push
DETAIL to see the fault data.
Fault Codes and Descriptions
Configurable1 = The fault type of this fault is configurable, fault type can be configured as
0 = No Action; 1 = Warning; 2 = Fault; 3= Fault, Coast
The fault remains active until it is cleared with the Reset button
(push for 2s) or with a reset signal from the I/O terminal or Fieldbus.
The memory of active faults can store the maximum of 10 faults in
the order of appearance.
The history fault will be stored until it is cleared with the OK button
(push for 5s).
The memory of active faults can store the maximum of 10 faults in
the order of appearance.
Table 52. Fault Codes and Descriptions
Fault
CodeFault NameFault Type
1Over CurrentFaultAC drive has detected too high a current
2Over VoltageFaultThe DC-link voltage has exceeded the
3Earth FaultConfigurableFaultCurrent measurement has detected that
5Charging SwitchFault The charging switch is open, when the
7Saturation TripFault• Short circuit in motor cables
Default
Fault TypePossible CauseRemedy
(>4*IH) in the motor cable:
• Sudden heavy load increase
• Short circuit in motor cables
• Unsuitable motor
limits defined:
• Too short a deceleration time
• Brake chopper is disabled
• High overvoltage spikes in supply
• Start/Stop sequence too fast
the sum of motor phase current is not zero:
• Insulation failure in cables or motor
START command has been given:
• Faulty operation
• Component failure
• IGBT module is damaged
• Check loading
• Check motor
• Check cables and connections
• Make identification run
• Check ramp times
• Make deceleration time longer
• Use brake chopper or brake resistor
(available as options)
• Activate overvoltage controller
• Check input voltage
Check motor cables and motor
• Reset the fault and restart
• Should the fault re-occur, contact the
distributor near you
Check cables and connections
Reset the fault and restart
Verify that EMC screw is installed
Should the fault re-occur, contact the
distributor near you
40Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 43
Appendix A—Fault and Warning Codes
Table 52. Fault Codes and Descriptions, continued
Fault
CodeFault NameFault Type
9UnderVoltageConfigurableFaultDC link voltage is under the voltage limits
10Input Phase SupervConfigurableFaultInput line phase is missingCheck supply voltage, fuses and cable
11Output Phase Superv ConfigurableFaultCurrent measurement has detected that there
12Brake Chopper
Superv
13Drive UnderTempConfigurableWarningToo low temperature measured in power
14Drive OverTempFaultToo high temperature measured in power
15Motor StalledConfigurableNo ActionMotor is stalledCheck motor and load
16Motor Over TempConfigurableNo ActionMotor is too hot, based on either the drive’s
17Motor Under LoadConfigurableNo ActionCondition defined by parameter
18IP Address ConflictConfigurableWarningIP setting issue.Check settings for IP address, verify no
19Power Board
EEPROM Fault
20FRAM FaultFaultFRAM data error in FRAM memory.Cycle power to drive. Try updating
21S-Flash FaultwarningSerial flash error, serial flash memory failed. Cycle power to drive. Try updating
25MCU WatchDog Fault FaultWatchdog register overflows in MCU Cycle power to drive. Try updating
26Start-up PreventFault The time when Interlock signal activates is
29Thermistor FaultConfigurableFaultOption board or control board thermistor
32Fan CoolingFaultFan is damaged or stalled.Check fan and fan connected wires, verify
Fault• No brake resistor installed
FaultPower board EEPROM fault, memory lost in
Default
Fault TypePossible CauseRemedy
In case of temporary supply voltage break,
defined:
• Most probable cause: Too low a supply
voltage
• AC drive internal fault
• Defect input fuse
• External charge switch not closed
Note: This fault is activated only if the drive is
in Run state.
is no current in one motor phase
• Brake resistor is broken
• Brake chopper failure
unit’s heat sink or board. Heat sink
temperature is under –10°C
unit’s heat sink or board. Heat sink
temperature is over 90°C
estimate or on temperature feedback
P6.1.11~P6.1.13 have been valid longer than
the time defined by P6.1.14
EEPROM.
over setting time.
resistor lager than 4.7K
reset the fault and restart the AC drive
Check the supply voltage. If it is adequate,
an internal failure has occurred. Contact
the distributor near you
Check motor cable and motor
Check brake resistor and cabling. If these
are OK, the chopper is faulty. Contact the
distributor near you
• Check the correct amount and flow of
cooling air
• Check the heat sink for dust
• Check the ambient temperature
• Make sure that the switching frequency
is not too high in relation to ambient
temperature and motor load
Decrease motor load. If no motor overload
exists, check the temperature model
parameters
Check load
duplicates are on the network.
Cycle power to drive. Try updating
software. If issue continues, contact
distributor near you.
software. If issue continues, contact
distributor near you.
software. If issue continues, contact
distributor near you.
software. If issue continues, contact
distributor near you.
Stop drive and resend start command.
Thermistor open or short, over temperature
24 Vdc is supplied to fan.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com41
Page 44
Appendix A—Fault and Warning Codes
Table 52. Fault Codes and Descriptions, continued
Fault
CodeFault NameFault Type
36Compatibility FaultFaultThe control board isn’t matched with the
37Device ChangeWarningPower board or option card change.Alarm will reset
38Device AddedWarningPower board or option board added.Device is ready for use
39Device RemovedFaultOptional board removed from slot, or power
41IGBT Over TempFaultIGBT temperature is too high.• Check output loading
50AI < 4mA (4to20mA) ConfigurableNo ActionLoss in analog input signal, dropped below
51External FaultConfigurableFaultDigital input is activated for external fault
52Keypad Comm Fault ConfigurableFaultThe connection between the control keypad
54Option Card FaultConfigurableFaultDefective option card or option card slotCheck right option card and option card
55Realtime Clock Fault ConfigurableWarning• Communication between MCU and RTC
56PT100 FaultConfigurableFaultTemperature is beyond the limit of sensing
57Motor ID faultFaultThe Motor parameters Identification running
58Current Measure
Fault
59Power Wiring ErrorFaultPower wiring connected to output of drive.Verify power input wiring is connected to
60Control Board
OverTemp
61Internal Control
Supply
62Speed Search FaultFaultSpeed searching failed when performing
64Replace BatteryConfigurableWarningRTC battery voltage is too low.Check the RTC battery voltage, contact
FaultCurrent measurement is out of rangeRestart the drive again. Should the fault
FaultControl board is over +85 degrees or under
Fault+24V port voltage is over 27V or under 17VCheck voltage range of +24V on terminals
Default
Fault TypePossible CauseRemedy
power board.
board removed from control board.
option board)
4mA.
input.
and frequency converter is broken when the
local reference is keypad or the local control
place is keypad.
chip isn’t normal
• The power of RTC chip isn’t normal
• The real time isn’t normal
capacity of PT100
was not completed successfully
–30 degrees
flying start.
Cycle power to drive. Try updating
software. If issue continues, contact
distributor near you.
Old parameter settings will be used
Device no longer available in drive.
Check EEPROM connection.
Check board connection on slot A/B
Power cycle to drive.
• Check motor size
• Decrease switching frequency
Verify analog input current reference value
on either AI1 or AI2, check cabling.
Check digital input settings and verify input
level, could be an external device causing
fault.
Check keypad connection and possible
keypad cable.
slot connections.
Check Board Status on Keypad for exact
cause of fault.
Contact distributor nearest you.
Check the RTC chip, power cycle to drive. If
issue continues, contact distributor near
you.
PT100 short, open or over temperature,
check PT100 temperature probe.
Check motor size
Verify the input and output wiring is
connected properly.
re-occur, contact the distributor near you
L1, L2 and L3 terminals and that they are
properly torqued.
Check NTC resistor
Check control board temperature
12 to 13. If voltage is out of range, contact
distributor near you.
Check motor parameters’ setting and
tor connectio
mo
distributor near you for replacement
battery.
ns.
42Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 45
Appendix A—Fault and Warning Codes
Table 52. Fault Codes and Descriptions, continued
Fault
CodeFault NameFault Type
65Replace FanConfigurableWarningFan life is less than 2 monthsCheck the fan, clean out any
66Safety Torque OffFaultSTO Triggered, STO input is open.Reset STO Trigger and verify wiring. Reset
67Current Limit Control WarningThe output current has reached the current
68Over Voltage Control WarningThe DC link voltage has reached its voltage
69System FaultFaultThermistor SPI communication error.Check thermistor chip.
70System FaultFaultMCU send wrong parameters to DSP.Restart the drive again. Should the fault
80FieldBus FaultConfigurableFaultLoss of communication with BACnet/IP, and
81FieldBus FaultConfigurableFaultLoss of communication with SA Bus, and the
82Bypass OverloadFaultOver load when motor is in bypass modeCheck motor connection situation
83FieldBus FaultConfigurableFaultLoss of communication with Modbus RTU, and
84FieldBus FaultConfigurableFaultLoss of communication with Modbus TCP, and
85FieldBus FaultConfigurableFaultLoss of communication with BACnet, and the
86FieldBus FaultConfigurableFaultLoss of communication with EtherNet/IP, and
87FieldBus FaultConfigurableFaultLoss of communication with Profibus/
88FieldBus FaultConfigurableFaultLoss of communication with Profibus/
89Under Voltage Stop FaultThe DC link voltage has reached the Drive
Default
Fault TypePossible CauseRemedy
contamination, contact distributor near you
for replacement fan.
fault after input is enabled.
limit value
limit value
the fieldbus reference is the remote reference
OR the fieldbus control place is the remote
control place
fieldbus reference is the remote reference OR
the fieldbus control place is the remote
control place
the fieldbus reference is the remote reference
OR the fieldbus control place is the remote
control place
the fieldbus reference is the remote reference
OR the fieldbus control place is the remote
control place
fieldbus reference is the remote reference OR
the fieldbus control place is the remote
control place, and the fault protection is not
“NO action”
the fieldbus reference is the remote reference
OR the fieldbus control place is the remote
control place, and the fault protection is not
“NO action”
CANopen/DeviceNet master on Slot A, and
the fieldbus reference is the remote reference
OR the fieldbus control place is the remote
control place, and the fault protection is not
“NO action”
CANopen/DeviceNet master on Slot B, and
the fieldbus reference is the remote reference
OR the fieldbus control place is the remote
control place, and the fault protection is not
“NO action”
under voltage stop limit value.
Check the load
Set the acceleration time longer
Check the input voltage
Set the acceleration/deceleration time
longer
re-occur, contact the distributor near you.
Check RS-485 communication wiring.
Verify drive parameters are set correctly.
Check master programming to verify proper
addressing.
Check RS-485 communication wiring.
Verify drive parameters are set correctly.
Check master programming to verify proper
addressing.
Check RS-485 communication wiring.
Verify drive parameters are set correctly.
Check master programming to verify proper
addressing.
Check Ethernet communication wiring.
Verify drive parameters are set correctly.
Check master programming to verify proper
addressing.
Check RS-485 communication wiring.
Verify drive parameters are set correctly.
Check BACnet master configuration
programming to verify proper addressing.
Check Ethernet communication wiring.
Verify drive parameters are set correctly.
Check EIP master configuration
programming to verify proper addressing.
Check Profibus/CANopen/DeviceNet
communication wiring. Verify drive
parameter are set correctly. Check
Profibus/CANopen/DeviceNet master
configuration
addressing.
Check Profibus/CANopen/DeviceNet
communication wiring. Verify drive
parameter are set correctly. Check
Profibus/CANopen/DeviceNet master
configuration programming to verify proper
addressing.
Check the input voltage.
programming to verify
proper
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com43
Page 46
Appendix A—Fault and Warning Codes
Table 52. Fault Codes and Descriptions, continued
Fault
CodeFault NameFault Type
90Drive Under TempWarning/Fault• Cold weather mode is not enabled, and
91Option Card FaultConfigurableFaultExternal supply on the DeviceNet
92External Fault 2ConfigurableFaultDigital input is activated for external
93External Fault 3ConfigurableFaultDigital input is activated for external
103Drive OverTemp
Warning
104Compatibility FaultWarningDSP firmware is not compatible with
105Compatibility FaultWarningKeypad firmware is not compatible with
106Compatibility FaultWarningIO1 card firmware is not compatible with
107Compatibility FaultWarningIO2 card firmware is not compatible
108Compatibility FaultWarningIO3 card firmware is not compatible
109Compatibility FaultWarningIO4 card firmware is not compatible
110Compatibility FaultWarningIO5 card firmware is not compatible
111Compatibility FaultWarningProfibus card firmware is not compatible
WarningDrive degree greater than
Default
Fault TypePossible CauseRemedy
unit temperature is less than -10 degree.
• Cold weather mode is enabled and Under
Temp Fault Override is not set, unit
temperature is less than -30 degree.
• Cold weather mode is enabled and Under
Temp Fault Override is not set, unit
temperature is -20~ -30 degree. The temp
<-20 degree when cold weather start
times out.
communication connector is not present.
fault input.
fault input.
(DCI_wDriveOverTempThreshold value -10
degree) and less than
DCI_wDriveOverTempThreshold value,report
drive over temperature warning.
MCB firmware
MCB firmware
MCB firmware
with MCB firmware
with MCB firmware
with MCB firmware
with MCB firmware
with MCB firmware
If unit temp -20 ~ -10 degree, start motor in
cold weather mode.
If unit temp <-20°, warm up unit above
-20°C for proper operation using cold
weather mode.If still < -20° when cold
weather mode times out, try higher output
voltage in cold weather mode.
Check voltage and wiring of power supply
of the DeviceNet communication.
Check digital input settings and verify input
level, could be an external device causing
fault.
Check digital input settings and verify input
level, could be an external device causing
fault.
Check the drive degree
Check the DSP firmware revision
Check the keypad firmware revision
Check the IO1 card firmware revision
Check the IO2 card firmware revision
Check the IO3 card firmware revision
Check the IO4 card firmware revision
Check the IO5 card firmware revision
Check the Profibus card firmware revision
44Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Page 47
Page 48
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com