READ AND UNDERSTAND
THIS MANUAL BEFORE
USING THIS HEAT PUMP
AIR CONDITIONER.
KEEP THIS MANUAL FOR
FUTURE REFERENCE.
P5417055
Important Notice
●Johnson Controls Inc. pursues a policy of continuing improvement in design and performance in its
products. As such, Johnson Controls Inc. reserves the right to make changes at any time without prior
notice.
●Johnson Controls Inc. cannot anticipate every possible circumstance that might involve a potential
hazard.
●This heat pump air conditioning unit is designed for standard air conditioning applications only. Do not use
this unit for anything other than the purposes for which it was intended.
●The installer and system specialist shall safeguard against leakage in accordance with local codes. The
following standards may be applicable, if local regulations are not available. International Organization for
Standardization: (ISO 5149 or European Standard, EN 378). No part of this manual may be reproduced in
any way without the expressed written consent of Johnson Controls Inc.
●This heat pump air conditioning unit is operated and serviced in the United States of America and comes
with a full complement of the appropriate Safety, Danger, and Caution, warnings.
●If you have questions, please contact your distributor or contractor.
●This manual provides common descriptions, basic and advanced information to maintain and service this
heat pump air conditioning unit which you operate as well for other models.
●This heat pump air conditioning unit has been designed for a specic temperature range. For optimum
performance and long life, operate this unit within the range limits according to the table below.
Temperature
MaximumMinimum
Cooling
Operation
Heating
Operation
Indoor89
Outdoor118
Indoor 80
Outdoor59
DB: Dry Bulb, WB: Wet Bulb
* The temperature may change depending on the outdoor unit.
3. Before Operation .............................................................................................................................................5
3.1 Operating Range ....................................................................................................................................5
3.2 Efcient Use of Indoor Unit .....................................................................................................................5
3.3 Efcient Use of Cooling and Heating ......................................................................................................6
4. Name of Parts and Indication of Safety Consideration ...................................................................................7
4.1 Indoor Unit ..............................................................................................................................................7
5.2 Cooling / Heating / Fan Operation ........................................................................................................10
5.3 Temperature Setting ............................................................................................................................. 11
5.4 Fan Speed ............................................................................................................................................12
5.8.1 Function ...................................................................................................................................... 17
5.8.2 Descriptions for Setting Items ..................................................................................................... 18
5.8.3 Setting the Motion Sensor .......................................................................................................... 19
6. Automatic Control .........................................................................................................................................26
8.1 This is Not Abnormal ............................................................................................................................30
8.2 Before Contact .....................................................................................................................................31
● For details on wiring between the indoor unit and the outdoor unit, refer to the installation and maintenance
manual for the outdoor unit.
● For details on the optional decorative panel, refer to the installation and maintenance manual for the
optional decorative panel.
● For details on the optional controller, refer to the installation and maintenance manual for that optional
controller module.
● For details on each optional part, refer to the installation and maintenance manual for each optional part.
● For central controller, refer to the installation and maintenance manual for the central controller.
2. Safety Instructions
Signal Words
Indicates a hazardous situation that, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or moderate
injury.
Indicates information considered important, but not hazard-related (for example,
messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions thoroughly
and follow all warnings or cautions included in all manuals that accompanied the
product and are attached to the unit. Refer back to these safety instructions as
needed.
●This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be qualied
according to local, state and national building and safety codes and regulations. Incorrect installation could
cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance requirements are
specied, the appropriate measures should be taken during installation to guard against possible damage
or injury that might occur in an earthquake. If the unit is not installed correctly, injuries may occur due to a
falling unit.
P5417055
1
●Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and, where
appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited for electrical
operation purposes. Keep a wet cloth and a re extinguisher nearby during brazing. Use care in handling,
rigging, and setting of bulky equipment
.
●When transporting, be careful when picking up, moving and mounting these units. Although the unit may
be packed using plastic straps, do not use them for transporting the unit from one location to another. Do
not stand on or put any material on the unit. Get a partner to help, and bend with your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum ns on the air conditioner can cut ngers, so
wear protective gloves.
●Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features,
disengagement, and interlocks must be in place and functioning correctly before the equipment is put into
operation. If these devices are improperly adjusted or tampered with in any way, a serious accident can
occur. Never bypass or jump-out any safety device or switch.
●Before servicing, turn-OFF current at the power source and use accepted lockout and tag out procedures
at all main switches.
●This unit is the pressurized system. Never loosen threaded joints while the system is under pressure and
never open pressurized system parts.
●Johnson Controls will not assume any liability for injuries or damage caused by not following steps outlined
or described in this manual. Unauthorized modications to Johnson Controls products are prohibited as
they…
◦May create hazards which could result in death, serious injury, equipment damage or property damage; ◦Will void product warranties; ◦May invalidate product regulatory certications;◦May violate OSHA standards;
2
P5417055
Operation
NOTICE
● Do not insert ngers or objects into air inlet/outlet. Injury can result from rotating fan blades or energized
electrical components.
● Do not touch the wired controller with wet hands. Failure of the wired controller or an electrical shock can
result.
● Hair spray, insecticides, lacquers, and other pressurized substances should not be used within 3.3ft (1m)
of any air conditioning unit. They can react with energized electrical components and cause re.
● Do not install the indoor unit anywhere discharge airow can pass directly toward nearby heating
equipment (space heaters). It may interfere with the combustion process in these units.
● When the indoor unit is operating with heating equipment, ventilate a room sufciently. Any leaked
refrigerant gas that happens to come into contact with any heat source can become toxic on contact and
can cause suffocation in the immediate area.
● Shut down at the main power source if the GFCI (Ground Fault Circuit Interrupter) activates frequently.
Contact your distributor or contractor immediately. Failure to act accordingly can result in serious injury
and damage to the unit.
● CAUTION! If you smell anything burning, shut down the unit and turn OFF the power at the main power
source. Contact the re department and your installer or electrical contractor.
● Make sure that a test for leakage of refrigerant gases has been performed. The refrigerant used for this
unit (HFC R410A) is a non-ammable, non-toxic, and odorless gas. However if refrigerant should leak
and make contact with sparks, re will erupt and generate toxic gas. Also, the uorocarbon, which is
heavier than air will cover the oor surface and can cause suffocation.
● If uorocarbon gas should leak, turn OFF all heating equipment and ventilate the room immediately. Mop
down or vacuum oor areas of residual toxic particulate.
● CAUTION! Do not operate indoor units with the electrical box and switch panel open and exposed.
Incidental contact with energized electrical components can prove fatal.
● Air circulation should be optimized to achieve the best distribution pattern and not settled into isolated
pockets that can make people uncomfortable.
P5417055
3
Repair / Relocation
NOTICE
● When the air conditioner is to be repaired or transported to a new location, contact your distributor or
contractor. If the repair and the installation are not completed, electric shock or re can result.
Others
● Turn OFF all power at the main power source before performing maintenance work. Failure to do so can
result in damage to internal components with severe or fatal electrical shock.
● Insulate all electrical components and connections from exposure to moisture. Failure to do so can result
in an electrical short, or re.
● Do not tamper with or attempt to "repair" electrical wiring or connections. Call your installer or electrical
contractor. Serious or fatal injury can occur.
● Perform all maintenance work on a rm and stable platform to minimize the risk of injury.
● Do not attempt to "clean" indoor unit components with liquid or powdered cleaning agents during
maintenance. Electric shock, sparks, ame, and serious or fatal injury can occur.
● System piping is charged with refrigerant and highly pressurized.
● Hold the air lter and the air inlet grille securely when attaching or removing it. Carelessness can result in
accident or injury.
● When cleaning the lens surface of the motion sensor, do not make unnecessary contact as the lens can
be easily scratched.
4
P5417055
3. Before Operation
NOTICE
Apply power to the outdoor unit(s) at least 12 hours prior to system operation to allow for preheating
of the compressor oil. Do not start the system immediately without preheating the compressor.
Otherwise, the compressor can be damaged. Check that the outdoor unit is free of ice and snow
cover. If snow covered, remove with hot water at (122°F or 50°C). If hot water temperature is higher
than 122oF (50oC), it can cause damage to plastic parts.
● When the system is restarted after a shutdown longer than approximately three months, it is recommended
that the system be checked by your service contractor.
● Turn OFF at the main switch when the system has been off for a long period of time.
If the main switch is not turned OFF, electricity is consumed, because the oil heater is always energized
during periods of compressor stoppage.
3.1 Operating Range
This heat pump air conditioner has been designed for the following temperatures. Operate the heat pump air
conditioner within this range.
Temperature
MaximumMinimum
Cooling
Operation
Heating
Operation
DB: Dry Bulb, WB: Wet Bulb
* The temperature may change depending on the outdoor unit.
● Do not leave windows or doors open.
Operating efciency is degraded.
Condensation and related problems can result. (Ventilate a room sufciently too.)
● Attach a curtain or a blind to a window.
Direct sunlight is blocked, and the cooling efciency is enhanced.
● Avoid using heating equipment during the cooling operation as much as possible.
Cooling efciency is decreased. It may cause dew condensation and dew.
● Use the built-in circulating fan, if warm air tends to remain around the ceiling.
Comfort is increased. Contact your distributor for the details.
● Redirect airow downward if ceiling surface areas become discolored due to airborne particulate.
It is recommended that airow be redirected 30° downward.
● Turn OFF power at the main power source if the indoor unit is not being used over a prolonged
period of time.
You are billed for excess electrical consumption while the unit rests in standby mode.
P5417055
5
3.3 Efcient Use of Cooling and Heating
HEATINGCOOLING
(1) Airow Direction
The appropriate air outlet angle is approximately 35
If cooling is not sufcient, change the airfow direction.
Each louver angle can be changed approximately 5
per step by the wired controller.
35°
35°
Air Outlet Angle (Above Center)
Louver
Angle
(1) Airow Direction
o
.
o
The appropriate air outlet angle is approximately 60
If heating is not sufcient, change the airow direction.
Each louver angle can be changed approximately 5
per step by the wired controller.
60°60°
Louver
Angle
Air Outlet Angle (Below Center)
o
.
o
(2) Airow Volume
”AUTO” is usually used. If the airow volume is set
as “HIGH” or "Low", freeze protection operation is
(2) Airow Volume
”AUTO” is usually used.
activated and cooling and fan operation is performed
in turn.
NOTE
For Multi-Split Systems
When the number of the indoor units in operation or the operating mode is changed, the change in air outlet
temperature can cause the indoor temperature to change. In this case, adjust the settings as follows.
● During Cooling Operation: Lower the setting temperature slightly.
● During Heating Operation: Raise the setting temperature slightly.
6
P5417055
4. Name of Parts and Indication of Safety Consideration
Safety labels are afxed to the indoor unit in order to ensure safe use.
Read and understand this manual before using the indoor unit.
4.1 Indoor Unit
WARNING Label
Motion Sensor
(Only for Decorative
Panel with Motion
Sensor)
Indoor Unit
Air Outlet
Unit Data Tag Location
for Indoor Unit Model
It is indicated on the specication
l
plate attached at the condensation
pan.(Open air inlet grille to check it.)
Place the brand logo where indicat-
l
ed on the indoor unit.
Louver
Decorative Panel
(Optional)
Air Inlet Grille
(The air lter is attached
inside.)
Wired Controller
(Optional)
The operating condition is
displayed on the LCD.
NOTE
● Press switches lightly to control the wired controller. Do not press them with a sharp object such as a pen,
as it could cause damage to the controller.
● Review the installation manual for the optional Wireless Controller and Receiver Kit.
P5417055
7
FLTR
4.2 Wired Controller (CIW01)
Following is an example of how the CIW01 is utilized. If other models of the controller are utilized, operate
the unit according to the manual for that controller.
The example below references the control panel and all
adjustable settings. The wired controller display may be
Display Part
different during actual operation.
Operation Mode
Indicator
“HEAT” and “AUTO” are
indicated only for the
heat pump type models.
Operation Guide
Indicator
“Central Control” is
indicated while the
controller operation is
prohibited.
Run Indicator
Illuminates while the
unit is operating, and it
ashes during abnormal
conditions.
On/Off
Swing Louver IndicatorFan Speed Indicator
Avoid Air and Receive
Indicator
is displayed only for the
decorative panel with motion/
radiation sensor.
Room Name
LOUV.
Avoid
*
TEMP
Indicator
A/C
MODE SPEED
COOL
Meeting Room
Motion Sensor ON
LOUV.Adj.
OK
FLTR
Menu
Back/Help
Schedule Timer Indicator
is displayed when the schedule
timer function is set. *
Operation Lock Indicator
is displayed when the operation
lock function is set. *
Filter Sign Indicator
is displayed to indicate that the
lter needs to be cleaned.
Setting Temperature
Indicator
Motion/Radiation
Sensor Indicator
is displayed only for the
decorative panel with
motion/radiation sensor.
Cold Draft Rest
Indicator
Menu Switch
ECO
To display Menu.
*
On/Off Switch
Directional KeyEnter Key
Operation Part
NOTE
* For detailed descriptions, refer to the "Operation Manual" for the wired controller.
8
ECO Switch
*
Back/Help Switch
To return to the previous
screen.
P5417055
Menu
p
Menu
p
5. Operation Method
5.1 Basic Operation
By pressing “ ”or “ ”, the icon “”
will move between “MODE”, “SPEED”,
“LOUV.” and “TEMP”.
Item
Selection
With “MODE”, “SPEED”, “LOUV.” or
“TEMP” selected, press “ ” or “ ”.
The setting is changed.
Change of
Settings
OK
OK
Back/Hel
Back/Hel
P5417055
9
Menu
p
Menu
p
5.2 Cooling / Heating / Fan Operation
Heating Operation is for VRF systems only and is not available for typical systems.
Function
* Cooling Operation: To decrease room temperature.
* Heating Operation: To increase room temperature.
* Dry Operation: To decrease humidity in the room.
* Fan Operation: To increase air circulation in the room.
● Dry operation may not run properly if there are other heat sources that exceed the capacity of the unit.
● The control of humidity is unavailable for this unit. If you require dehumidification and the control of
humidity, choose specialized equipments.
● In cases where individual settings are used, the ability to reduce humidity levels during the Dry Operation
function might not be available.
Turn ON the power supply.
Turn ON the main power for
approximately 12 hours before operation
Before
in order to preheat the compressor.
Connecting
Operation
Do not turn OFF the main power to the
indoor unit during heating or cooling
season.
Press “ ” or “ ” to select “MODE”.
1
OK
Back/Hel
By pressing “ ” or “ ”, the mode is
changed as follows.
2
OK
FAN(AUTO)DRYHEATCOOL
Back/Hel
● Automatic heating/cooling operation requires extra settings. Contact your distributor or contractor for
details.
10
P5417055
Menu
p
Menu
p
5.3 Temperature Setting
Press “ ” or “ ” and select “TEMP”.
1
OK
Back/Hel
By pressing “ ”, temperature is increased
by 1oF (0.5oC).
(Max. 86oF (30oC))
2
By pressing “ ”, temperature is
decreased by 1oF (0.5oC).
OK
Back/Hel
COOL, FAN operation: Min. 66oF (19oC)
HEAT operation: Min. 62oF (17oC)
● In case that the optional function “Automatic Reset of Setting Temperature” is set:
Even if changing the setting temperature on the wired controller, it automatically returns to the set
temperature by “Automatic Reset Temperature” after a set time.
●The minimum/maximum temperature settings can be changed by adjusting the lower limit for set
temperature for cooling (or the upper limit for setting temperature for heating) from the function selection.
● Contact your distributor or contractor for details on optional functions “Automatic Reset for Setting
Temperature,” "Cooling Lower Limit for Set Temperature” and “Heating Upper Limit for Set Temperature.”
P5417055
11
Menu
p
Menu
p
5.4 Fan Speed
Press “ ” or “ ” and select “SPEED”.
1
OK
Back/Hel
By pressing “ ” or “ ”, fan speed is
changed as follows.
2
HIGH 2
HIGHMEDLOW
OK
AUTO
Back/Hel
● During the dry operation, the fan speed is automatically adjusted to “LOW” and cannot be changed to any
other fan speed. (“LOW” is NOT displayed on the LCD (Liquid Crystal Display) at this time. The present
setting condition is displayed on the LCD.)
● The fan speed setting “HIGH 2” may not be available depending on the indoor unit type.
5.5 Operation
Press “ On/Off”.
The RUN indicator is turned ON and the
Operation
operation will start.
On/Off
OK
Start
Temperature/Airow Setting
● The setting is stored. Therefore, no daily setting is required. In a case where a setting change is required,
refer to Sections 5.2 to 5.4.
Press “ On/Off” again.
The RUN indicator is turned OFF and the
operation will stop.
Operation
On/Off
OK
Stop
● The indoor unit fan may continue to operate for up to two minutes following the heating cycle to dissipate
residual heat from the indoor unit.
12
P5417055
5.6 Louver Swing Direction
Menu
p
Menu
p
Step1234567-
Press “ On/Off”.
Make sure that the operation is started.
Press “
” or “ ” and select “LOUV.”.
1
By pressing “ ” or “ ”, the louver
direction are changed as follows.
NOTE:
Even if 60o or 65o is selected during cooling and drying operations, the louver angle
is automatically xed at 55o.
If “Individual Louver Setting” mode is used, a louver setting of 60o or 65o can be
corrected.
: Auto-swing operation is activated.
At this time, the animated louver graphic on the LCD appears to swing.
● The louver angle indicated on the LCD and the actual louver angle do not correspond precisely with
each other during auto-swing mode operation. When the louver angle is established, set the louver angle
according to the louver position indicated on the LCD.
● Louver movement may NOT stop immediately after the switch is pressed.
P5417055
13
5.7 Individual Louver Setting
NOTICE
Menu
p
Menu
p
Function
● This setting is available only for indoor models equipped with the individual louver.
● Each louver angle can be set individually.
Example
Units equipped with Auto-Swing have a set of options to allow for airow adjustment from vertical to
horizontal.
This function cannot be set while the unit is not in operation.
l
After the individual louver setting is set during the heating operation, the louver angles can be adjusted
l
automatically to 25
Fan speed slows down to “LOW” while this function is being set. (After the setting process is completed,
l
the unit operation returns to normal speed.)
As for “Start-up of Heating Operation”, “During Defrost Operation” and “Activation of Thermistors”, all
l
louver angles become xed at 25
This function is not displayed if 2 (two) controllers (including wired controller + wireless controller) are
l
used.
Less than 16 units can be set to Individual Louver Setting per wired controller.
l
o
. Louver angles assume this setting after a short period of time.
o
automatically, even when this function is set.
5.7.1 Individual Louver Settings
Press “Menu”.
Select “Individual Louver Setting” from
the menu by pressing “ ” or “ ” and
press “OK”.
1
The individual louver setting menu is
displayed.
Select “Individual Louver Setting” from the individual louver
setting menu and press “OK”.
The connected indoor units selection for the individual louver
2
setting will be displayed.
NOTE:
If the connected indoor unit is one (1) in the system, the
louver direction setting at the procedure “4” is displayed.
Select the indoor unit to change the louver direction by
pressing “ ”, “ ”, “ ” or “ ”. Press “OK”.
The louver direction setting is displayed.
3
NOTE:
The indoor unit displayed on the screen ashes when the
individual louver is set.
OK
OK
Back/Hel
Back/Hel
Menu
Individual Louver Setting
Louver Open/Close
VENTI
Total Heat Exchanger SET
Motion Sensor Setting
OKBack
Individual Louver Setting
Individual Louver Setting
Cancel INDV Louver SET
OKBack
Individual Louver Setting
01-01
01-02
01-03
01-04
Select unit to set.
OKBack
15:10(Fri)
03
/
05
EntrRtrnSel.
EntrRtrnSel.
EntrRtrnSel.
14
P5417055
Press “ ” or “ ” and select the louver direction from 1 to 4 (as
34
INDVINDVINDVINDVINDVINDVINDVINDV
34
shown). The selected louver is opened and the other louvers
Individual Louver Setting:01-02
12
are seen horizontally.
4
Adjust air direction & louver angle.
● If the louver position is hard to distinguish, press “ ” or “ ” to set the position .
● In the default setting, the number-one louver is on the electrical box. Looking up from underneath the unit,
the louver numbers run in a clockwise direction: numbered "one", "two", "three", and "four". The louver
number can also be changed. Contact your distributor for details.
Select the louver angle by pressing “ ” or “ ” and press “OK”.
The conrmation screen is displayed.
The louver angle is changed as shown below.
Individual Louver Setting:01-02
12
OKBack
EntrRtrnSel.Adj.
5
NOTE:
The louver direction without “INDV” complies with the normal
mode setting.
Adjust air direction & louver angle.
OKBack
EntrRtrnSel.Adj.
6
7
Select “Yes” by pressing “ ” or “ ” and press “OK”. The
setting is conrmed and the screen returns to the normal
mode.
Verify that “INDV” is turned on at the airow section on the
normal mode.
Individual Louver Setting:01-02
Fix individual louver setting?
YesNo
Sel.EntrRtrn
A/C
MODE SPEED LOUV. TEMP
COOL
SPEEDAdj.
OKBack
Meeting Room
INDV
P5417055
15
Menu
p
Menu
p
5.7.2 Cancellation of Louver Setting
Press “Menu”.
Select “Individual Louver Setting” from
the menu by pressing “ ” or “ ” and
press “OK”.
1
The individual louver setting menu is
displayed.
Select “Cancel INDV Louver SET” from the individual louver
setting menu and press “OK”.
The connected indoor units selection of the cancelled louver
setting is displayed.
2
NOTE:
If the connected indoor unit is one (1) in the system, the
cancel individual louver setting at the procedure “4” is
displayed.
OK
OK
Back/Hel
Back/Hel
Menu
Individual Louver Setting
Louver Open/Close
VENTI
Total Heat Exchanger SET
Motion Sensor Setting
OKBack
Individual Louver Setting
Individual Louver Setting
Cancel INDV Louver SET
OKBack
15:10(Fri)
03
/
05
EntrRtrnSel.
EntrRtrnSel.
3
4
Select the indoor unit to cancel by pressing “ ”, “ ”, “ ” or
“ ”. Press “OK”.
NOTE:
The indoor unit displayed on the screen ashes when the
individual louver is set.
Select “Yes” by pressing “ ” or “ ” and press “OK”. The
individual louver setting is canceled and the screen returns
to the normal mode.
NOTE:
All the individual louver settings are canceled.
Cancel INDV Louver SET
01-01
01-02
01-03
01-04
Select unit to cancel.
Cancel INDV Louver SET:01-01
Cancel individual
louver setting?
YesNo
Sel.EntrRtrn
OKBack
EntrRtrnSel.
OKBack
16
P5417055
5.8 Motion Sensor
NOTICE
Detecting Area
r
10.5ft
approx. φ28.9ft (8.8m)
5.8.1 Function
The decorative panel (P-AP160NAE1) is equipped with four motion sensors and one radiation sensor.
● Motion Sensor
These sensors can detect human activity by
measuring the level of change in infrared light
emitted by humans or objects.
● Radiation Sensor
These sensors can detect the radiation
temperature of humans or objects by
(3.2m)
2.6ft
(0.8m)
123°
measuring the level of infrared light emitted by
humans or objects.
Function 1 Automatic Capacity Save Operation
This function can automatically perform the capacity save operation by a human activity in the air-
conditioned area. If there is insufcient or absence of human activity in the air-conditioned area, the motion
sensors detect it and save the air conditioning capacity. In addition, after the motion sensors detect absence
for the period, the operation mode is changed to “If absent”.
● During Capacity Save Operation
* Setting Temperature: The temperature is adjusted 2
o
or 3oF (1o or 2oC) for saving capacity.
* Airow Volume: The airow volume is lowered to one step or to “Slow”.
(except during “dry” operation).
* Airow Direction: The louver angle of controlling airow direction is adjusted horizontally or
downward depending on the operation conditions.
● If absent
The unit performs the operation set by the controller. Refer to Section 5.8.2, “Descriptions for Setting
Items”.
Area of Motion Sensors
(Divided into four areas
among each air outlet)
Area of Radiation Senso
P5417055
● Do not use the motion sensor function in situations where there is a disabled person or an infant. The
motion sensor may detect little motion for a long time as absence, and the operation may be stopped.
● The motion sensor detects human activity. If someone is in a room with little motion, the motion sensor may
detect an absence.
● The motion sensor may detect as human activity if the indoor unit with the motion sensor is installed near a
moving object (ex. swing operation of the heating equipment) which creates a difference in temperature in
the room.
● The indoor unit operation can be stopped by the motion sensor control.
NOTE:
Indoor units with and without motion sensors can be integrated together into a system installation.
In this case, when the operation is stopped by the motion sensor control, the indoor unit without the motion
sensor also stops the operation.
When the total heat exchanger is interlocked with the indoor unit motion sensor, the total heat exchanger
can be stopped with the indoor unit under the following condition:
* The operation mode of the total heat exchanger is set to A/C + VENTI and “If absent” is set to STOP.
However, the total heat exchanger operation mode is “VENTI”, it cannot be stopped even if the “If Absent”
setting is set to “Stop”. This is so because during the “VENTI” operation of the total heat exchanger, the
indoor unit is not activated (because the motion sensor is not active).
● While air conditioning capacity is saved or operation is stopped by the motion sensor control, “Motion
sensor is activated” is displayed on the LCD.
● If the function: “Prohibiting operation by controller”, is activated from the centralized controller, select the
command: “Running” or “Standby” inside the “If absent” condition at the motion sensor controls setting. If
the command “Stop” is selected, motion sensor control is lost and cannot be performed correctly as follows:
* In the case that “If absent: Stop” of motion sensor setting is set by the controller and “Prohibiting
operation by controller” (for all items) is set by the centralized controller, the operation can not be
stopped even if in the indoor unit operation stoppage condition of “If absent: Stop”.
* In the case that “If absent: Stop” of motion sensor setting is set and “Prohibiting operation by controller”
(for part of items) is set by the centralized controller, the indoor unit operation is stopped by the motion
sensor control. However, the indoor unit operation cannot be restarted from the centralized controller.
17
Function 2 Adjusting Capacity by Increase or Decrease in the Number of People
NOTICE
(1) In instances where people are gathered within or are beyond the range of the motion sensor.
The air conditioning capacity is adjusted by the automatic setting temperature correction depending on
human activity and movements of a heat source in the detecting area of the motion sensor .
Cooling or Dry
Operation
Heating
Operation
Increase in the
number of people
Decrease in the
number of people
Increase in the
number of people
Decrease in the
number of people
The setting temperature is adjusted
from -2
The setting temperature is adjusted
from +2
The setting temperature is adjusted
from -2
o
F to -3oF (-1oC to -2oC).
o
F to +3oF (+1oC to +2oC).
o
F to -3oF (-1oC to -2oC).
The function is invalided.
(2) The adjusted setting temperature will return to normal setting temperature after 10 to 30 minutes,
depending on the conditions.
● If human activity and movements of a heat source are small, the motion sensor cannnot detect them.
● If room temperature is high and there is little difference between the radiation temperature of walls, oor
space, and humans, the motion sensor may not detect increase or decrease in the number of humans.
(For example: The cooling operation is performed with a setting at 86°F (30°C) in the summer season.)
● During the “Capacity Save” and “If absent” phase of operation of Function 1, the Function 2 is unavailable.
5.8.2 Descriptions for Setting Items
● Motion Sensor Setting
The operation mode for activations of functions 1 and 2 can be selected as follows:
* “ALL MODES” : Functions 1 and 2 are available when the operation mode is “COOL”, “DRY”,
“HEAT”, or “FAN”.
* “COOL + DRY” : Functions 1 and 2 are available when the operation mode is “COOL”, “DRY”,
or “FAN”.
* “HEAT” : Functions 1 and 2 are available when the operation mode is “HEAT”.
* “OFF” : Functions 1 and 2 are not available.
(The default setting is “ALL MODES”.)
● If absent
The operation mode for activations during the automatic capacity save operation for Function 1 can
be selected from “Running”, “Stand-by”, or “Stop” on the wired controller. It is set for the indoor unit
operation after the motion sensor detects as an absence for the set time in “Check Interval”.
* Running:
The operation continues with saving the capacity after being detected as an absence.
If human activity is detected over a period of time, normal operation is performed again.
* Stand-by:
The operation mode is the fan operating at “Slow” speed. If human activity is detected for a period of
time, normal operation is performed again.
* Stop:
The operation is stopped by the wired controller when all the indoor units with motion sensor detect an
absence that is connected with the same wired controller. If human activity is detected for a period of
time by the stoppage, normal operation is performed again.
● Check Interval
When the motion sensor detects an absence at a selected check time interval, the function “If absent”
(Function 1) is executed. The interval can be selected from choices ranging from: 30, 60, 90, 120, or
180 minutes.
(The default setting is 30 minutes.)
18
P5417055
5.8.3 Setting the Motion Sensor
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Press “Menu”.
Select “Motion Sensor Setting” from the
menu by pressing “ ” or “ ” and press
“OK”.
1
"Motion Sensor Setting” is displayed.
The highlighted item changes to “Sensor”,
“If absent”, and “Check interval” by
pressing “ ” or “ ”.
2
• To set “Sensor”,
go to procedure "3".
• To set “If absent”,
go to procedure "5".
• To set “Check interval”,
go to procedure "7".
OK
OK
OK
Back/Hel
Back/Hel
Back/Hel
Menu
Individual Louver Setting
Louver Open/Close
VENTI
Total Heat Exchanger SET
Motion Sensor Setting
OKBack
Motion Sensor Setting
Sensor
If absent
Check interval
Running
30MIN
OKBack
15:10(Fri)
03
/
05
EntrRtrnSel.
ON
EntrRtrnSel.Adj.
3
4
5
Press “ ” or “ ” and select “Sensor”.
The display is switched “ON” and “OFF”
in order by pressing “ ” or “ ” and
change the setting.
If other settings are not required, go to
procedure "9".
Press “ ” or “ ” and select “If absent”.
OK
OK
OK
Back/Hel
Back/Hel
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
Motion Sensor Setting
Sensor
If absent
Check interval
Motion Sensor Setting
Sensor
If absent
Check interval
ON
Running
30MIN
OKBack
EntrRtrnSel.Adj.
ON
Running
30MIN
OKBack
EntrRtrnSel.Adj.
ON
Running
30MIN
OKBack
EntrRtrnSel.Adj.
P5417055
6
The display changes to “Running”,
“Stand-by” and “Stop” in order by
pressing “ ” or “ ” and change the
setting.
If other settings are not required, go to
procedure "9".
OK
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
ON
Running
30MIN
OKBack
EntrRtrnSel.Adj.
19
NOTICE
7
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Press “ ” or “ ” and select “Check
interval”.
OK
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
ON
Running
30MIN
OKBack
EntrRtrnSel.Adj.
8
9
The display will display: “30MIN”, “60MIN”,
“90MIN”, “120MIN”, and “180MIN” in
order by pressing “ ” or “ ” to change
the setting.
If other settings are not required, go to
procedure "9".
Press “OK” after the setting is made.
The conrmation screen is displayed.
Select “Yes” by pressing “ ” or “ ” and
press “OK”. The motion sensor setting
is conrmed and the screen returns to
normal mode (operation mode indicator).
OK
OK
OK
OK
Back/Hel
Back/Hel
Back/Hel
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
Motion Sensor Setting
Save changes in
motion sensor setting?
YesNo
Sel.EntrRtrn
ON
Running
30MIN
OKBack
EntrRtrnSel.Adj.
OKBack
If more than two controllers are utilized, use the main controller only to set the motion sensor.
20
P5417055
5.9 Comfort Setting
NOTICE
Detecting Area of Motion Sensor
5.9.1 Setting of “Control Cool Air” (Cold Draft Control during Cooling Operation)
(1) Function
This function controls the overcooling airow to prevent of cold draft.
(2) Setting Items
* OFF : This function is not available.
* LOW : The over-cooling airow temperature is controlled low degree.
* MID : The over-cooling airow temperature is controlled medium degree.
* HIGH : The over-cooling airow temperature is controlled high degree.
(The default setting is “OFF”)
(3) Supplement of Function
• The discharge air temperature is elevated higher in “HIGH” > “MID” > “LOW” order.
• The recommended discharge air temperature setting is “LOW”. (When feeling cold at "LOW", change
the setting to “MID” or “HIGH”.)
* This function also reduces the formation of dew condensation on the decorative panel when the
discharge air temperature is lower than the inlet air temperature in a very humid room.
(The recommended discharge air temperature setting is “LOW”.)
●
The "Control Cool Air" function may not have much effect depending on the operating conditions of the outdoor
unit.
● In case one outdoor unit is connected to multiple indoor units and the rate of these indoor units which are
equipped with the "Control Cool Air" function is low, this function may not have much of an effect.
● When this function is set, it may take a few minutes to cool the entire room.
● While this function is activated, “Cold draft rest.” is displayed on the LCD control panel of the wired
controller.
5.9.2 Setting of Avoid Air and Receive
(1) Function
This function automatically activates the louver under
the setting of “Avoid Air” or “Receive” when the motion
sensor detects human activity.
The “Avoid Air” setting is the reduction of airow set
by the wired controller.
The "Receive" setting allows airow set by the wired
controller.
Each Detection Area:
area a to d as shown on the right.
(2) Descriptions for Setting Items
Louver in COOL (Louver Activation at Cooling Operation)
Louver in HEAT (Louver Activation at Heating Operation)
• NORMAL: The function is not activated.
• AVOID AIR: The louver angle is automatically adjusted to the highest angle if human activity is
• RECEIVE: The louver operation is automatically changed to “AUTO” (Auto-Swing) mode if
(The default setting is “NORMAL”.)
Motion Sensor
a
B
D
A
to D ,corresponds to each
A
(The louvers are situated in the setting directions on the main menu.)
detected by the motion sensor.
human activity is detected by the motion sensor.
d
c
b
C
P5417055
21
(3) Supplement of Function
NOTICE
• The louver angle is adjusted by the motion sensor to compensate for the presence or absence of
human activity and can be set for manual override at the wired controller.
• Each of the four louvers can move independently of the others.
• When the motion sensor detects continuous human activity, louver operation remains at: “Avoid Air”
or the “Receive” setting.
• If the motion sensor detects an absence of human activity for 15 minutes or longer, louver angles
can be adjusted to the “Avoid Air” or “Reserve” settings to save on energy consumption or manually
overridden from the wired controller.
• The commands: “Avoid Air” and “Receive” are shown on the LCD display as variations of angular
louver positioning. See below:
Avoid Air
● The function diminishes to (sleep mode) in times of sparse human activity. To reactivate, stand up and
begin walking.
● Objects with higher temperature signatures can be mistaken for humans and can activate this system
function.
● Louver settings: “Avoid Air” or “Receive” in FAN or DRY operations are the equivalent settings for the “Louver
in COOL”.
Receive
22
P5417055
NOTICE
NOTICE
5.9.3 Setting of “Floor HEAT Control” (Radiation Sensor during Heating Operation)
(1) Function
If a steep temperature difference is detected between the radiation temperature and the setting
temperature, this function heats the entire room efciently by adjusting airow direction and airow
volume.
(2) Descriptions for Setting Items:
The setting of “Floor HEAT Control”
• OFF: This function is unavailable.
• ON: This function is available.
(The default setting is OFF.)
(3) Supplement of Function
• When this function is activated, airow direction is directed downwards and the airow volume
changes to “AUTO”.
• This function continues to be active for 20 to 60 minutes, depending on the difference between the
ambient air temperature and the set temperature.
• This function will repeat, depending on the temperature difference between a radiation temperature
and the setting temperature.
● If the radiation temperature (Floor Temperature) in the detecting area is low, this function may be activated
frequently.
● This louver direction is downward during this function. Avoid a cold draft from a direct airow by setting
function “Individual Louver Setting” or “Avoid Air”.
● During the activation of this function, “Floor HEAT control” is indicated on the LCD.
5.9.4 Useful Tips on Setting the Swing Louver Direction
The swing louver direction can be varied according to each set function. If the set airow direction is not
comfortable, refer to the following descriptions and adjust the airow direction.
Order of Priority for Setting the Swing Louver Direction
HIGH
LOW
If two wired controllers are utilized, the comfort setting is available by using the wired controller 1 only.
● Capacity save operation (Function 1) set as “Motion Sensor Setting”.
● Setting of “Individual Louver Setting”
● Swing louver direction at detecting human activity side by “Avoid Air” and “Receive”
function.
● Setting of “Floor HEAT Control”
● Louver direction set on the main menu of a wired controller.
P5417055
23
5.9.5 Creating Comfort Settings
Menu
p
Menu
p
Menu
p
Press “Menu”.
Select "Comfort Setting” from the menu
by pressing “ ” or “ ” and press “OK”.
1
OK
Back/Hel
2
3
OK
Back/Hel
"Motion Sensor Setting” is displayed.
The highlighted item is changed to
“Control Cool Air”, “Louver in COOL”,
“Louver in HEAT” and "Floor HEAT
control" by pressing “ ” or “ ”.
After selecting set item, set function by
pressing “
” or “ ”. Setting details are
as shown below.
OK
Back/Hel
• Control Cool Air:
“OFF” ↔ “LOW” ↔ “MED" ↔ “HI”
• Louver in COOL:
“Normal” ↔ “Avoid Air” ↔ “Receive”
• Louver in HEAT:
“Normal” ↔ “Avoid Air” ↔ “Receive”
• Floor HEAT Control:
OFF ↔ ON
Press “OK”.
The conrmation screen is displayed. Select “Yes” by
pressing “
” or “ ” and press “OK”.
The “Comfort Setting” is completed and the LCD indication
returns to the normal mode.
24
P5417055
An automatic heating/cooling operation and setback operation requires extra settings.
Contact your distributor or contractor for details.
5.10 Automatic Heating/Cooling Operation
In case dual setpoint is selected in automatic heating/cooling
operation, during auto mode both cooling setpoint and heating
setpoint can be selected.
By default, temperature when the heating/cooling mode changes
are as follows.
Cooling mode changes to heating mode when the indoor
temperature is at the heating setpoint -2oF (-1oC).
Heating mode changes to cooling mode when the indoor
temperature is at the cooling setpoint +2oF (+1oC).
If the temperature for changing modes must be changed, contact
your distributor or contractor for details.
5.11 Setback Operation
If the setback operation is enabled and the card key is removed,
the louver starts to open in approximately 5 seconds, the setpoint is
adjusted for setback, and the fan operates at “Low” speed.
During this time, “Setback” is displayed on the LCD.
By default,
Cooling: Setpoint +4oF (+2.5oC)
Heating: Setpoint -4oF (-2.5oC)
If the adjustment for setback operation must be changed, contact
your distributor or contractor for details.
NOTE:
In case of Celsius Indication.
NOTE:
In case of Fahrenheit Indication.
P5417055
25
6. Automatic Control
This air conditioner automatically starts the following operations according to the conditions.
The system is equipped with the following functions:
Enforced Stoppage:
The compressor remains OFF for at least three minutes once it has
stopped.
If the system is restarted within approximately three minutes after it has
stopped, the RUN indicator is activated.
However, the cooling operation or the heating operation remains OFF
Three-Minute Guard
Cooling
Frost Prevention
and
Dry
Self-Cleaning of
Expansion Valve
Hot Start
Defrosting
Heating
Operation
and does not start until after three minutes has elapsed.
Enforced Operation:
If all indoor units of a system are Thermo-OFF within approximately
three minutes after the compressor has started, compressor operates
continuously during those three minutes.
However, if all indoor units of a system are stopped by a controller,
compressor is stopped.
When the indoor unit is operating at a low discharge air temperature,
the cooling operation may be changed to a fan operation for a while to
avoid frost formation on the indoor heat exchanger.
It is for self-cleaning the expansion valve when the operation is stopped
at cooling. The sound of the refrigerant ow may be heard from the
indoor unit during the self-cleaning. However, this is not abnormal.
To prevent cold air discharge into a heated space, the fan speed is
changed from the SLOW / LOW setting to a set position based on
discharge air temperature.
At this time, the louver is in a xed horizontal position and “HOT
START” is displayed on the LCD of the wired controller.
The indoor unit fan operation is stopped to prevent cold air discharge
during the defrosting operation. At this time, the message “HOT-START”
is displayed on the LCD of the wired controller and the indoor unit fan
louver angle is xed horizontally.
Residual
Heat Removal
Prevention
of Overload
Operation
When the heating operation is stopped, indoor fan operation may
remain at the slow speed for a maximum of two minutes to lower the
internal temperature of the indoor unit.
When the outdoor temperature is high (approximately 70oF (21oC) or
more) during heating operation, the operation is stopped by activation
of the outdoor thermistor.
NOTE
● This air conditioner adopts hot air circulaition system for the heating operation.
● Any oversized room with a low ambient air temperature will require an extended amount of time to warm
up. Once the air temperature gets to the required setting temperature, the display “HOT START” is turned
OFF.
● The indication “HOT-START” may be displayed during or right after the defrosting operation. It is
activated during the hot start operation to prevent the perception of cold draft. This is NOT abnormal.
26
P5417055
7. Maintenance
(Two places)
Upper Part of Filter
Lower Part of Filter
A
NOTICE
● Turn OFF the power source before maintenance work. If the power source is not turned off, a re or an
electric shock may result.
● Perform the maintenance work with a stable foothold or foundation. This may prevent falling or injury.
● Hold the air lter and the air inlet grille securely by hand when attaching or removing it. If not, it may
cause the unit to fall, resulting in serious injury.
● Use light pressure with a clean soft cloth when cleaning the lens of the motion sensor. The surface
material of the lens is easily scratched, blemished, and can result in degraded performance of the sensor.
7.1 Daily Maintenance
7.1.1 Cleaning Air Filter
Clean the air lter when the lter sign is turned ON.
On/Off
A/C
MODE SPEED
COOL
Motion Sensor ON
LOUV.Adj.
Meeting Room
LOUV.
Avoid
OK
TEMP
FLTR
Menu
Back/Help
Filter Sign
ECO
(1) Open the air inlet grille.
Slide the knobs on both sides of the air inlet grille
in the direction of the arrows as shown, and open
the air inlet grille.
Air Inlet Grille
Knobs
(2) Remove the air lter.
Support the underside of the air inlet grille
Hook
as shown. Unhook the lter from the air inlet
grille and remove the air lter.
P5417055
ir Inlet Grille
Air Filter
Hook
27
(3) Clean the air lter.
•Vacuum dust off with hand-held vacuum cleaner, or wash the air lter with water or a neutral detergent.
• Dry the air lter in a shaded area.
NOTE
• Do not use water warmer than 122°F (50°C). Filter elements can be damaged.
• Do not dry the air lter by holding it over open ame, with a hair dryer, or any type of heating device. Filter
elements can be damaged by heat.
(4) Attach the air lter.
After the air lter is dried, attach it in the reverse order from what is shown procedure "2".
(5) Close the air inlet grille.
NOTE
• Be sure to attach the air lter.
Operating the indoor unit without a lter installed will cause serious damage and breakdown.
• Make sure that the air inlet grille is securely locked with the knobs. If not properly secured, it could swing
open and strike someone below and cause minor injuries.
(6) Reset the lter sign.
NOTE
If the accumulated operation time is shorter than that indicated by the lter sign setting, the icon displaying
“ ” activates and “Setting Disabled” is displayed.
•Press “Menu”.
Select “Reset Filter Sign Time” from the menu and press “OK”.
The conrmation screen is displayed.
Menu
Simple Timer
Reset Filter Sign Time
Operation Schedule
Elevating Grille
Power Saving Setting
•Select “Yes” by pressing “
” or “ ” and press “OK”.
The “FLTR” indication is turned OFF and the screen returns to the normal mode.
15:10(Fri)
OKBack
EntrRtrnSel.
01
/
05
28
P5417055
7.1.2 Removing, Cleaning and Attaching Air Inlet Grille
(Two places)
Supporting String
NOTICE
Air Inlet Grille
Lift it with inclined.
Wipe down the air inlet grille with a soft cloth soaked in lukewarm water and wrung-out.
l
Gently wipe down using only a clean soft cloth. Avoid the use of Benzene type thinners or chemical
l
detergents and abrasives as cleaning agents which will damage the nish of outer plastic surfaces and
louvers. Avoid using excessive force when cleaning these surfaces as they can be easily damaged.
When cleaning the lens of the motion sensor, the surface material of the lens is easily scratched, and can
l
result in degraded performance of the sensor.
The air inlet grille can be removed and cleaned.
(1) Open the air inlet grille.
While sliding the knobs on both sides of the air inlet
grille in the arrow direction, open the air inlet grille.
Air Inlet Grille
Knobs
(2) Remove the air inlet grille.
• Unhook the supporting string from the decorative
panel.
• Open the air inlet grille at an approximately 45° angle from the
decorative panel surface.
• Tilt the air inlet grille and lift it up to remove it.
NOTE:
Although the air inlet grille can be opened up to 90°, it cannot be
removed from the decorative panel at that angle. Tilt it to a 45°
angle when removing it.
(3) Clean the air inlet grille.
(4) Reattach the air inlet grille.
Reattach in reverse order.
Ceiling
Decorative
Panel
45
o
7.2 Maintenance Prior to and After Use
Prior to Use
• Remove any obstacles around the air inlet grilles
and the air outlet of both the indoor and outdoor
units.
• Check that the air lter is not clogged with dust
and dirt.
P5417055
After Use
• Clean the air lter, the air inlet grille and the
decorative panel.
29
8.Troubleshooting
8.1 This is Not Abnormal
PhenomenonCause and Action
All indicator LEDs on the
wired controller are turned
OFF.
Operation Stopped
White Steam
from Indoor Unit
White Smoke
from Indoor Unit
Mist from Indoor Unit
Odor from Indoor Unit
Sound from Indoor Unit
Dew Condensation on
Decorative Panel
Temperature Irregularity
“HOT-START” on LCD Illuminated (ON)
Operation Mode on LCD Flashing
“Motion Sensor ON” is turned
ON the wired controller.
After Power Failure
During Heating OperationDust attached to the heat exchanger has dried.
At Beginning of Heating
Season
In Restaurant or Kitchen
During Dry Operation
During Cooling Operation
in Humid Environment
Odors Emanating from Indoor
Unit Air Dischagre
A grating sound is heard
when starting or stopping the
operation.
Sound of water owing or
bubbling is heard during the
operation.
A growling sound may be
heard temporarily right after
the airow volume is changed.
Dew condensation on
Decorative Panel or Cabinet
or Dew Drops
Airow volume and
temperature irregularities exist
for each outlet.
The micro-computer is activated to protect the
device from electromagnetic interference. Restart
the operation.
The operation has stopped automatically because
the motion sensor is set as “If absent: Stop” and it
detects an absence of motion for a period of time. (All
indoor units connected to the same controller are
stopped.)
Restart the operation. If the instantaneous power
failure is within 2 seconds, the operation restarts
automatically.
This might occur when dust attached to the heat
exchanger has dried.
This can occur when oily residue coats the ns and
heat exchanger efciency is degraded.
This might occur due to the air outlet temperature
decreasing. Change the operation mode.
This might occur due to the air outlet temperature
decreasing. Raise the set temperature and airow
volume.
The intake of cigarette smoke is the likely reason,
with nicotine deposits coating or clogging the cells
and surfaces of the air lter.
Ventilate the unit well in fan mode and clean the air
lter, the air outlet and air inlet grill.
This is the sound made when the components
are rubbing up against one another due to the
expansion and contraction of plastic formed parts
brought on by temperature change.
This is the sound made when the refrigerant ows
or the drain-up mechanism drains water. The sound
may be heard especially when starting the operation
or stopping the compressor (for approximately 3
minutes).
It is generated because the fan motor makes
temporary sound by change of fan speed.
This might occur when the operation is performed
in a humid environment over a prolonged period of
time (relative humidity around 80%).
This might occur for structural reasons, such as
the size of an air outlet and the location of heat
exchanger.
This might occur according to the operation mode
or operational conditions.
30
P5417055
8.2 Before Contact
Check these items over before contacting a contractor.
TroubleChecking PointAction
Check that the main power
source is turned ON.
Operation Unavailable
Cooling
Immediate
shutdown after
start-up
Insufcient Cooling or
Heating
Heating
Check that the fuse is not
blown or the circuit breaker
from the main power source is
not tripped.
Check if the air inlet and outlet
for the outdoor unit are not
obstructed.
Check if there are any
obstacles impeding the airow
near the air inlet and outlet of
the outdoor unit.
Check that the outlet air is not
redirected into the air inlet.
Check that the operation
mode is appropriate.
Check that the set
temperature is appropriate.
Check that the airow
direction is appropriate.
Check that the air lter is not
clogged.
Verify that there are no open
windows and doorways.
Check that there are no
obstacles impeding airow
near the air inlet and outlet for
both indoor and outdoor units.
Turn ON the power at the main power source for
the air conditioner.
Replace the fuse or reset the circuit breaker.
If trouble recurs, contact your contractor or
distributor.
Remove objects obstructing the air inlet and outlet.
Remove any obstacles obstructing airow.
If the fan mode is selected, switch the operation
mode to cooling/heating.
If not, change the setting temperature by pressing
” or “ ” by the wired controller.
“
If not, change the airow direction.
In case the footing is not heated well during the
heating operation, change the louver downward.
Clean the air lter.
Close windows and doors.
Remove the obstacles.
P5417055
31
8.3 Contact Distributor
Indoor Unit Number
If trouble still persists, even after checking off previously listed items or detecting problems not mentioned in
the previous pages, stop using this product and call your distributor or contractor immediately.
If there is any perceived abnormality present (noises or odors associated with electrical short,
re, or burning elements), shut down immediately and shut OFF at the main power source.
Contact your distributor or contractor without delay.
TroubleAction before Contact
Protection devices (fuses, breakers, and GFCI's) activate
frequently or the operation switch does not work.
Water leakage from the indoor unit.Stop the operation.
"Motion Sensor ON" or "Radiation Sensor" is ashing.
● The RUN indicator (red) is ashing.
● The indoor unit number, alarm code, unit model code,
and the number of connected indoor units are displayed
on LCD.
● If multiple indoor units are connected to one controller,
the above abnormality informations for each indoor unit
are displayed individually.
Turn OFF the power source.
There is a possibility of the failure of motion sensor
or radiation sensor.
Make the setting of motion sensor and
Control
invalid and contact your distributor. In
”
Floor HEAT
“
that case, after the LCD of wired controller display
has disappeared and until service is nished, the
operation of this unit is available.
Check the details on LCD and contact your distributor.
Refer to Section 8.4, the alarm code table.
Contact your distributor and inform them of the alarm
code indicated on the LCD of the wired controller.
01-02
Alarm Code:
MODEL : F .08
I.U. :
IDU :
ODU :
O.U. :
RCI-3.0FSN3
******
RAS-3HVRNM2
******
Sel.OP MODE
23
OK
Chek
AlarmRST
Address
Entr
Provide the following information when contacting your distributor.
1) Unit model
2) Symptoms and nature of the problem.
3) Number of the alarm code or any ashing indicator on the LCD.
32
P5417055
8.4 Alarm Codes
CodeCategoryContent of AbnormalityCodeCategoryContent of Abnormality
01Indoor UnitActivation of Protection Device35
02Outdoor Unit
03
Communication
04
05Supply Phase Problem of Power Source Phases41
06Voltage
07
Cycle
08
09Outdoor Unit
11
12Outlet Air Thermistor Failure47
13Freeze Protection Thermistor Failure48
14Gas Piping Thermistor Failure51
19Fan Motor
20
21High Pressure Sensor Failure54
22Outdoor Air Thermistor Failure56
23Discharge Gas Thermistor Failure57Activation of Fan Controller Protection
Sensor on
Indoor Unit
Sensor on
Outdoor Unit
Activation of Protection Device
(High Pressure Cut)
Operational Irregularities between
Indoor and Outdoor
Problem between Inverter PCB and
Outdoor PCB
Abnormal Voltage Drop in
Outdoor Unit
Decrease in Superheated Discharge
Gas
Increase in Discharge Gas Temperature
Activation of Protection Device for
Outdoor Fan
Inlet Air Thermistor Failure46
Activation of Protection Device for
Indoor Fan
Compressor Thermistor Failure53
36Incorrect Indoor Unit Combination
38
39Compressor
42Overload Heating
43
44
45
52
System
Pressure
Protection
Device
Inverter
Outdoor Fan
Incorrect Setting of Indoor Unit No.
Problem with Protective Pickup Circuit
in Outdoor Unit
Problem with Running Current at Constant Speed Compressor
Overload Cooling
Activation of Pressure Ratio Decrease
Protection Device
Activation of Low Pressure Decrease
Protection Device
Activation of Low Pressure Increase
Protection Device
Activation of High Pressure Increase
Protection Device
Activation of High Pressure Decrease
Protection Device
Activation of Overcurrent Protection
Device
Problem with Inverter Current Sensor
Activation of Inverter Overcurrent
Protection
Activation of Transistor Module
Protection
Abnormality of Inverter Fin
Temperature
Abnormality of Detection for Fan Motor Position
24Evaporating Thermistor Failure58Abnormality of Fan Controller
29Low Pressure Sensor Failureb0
31
System
32
Incorrect Capacity Setting of
Outdoor Unit and Indoor Unit
Incorrect Setting of Other Indoor Unit
Number
b1
EECompressorCompressor Protection Alarm
System
Incorrect Setting of Unit Capacity
Incorrect Setting of Unit and
Refrigerant Cycle No.