Johnson Controls HH-6705 Installation Guide

24-7701-136, Rev. B
FANs 216, 1628.3 Installation Instructions HH-6705 Issue Date 0316
TRUERH
HH-6705 Duct Humidistat
nstallation
I
IMPORTANT: Use this HH-6705 Series Duct
Humidistat only as an operating control. Where failure or malfunction of the HH-6705 Humidistat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the HH-6705 Humidistat.
IMPORTANT: Utiliser ce HH-6705 Series Duct
Humidistat uniquement en tant que dispositif de régulation. Lorsqu'une défaillance ou un dysfonctionnement du HH-6705 Humidistat risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du HH-6705 Humidistat.
Series

Tools Required

hole saw with 1-3/4 in. (45 mm) diameter blade
drill with 3/32 in. (mm) drill bit
1/4 in. (7 mm) and 1/8 in. (3 mm) flat-blade
screwdrivers
gasket, sealer, or other material to seal the area between the unit and the duct
ocation Requirements
L
IMPORTANT: To avoid damage to the circuit board
and components, do not mount the unit in a location where high concentrations of corrosive vapors are present.
Place the humidistat in a location that complies with the following:
Position: The humidistat is designed for duct mounting in any position, except with the probe tip pointed up.
Duct Diameter: Recommended minimum diameter (round ducts) or width (square ducts) is 12 in. (305 mm).
Air Stratification (when the unit is mounted on the discharge side of the fan): Recommended location is at least 8 ft (2.4 m) downstream from the humidification equipment, where duct air and water vapor are sufficiently mixed. Avoid areas where the probe may be exposed to condensation.

Parts Included

HH-6705-9N0GP duct humidistat
No. 6-32 x 1/4 in. binder-head cover screw
3 in. (76 mm) outside diameter steel washer
© 2016 Johnson Controls, Inc. 1 Part No. 24-7701-136, Rev. B www.johnsoncontrols.com Code No. LIT-216605
etpoint
30
50
Mounting Hole
Mounting Hole
Setpoint Potentiometer
70
90
Cover
Duct
Washer
S
The setpoint is adjustable from 30 to 90% Relative Humidity (RH). Use a 1/8 in. (3 mm) flat-blade screwdriver to adjust the setpoint potentiometer located under the cover. (See Figure 1.)
Figure 1: Adjusting the Setpoint
ounting
M
Mount the humidistat as follows:
1. Remove any excess insulation from the duct that prevents the probe from extending a minimum of 3 in. (76 mm) into the airstream.
2. Use the hole saw to make a 1-3/4 in. (44.5 mm) hole in the duct for inserting the probe.
Note: If the duct hole is larger, use the 3 in. (76 mm)
washer provided when installing the humidistat. (See Figure 2.)
3. Loosen the cover screw, and lift the cover off the unit. (See Figure 2.)
Figure 2: Mounting the Humidistat
4. Insert the probe into the duct, and mark the holes for the two mounting screws.
5. Remove the unit, and drill a 3/32 in. (2.4 mm) hole for each mounting screw.
6. Use a gasket, sealer, or other means to seal the area around the hole between the unit and duct.
IMPORTANT: Seal any holes created during
installation to help reduce drafts and for more accurate humidity readings. Use the washer provided, in addition to one of the materials in Step 6 if the duct hole is larger than 1-3/4 in. (44.5 mm).
7. Reinsert the probe, and secure the housing to the
2 TRUERH Series HH-6705 Duct Humidistat Installation Instructions
duct using two No. 6 sheet metal screws (not provided).
W
!
Wire Color
Designation
iring
roubleshooting
T
If the humidistat is not functioning properly:
WARNING: Risk of Electric Shock.
Disconnect the power supply before making electrical connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
AVERTISSEMENT: Risque de décharge
électrique.
Débrancher l'alimentation avant de réaliser tout branchement électrique. Tout contact avec des composants porteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.
Observe the following when wiring the humidistat:
Do not run low voltage wiring in the same conduit as line voltage wiring or other conductors that supply highly inductive loads.
1. Check all supply voltage connections and output wiring to make sure the wiring is correct.
2. Move the setpoint up and down to ensure the humidistat is responding. (The relay should switch on and off when the setpoint is adjusted above and below the humidity level being sensed.)
Note: The humidity in the duct must be within the
30 to 90% RH setpoint range before the HH-6700 responds.
3. If the troubleshooting suggestions fail to remedy the problem, replace the unit.
dditional Information
A
There are no accessories for the HH-6705-9N0GP humidistat. See Table 2 for product specifications.
Use 18 or 24 AWG wire.
Make all wiring connections in accordance with the
National Electrical Code and all local regulations.
The power requirements of the HH-670 Series are 20 to 30 VDC at 33 mA or 20 to 30 VAC, 50/60 Hz at 45 mA (1.35 VA maximum). Make wiring connections using four color-coded, 6 in. (152 mm) 18 to 24 AWG lead wires. Designations are indicated in Table 1.
Table 1: Wire Designations
Red Input Power
Black Common Yellow Relay Contact Yellow Relay Contact
TRUERH Series HH-6705 Duct Humidistat Installation Instructions 3
T
RH
Series HH-6705 Duct Humidistat
0 to 100% RH, non-condensing; 86°F (30°C) maximum dew point
1.5 lb (0.7 kg)
European Single Point of Contact:
NA/SA Single Point of Contact:
APAC Single Point of Contact:
CHINA
Building Efficiency
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Table 2: Specifications
Product Power Requirements Output
Relay Contact Rating
Humidity
Ambient Operating Conditions
Survival Operating Conditions
Ambient Storage Conditions
Materials Dimensions
Shipping Weight
The performance specificati ons are nominal and conform to acceptable industry standards. For application at condi tions beyond these specifications, consult the local Johnson Controls office. Johnson Control s, Inc. shall not be liable f or damages resulting from misapplication or misuse of its products .
RUE
20 to 30 VDC at 33 mA or 20 to 30 VAC, 50/60 Hz at 45 mA (1.35 VA maximum), Class 2 Single-Pole, Single-Throw (SPST), normally open relay contact:
Opens at setpoint on increasing RH Closes at 5% RH below setpoint on decreasing RH
Maximum: 4 ampere at 24 VAC; pilot duty 42.4 VA at 24 VAC, Class 2 Minimum: 100 mA at 5 VDC
Element: All-Polymer Setpoint: Adjustable from 30 to 90% RH Sensing Range: 0 to 100% RH, non-condensing Differential: Fixed 5% RH
32 to 122°F (0 to 50°C)
-22 to 140°F (-30 to 60°C) 0 to 100% RH, non-condensing; 86°F (30°C) maximum dew point
-40 to 176°F (-40 to 80°C) 0 to 100% RH, non-condensing; 86°F (30°C) maximum dew point
Metal cover and housing with polymeric duct probe Overall (H x W x D): 4.44 x 2.19 x 7.87 in. (113 x 56 x 200 mm)
Probe (D x L): 1.62 x 6.12 in. (41 x 155 mm)
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
4 TRUERH Series HH-6705 Duct Humidistat Installation Instructions
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 2 14142
507 E. Michigan Street, Milwaukee, WI 53202
TRUERH Series HH-6705 Duct Humidistat Installation Instructions 5
Loading...