Johnson Controls HH-6705 Series Catalog Page

HH-6705 Series
Mounting Holes (2)
3/32 in. (2.4 mm) for No. 6 Screws
6.12 155
4.44 112
1.62 42
1.75 45
0.25 7
3.75 96
0.50 13
1.75 45
2.19 55
HH-6705 Dimensions, in. (mm)
hh67052p.eps
HH-6705-9N0GP Duct Humidistat
TRUERH
True ±2% Accur
TM
T
RUE
RH™
Description
The HH-6705 Series Duct Humidistat is typically mounted downstream from a humidifier, and turns the humidifier off (contact opens) when the setpoint is reached. Setpoint is adjustable from 30 to 90% Relative Humidity (RH). To reduce equipment cycling, the HH-6705 Series turns the humidifier on (contact closes) when the humidity in the duct falls 5% below the setpoint.
Repair Information
If the HH-6705 Series TRUERH™ Duct Humidistat fails to operate within its specifications, replace the unit. For a replacement humidistat, contact the nearest Johnson Controls® representative.
Selection Chart
Code Number Description
HH-6705-9N0GP Duct Humidistat
Code No. LIT-1900106 Issued September 12, 2007
Features
•TRUERH™ circuitry and calibration techniques for which patent is pending
• All-Polymer™ humidity sensor with patented sensing element provides accurate and reliable humidity sensing with improved resistance to chemical corrosion
• 30 to 90% RH adjustable setpoint covers most application requirements, including humidification and dehumidification
• 5% fixed differential reduces humidification equipment cycling
• plastic duct probe improves thermal performance
• quick-mount, 2-screw installation reduces installation time and simplifies retrofits
Technical Specifications
HH-6705 Series TRUERH™ Duct Humidistat
Power Requirements 20 to 30 VDC at 33 mA
Output Single-Pole, Single-Throw (SPST), normally open relay contact
Relay Contact Rating
Humidity Element All-Polymer
Ambient Operating Conditions 32 to 122°F (0 to 50°C)
Survival Operating Conditions -22 to 140°F (-30 to 60°C)
Ambient Storage Conditions -40 to 176°F (-40 to 80°C)
Materials Metal cover and housing with polymeric duct probe Dimensions Overall (H x W x D) 4.44 x 2.19 x 7.87 in. (113 x 56 x 200 mm)
Shipping Weight 1.5 lb (0.7 kg)
Maximum 4 ampere at 24 VAC;
Minimum 100 mA at 5 VDC
Setpoint Adjustable from 30 to 90% RH Sensing Range 0 to 100% RH, non-condensing Differential Fixed 5% RH
Probe (D x L) 1.62 x 6.12 in.(41 x 155 mm)
or 20 to 30 VAC, 50/60 Hz at 45 mA (1.35 VA maximum), Class 2
Opens at setpoint on increasing RH Closes at 5% RH below setpoint on decreasing RH
pilot duty 42.4 VA at 24 VAC, Class 2
0 to 100% RH, non-condensing; 86°F (30°C) maximum dew point
0 to 100% RH, non-condensing; 86°F (30°C) maximum dew point
0 to 100% RH, non-condensing; 86°F (30°C) maximum dew point
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.