
FANs 216, 1628.3
Installation Instructions HL-67x5
Issue Date 0316
TRUERH
Series
HL-67x5 Multi-function Humidity Dev ice with Temperature Sensor
nstallation
I
IMPORTANT: The HL-67x5 Series Multi-function
Humidity Device is intended to
provide an input to equipment
under normal operating conditions.
Where failure or malfunction of the
HL-67x5 Device could lead to
personal injury or property damage
to the controlled equipment or other
property, additional precautions
must be designed into the control
system. Incorporate and maintain
other devices, such as supervisory
or alarm systems or safety or limit
controls, intended to warn of or
protect against failure or
malfunction of the HL-67x5 Device.
IMPORTANT: Le HL-67x5 Series Multi-function
Humidity Device est destiné à
transmettre des données entrantes
à un équipement dans des
conditions normales de
fonctionnement. Lorsqu'une
défaillance ou un
dysfonctionnement du HL-67x5
Device risque de provoquer des
blessures ou d'endommager
l'équipement contrôlé ou un autre
équipement, la conception du
système de contrôle doit intégrer
des dispositifs de protection
supplémentaires. Veiller dans ce
cas à intégrer de façon permanente
d'autres dispositifs, tels que des
systèmes de supervision ou
d'alarme, ou des dispositifs de
sécurité ou de limitation, ayant une
fonction d'avertissement ou de
protection en cas de défaillance ou
de dysfonctionnement du HL-67x5
Device.
Parts Included
• HL-67N5-8N00P
• No. 8 x 1 in. Phillips-head sheet metal screw (2)
• washer for use with conduit fitting (conduit fitting
and nut not provided)
Tools Required
• hole saw with 1 in. (25 mm) diameter blade
• drill with 1/8 in. (3 mm) drill bit
• 1/8 in. (3 mm) flat-blade and No. 2 Phillips
screwdrivers
• pliers
• gasket, sealer, or other means to seal the area
between the unit and the duct
ocation Requirements
L
IMPORTANT: To avoid damage to the circuit
board and components, do not
mount the unit in a location where
high concentrations of corrosive
vapors are present.
When selecting a location for the HL-67N5-8N00P,
consider the following:
• Position: The HL-67N5-8N00P is designed for
duct mounting in any position, except with the
probe tip pointed up.
• Duct Diameter: Recommended minimum diameter
(round ducts) or width (square ducts) is 12 in.
(305 mm).
• Air Stratification (when the unit is mounted on the
discharge side of the fan): Recommended location
is at least 8 ft (2.4 m) downstream from
humidification equipment, where duct air and water
vapor are sufficiently mixed. Avoid areas where the
probe might be exposed to condensation.
© 2016 Johnson Controls, Inc. 1
Part No. 24-7701-128, Rev. C www.johnsoncontrols.com
Code No. LIT-216024

pplication Setup
Output
Jumper
Input
Jumper
Setpoint
Potentiometer
5 30
60 95
5
678
Probe
14 3 2
Label
Input:
Output:
0 to 10 VDC or Relay
(Factory Set)
0 to 20 mA
0 to 10 VDC
(Factory Set)
0 to 20 mA
No Input
VDC
VDC
MA
MA
NONE
27-4523-9
RY10048
RELAY TEMP
8 7 6
5
4
2
1
OUTPUT
INPUT
OUT IN COM PWR
Holes for
Mounting Screw (2)
Terminal
Block
Proportiona l Band
Potentiometer
24 VAC
Transformer
Humidification
Equipment
8
7 6
5
4
3
2
1
HL-67N5
Common
Power
Common
Output
24 VAC
Transformer
System
Controller
Humidification
Equipment
876
5
4
3 2 1
HL-67N5
Input
Common
Power
Common
Output
A
The multi-function humidity device must be configured
prior to installation for the following: input and output
signals and setpoint and proportional band.
The HL-67N5-8N00P has a setpoint potentiometer
(adjustable from 60 to 95% Relative Humidity [RH]) and
a proportional band potentiometer (adjustable from 5 to
30% RH). Refer to Figure 1 to change the setpoint or
proportional band for the application desired.
Figure 2: HL-67N5-8N00P as a Standalone Device
b. If the HL-67x5 is used as a proportional
override device, refer to Table 1 for jumper
positions.
Table 1: Jumper Positions with
HL-67N5-8N00P Used as a
Proportional Override Device
1. Use a 1/8 in. (3 mm) flat-blade screwdriver to
2. Adjust the proportional band potentiometer to the
Note: Setpoint minus proportional band is the highest
IMPORTANT: Set the proportional band to the
3. Select the appropriate input and output jumpers for
2 TRUERH Series HL-67x5 Multi-function Humidity Device with Temperature Sensor Installation Instructions
Figure 1: Internal View of the HL-67N5-8N00P
adjust the setpoint potentiometer to the humidity
level where the humidification equipment is
completely off.
desired range of humidity below the setpoint.
duct humidity reading at which the HL-67x5 will
allow the humidity equipment to be fully on.
highest number to reduce excessive
cycling of the humidification
equipment for optimum system
the application.
a. If the HL-67N5 is used as a standalone device
as shown in Figure 2, set the input jumper for
no input. Set the output jumper for the type of
signal the humidifier receives. (See Figure 1.)
performance without oscillation.
System
Air Handling Unit
DX-9xxx or
Input Jumper
Output Jumper
0 to 20 mA User selectable
0 to 10 VDC
(See Figure 1.)
Digital Control
Module via an
System 350 with a
W351P
Generic
0 to 20 mA or
0 to 10 VDC
User selectable
Figure 3 shows a typical proportional override
application for the HL-67x5. The relay output cannot be
used in this application.
Figure 3: HL-67N5-8N00P Using a System Controller