Johnson Controls Hx-68P3 Installation Manual

Page 1
Hx-68P3 Series Outside Humidity and
Temperature Transmitters Installation Guide
Part No. 24-9647-10 Rev. B
2021-04-08

Application Requirements

The Hx-68P3 Series Outside Humidity and Temperature Transmitter measures and transmits outside relative humidity (RH) from 0 to 100% and temperatures from -40 to 140°F (-40 to 60°C). In addition to RH, the transmitter offers selectable parameters including dew point, wet bulb temperature, and enthalpy.
The integral weather shield provides ventilation, blocks direct and reflected solar radiation, and blocks precipitation without affecting performance. Mount the transmitter outside on a pole or on a side of a building.
Important: The Hx-68P3 Series Outside Humidity and Temperature Transmitter is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the humidity and temperature transmitter could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the humidity and temperature transmitter.
Important: Le Hx-68P3 Series Outside Humidity and Temperature Transmitter est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du humidity and temperature transmitter risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du humidity and temperature transmitter.

North American emissions compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful
interference, in which case the users will be required to correct the interference at their own expense.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Industry Canada Statement(s)
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions:
1. This device may not cause interference, and
2. This device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes :
1. L'appareil ne doit pas produire de brouillage, et
2. L'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

Installation

Parts Included

• relative humidity and temperature transmitter with cable gland
• conduit adaptor
• weather shield
• pole mounting clamp with screws (wall mount screws and anchors not included)
• installation instructions

Tools Needed

• medium Phillips screwdriver
• small slotted screwdriver
• wire cutters
• open-ended wrench
• zip ties
• cable clips
*24964710B*
HE-68P3-0N000, HT-68P3-0N000
Page 2

Dimensions

Figure 1: Hx-68P3 Series Outside Humidity and Temperature Transmitter Dimensions, in. (mm)

DIP Switch Settings

The DIP switches on the component board control the humidity output parameter and scaling. Figure 2 shows the default DIP switch settings.
Figure 2: DIP Switch Positions
Table 1: DIP Switch Positions for Metric Output
Analog Output Parameter
DIP Switch Position
and Scaling
Relative Humidity (RH)0 to 100%Temperature (T)-40 to 60°C
Dewpoint (Td)-40 to 60°CTemperature (T)-40 to 60°C
Enthalpy (h)-40 to 460 kJ/ kgTemperature (T)-40 to 60°C
Wet Bulb Temperature (Tw)-40 to 60°CTemperature (T)-40 to 60°C
Change the position of the DIP switches to the desired setting.
Table 2: DIP Switch Positions for Non-Metric Output
Analog Output Parameter
DIP Switch Position
and Scaling
Relative Humidity (RH)0 to 100%Temperature (T)-40 to 140 ° F
Dewpoint (Td)-40 to 140°FTemperature (T)-40 to 140°F
Enthalpy (h)-10 to 190 BTU/ lbTemperature (T)-40 to 140°F
Wet Bulb Temperature (Tw)-40 to 140°FTemperature (T)-40 to 140°F
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide2
Page 3
Installing the Conduit Adaptor ­Optional
About this task:
Using the conduit adaptor is optional. If you do not use the conduit adaptor, proceed to Mounting. To install the conduit adaptor, follow these steps.
1. Loosen the six captive screws that hold the transmitter cover in place. See Figure 4.
2. Unscrew the cable gland from the transmitter cover. See Figure for the location of the cable gland.
3. Align the nut with the opening inside the transmitter cover, and insert the adaptor body into the transmitter conduit opening.
Figure 3: Conduit Adaptor
4. Manually tighten the adaptor into the nut, turning in a clockwise direction.
5. Tighten the adaptor onto the adaptor body, turning in a clockwise direction.

Mounting

About this task:
CAUTION
Electric Shock.Disconnect the power supply before making electrical connections to avoid electric shock. décharge électrique.Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Location Considerations
• Install the transmitter in a place that receives minimal direct sunlight.
• Avoid placing the transmitter near windows, air conditioning units, or other heat and moisture sources such as cooling towers.
• Install the transmitter at least 8 ft (2.5 m) above the ground.
Important: To minimize the time spent working on a ladder, prepare the transmitter configuration and wiring before mounting the transmitter.
Figure 4: Preparing the Transmitter for Mounting
1. Loosen the six captive screws that hold the transmitter cover in place.
2. Be sure the DIP switches are set to the desired setting. See DIP Switch Settings.
3. Route the power and signal cable through the cable gland or the conduit adaptor to the screw terminals, and connect the wires.
4. Disconnect the terminal block by pulling it away from the component board.
5. Adjust the cable length between the cable gland and the terminal block. Make sure the cover closes without leaving a loop within the transmitter.
6. Tighten the cable gland or conduit adaptor.
Important: Do not attach the cover to the transmitter until the transmitter has been mounted on the pole or wall.

Pole Mounting

About this task:
Important: We recommend a pole diameter of
2-11/32 to 3-3/32 in. (25 to 60 mm) if you use the supplied clamp and screws.
To mount the Hx-68P3 Series Outside Humidity and Temperature Transmitter to a pole:
1. Attach the clamp to the pole with the set screw. See Figure 5.
2. Align the transmitter mounting bracket with the holes on the clamp, and insert the screws through the holes of the transmitter mounting bracket and into the clamp.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide 3
Page 4
Figure 5: Pole Installation
3. Tighten the screws securing the transmitter assembly onto the pole.
4. Plug in the screw terminal block (terminal screws facing the transmitter cover), close the cover, and tighten the cover screws. See Figure 4 for plugging in the terminal block and attaching the cover.
5. Secure the cable to the pole using cable ties. Incorporate a drip loop below the cable gland to prevent water from running into the transmitter along the cable.
Figure 6: Securing Cable to a Pole
2. Insert the anchors into the holes.
3. Align the transmitter up to the holes, and insert the screws through the holes and into the anchors.
Figure 7: Wall Installation, in. (mm)
4. Tighten the screws securing the transmitter onto the wall.
5. Plug in the screw terminal block (terminal screws facing the transmitter cover), close the cover, and tighten the cover screws. See Figure 4 for plugging in the terminal block and attaching the cover.
6. Secure the cable to the wall using cable ties. Incorporate a drip loop below the cable gland to prevent water from running into the transmitter along the cable.
Figure 8: Securing Cable on a Wall

Wall Mounting

About this task:
To mount the Hx-68P3 Series Outside Humidity and Temperature Transmitter to a wall:
1. Drill two holes for the wall plugs 3-15/16 in.(100 mm) apart.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide4
Page 5

Wiring

CAUTION
Electric Shock.Disconnect the power supply before making electrical connections to avoid electric shock. décharge électrique.Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Figure 9: HT-68P3-0N000 Wiring
Figure 10: HE-68P3-0N000 Wiring

Troubleshooting

Analog Output Error State

The output channel is in a defined error level instead of the measured result in two situations.
• The transmitter detects a measurement malfunction such as a damaged sensor or unfavorable environmental conditions.
• The measured values are outside of the scaled output range. See Analog Output Overrange Behavior.
The error level depends on the output type.
• For a 0 to 10 V output, the error level is 11 V.
• For a 4 to 20 mA output, the error level is 3.6 mA.
The transmitter resumes normal operation of the analog outputs when the cause of the error state is removed.

Analog Output Overrange Behavior

The Analog outputs have a defined behavior when the values measure by the transmitter are outside the scaled analog output range.
• The output is clipped at the end of the range.
• The output is set to the error state when the measured value is 5% outside of the scaled range.
• The output resumes normal function when the measured value is back on the scaled range.
Calibration
There are no calibration adjustments to make for this device.

Repair Information

If the Hx-68P3 Series Outside Humidity and Temperature Transmitter fails to operate within its specifications, replace the unit. For a replacement transmitter, contact the nearest Johnson Controls® representative.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide 5
Page 6

Technical specifications

Table 3: Hx-68P3 Series Outside Humidity and Temperature Transmitters technical specifications
Specification Description Range
Temperature -40 to 140 ° F (-40 to 60 ° C)Operating Conditions
Humidity 0 to 100% RH
Relative Humidity
Temperature
Dewpoint ±1.6 ° F (±0.9 ° C)
Wet Bulb ±1.3 ° F (±0.7 ° C)
Enthalpy
Ingress Protection IP65
Maximum Wind/Flow Speed 98.42 ft/s (30 m/s)
Storage Temperature -40 to 140 ° F (-40 to 60 ° C)
Current Output(HT-68P3-0N000) (Two­Wire)
Voltage Output (HE-68P3-0N000) (Three-Wire)
Wire Size
Electromagnetic Compliance EN61326-1 Industrial Environment
Standard Housing Color White (RAL9003)
Compliance
Measurement range 0 to 100% RH
Accuracy: Temperature Range50 to 86°F (10 to 30°C):0 to 90% RH90 to 100% RH
Accuracy: Temperature Range-4 to 50°F (-20 to 10°C)86 to 140°F (30 to 60°C):0 to 90% RH90 to 100% RH
Accuracy: Temperature Range-40 to -4°F (-40 to -20°C):0 to 100% RH
Stability in typical HVAC app. ±2% RH over 2 years
Measurement range -40 to 140°F (-40 to 60°C)
Accuracy at 68°F (20°C) ±0.54°F (±0.3°C)
Temperature dependance ±0.01°C/°C
Temperature sensor Pt1000 RTD Class F0.1 IEC60751
Accuracy at 68°F (20°C) and 80% RH
Outputs 4 to 20 mA, loop powered
Loop resistance 0 to 600 ohm
Supply voltage 20 to 28 VDC at 600 ohm load;10 to 28 VDC at 0
Outputs 0 to 10 V
Load resistance 10k ohm minimum
Supply voltage 18 to 35 VDC; 24 VAC ±20%, 50/60 Hz
United States FCC compliant to CFR 47, Part 15, Subpart B, Class
Canada Under CAN/CSA-CEI/IEC CISPR 22:02, Class A
Europe CE Mark - Johnson Controls, Inc. declares that
Australia and New Zealand RCM Mark, Australia/NZ Emissions Compliant
±3% RH±5% RH
±5% RH±7% RH
±7% RH
±0.9 BTU/lb (±2kj/kg)
ohm load
16 AWG (1.5 mm2) maximum
A
this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive.
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide6
Page 7

Product warranty

This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/
buildingswarranty.

Software terms

Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted services applicable to this product, if any, is subject to applicable end-user license, open-source software information, and other terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms.

Patents

Patents: https://jcipat.com

Single point of contact

APAC Europe NA/SA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA

Contact information

Contact your local branch office: www.johnsoncontrols.com/locations Contact Johnson Controls: www.johnsoncontrols.com/contact-us
Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Guide 7
Page 8
© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice.
www.johnsoncontrols.com