HE-6800 Series Humidity Transmitters with Temperature Sensor
Code No. LIT-1900655
Issued July 8, 2015
HE-6800 Series Humidity Transmitters with Temperature Sensor
Description
The HE-6800 Series Humidity Transmitters with Temperature Sensor
provide both humidity and temperature sensing in room wall-mount
applications. The transmitter offers local warmer/cooler temperature
setpoint adjustment and temporary occupancy override. The humidity
sensor provides Relative Humidity (RH) accuracy of ±2% or ±3% RH
and measures RH over the entire range of 0 to 100%.
A warmer/cooler dial is included on certain models for minor
temperature adjustments from the setpoint. All models feature an
occupancy override button that allows the user to override time-of-day
scheduling when the space is occupied outside of the normal occupied
hours schedule. The transmitter also includes DIP switches to enable
or disable override and Light-Emitting Diode (LED) functions. In
addition, all models feature a user-selectable 0 to 5 VDC or
0 to 10 VDC humidity output switch, and a power supply selection
switch.
The HE-6800 Series Humidity Transmitters include screw terminal
block terminations that provide flexibility for field wiring. All models
include a 6-pin modular jack access port for connecting accessories to
the Zone Bus. This feature allows a technician to commission or
service the controller via the transmitter.
Features
• controller configuration DIP switch — allows users to adjust the
room comfort and choose occupancy features that match the
application and transmitter
• power supply selection switch — enables transmitter use in high
input voltage applications
• user-selectable humidity output — provides either a 0 to 5 VDC or
0 to 10 VDC output for compatibility with various controllers
• occupancy Light-Emitting Diode (LED) indicator — displays the
current operating mode of the controller (VMA12 and VMA14 Series
only)
• manual override pushbutton (PB) — overrides time-of-day
scheduling when the space is occupied outside of the normal
occupied hours schedule
• warmer/cooler setpoint dial (select models) — allows for minor
temperature adjustments from the setpoint
Repair Information
If the HE-6800 Series Humidity Transmitter fails to operate within its
specifications, replace the unit. For a replacement transmitter, contact
the nearest Johnson Controls® representative.
Selection Charts
HE-6800 Series Humidity Transmitter with Temperature Sensor Product Code Numbers
Product Code Number Temperature Sensing
Element
HE-68N2-0N00WS Nickel ±2% No 80 x 80
HE-68N3-0N00WS Nickel ±3% No 80 x 80
HE-68N2-1N00WS Nickel ±2% Yes 80 x 80
HE-68N3-1N00WS Nickel ±3% Yes 80 x 80
HE-68P2-0N00WS Platinum ±2% No 80 x 80
HE-68P3-0N00WS Platinum ±3% No 80 x 80
HE-68P2-1N00WS Platinum ±2% Yes 80 x 80
HE-68P3-1N00WS Platinum ±3% Yes 80 x 80
HE-6863-0N00WS 10,000 Thermistor ±3% No 80 x 80
HE-6863-1N00WS 10,000 Thermistor ±3% Yes 80 x 80
Optional Accessories
Product Code Number Description
ACC-INSL-0
ACC-INSL-1
NS-WALLPLATE-0 Adapts an HE-6800 Series Humidity Transmitter (3-3/16 x 3-3/16 in. [80 x 80 mm]) to a Standard
T-4000-119 Allen-Head Adjustment Tool (30 per Bag)
1. These foam pads help prevent drafts from entering the unit through the wall, and make installation easier when mounting on an uneven surface.
1
1
Wallbox Mounting Pad (10 per Bag)
Surface Mounting Pad (10 per Bag)
3-3/16 x 4-3/4 in.
(80 x 120 mm) Wallbox
Humidity Accuracy
(% RH)
Warmer/Cooler Temperature
Setpoint Adjustment Override
Enclosure
Dimensions (mm)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Jo hnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
www.johnsoncontrols.com
1
HE-6800 Series Humidity Transmitters with Temperature Sensor (Continued)
Technical Specifications
HE-6800 Series Humidity Transmitters with Temperature Sensor
Power Requirements 4.5 to 7.5 mA at 14 to 30 VDC and 5K ohm Load, or 18 to 25 mA at 20 to 30 VAC and 5K ohm Load
Terminations 9-Position Screw Clamp Terminal Block
Wire Size 16 to 24 AWG (1.3 to 0.6 mm Diameter); 18 AWG (1.0 mm Diameter) Recommended
Temperature Measurement Range 32 to 131°F (0 to 55°C)
Humidity Measurement
Range
Temperature Sensor Nickel
Humidity Sensor Type Capacitive Polymer Sensor
Humidity Element
Accuracy
Setpoint Range Warmer/Cooler
Temperature Sensor Time Constant 10 Minutes at 10 ft per Minute
Manual Override Integral Momentary Pushbutton (DIP Switch Selectable)
LED Green LED Indicates Three Modes of Operation (VMA12 and VMA14 Series Controllers Only)
Ambient Operating Conditions 32 to 131°F (0 to 55°C), 10 to 95% RH Noncondensing;
Ambient Storage Conditions -40 to 140°F (-40 to 60°C), 5 to 95% RH Noncondensing;
Materials White Thermoplastic
Dimensions
(H x W x D)
Shipping Weight 0.44 lb (0.20 kg)
Compliance United States UL Listed, File E107041,
Full Range 0 to 100% RH
Calibrated Range 10 to 90% RH
(HE-68Nx Models)
Platinum
(HE-68Px Models)
Nonlinear NTC,
Thermistor, Type II
(HE-686x Models)
HE-68x2 Models ±2% RH for 20 to 80% RH at 50 to 95°F (10 to 35°C);
HE-68x3 Models ±3% RH for 20 to 80% RH at 77°F (25°C);
HE-68xx-0 Models 3-3/16 x 3-3/16 x 1-5/16 in. (80 x 80 x 32 mm)
HE-68xx-1 Models 3-3/16 x 3-3/16 x 1-7/16 in. (80 x 80 x 35 mm)
Canada UL Listed, File E107041,
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential
Australia and New
Zealand
Sensor Type 1,000 ohm Thin Film Nickel
Coefficient Approximately 3 ohm per F° (5.4 ohm per C°)
Reference Resistance 1,000 ohm at 70°F (0°C)
Accuracy ±0.34F° at 70°F (±0.18C° at 21°C)
Sensor Type 1,000 ohm Thin Film Platinum
Coefficient Approximately 2 ohm per F° (3.9 ohm per C°)
Reference Resistance 1,000 ohm at 32°F (0°C)
Accuracy ±0.35F° at 70°F (±0.19C° at 21°C)
Sensor Type 10,000 ohm NTC Thermistor
Coefficient Nonlinear NTC, Johnson Controls Type II
Reference Resistance 10,000 ohm at 77°F (25°C)
Accuracy ±0.9F° (±0.5C°) at 32 to 158°F (0 to 70°C)
±4% RH for 10 to 20% RH and 80 to 90% RH at 50 to 95°F (10 to 35°C)
±6% RH for 10 to 20% RH and 80 to 90% at 77°F (25°C)
86°F (30°C) Maximum Dew Point
86°F (30°C) Maximum Dew Point
Protection: IP30 (EN 60529)
CCN PAZX, Under UL 916, Energy Management Equipment
CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment
requirements and other relevant provisions of the EMC Directive 2004/108/EC.
WEEE Directive 2002/96/EC
RoHS Directive 2002/95/EC
C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
www.johnsoncontrols.com
2