Johnson Controls HL-67x5 Installation Guide

24-7701-128, Rev. C
FANs 216, 1628.3 Installation Instructions HL-67x5 Issue Date 0316
TRUERH
Series
HL-67x5 Multi-function Humidity Dev ice with Temperature Sensor
nstallation
I
IMPORTANT: The HL-67x5 Series Multi-function
Humidity Device is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the HL-67x5 Device could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the HL-67x5 Device.
IMPORTANT: Le HL-67x5 Series Multi-function
Humidity Device est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du HL-67x5 Device risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du HL-67x5 Device.

Parts Included

HL-67N5-8N00P
No. 8 x 1 in. Phillips-head sheet metal screw (2)
washer for use with conduit fitting (conduit fitting
and nut not provided)

Tools Required

hole saw with 1 in. (25 mm) diameter blade
drill with 1/8 in. (3 mm) drill bit
1/8 in. (3 mm) flat-blade and No. 2 Phillips
screwdrivers
pliers
gasket, sealer, or other means to seal the area
between the unit and the duct
ocation Requirements
L
IMPORTANT: To avoid damage to the circuit
board and components, do not mount the unit in a location where high concentrations of corrosive vapors are present.
When selecting a location for the HL-67N5-8N00P, consider the following:
Position: The HL-67N5-8N00P is designed for duct mounting in any position, except with the probe tip pointed up.
Duct Diameter: Recommended minimum diameter (round ducts) or width (square ducts) is 12 in. (305 mm).
Air Stratification (when the unit is mounted on the discharge side of the fan): Recommended location is at least 8 ft (2.4 m) downstream from humidification equipment, where duct air and water vapor are sufficiently mixed. Avoid areas where the probe might be exposed to condensation.
© 2016 Johnson Controls, Inc. 1 Part No. 24-7701-128, Rev. C www.johnsoncontrols.com Code No. LIT-216024
pplication Setup
Output
Jumper
Input
Jumper
Setpoint
Potentiometer
5 30
60 95
5
678
Probe
14 3 2
Label
Input:
Output:
0 to 10 VDC or Relay (Factory Set)
0 to 20 mA
0 to 10 VDC (Factory Set)
0 to 20 mA
No Input
VDC
VDC
MA
MA
NONE
27-4523-9
RY10048
RELAY TEMP
8 7 6
5
4
2
1
OUTPUT
INPUT
OUT IN COM PWR
Holes for
Mounting Screw (2)
Terminal
Block
Proportiona l Band
Potentiometer
24 VAC
Transformer
Humidification
Equipment
8
7 6
5
4
3
2
1
HL-67N5
Common
Power
Common
Output
Controller
Position
Position
AS-LCPx00-0
FM-OAE
24 VAC
Transformer
System
Controller
Humidification
Equipment
876
5
4
3 2 1
HL-67N5
Input
Common
Power
Common
Output
A
The multi-function humidity device must be configured prior to installation for the following: input and output signals and setpoint and proportional band.
The HL-67N5-8N00P has a setpoint potentiometer (adjustable from 60 to 95% Relative Humidity [RH]) and a proportional band potentiometer (adjustable from 5 to 30% RH). Refer to Figure 1 to change the setpoint or proportional band for the application desired.
Figure 2: HL-67N5-8N00P as a Standalone Device
b. If the HL-67x5 is used as a proportional
override device, refer to Table 1 for jumper positions.
Table 1: Jumper Positions with HL-67N5-8N00P Used as a Proportional Override Device
1. Use a 1/8 in. (3 mm) flat-blade screwdriver to
2. Adjust the proportional band potentiometer to the
Note: Setpoint minus proportional band is the highest
IMPORTANT: Set the proportional band to the
3. Select the appropriate input and output jumpers for
2 TRUERH Series HL-67x5 Multi-function Humidity Device with Temperature Sensor Installation Instructions
Figure 1: Internal View of the HL-67N5-8N00P
adjust the setpoint potentiometer to the humidity level where the humidification equipment is completely off.
desired range of humidity below the setpoint.
duct humidity reading at which the HL-67x5 will allow the humidity equipment to be fully on.
highest number to reduce excessive cycling of the humidification equipment for optimum system
the application. a. If the HL-67N5 is used as a standalone device
as shown in Figure 2, set the input jumper for no input. Set the output jumper for the type of signal the humidifier receives. (See Figure 1.)
performance without oscillation.
System
Air Handling Unit DX-9xxx or
Input Jumper
Output Jumper
0 to 20 mA User selectable 0 to 10 VDC
(See Figure 1.)
Digital Control Module via an
System 350 with a W351P
Generic
0 to 20 mA or 0 to 10 VDC
User selectable
Figure 3 shows a typical proportional override application for the HL-67x5. The relay output cannot be used in this application.
Figure 3: HL-67N5-8N00P Using a System Controller
Loading...
+ 3 hidden pages