Johnson Controls HIC4030B21S, HIC4012B21S, HIC4036B21S, HIC4048B21S, YIC4008B21S Operation Manual

...
Operation
Manual
INVERTER-DRIVEN
MULTI-SPLIT SYSTEM
HEAT PUMP
AIR CONDITIONERS
Type Model
(H,Y,C)IC4008B21S (H,Y,C)IC4012B21S (H,Y,C)IC4015B21S
(H,Y,C)IC4018B21S (H,Y,C)IC4024B21S (H,Y,C)IC4030B21S (H,Y,C)IC4036B21S (H,Y,C)IC4048B21S
IMPORTANT:
READ AND UNDERSTAND THIS MANUAL BEFORE USING THIS HEAT PUMP AIR CONDITIONER. KEEP THIS MANUAL FOR FUTURE REFERENCE.
P5417055
Important Notice
Johnson Controls Inc. pursues a policy of continuing improvement in design and performance in its products. As such, Johnson Controls Inc. reserves the right to make changes at any time without prior notice.
Johnson Controls Inc. cannot anticipate every possible circumstance that might involve a potential hazard.
This heat pump air conditioning unit is designed for standard air conditioning applications only. Do not use this unit for anything other than the purposes for which it was intended.
The installer and system specialist shall safeguard against leakage in accordance with local codes. The following standards may be applicable, if local regulations are not available. International Organization for Standardization: (ISO 5149 or European Standard, EN 378). No part of this manual may be reproduced in any way without the expressed written consent of Johnson Controls Inc.
This heat pump air conditioning unit is operated and serviced in the United States of America and comes with a full complement of the appropriate Safety, Danger, and Caution, warnings.
If you have questions, please contact your distributor or contractor.
This manual provides common descriptions, basic and advanced information to maintain and service this heat pump air conditioning unit which you operate as well for other models.
This heat pump air conditioning unit has been designed for a specic temperature range. For optimum performance and long life, operate this unit within the range limits according to the table below.
Temperature
Maximum Minimum
Cooling Operation
Heating Operation
Indoor 89
Outdoor 118
Indoor 80
Outdoor 59
DB: Dry Bulb, WB: Wet Bulb
* The temperature may change depending on the outdoor unit.
o
F DB/73oF WB (32oC DB/23oC WB) 69oF DB/59oF WB (21oC DB/15oC WB)
o
F DB (48oC DB) * 14oF DB (-10oC DB) *
o
F DB (27oC DB) 59oF DB ( 15oC DB)
o
F WB (15oC WB) * -4oF WB (-20oC WB) *
This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air conditioning equipment.
P5417055
i
TABLE OF CONTENTS
1. Introduction .....................................................................................................................................................1
2. Safety Instructions ...........................................................................................................................................1
3. Before Operation .............................................................................................................................................5
3.1 Operating Range ....................................................................................................................................5
3.2 Efcient Use of Indoor Unit .....................................................................................................................5
3.3 Efcient Use of Cooling and Heating ......................................................................................................6
4. Name of Parts and Indication of Safety Consideration ...................................................................................7
4.1 Indoor Unit ..............................................................................................................................................7
4.2 Wired Controller (CIW01) .......................................................................................................................8
5. Operation Method ...........................................................................................................................................9
5.1 Basic Operation ......................................................................................................................................9
5.2 Cooling / Heating / Fan Operation ........................................................................................................10
5.3 Temperature Setting ............................................................................................................................. 11
5.4 Fan Speed ............................................................................................................................................12
5.5 Operation ..............................................................................................................................................12
5.6 Louver Swing Direction ........................................................................................................................13
5.7 Individual Louver Setting ......................................................................................................................14
5.7.1 Individual Louver Settings ........................................................................................................... 14
5.7.2 Cancellation of Louver Setting .................................................................................................... 16
5.8 Motion Sensor ......................................................................................................................................17
5.8.1 Function ...................................................................................................................................... 17
5.8.2 Descriptions for Setting Items ..................................................................................................... 18
5.8.3 Setting the Motion Sensor .......................................................................................................... 19
5.9 Comfort Setting ....................................................................................................................................21
5.9.1 Setting of “Control Cool Air” (Cold Draft Control during Cooling Operation) ............................... 21
5.9.2 Setting of Avoid Air and Receive .................................................................................................21
5.9.3 Setting of “Floor HEAT Control” (Radiation Sensor during Heating Operation) ..........................23
5.9.4 Useful Tips on Setting the Swing Louver Direction .................................................................... 23
5.9.5 Creating Comfort Settings .......................................................................................................... 24
5.10 Automatic Heating/Cooling Operation ..................................................................................................25
5.11 Setback Operation ................................................................................................................................25
6. Automatic Control .........................................................................................................................................26
7. Maintenance .................................................................................................................................................27
7.1 Daily Maintenance ................................................................................................................................27
7.1.1 Cleaning Air Filter .......................................................................................................................27
7.1.2 Removing, Cleaning and Attaching Air Inlet Grille ......................................................................29
7.2 Maintenance Prior to and After Use .....................................................................................................29
8. Troubleshooting ............................................................................................................................................30
8.1 This is Not Abnormal ............................................................................................................................30
8.2 Before Contact .....................................................................................................................................31
8.3 Contact Distributor ................................................................................................................................32
8.4 Alarm Codes .........................................................................................................................................33
ii
P5417055
1. Introduction
Read this manual carefully before working with this product. Keep this information with the product.
Forward this manual and the warranty to the next team of installers and then users. Ask them to keep this manual with the air conditioning unit.
(Refrigerant Piping Work) (Electrical Wiring Work) (Ref. Charge Work) (Test Run) (User)
● For details on wiring between the indoor unit and the outdoor unit, refer to the installation and maintenance
manual for the outdoor unit.
● For details on the optional decorative panel, refer to the installation and maintenance manual for the
optional decorative panel.
● For details on the optional controller, refer to the installation and maintenance manual for that optional
controller module.
● For details on each optional part, refer to the installation and maintenance manual for each optional part.
● For central controller, refer to the installation and maintenance manual for the central controller.
2. Safety Instructions
Signal Words
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or moderate
injury.
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions thoroughly and follow all warnings or cautions included in all manuals that accompanied the product and are attached to the unit. Refer back to these safety instructions as
needed.
This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be qualied according to local, state and national building and safety codes and regulations. Incorrect installation could
cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance requirements are specied, the appropriate measures should be taken during installation to guard against possible damage
or injury that might occur in an earthquake. If the unit is not installed correctly, injuries may occur due to a falling unit.
P5417055
1
Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and, where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited for electrical
operation purposes. Keep a wet cloth and a re extinguisher nearby during brazing. Use care in handling,
rigging, and setting of bulky equipment
.
When transporting, be careful when picking up, moving and mounting these units. Although the unit may be packed using plastic straps, do not use them for transporting the unit from one location to another. Do not stand on or put any material on the unit. Get a partner to help, and bend with your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum ns on the air conditioner can cut ngers, so
wear protective gloves.
Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features, disengagement, and interlocks must be in place and functioning correctly before the equipment is put into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident can occur. Never bypass or jump-out any safety device or switch.
Before servicing, turn-OFF current at the power source and use accepted lockout and tag out procedures at all main switches.
This unit is the pressurized system. Never loosen threaded joints while the system is under pressure and never open pressurized system parts.
Johnson Controls will not assume any liability for injuries or damage caused by not following steps outlined
or described in this manual. Unauthorized modications to Johnson Controls products are prohibited as
they…
May create hazards which could result in death, serious injury, equipment damage or property damage; Will void product warranties; May invalidate product regulatory certications; May violate OSHA standards;
2
P5417055
Operation
NOTICE
● Do not insert ngers or objects into air inlet/outlet. Injury can result from rotating fan blades or energized
electrical components.
● Do not touch the wired controller with wet hands. Failure of the wired controller or an electrical shock can
result.
● Hair spray, insecticides, lacquers, and other pressurized substances should not be used within 3.3ft (1m) of any air conditioning unit. They can react with energized electrical components and cause re.
● Do not install the indoor unit anywhere discharge airow can pass directly toward nearby heating
equipment (space heaters). It may interfere with the combustion process in these units.
● When the indoor unit is operating with heating equipment, ventilate a room sufciently. Any leaked
refrigerant gas that happens to come into contact with any heat source can become toxic on contact and can cause suffocation in the immediate area.
● Shut down at the main power source if the GFCI (Ground Fault Circuit Interrupter) activates frequently. Contact your distributor or contractor immediately. Failure to act accordingly can result in serious injury
and damage to the unit.
● CAUTION! If you smell anything burning, shut down the unit and turn OFF the power at the main power source. Contact the re department and your installer or electrical contractor.
● Make sure that a test for leakage of refrigerant gases has been performed. The refrigerant used for this unit (HFC R410A) is a non-ammable, non-toxic, and odorless gas. However if refrigerant should leak and make contact with sparks, re will erupt and generate toxic gas. Also, the uorocarbon, which is heavier than air will cover the oor surface and can cause suffocation.
● If uorocarbon gas should leak, turn OFF all heating equipment and ventilate the room immediately. Mop down or vacuum oor areas of residual toxic particulate.
● CAUTION! Do not operate indoor units with the electrical box and switch panel open and exposed.
Incidental contact with energized electrical components can prove fatal.
● Air circulation should be optimized to achieve the best distribution pattern and not settled into isolated
pockets that can make people uncomfortable.
P5417055
3
Repair / Relocation
NOTICE
● When the air conditioner is to be repaired or transported to a new location, contact your distributor or contractor. If the repair and the installation are not completed, electric shock or re can result.
Others
● Turn OFF all power at the main power source before performing maintenance work. Failure to do so can
result in damage to internal components with severe or fatal electrical shock.
● Insulate all electrical components and connections from exposure to moisture. Failure to do so can result in an electrical short, or re.
● Do not tamper with or attempt to "repair" electrical wiring or connections. Call your installer or electrical
contractor. Serious or fatal injury can occur.
● Perform all maintenance work on a rm and stable platform to minimize the risk of injury.
● Do not attempt to "clean" indoor unit components with liquid or powdered cleaning agents during maintenance. Electric shock, sparks, ame, and serious or fatal injury can occur.
● System piping is charged with refrigerant and highly pressurized.
● Hold the air lter and the air inlet grille securely when attaching or removing it. Carelessness can result in
accident or injury.
● When cleaning the lens surface of the motion sensor, do not make unnecessary contact as the lens can
be easily scratched.
4
P5417055
3. Before Operation
NOTICE
Apply power to the outdoor unit(s) at least 12 hours prior to system operation to allow for preheating of the compressor oil. Do not start the system immediately without preheating the compressor. Otherwise, the compressor can be damaged. Check that the outdoor unit is free of ice and snow cover. If snow covered, remove with hot water at (122°F or 50°C). If hot water temperature is higher than 122oF (50oC), it can cause damage to plastic parts.
● When the system is restarted after a shutdown longer than approximately three months, it is recommended
that the system be checked by your service contractor.
● Turn OFF at the main switch when the system has been off for a long period of time. If the main switch is not turned OFF, electricity is consumed, because the oil heater is always energized
during periods of compressor stoppage.
3.1 Operating Range
This heat pump air conditioner has been designed for the following temperatures. Operate the heat pump air conditioner within this range.
Temperature
Maximum Minimum
Cooling Operation
Heating Operation
DB: Dry Bulb, WB: Wet Bulb
* The temperature may change depending on the outdoor unit.
Indoor 89
Outdoor 118
Indoor 80
Outdoor 59
o
F DB/73oF WB (32oC DB/23oC WB) 69oF DB/59oF WB (21oC DB/15oC WB)
o
F DB (48oC DB) * 14oF DB (-10oC DB) *
o
F DB (27oC DB) 59oF DB ( 15oC DB)
o
F WB (15oC WB) * -4oF WB (-20oC WB) *
3.2 Efcient Use of Indoor Unit
Do not leave windows or doors open. Operating efciency is degraded. Condensation and related problems can result. (Ventilate a room sufciently too.)
Attach a curtain or a blind to a window. Direct sunlight is blocked, and the cooling efciency is enhanced.
Avoid using heating equipment during the cooling operation as much as possible. Cooling efciency is decreased. It may cause dew condensation and dew.
Use the built-in circulating fan, if warm air tends to remain around the ceiling.
Comfort is increased. Contact your distributor for the details.
Redirect airow downward if ceiling surface areas become discolored due to airborne particulate. It is recommended that airow be redirected 30° downward.
Turn OFF power at the main power source if the indoor unit is not being used over a prolonged
period of time. You are billed for excess electrical consumption while the unit rests in standby mode.
P5417055
5
3.3 Efcient Use of Cooling and Heating
HEATINGCOOLING
(1) Airow Direction
The appropriate air outlet angle is approximately 35
If cooling is not sufcient, change the airfow direction.
Each louver angle can be changed approximately 5 per step by the wired controller.
35°
35°
Air Outlet Angle (Above Center)
Louver Angle
(1) Airow Direction
o
.
o
The appropriate air outlet angle is approximately 60
If heating is not sufcient, change the airow direction.
Each louver angle can be changed approximately 5 per step by the wired controller.
60° 60°
Louver Angle
Air Outlet Angle (Below Center)
o
.
o
(2) Airow Volume
”AUTO” is usually used. If the airow volume is set as “HIGH” or "Low", freeze protection operation is
(2) Airow Volume
”AUTO” is usually used. activated and cooling and fan operation is performed in turn.
NOTE
For Multi-Split Systems
When the number of the indoor units in operation or the operating mode is changed, the change in air outlet temperature can cause the indoor temperature to change. In this case, adjust the settings as follows.
● During Cooling Operation: Lower the setting temperature slightly.
● During Heating Operation: Raise the setting temperature slightly.
6
P5417055
4. Name of Parts and Indication of Safety Consideration
Safety labels are afxed to the indoor unit in order to ensure safe use.
Read and understand this manual before using the indoor unit.
4.1 Indoor Unit
WARNING Label
Motion Sensor
(Only for Decorative Panel with Motion Sensor)
Indoor Unit
Air Outlet
Unit Data Tag Location
for Indoor Unit Model
It is indicated on the specication
l
plate attached at the condensation pan.(Open air inlet grille to check it.)
Place the brand logo where indicat-
l
ed on the indoor unit.
Louver
Decorative Panel
(Optional)
Air Inlet Grille
(The air lter is attached inside.)
Wired Controller
(Optional)
The operating condition is
displayed on the LCD.
NOTE
● Press switches lightly to control the wired controller. Do not press them with a sharp object such as a pen,
as it could cause damage to the controller.
● Review the installation manual for the optional Wireless Controller and Receiver Kit.
P5417055
7
FLTR
4.2 Wired Controller (CIW01)
Following is an example of how the CIW01 is utilized. If other models of the controller are utilized, operate
the unit according to the manual for that controller.
The example below references the control panel and all adjustable settings. The wired controller display may be
Display Part
different during actual operation.
Operation Mode Indicator
“HEAT” and “AUTO” are indicated only for the heat pump type models.
Operation Guide Indicator
“Central Control” is indicated while the controller operation is prohibited.
Run Indicator
Illuminates while the unit is operating, and it
ashes during abnormal
conditions.
On/Off
Swing Louver IndicatorFan Speed Indicator
Avoid Air and Receive Indicator
is displayed only for the
decorative panel with motion/
radiation sensor.
Room Name
LOUV.
Avoid
*
TEMP
Indicator
A/C
MODE SPEED
COOL
Meeting Room
Motion Sensor ON
LOUV. Adj.
OK
FLTR
Menu
Back/Help
Schedule Timer Indicator
is displayed when the schedule timer function is set. *
Operation Lock Indicator
is displayed when the operation lock function is set. *
Filter Sign Indicator
is displayed to indicate that the
lter needs to be cleaned.
Setting Temperature Indicator
Motion/Radiation Sensor Indicator
is displayed only for the decorative panel with
motion/radiation sensor.
Cold Draft Rest Indicator
Menu Switch
ECO
To display Menu.
*
On/Off Switch
Directional Key Enter Key
Operation Part
NOTE
* For detailed descriptions, refer to the "Operation Manual" for the wired controller.
8
ECO Switch
*
Back/Help Switch
To return to the previous screen.
P5417055
Menu
p
Menu
p
5. Operation Method
5.1 Basic Operation
By pressing “ ”or “ ”, the icon “ ” will move between “MODE”, “SPEED”, “LOUV.” and “TEMP”.
Item
Selection
With “MODE”, “SPEED”, “LOUV.” or “TEMP” selected, press “ ” or “ ”. The setting is changed.
Change of
Settings
OK
OK
Back/Hel
Back/Hel
P5417055
9
Menu
p
Menu
p
5.2 Cooling / Heating / Fan Operation
Heating Operation is for VRF systems only and is not available for typical systems.
Function
* Cooling Operation: To decrease room temperature.
* Heating Operation: To increase room temperature.
* Dry Operation: To decrease humidity in the room.
* Fan Operation: To increase air circulation in the room.
Dry operation may not run properly if there are other heat sources that exceed the capacity of the unit.
● The control of humidity is unavailable for this unit. If you require dehumidification and the control of
humidity, choose specialized equipments.
● In cases where individual settings are used, the ability to reduce humidity levels during the Dry Operation
function might not be available.
Turn ON the power supply. Turn ON the main power for approximately 12 hours before operation
Before
in order to preheat the compressor.
Connecting
Operation
Do not turn OFF the main power to the
indoor unit during heating or cooling season.
Press “ ” or “ ” to select “MODE”.
1
OK
Back/Hel
By pressing “ ” or “ ”, the mode is changed as follows.
2
OK
FAN(AUTO)DRYHEATCOOL
Back/Hel
● Automatic heating/cooling operation requires extra settings. Contact your distributor or contractor for
details.
10
P5417055
Menu
p
Menu
p
5.3 Temperature Setting
Press “ ” or “ ” and select “TEMP”.
1
OK
Back/Hel
By pressing “ ”, temperature is increased by 1oF (0.5oC). (Max. 86oF (30oC))
2
By pressing “ ”, temperature is decreased by 1oF (0.5oC).
OK
Back/Hel
COOL, FAN operation: Min. 66oF (19oC)
HEAT operation: Min. 62oF (17oC)
In case that the optional function “Automatic Reset of Setting Temperature” is set: Even if changing the setting temperature on the wired controller, it automatically returns to the set temperature by “Automatic Reset Temperature” after a set time.
The minimum/maximum temperature settings can be changed by adjusting the lower limit for set temperature for cooling (or the upper limit for setting temperature for heating) from the function selection.
Contact your distributor or contractor for details on optional functions “Automatic Reset for Setting Temperature,” "Cooling Lower Limit for Set Temperature” and “Heating Upper Limit for Set Temperature.”
P5417055
11
Menu
p
Menu
p
5.4 Fan Speed
Press “ ” or “ ” and select “SPEED”.
1
OK
Back/Hel
By pressing “ ” or “ ”, fan speed is changed as follows.
2
HIGH 2
HIGH MED LOW
OK
AUTO
Back/Hel
During the dry operation, the fan speed is automatically adjusted to “LOW” and cannot be changed to any other fan speed. (“LOW” is NOT displayed on the LCD (Liquid Crystal Display) at this time. The present setting condition is displayed on the LCD.)
The fan speed setting “HIGH 2” may not be available depending on the indoor unit type.
5.5 Operation
Press “ On/Off”. The RUN indicator is turned ON and the
Operation
operation will start.
On/Off
OK
Start
Temperature/Airow Setting
The setting is stored. Therefore, no daily setting is required. In a case where a setting change is required, refer to Sections 5.2 to 5.4.
Press “ On/Off” again.
The RUN indicator is turned OFF and the
operation will stop.
Operation
On/Off
OK
Stop
The indoor unit fan may continue to operate for up to two minutes following the heating cycle to dissipate residual heat from the indoor unit.
12
P5417055
5.6 Louver Swing Direction
Menu
p
Menu
p
Step 1 234567-
Press “ On/Off”. Make sure that the operation is started. Press “
” or “ ” and select “LOUV.”.
1
By pressing “ ” or “ ”, the louver direction are changed as follows.
OK
Back/Hel
2
LCD Indication
Louver Angle
FAN
Louver Angle Approx. 25
COOL and DRY
Louver Angle
HEAT
Approx. 25
Approx. 30
OK
o
Approx. 35oApprox. 42oApprox. 49oApprox. 55oApprox. 60oApprox. 65
Recommended
Angle
o
Approx. 35oApprox.42oApprox. 49oApprox. 55
Recommended
Angle
o
Approx. 35oApprox. 41oApprox. 47oApprox. 53oApprox. 60oApprox. 66
Angle Range
Auto-Swing Range
Angle Range
Auto-Swing Range
Angle Range
Auto-Swing Range
Back/Hel
o
Approx. 60oApprox. 65
Recommended
Angle
o
o
Auto
Swing
o
NOTE: Even if 60o or 65o is selected during cooling and drying operations, the louver angle
is automatically xed at 55o.
If “Individual Louver Setting” mode is used, a louver setting of 60o or 65o can be
corrected.
: Auto-swing operation is activated.
At this time, the animated louver graphic on the LCD appears to swing.
The louver angle indicated on the LCD and the actual louver angle do not correspond precisely with each other during auto-swing mode operation. When the louver angle is established, set the louver angle according to the louver position indicated on the LCD.
Louver movement may NOT stop immediately after the switch is pressed.
P5417055
13
5.7 Individual Louver Setting
NOTICE
Menu
p
Menu
p
Function
● This setting is available only for indoor models equipped with the individual louver.
Each louver angle can be set individually.
Example
Units equipped with Auto-Swing have a set of options to allow for airow adjustment from vertical to
horizontal.
This function cannot be set while the unit is not in operation.
l
After the individual louver setting is set during the heating operation, the louver angles can be adjusted
l
automatically to 25
Fan speed slows down to “LOW” while this function is being set. (After the setting process is completed,
l
the unit operation returns to normal speed.)
As for “Start-up of Heating Operation”, “During Defrost Operation” and “Activation of Thermistors”, all
l
louver angles become xed at 25
This function is not displayed if 2 (two) controllers (including wired controller + wireless controller) are
l
used.
Less than 16 units can be set to Individual Louver Setting per wired controller.
l
o
. Louver angles assume this setting after a short period of time.
o
automatically, even when this function is set.
5.7.1 Individual Louver Settings
Press “Menu”. Select “Individual Louver Setting” from the menu by pressing “ ” or “ ” and press “OK”.
1
The individual louver setting menu is displayed.
Select “Individual Louver Setting” from the individual louver setting menu and press “OK”. The connected indoor units selection for the individual louver
2
setting will be displayed.
NOTE: If the connected indoor unit is one (1) in the system, the louver direction setting at the procedure “4” is displayed.
Select the indoor unit to change the louver direction by pressing “ ”, “ ”, “ ” or “ ”. Press “OK”. The louver direction setting is displayed.
3
NOTE:
The indoor unit displayed on the screen ashes when the
individual louver is set.
OK
OK
Back/Hel
Back/Hel
Menu
Individual Louver Setting
Louver Open/Close VENTI Total Heat Exchanger SET Motion Sensor Setting
OK Back
Individual Louver Setting
Individual Louver Setting
Cancel INDV Louver SET
OK Back
Individual Louver Setting
01-01
01-02
01-03
01-04
Select unit to set.
OK Back
15:10(Fri)
03
/
05
Entr RtrnSel.
Entr RtrnSel.
Entr RtrnSel.
14
P5417055
Press “ ” or “ ” and select the louver direction from 1 to 4 (as
34
INDVINDVINDVINDVINDVINDVINDVINDV
34
shown). The selected louver is opened and the other louvers
Individual Louver Setting:01-02
1 2
are seen horizontally.
4
Adjust air direction & louver angle.
● If the louver position is hard to distinguish, press “ ” or “ ” to set the position .
● In the default setting, the number-one louver is on the electrical box. Looking up from underneath the unit,
the louver numbers run in a clockwise direction: numbered "one", "two", "three", and "four". The louver
number can also be changed. Contact your distributor for details.
Select the louver angle by pressing “ ” or “ ” and press “OK”.
The conrmation screen is displayed.
The louver angle is changed as shown below.
Individual Louver Setting:01-02
1 2
OK Back
Entr RtrnSel. Adj.
5
NOTE: The louver direction without “INDV” complies with the normal mode setting.
Adjust air direction & louver angle.
OK Back
Entr RtrnSel. Adj.
6
7
Select “Yes” by pressing “ ” or “ ” and press “OK”. The
setting is conrmed and the screen returns to the normal
mode.
Verify that “INDV” is turned on at the airow section on the
normal mode.
Individual Louver Setting:01-02
Fix individual louver setting?
Yes No
Sel. Entr Rtrn
A/C
MODE SPEED LOUV. TEMP
COOL
SPEED Adj.
OK Back
Meeting Room
INDV
P5417055
15
Menu
p
Menu
p
5.7.2 Cancellation of Louver Setting
Press “Menu”. Select “Individual Louver Setting” from the menu by pressing “ ” or “ ” and press “OK”.
1
The individual louver setting menu is displayed.
Select “Cancel INDV Louver SET” from the individual louver setting menu and press “OK”. The connected indoor units selection of the cancelled louver setting is displayed.
2
NOTE: If the connected indoor unit is one (1) in the system, the cancel individual louver setting at the procedure “4” is displayed.
OK
OK
Back/Hel
Back/Hel
Menu
Individual Louver Setting
Louver Open/Close VENTI Total Heat Exchanger SET Motion Sensor Setting
OK Back
Individual Louver Setting
Individual Louver Setting
Cancel INDV Louver SET
OK Back
15:10(Fri)
03
/
05
Entr RtrnSel.
Entr RtrnSel.
3
4
Select the indoor unit to cancel by pressing “ ”, “ ”, “ ” or “ ”. Press “OK”.
NOTE:
The indoor unit displayed on the screen ashes when the
individual louver is set.
Select “Yes” by pressing “ ” or “ ” and press “OK”. The individual louver setting is canceled and the screen returns to the normal mode.
NOTE: All the individual louver settings are canceled.
Cancel INDV Louver SET
01-01
01-02
01-03
01-04
Select unit to cancel.
Cancel INDV Louver SET:01-01
Cancel individual louver setting?
Yes No
Sel. Entr Rtrn
OK Back
Entr RtrnSel.
OK Back
16
P5417055
5.8 Motion Sensor
NOTICE
Detecting Area
r
10.5ft
approx. φ28.9ft (8.8m)
5.8.1 Function
The decorative panel (P-AP160NAE1) is equipped with four motion sensors and one radiation sensor.
● Motion Sensor These sensors can detect human activity by measuring the level of change in infrared light emitted by humans or objects.
● Radiation Sensor These sensors can detect the radiation temperature of humans or objects by
(3.2m)
2.6ft (0.8m)
123°
measuring the level of infrared light emitted by humans or objects.
Function 1 Automatic Capacity Save Operation
This function can automatically perform the capacity save operation by a human activity in the air-
conditioned area. If there is insufcient or absence of human activity in the air-conditioned area, the motion
sensors detect it and save the air conditioning capacity. In addition, after the motion sensors detect absence for the period, the operation mode is changed to “If absent”.
● During Capacity Save Operation
* Setting Temperature: The temperature is adjusted 2
o
or 3oF (1o or 2oC) for saving capacity.
* Airow Volume: The airow volume is lowered to one step or to “Slow”.
(except during “dry” operation).
* Airow Direction: The louver angle of controlling airow direction is adjusted horizontally or
downward depending on the operation conditions.
● If absent
The unit performs the operation set by the controller. Refer to Section 5.8.2, “Descriptions for Setting
Items”.
Area of Motion Sensors
(Divided into four areas
among each air outlet)
Area of Radiation Senso
P5417055
● Do not use the motion sensor function in situations where there is a disabled person or an infant. The
motion sensor may detect little motion for a long time as absence, and the operation may be stopped.
● The motion sensor detects human activity. If someone is in a room with little motion, the motion sensor may
detect an absence.
● The motion sensor may detect as human activity if the indoor unit with the motion sensor is installed near a
moving object (ex. swing operation of the heating equipment) which creates a difference in temperature in the room.
● The indoor unit operation can be stopped by the motion sensor control.
NOTE: Indoor units with and without motion sensors can be integrated together into a system installation. In this case, when the operation is stopped by the motion sensor control, the indoor unit without the motion sensor also stops the operation. When the total heat exchanger is interlocked with the indoor unit motion sensor, the total heat exchanger can be stopped with the indoor unit under the following condition:
* The operation mode of the total heat exchanger is set to A/C + VENTI and “If absent” is set to STOP.
However, the total heat exchanger operation mode is “VENTI”, it cannot be stopped even if the “If Absent” setting is set to “Stop”. This is so because during the “VENTI” operation of the total heat exchanger, the indoor unit is not activated (because the motion sensor is not active).
● While air conditioning capacity is saved or operation is stopped by the motion sensor control, “Motion
sensor is activated” is displayed on the LCD.
● If the function: “Prohibiting operation by controller”, is activated from the centralized controller, select the
command: “Running” or “Standby” inside the “If absent” condition at the motion sensor controls setting. If the command “Stop” is selected, motion sensor control is lost and cannot be performed correctly as follows:
* In the case that “If absent: Stop” of motion sensor setting is set by the controller and “Prohibiting
operation by controller” (for all items) is set by the centralized controller, the operation can not be stopped even if in the indoor unit operation stoppage condition of “If absent: Stop”.
* In the case that “If absent: Stop” of motion sensor setting is set and “Prohibiting operation by controller”
(for part of items) is set by the centralized controller, the indoor unit operation is stopped by the motion sensor control. However, the indoor unit operation cannot be restarted from the centralized controller.
17
Function 2 Adjusting Capacity by Increase or Decrease in the Number of People
NOTICE
(1) In instances where people are gathered within or are beyond the range of the motion sensor.
The air conditioning capacity is adjusted by the automatic setting temperature correction depending on human activity and movements of a heat source in the detecting area of the motion sensor .
Cooling or Dry Operation
Heating Operation
Increase in the number of people Decrease in the number of people Increase in the number of people Decrease in the number of people
The setting temperature is adjusted from -2 The setting temperature is adjusted from +2 The setting temperature is adjusted from -2
o
F to -3oF (-1oC to -2oC).
o
F to +3oF (+1oC to +2oC).
o
F to -3oF (-1oC to -2oC).
The function is invalided.
(2) The adjusted setting temperature will return to normal setting temperature after 10 to 30 minutes,
depending on the conditions.
● If human activity and movements of a heat source are small, the motion sensor cannnot detect them.
● If room temperature is high and there is little difference between the radiation temperature of walls, oor
space, and humans, the motion sensor may not detect increase or decrease in the number of humans.
(For example: The cooling operation is performed with a setting at 86°F (30°C) in the summer season.)
● During the “Capacity Save” and “If absent” phase of operation of Function 1, the Function 2 is unavailable.
5.8.2 Descriptions for Setting Items
● Motion Sensor Setting The operation mode for activations of functions 1 and 2 can be selected as follows:
* “ALL MODES” : Functions 1 and 2 are available when the operation mode is “COOL”, “DRY”,
“HEAT”, or “FAN”.
* “COOL + DRY” : Functions 1 and 2 are available when the operation mode is “COOL”, “DRY”,
or “FAN”.
* “HEAT” : Functions 1 and 2 are available when the operation mode is “HEAT”.
* “OFF” : Functions 1 and 2 are not available.
(The default setting is “ALL MODES”.)
● If absent The operation mode for activations during the automatic capacity save operation for Function 1 can
be selected from “Running”, “Stand-by”, or “Stop” on the wired controller. It is set for the indoor unit operation after the motion sensor detects as an absence for the set time in “Check Interval”.
* Running:
The operation continues with saving the capacity after being detected as an absence. If human activity is detected over a period of time, normal operation is performed again.
* Stand-by:
The operation mode is the fan operating at “Slow” speed. If human activity is detected for a period of time, normal operation is performed again.
* Stop:
The operation is stopped by the wired controller when all the indoor units with motion sensor detect an absence that is connected with the same wired controller. If human activity is detected for a period of time by the stoppage, normal operation is performed again.
● Check Interval When the motion sensor detects an absence at a selected check time interval, the function “If absent”
(Function 1) is executed. The interval can be selected from choices ranging from: 30, 60, 90, 120, or
180 minutes. (The default setting is 30 minutes.)
18
P5417055
5.8.3 Setting the Motion Sensor
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Press “Menu”. Select “Motion Sensor Setting” from the menu by pressing “ ” or “ ” and press “OK”.
1
"Motion Sensor Setting” is displayed. The highlighted item changes to “Sensor”, “If absent”, and “Check interval” by pressing “ ” or “ ”.
2
• To set “Sensor”,
go to procedure "3".
• To set “If absent”,
go to procedure "5".
• To set “Check interval”,
go to procedure "7".
OK
OK
OK
Back/Hel
Back/Hel
Back/Hel
Menu
Individual Louver Setting Louver Open/Close VENTI Total Heat Exchanger SET
Motion Sensor Setting
OK Back
Motion Sensor Setting
Sensor
If absent
Check interval
Running
30MIN
OK Back
15:10(Fri)
03
/
05
Entr RtrnSel.
ON
Entr RtrnSel. Adj.
3
4
5
Press “ ” or “ ” and select “Sensor”.
The display is switched “ON” and “OFF”
in order by pressing “ ” or “ ” and change the setting. If other settings are not required, go to
procedure "9".
Press “ ” or “ ” and select “If absent”.
OK
OK
OK
Back/Hel
Back/Hel
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
Motion Sensor Setting
Sensor
If absent
Check interval
Motion Sensor Setting
Sensor
If absent
Check interval
ON
Running
30MIN
OK Back
Entr RtrnSel. Adj.
ON
Running
30MIN
OK Back
Entr RtrnSel. Adj.
ON
Running
30MIN
OK Back
Entr RtrnSel. Adj.
P5417055
6
The display changes to “Running”, “Stand-by” and “Stop” in order by pressing “ ” or “ ” and change the setting. If other settings are not required, go to
procedure "9".
OK
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
ON
Running
30MIN
OK Back
Entr RtrnSel. Adj.
19
NOTICE
7
Menu
p
Menu
p
Menu
p
Menu
p
Menu
p
Press “ ” or “ ” and select “Check interval”.
OK
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
ON
Running
30MIN
OK Back
Entr RtrnSel. Adj.
8
9
The display will display: “30MIN”, “60MIN”, “90MIN”, “120MIN”, and “180MIN” in order by pressing “ ” or “ ” to change the setting. If other settings are not required, go to
procedure "9".
Press “OK” after the setting is made. The conrmation screen is displayed. Select “Yes” by pressing “ ” or “ ” and press “OK”. The motion sensor setting
is conrmed and the screen returns to
normal mode (operation mode indicator).
OK
OK
OK
OK
Back/Hel
Back/Hel
Back/Hel
Back/Hel
Motion Sensor Setting
Sensor
If absent
Check interval
Motion Sensor Setting
Save changes in motion sensor setting?
Yes No
Sel. Entr Rtrn
ON
Running
30MIN
OK Back
Entr RtrnSel. Adj.
OK Back
If more than two controllers are utilized, use the main controller only to set the motion sensor.
20
P5417055
5.9 Comfort Setting
NOTICE
Detecting Area of Motion Sensor
5.9.1 Setting of “Control Cool Air” (Cold Draft Control during Cooling Operation)
(1) Function
This function controls the overcooling airow to prevent of cold draft.
(2) Setting Items
* OFF : This function is not available.
* LOW : The over-cooling airow temperature is controlled low degree.
* MID : The over-cooling airow temperature is controlled medium degree.
* HIGH : The over-cooling airow temperature is controlled high degree.
(The default setting is “OFF”)
(3) Supplement of Function
• The discharge air temperature is elevated higher in “HIGH” > “MID” > “LOW” order.
• The recommended discharge air temperature setting is “LOW”. (When feeling cold at "LOW", change
the setting to “MID” or “HIGH”.)
* This function also reduces the formation of dew condensation on the decorative panel when the
discharge air temperature is lower than the inlet air temperature in a very humid room. (The recommended discharge air temperature setting is “LOW”.)
The "Control Cool Air" function may not have much effect depending on the operating conditions of the outdoor
unit.
● In case one outdoor unit is connected to multiple indoor units and the rate of these indoor units which are equipped with the "Control Cool Air" function is low, this function may not have much of an effect.
● When this function is set, it may take a few minutes to cool the entire room.
● While this function is activated, “Cold draft rest.” is displayed on the LCD control panel of the wired
controller.
5.9.2 Setting of Avoid Air and Receive
(1) Function
This function automatically activates the louver under the setting of “Avoid Air” or “Receive” when the motion
sensor detects human activity.
The “Avoid Air” setting is the reduction of airow set
by the wired controller.
The "Receive" setting allows airow set by the wired
controller.
Each Detection Area: area a to d as shown on the right.
(2) Descriptions for Setting Items
Louver in COOL (Louver Activation at Cooling Operation) Louver in HEAT (Louver Activation at Heating Operation)
• NORMAL: The function is not activated.
• AVOID AIR: The louver angle is automatically adjusted to the highest angle if human activity is
• RECEIVE: The louver operation is automatically changed to “AUTO” (Auto-Swing) mode if
(The default setting is “NORMAL”.)
Motion Sensor
a
B
D
A
to D ,corresponds to each
A
(The louvers are situated in the setting directions on the main menu.)
detected by the motion sensor.
human activity is detected by the motion sensor.
d
c
b
C
P5417055
21
(3) Supplement of Function
NOTICE
• The louver angle is adjusted by the motion sensor to compensate for the presence or absence of human activity and can be set for manual override at the wired controller.
• Each of the four louvers can move independently of the others.
• When the motion sensor detects continuous human activity, louver operation remains at: “Avoid Air” or the “Receive” setting.
• If the motion sensor detects an absence of human activity for 15 minutes or longer, louver angles can be adjusted to the “Avoid Air” or “Reserve” settings to save on energy consumption or manually overridden from the wired controller.
• The commands: “Avoid Air” and “Receive” are shown on the LCD display as variations of angular louver positioning. See below:
Avoid Air
● The function diminishes to (sleep mode) in times of sparse human activity. To reactivate, stand up and
begin walking.
● Objects with higher temperature signatures can be mistaken for humans and can activate this system
function.
● Louver settings: “Avoid Air” or “Receive” in FAN or DRY operations are the equivalent settings for the “Louver
in COOL”.
Receive
22
P5417055
NOTICE
NOTICE
5.9.3 Setting of “Floor HEAT Control” (Radiation Sensor during Heating Operation)
(1) Function
If a steep temperature difference is detected between the radiation temperature and the setting
temperature, this function heats the entire room efciently by adjusting airow direction and airow
volume.
(2) Descriptions for Setting Items:
The setting of “Floor HEAT Control”
• OFF: This function is unavailable.
• ON: This function is available.
(The default setting is OFF.)
(3) Supplement of Function
• When this function is activated, airow direction is directed downwards and the airow volume
changes to “AUTO”.
• This function continues to be active for 20 to 60 minutes, depending on the difference between the ambient air temperature and the set temperature.
• This function will repeat, depending on the temperature difference between a radiation temperature and the setting temperature.
● If the radiation temperature (Floor Temperature) in the detecting area is low, this function may be activated
frequently.
● This louver direction is downward during this function. Avoid a cold draft from a direct airow by setting
function “Individual Louver Setting” or “Avoid Air”.
● During the activation of this function, “Floor HEAT control” is indicated on the LCD.
5.9.4 Useful Tips on Setting the Swing Louver Direction
The swing louver direction can be varied according to each set function. If the set airow direction is not comfortable, refer to the following descriptions and adjust the airow direction.
Order of Priority for Setting the Swing Louver Direction
HIGH
LOW
If two wired controllers are utilized, the comfort setting is available by using the wired controller 1 only.
● Capacity save operation (Function 1) set as “Motion Sensor Setting”.
● Setting of “Individual Louver Setting”
● Swing louver direction at detecting human activity side by “Avoid Air” and “Receive”
function.
● Setting of “Floor HEAT Control”
● Louver direction set on the main menu of a wired controller.
P5417055
23
5.9.5 Creating Comfort Settings
Menu
p
Menu
p
Menu
p
Press “Menu”.
Select "Comfort Setting” from the menu
by pressing “ ” or “ ” and press “OK”.
1
OK
Back/Hel
2
3
OK
Back/Hel
"Motion Sensor Setting” is displayed. The highlighted item is changed to “Control Cool Air”, “Louver in COOL”,
“Louver in HEAT” and "Floor HEAT control" by pressing “ ” or “ ”.
After selecting set item, set function by pressing “
” or “ ”. Setting details are
as shown below.
OK
Back/Hel
• Control Cool Air: “OFF“LOW”MED" ↔ “HI”
• Louver in COOL: “Normal”“Avoid Air”“Receive”
• Louver in HEAT: “Normal”“Avoid Air”“Receive”
Floor HEAT Control:
OFF ↔ ON
Press “OK”.
The conrmation screen is displayed. Select “Yes” by
pressing “
” or “ ” and press “OK”. The “Comfort Setting” is completed and the LCD indication returns to the normal mode.
24
P5417055
An automatic heating/cooling operation and setback operation requires extra settings.
Contact your distributor or contractor for details.
5.10 Automatic Heating/Cooling Operation
In case dual setpoint is selected in automatic heating/cooling
operation, during auto mode both cooling setpoint and heating setpoint can be selected.
By default, temperature when the heating/cooling mode changes
are as follows. Cooling mode changes to heating mode when the indoor temperature is at the heating setpoint -2oF (-1oC). Heating mode changes to cooling mode when the indoor temperature is at the cooling setpoint +2oF (+1oC).
If the temperature for changing modes must be changed, contact your distributor or contractor for details.
5.11 Setback Operation
If the setback operation is enabled and the card key is removed, the louver starts to open in approximately 5 seconds, the setpoint is adjusted for setback, and the fan operates at “Low” speed. During this time, “Setback” is displayed on the LCD.
By default, Cooling: Setpoint +4oF (+2.5oC) Heating: Setpoint -4oF (-2.5oC)
If the adjustment for setback operation must be changed, contact your distributor or contractor for details.
NOTE: In case of Celsius Indication.
NOTE:
In case of Fahrenheit Indication.
P5417055
25
6. Automatic Control
This air conditioner automatically starts the following operations according to the conditions.
The system is equipped with the following functions:
Enforced Stoppage:
The compressor remains OFF for at least three minutes once it has
stopped. If the system is restarted within approximately three minutes after it has stopped, the RUN indicator is activated.
However, the cooling operation or the heating operation remains OFF
Three-Minute Guard
Cooling
Frost Prevention
and
Dry
Self-Cleaning of
Expansion Valve
Hot Start
Defrosting
Heating
Operation
and does not start until after three minutes has elapsed. Enforced Operation:
If all indoor units of a system are Thermo-OFF within approximately
three minutes after the compressor has started, compressor operates continuously during those three minutes. However, if all indoor units of a system are stopped by a controller, compressor is stopped.
When the indoor unit is operating at a low discharge air temperature, the cooling operation may be changed to a fan operation for a while to avoid frost formation on the indoor heat exchanger.
It is for self-cleaning the expansion valve when the operation is stopped
at cooling. The sound of the refrigerant ow may be heard from the
indoor unit during the self-cleaning. However, this is not abnormal.
To prevent cold air discharge into a heated space, the fan speed is
changed from the SLOW / LOW setting to a set position based on
discharge air temperature.
At this time, the louver is in a xed horizontal position and “HOT
START” is displayed on the LCD of the wired controller.
The indoor unit fan operation is stopped to prevent cold air discharge during the defrosting operation. At this time, the message “HOT-START” is displayed on the LCD of the wired controller and the indoor unit fan
louver angle is xed horizontally.
Residual
Heat Removal
Prevention
of Overload
Operation
When the heating operation is stopped, indoor fan operation may remain at the slow speed for a maximum of two minutes to lower the internal temperature of the indoor unit.
When the outdoor temperature is high (approximately 70oF (21oC) or more) during heating operation, the operation is stopped by activation of the outdoor thermistor.
NOTE
● This air conditioner adopts hot air circulaition system for the heating operation.
● Any oversized room with a low ambient air temperature will require an extended amount of time to warm
up. Once the air temperature gets to the required setting temperature, the display “HOT START” is turned
OFF.
● The indication “HOT-START” may be displayed during or right after the defrosting operation. It is
activated during the hot start operation to prevent the perception of cold draft. This is NOT abnormal.
26
P5417055
7. Maintenance
(Two places)
Upper Part of Filter
Lower Part of Filter
A
NOTICE
● Turn OFF the power source before maintenance work. If the power source is not turned off, a re or an
electric shock may result.
● Perform the maintenance work with a stable foothold or foundation. This may prevent falling or injury.
● Hold the air lter and the air inlet grille securely by hand when attaching or removing it. If not, it may
cause the unit to fall, resulting in serious injury.
● Use light pressure with a clean soft cloth when cleaning the lens of the motion sensor. The surface
material of the lens is easily scratched, blemished, and can result in degraded performance of the sensor.
7.1 Daily Maintenance
7.1.1 Cleaning Air Filter
Clean the air lter when the lter sign is turned ON.
On/Off
A/C
MODE SPEED
COOL
Motion Sensor ON
LOUV. Adj.
Meeting Room
LOUV.
Avoid
OK
TEMP
FLTR
Menu
Back/Help
Filter Sign
ECO
(1) Open the air inlet grille.
Slide the knobs on both sides of the air inlet grille
in the direction of the arrows as shown, and open the air inlet grille.
Air Inlet Grille
Knobs
(2) Remove the air lter.
Support the underside of the air inlet grille
Hook
as shown. Unhook the lter from the air inlet grille and remove the air lter.
P5417055
ir Inlet Grille
Air Filter
Hook
27
(3) Clean the air lter.
•Vacuum dust off with hand-held vacuum cleaner, or wash the air lter with water or a neutral detergent.
• Dry the air lter in a shaded area.
NOTE
• Do not use water warmer than 122°F (50°C). Filter elements can be damaged.
• Do not dry the air lter by holding it over open ame, with a hair dryer, or any type of heating device. Filter
elements can be damaged by heat.
(4) Attach the air lter.
After the air lter is dried, attach it in the reverse order from what is shown procedure "2".
(5) Close the air inlet grille.
NOTE
• Be sure to attach the air lter. Operating the indoor unit without a lter installed will cause serious damage and breakdown.
• Make sure that the air inlet grille is securely locked with the knobs. If not properly secured, it could swing open and strike someone below and cause minor injuries.
(6) Reset the lter sign.
NOTE
If the accumulated operation time is shorter than that indicated by the lter sign setting, the icon displaying “ ” activates and “Setting Disabled” is displayed.
•Press “Menu”.
Select “Reset Filter Sign Time” from the menu and press “OK”. The conrmation screen is displayed.
Menu
Simple Timer
Reset Filter Sign Time
Operation Schedule Elevating Grille Power Saving Setting
•Select “Yes” by pressing “
” or “ ” and press “OK”.
The “FLTR” indication is turned OFF and the screen returns to the normal mode.
15:10(Fri)
OK Back
Entr RtrnSel.
01
/
05
28
P5417055
7.1.2 Removing, Cleaning and Attaching Air Inlet Grille
(Two places)
Supporting String
NOTICE
Air Inlet Grille
Lift it with inclined.
Wipe down the air inlet grille with a soft cloth soaked in lukewarm water and wrung-out.
l
Gently wipe down using only a clean soft cloth. Avoid the use of Benzene type thinners or chemical
l
detergents and abrasives as cleaning agents which will damage the nish of outer plastic surfaces and
louvers. Avoid using excessive force when cleaning these surfaces as they can be easily damaged.
When cleaning the lens of the motion sensor, the surface material of the lens is easily scratched, and can
l
result in degraded performance of the sensor.
The air inlet grille can be removed and cleaned.
(1) Open the air inlet grille.
While sliding the knobs on both sides of the air inlet
grille in the arrow direction, open the air inlet grille.
Air Inlet Grille
Knobs
(2) Remove the air inlet grille.
• Unhook the supporting string from the decorative
panel.
• Open the air inlet grille at an approximately 45° angle from the
decorative panel surface.
• Tilt the air inlet grille and lift it up to remove it.
NOTE:
Although the air inlet grille can be opened up to 90°, it cannot be removed from the decorative panel at that angle. Tilt it to a 45°
angle when removing it.
(3) Clean the air inlet grille.
(4) Reattach the air inlet grille.
Reattach in reverse order.
Ceiling
Decorative Panel
45
o
7.2 Maintenance Prior to and After Use
Prior to Use
• Remove any obstacles around the air inlet grilles and the air outlet of both the indoor and outdoor units.
• Check that the air lter is not clogged with dust
and dirt.
P5417055
After Use
• Clean the air lter, the air inlet grille and the
decorative panel.
29
8. Troubleshooting
8.1 This is Not Abnormal
Phenomenon Cause and Action
All indicator LEDs on the wired controller are turned
OFF.
Operation Stopped
White Steam from Indoor Unit
White Smoke from Indoor Unit
Mist from Indoor Unit
Odor from Indoor Unit
Sound from Indoor Unit
Dew Condensation on Decorative Panel
Temperature Irregularity
“HOT-START” on LCD Illuminated (ON)
Operation Mode on LCD Flashing
“Motion Sensor ON” is turned ON the wired controller.
After Power Failure
During Heating Operation Dust attached to the heat exchanger has dried.
At Beginning of Heating Season
In Restaurant or Kitchen
During Dry Operation
During Cooling Operation in Humid Environment
Odors Emanating from Indoor Unit Air Dischagre
A grating sound is heard when starting or stopping the operation.
Sound of water owing or
bubbling is heard during the operation.
A growling sound may be heard temporarily right after
the airow volume is changed.
Dew condensation on Decorative Panel or Cabinet or Dew Drops
Airow volume and
temperature irregularities exist for each outlet.
The micro-computer is activated to protect the device from electromagnetic interference. Restart the operation.
The operation has stopped automatically because the motion sensor is set as “If absent: Stop” and it detects an absence of motion for a period of time. (All indoor units connected to the same controller are stopped.)
Restart the operation. If the instantaneous power failure is within 2 seconds, the operation restarts automatically.
This might occur when dust attached to the heat exchanger has dried.
This can occur when oily residue coats the ns and heat exchanger efciency is degraded.
This might occur due to the air outlet temperature decreasing. Change the operation mode.
This might occur due to the air outlet temperature
decreasing. Raise the set temperature and airow
volume.
The intake of cigarette smoke is the likely reason, with nicotine deposits coating or clogging the cells
and surfaces of the air lter.
Ventilate the unit well in fan mode and clean the air
lter, the air outlet and air inlet grill.
This is the sound made when the components are rubbing up against one another due to the expansion and contraction of plastic formed parts brought on by temperature change.
This is the sound made when the refrigerant ows
or the drain-up mechanism drains water. The sound may be heard especially when starting the operation or stopping the compressor (for approximately 3 minutes).
It is generated because the fan motor makes temporary sound by change of fan speed.
This might occur when the operation is performed in a humid environment over a prolonged period of time (relative humidity around 80%).
This might occur for structural reasons, such as the size of an air outlet and the location of heat exchanger.
This might occur according to the operation mode or operational conditions.
30
P5417055
8.2 Before Contact
Check these items over before contacting a contractor.
Trouble Checking Point Action
Check that the main power source is turned ON.
Operation Unavailable
Cooling
Immediate shutdown after start-up
Insufcient Cooling or
Heating
Heating
Check that the fuse is not blown or the circuit breaker from the main power source is not tripped.
Check if the air inlet and outlet for the outdoor unit are not obstructed.
Check if there are any
obstacles impeding the airow
near the air inlet and outlet of the outdoor unit.
Check that the outlet air is not redirected into the air inlet.
Check that the operation mode is appropriate.
Check that the set temperature is appropriate.
Check that the airow
direction is appropriate.
Check that the air lter is not
clogged.
Verify that there are no open windows and doorways.
Check that there are no
obstacles impeding airow
near the air inlet and outlet for both indoor and outdoor units.
Turn ON the power at the main power source for the air conditioner.
Replace the fuse or reset the circuit breaker. If trouble recurs, contact your contractor or distributor.
Remove objects obstructing the air inlet and outlet.
Remove any obstacles obstructing airow.
If the fan mode is selected, switch the operation
mode to cooling/heating.
If not, change the setting temperature by pressing
” or “ ” by the wired controller.
If not, change the airow direction.
In case the footing is not heated well during the heating operation, change the louver downward.
Clean the air lter.
Close windows and doors.
Remove the obstacles.
P5417055
31
8.3 Contact Distributor
Indoor Unit Number
If trouble still persists, even after checking off previously listed items or detecting problems not mentioned in the previous pages, stop using this product and call your distributor or contractor immediately.
If there is any perceived abnormality present (noises or odors associated with electrical short,
re, or burning elements), shut down immediately and shut OFF at the main power source.
Contact your distributor or contractor without delay.
Trouble Action before Contact
Protection devices (fuses, breakers, and GFCI's) activate
frequently or the operation switch does not work.
Water leakage from the indoor unit. Stop the operation.
"Motion Sensor ON" or "Radiation Sensor" is ashing.
● The RUN indicator (red) is ashing.
● The indoor unit number, alarm code, unit model code,
and the number of connected indoor units are displayed on LCD.
● If multiple indoor units are connected to one controller,
the above abnormality informations for each indoor unit are displayed individually.
Turn OFF the power source.
There is a possibility of the failure of motion sensor or radiation sensor. Make the setting of motion sensor and Control
invalid and contact your distributor. In
Floor HEAT
that case, after the LCD of wired controller display
has disappeared and until service is nished, the
operation of this unit is available.
Check the details on LCD and contact your distributor.
Refer to Section 8.4, the alarm code table. Contact your distributor and inform them of the alarm code indicated on the LCD of the wired controller.
01-02
Alarm Code:
MODEL : F .08
I.U. :
IDU : ODU :
O.U. :
RCI-3.0FSN3
******
RAS-3HVRNM2
******
Sel. OP MODE
23
OK
Chek
AlarmRST
Address
Entr
Provide the following information when contacting your distributor.
1) Unit model
2) Symptoms and nature of the problem.
3) Number of the alarm code or any ashing indicator on the LCD.
32
P5417055
8.4 Alarm Codes
Code Category Content of Abnormality Code Category Content of Abnormality
01 Indoor Unit Activation of Protection Device 35
02 Outdoor Unit
03
Communication
04
05 Supply Phase Problem of Power Source Phases 41
06 Voltage
07
Cycle
08
09 Outdoor Unit
11
12 Outlet Air Thermistor Failure 47
13 Freeze Protection Thermistor Failure 48
14 Gas Piping Thermistor Failure 51
19 Fan Motor
20
21 High Pressure Sensor Failure 54
22 Outdoor Air Thermistor Failure 56
23 Discharge Gas Thermistor Failure 57 Activation of Fan Controller Protection
Sensor on
Indoor Unit
Sensor on
Outdoor Unit
Activation of Protection Device (High Pressure Cut)
Operational Irregularities between Indoor and Outdoor
Problem between Inverter PCB and Outdoor PCB
Abnormal Voltage Drop in Outdoor Unit
Decrease in Superheated Discharge Gas
Increase in Discharge Gas Tempera­ture
Activation of Protection Device for
Outdoor Fan
Inlet Air Thermistor Failure 46
Activation of Protection Device for
Indoor Fan
Compressor Thermistor Failure 53
36 Incorrect Indoor Unit Combination
38
39 Compressor
42 Overload Heating
43
44
45
52
System
Pressure
Protection
Device
Inverter
Outdoor Fan
Incorrect Setting of Indoor Unit No.
Problem with Protective Pickup Circuit in Outdoor Unit
Problem with Running Current at Con­stant Speed Compressor
Overload Cooling
Activation of Pressure Ratio Decrease Protection Device
Activation of Low Pressure Decrease Protection Device
Activation of Low Pressure Increase Protection Device
Activation of High Pressure Increase Protection Device
Activation of High Pressure Decrease Protection Device
Activation of Overcurrent Protection Device
Problem with Inverter Current Sensor
Activation of Inverter Overcurrent Protection
Activation of Transistor Module Protection
Abnormality of Inverter Fin Temperature
Abnormality of Detection for Fan Mo­tor Position
24 Evaporating Thermistor Failure 58 Abnormality of Fan Controller
29 Low Pressure Sensor Failure b0
31
System
32
Incorrect Capacity Setting of Outdoor Unit and Indoor Unit
Incorrect Setting of Other Indoor Unit Number
b1
EE Compressor Compressor Protection Alarm
System
Incorrect Setting of Unit Capacity
Incorrect Setting of Unit and Refrigerant Cycle No.
P5417055
33
© 2017 Johnson Controls, Inc.
P5417055
Code No. LIT-12012618 Issued November 2017
Loading...