Johnson Controls Hx-68P3 Series Installation Guide

Hx-68P3 Series Outside Humidity and Temperature
24- 9647- 10, Rev. B
Transmitters
Installation Instructions
HE-68P3-0N000, HT-68P3-0N000
Refer to the QuickLIT website for the most up-to-date version of this document.

Application Requirements

The Hx-68P3 Series Outside Humidity and Temperature Transmitter measures and transmits outside relative humidity (RH) from 0 to 100% and temperatures from -40 to 140 addition to RH, the transmitter offers selectable parameters including dew point, wet bulb temperature, and enthalpy.
The integral weather shield provides ventilation, blocks direct and reflected solar radiation, and blocks precipitation without affecting performance. Mount the transmitter outside on a pole or on a side of a building.
IMPORTANT: The Hx-68P3 Series Outside
Humidity and Temperature Transmitter is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the humidity and temperature transmitter could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the humidity and temperature transmitter.
F (-40 to 60C). In
Part No. 24-9647-10, Rev. B
Issued March 2016

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case users will be required to correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
IMPORTANT: Le Hx-68P3 Series Outside Humidity
and Temperature Transmitter est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du humidity and temperature transmitter risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du humidity and temperature transmitter.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation
1
Instructions
Figure 1: Hx-68P3 Series Outside Humidity and Temperature Transmitter Features
FIG:Features
Radiation Shield
Radiation Shield Screws
Humidity Sensor and Temperature Sensor
(Under PTFE Membrane Filt er)
Transmi tter
Body
Screw
Te rm i na l
DIP
Switches
Pole Mounting
Screw
Pole
Mounting
Clamp
Set Screw
Cable Gland
Transmitter
Cover
Transmi tter
Cover Screw (Captured)

Installation

Parts Included

relative humidity and temperature transmitter with
conduit adaptor
weather shield
pole mounting clamp with screws (wall mount
installation instructions

Tools Needed

medium Phillips screwdriver
small slotted screwdriver
cable gland
screws and anchors not included)
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions2
wire cutters
open-ended wrench
zip ties
cable clips

Dimensions

Figure 2: Hx-68P3 Series Outside Humidity and Temperature Transmitter Dimensions, in. (mm)
4-7/8 (122)
10-3/8 (264)
FIG:Dimensio ns
Cable Gland Suitable for
5/32 to 5/16 (4 to 8) Cable
Diameter 3/32 to 2-11/32 (25 to 60)
Diameter 7/32 (6)
Figure 3: DIP Switch Positions
Non-Metric
Td
h
Tw
Metric
RH
RH
RH

DIP Switch Settings

The DIP switches on the component board control the humidity output parameter and scaling. Figure 3 shows the default DIP switch settings.
Change the position of the DIP switches to the desired setting.
Table 1: DIP Switch Positions for Metric Output
DIP Switch Position Analog Output
Parameter and Scaling
Relative Humidity (RH) 0 to 100%
Temperature (T)
-40 to 60C
Dewpoint (Td)
-40 to 60C
Temperature (T)
-40 to 60C
Enthalpy (h)
-40 to 460kJ/kg
Temperature (T)
-40 to 60C
Wet Bulb Temperature (Tw)
-40 to 60C
Temperature (T)
-40 to 60C
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions 3
Table 2: DIP Switch Positions for Non-Metric
Figure 4: Conduit Adaptor
FIG:NAAdaptor
Adaptor
Nut
!
Figure 5: Preparing the Transmitter for Mounting
FIG:Terminal
Cable Gland (Shown)
Screw Terminal
Output
DIP Switch Position Analog Output
Parameter and Scaling
Relative Humidity (RH) 0 to 100%
4. Manually tighten the adaptor into the nut, turning in a clockwise direction.
5. Tighten the adaptor onto the adaptor body, turning in a clockwise direction.

Mounting

Temperature (T)
-40 to 140F
Dewpoint (Td)
-40 to 140F
Temperature (T)
-40 to 140F
Enthalpy (h)
-10 to 190 BTU/lb
Temperature (T)
-40 to 140F
Wet Bulb Temperature (Tw)
-40 to 140F
Temperature (T)
-40 to 140F

Installing the Conduit Adaptor - Optional

Using the conduit adaptor is optional. If you do not use
the conduit adaptor, proceed to Mounting
.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.

Location Considerations

Install the transmitter in a place that receives minimal direct sunlight.
Avoid placing the transmitter near windows, air conditioning units, or other heat and moisture sources such as cooling towers.
Install the transmitter at least 8 ft (2.5 m) above the ground.
IMPORTANT: To minimize the time spent working
on a ladder, prepare the transmitter configuration and wiring before mounting the transmitter.
To install the conduit adaptor, follow these steps.
1. Loosen the six captive screws that hold the transmitter cover in place. See Figure 5.
2. Unscrew the cable gland from the transmitter cover. See Figure 1 for the location of the cable gland.
3. Align the nut with the opening inside the transmitter cover, and insert the adaptor body into the transmitter conduit opening.
1. Loosen the six captive screws that hold the transmitter cover in place.
2. Be sure the DIP switches are set to the desired
setting. See DIP Switch Settings
.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions4
3. Route the power and signal cable through the
Figure 6: Pole Installation
FIG:Pole
Figure 7: Securing Cable to a Pole
FIG:Cable Pole
Figure 8: Wall Installation, in. (mm)
3-15/16 (100)
Diameter 7/ 32 (6)
FIG:Wall
cable gland or the conduit adaptor to the screw terminals, and connect the wires.
4. Disconnect the terminal block by pulling it away from the component board.
5. Adjust the cable length between the cable gland and the terminal block. Make sure the cover closes without leaving a loop within the transmitter.
6. Tighten the cable gland or conduit adaptor.
IMPORTANT: Do not attach the cover to the
transmitter until the transmitter has been mounted on the pole or wall.

Pole Mounting

IMPORTANT: We recommend a pole diameter of
2-11/32 to 3-3/32 in. (25 to 60 mm) if you use the supplied clamp and screws.
5. Secure the cable to the pole using cable ties. Incorporate a drip loop below the cable gland to prevent water from running into the transmitter along the cable.
To mount the Hx-68P3 Series Outside Humidity and Temperature Transmitter to a pole:
1. Attach the clamp to the pole with the set screw. See Figure 6.
2. Align the transmitter mounting bracket with the holes on the clamp, and insert the screws through the holes of the transmitter mounting bracket and into the clamp.
3. Tighten the screws securing the transmitter assembly onto the pole.
4. Plug in the screw terminal block (terminal screws facing the transmitter cover), close the cover, and tighten the cover screws. See Figure 5 for plugging in the terminal block and attaching the cover.

Wall Mounting

To mount the Hx-68P3 Series Outside Humidity and Temperature Transmitter to a wall:
1. Drill two holes for the wall plugs 3-15/16 in. (100 mm) apart.
2. Insert the anchors into the holes.
3. Align the transmitter up to the holes, and insert the screws through the holes and into the anchors.
4. Tighten the screws securing the transmitter onto the wall.
5. Plug in the screw terminal block (terminal screws facing the transmitter cover), close the cover, and tighten the cover screws. See Figure 5 for plugging in the terminal block and attaching the cover.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions 5
6. Secure the cable to the wall using cable ties.
!
Figure 9: Securing Cable on a Wall
FIG:Cable Wall
Figure 10: HT-68P3-0N000 Wiring
Two 4 to 20 mA outputs, temperature output scaling -40 to 140°F (-40 to 60°C)
Alternate wiring with one power supply.
1
2
3
4
mA
mA
mA
mA
HUM+ HUM­T+ T-
HUM+ HUM­T+ T-
+
+
+
1
2
3
4
FIG:HT-6803-0N00
Figure 11: HE-68P3-0N000 Wiring
1 2
3
4 5
VDC+/AC VDC-/AC T+
T-/
HUM+
HUM-
+
+
V
1 2
3
4 5
1
2
3
4 5
1
2
3
4 5
V
V
V
VDC+/AC VDC-/AC T+
T-/
HUM+
HUM-
Two 0 to 10 V outputs, temperature output scaling
-40 to 140°F (-40 to 60°C)
Terminals 2 and 5 are internally connected on the transmitter, so you can use a cable with four wires.
Incorporate a drip loop below the cable gland to prevent water from running into the transmitter along the cable.
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Calibration
There are no calibration adjustments to make for this device.

T roubleshooting

Analog Output Error State

The output channel is in a defined error level instead of the measured result in two situations.
The transmitter detects a measurement malfunction such as a damaged sensor or unfavorable environmental conditions.
The measured values are outside of the scaled
output range. See Analog Output Overrange Behavior.
The error level depends on the output type.
For a 0 to 10 V output, the error level is 11 V.
For a 4 to 20 mA output, the error level is 3.6 mA.
The transmitter resumes normal operation of the analog outputs when the cause of the error state is removed.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions6

Analog Output Overrange Behavior

The Analog outputs have a defined behavior when the values measure by the transmitter are outside the scaled analog output range.
The output is clipped at the end of the range.
The output is set to the error state when the measured value is 5% outside of the scaled range.
The output resumes normal function when the measured value is back on the scaled range.

Repair Information

If the Hx-68P3 Series Outside Humidity and Temperature Transmitter fails to operate within its specifications, replace the unit. For a replacement transmitter, contact the nearest Johnson Controls® representative.

Technical Specifications

Hx-68P3 Series Outside Humidity and Temperature Transmitters (Part 1 of 2)

Operating Conditions T emperature
Humidity 0 to 100% RH
Relative Humidity Measurement range 0 to 100% RH
Accuracy: Temperature Range 50 to 86F (10 to 30C): 0 to 90% RH 90 to 100% RH
Accuracy: Temperature Range
-4 to 50F (-20 to 10C) 86 to 140F (30 to 60C):
0 to 90% RH 90 to 100% RH
Accuracy: Temperature Range
-40 to -4F (-40 to -20C): 0 to 100% RH ±7% RH
Stability in typical HVAC app. ±2% RH over 2 years
Temperature Measurement range
Accuracy at 68F (20C) ±0.54F (±0.3C) Temperature dependance ±0.01C/C
Temperature sensor Pt1000 RTD Class F0.1 IEC60751 Dewpoint Accuracy at 68F (20C) and Wet Bulb ±1.3F (±0.7C) Enthalpy ±0.9 BTU/lb (±2kj/kg) Ingress Protection IP65 Maximum Wind/Flow Speed 98.42 ft/s (30 m/s) Storage Temperature Current Output
(HT-68P3-0N000) (Two-Wire)
Voltage Output (HE-68P3­0N000) (Three-Wire)
Wire Size
80% RH
Outputs 4 to 20 mA, loop powered
Loop resistance 0 to 600 ohm
Supply voltage 20 to 28 VDC at 600 ohm load;
Outputs 0 to 10 V
Load resistance 10k ohm minimum
Supply voltage 18 to 35 VDC; 24 VAC ±20%, 50/60 Hz
-40 to 140F (-40 to 60C)
±3% RH ±5% RH
±5% RH ±7% RH
-40 to 140F (-40 to 60C)
±1.6F (±0.9C)
-40 to 140F (-40 to 60C)
10 to 28 VDC at 0 ohm load
2
16 AWG (1.5 mm
) maximum
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions 7
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Hx-68P3 Series Outside Humidity and Temperature Transmitters (Part 2 of 2)
Electromagnetic Compliance EN61326-1 Industrial Environment Standard Housing Color White (RAL9003) Compliance United States FCC compliant to CFR 47, Part 15, Subpart B,
Class A
Canada Under CAN/CSA-CEI/IEC CISPR 22:02, Class A Europe CE Mark - Johnson Controls, Inc. declares that this
product is in compliance with the essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand RCM Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions8
Published in U.S.A. www.johnsoncontrols.com
Loading...