Johnson Controls Hx-68P3 Installation Manual

Hx-68P3 Series Outside Humidity and
Temperature Transmitters Installation Guide
Part No. 24-9647-10 Rev. B
2021-04-08

Application Requirements

The Hx-68P3 Series Outside Humidity and Temperature Transmitter measures and transmits outside relative humidity (RH) from 0 to 100% and temperatures from -40 to 140°F (-40 to 60°C). In addition to RH, the transmitter offers selectable parameters including dew point, wet bulb temperature, and enthalpy.
The integral weather shield provides ventilation, blocks direct and reflected solar radiation, and blocks precipitation without affecting performance. Mount the transmitter outside on a pole or on a side of a building.
Important: The Hx-68P3 Series Outside Humidity and Temperature Transmitter is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the humidity and temperature transmitter could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the humidity and temperature transmitter.
Important: Le Hx-68P3 Series Outside Humidity and Temperature Transmitter est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du humidity and temperature transmitter risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du humidity and temperature transmitter.

North American emissions compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful
interference, in which case the users will be required to correct the interference at their own expense.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Industry Canada Statement(s)
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions:
1. This device may not cause interference, and
2. This device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes :
1. L'appareil ne doit pas produire de brouillage, et
2. L'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

Installation

Parts Included

• relative humidity and temperature transmitter with cable gland
• conduit adaptor
• weather shield
• pole mounting clamp with screws (wall mount screws and anchors not included)
• installation instructions

Tools Needed

• medium Phillips screwdriver
• small slotted screwdriver
• wire cutters
• open-ended wrench
• zip ties
• cable clips
*24964710B*
HE-68P3-0N000, HT-68P3-0N000

Dimensions

Figure 1: Hx-68P3 Series Outside Humidity and Temperature Transmitter Dimensions, in. (mm)

DIP Switch Settings

The DIP switches on the component board control the humidity output parameter and scaling. Figure 2 shows the default DIP switch settings.
Figure 2: DIP Switch Positions
Table 1: DIP Switch Positions for Metric Output
Analog Output Parameter
DIP Switch Position
and Scaling
Relative Humidity (RH)0 to 100%Temperature (T)-40 to 60°C
Dewpoint (Td)-40 to 60°CTemperature (T)-40 to 60°C
Enthalpy (h)-40 to 460 kJ/ kgTemperature (T)-40 to 60°C
Wet Bulb Temperature (Tw)-40 to 60°CTemperature (T)-40 to 60°C
Change the position of the DIP switches to the desired setting.
Table 2: DIP Switch Positions for Non-Metric Output
Analog Output Parameter
DIP Switch Position
and Scaling
Relative Humidity (RH)0 to 100%Temperature (T)-40 to 140 ° F
Dewpoint (Td)-40 to 140°FTemperature (T)-40 to 140°F
Enthalpy (h)-10 to 190 BTU/ lbTemperature (T)-40 to 140°F
Wet Bulb Temperature (Tw)-40 to 140°FTemperature (T)-40 to 140°F
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide2
Installing the Conduit Adaptor ­Optional
About this task:
Using the conduit adaptor is optional. If you do not use the conduit adaptor, proceed to Mounting. To install the conduit adaptor, follow these steps.
1. Loosen the six captive screws that hold the transmitter cover in place. See Figure 4.
2. Unscrew the cable gland from the transmitter cover. See Figure for the location of the cable gland.
3. Align the nut with the opening inside the transmitter cover, and insert the adaptor body into the transmitter conduit opening.
Figure 3: Conduit Adaptor
4. Manually tighten the adaptor into the nut, turning in a clockwise direction.
5. Tighten the adaptor onto the adaptor body, turning in a clockwise direction.

Mounting

About this task:
CAUTION
Electric Shock.Disconnect the power supply before making electrical connections to avoid electric shock. décharge électrique.Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Location Considerations
• Install the transmitter in a place that receives minimal direct sunlight.
• Avoid placing the transmitter near windows, air conditioning units, or other heat and moisture sources such as cooling towers.
• Install the transmitter at least 8 ft (2.5 m) above the ground.
Important: To minimize the time spent working on a ladder, prepare the transmitter configuration and wiring before mounting the transmitter.
Figure 4: Preparing the Transmitter for Mounting
1. Loosen the six captive screws that hold the transmitter cover in place.
2. Be sure the DIP switches are set to the desired setting. See DIP Switch Settings.
3. Route the power and signal cable through the cable gland or the conduit adaptor to the screw terminals, and connect the wires.
4. Disconnect the terminal block by pulling it away from the component board.
5. Adjust the cable length between the cable gland and the terminal block. Make sure the cover closes without leaving a loop within the transmitter.
6. Tighten the cable gland or conduit adaptor.
Important: Do not attach the cover to the transmitter until the transmitter has been mounted on the pole or wall.

Pole Mounting

About this task:
Important: We recommend a pole diameter of
2-11/32 to 3-3/32 in. (25 to 60 mm) if you use the supplied clamp and screws.
To mount the Hx-68P3 Series Outside Humidity and Temperature Transmitter to a pole:
1. Attach the clamp to the pole with the set screw. See Figure 5.
2. Align the transmitter mounting bracket with the holes on the clamp, and insert the screws through the holes of the transmitter mounting bracket and into the clamp.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide 3