Johnson Controls HE-6800 Series Installation Guide

HE-6800 Series Humidity Transmitters with
24-10409-28, Rev. E
Temperature Sensor
Installation Instructions
HE-68xx-xN00WS
Refer to the QuickLIT website for the most up-to-date version of this document.

Applications

The HE-6800 Series Humidity Transmitters with Temperature Sensor provide both humidity and temperature sensing in room wall-mount applications. The transmitter offers local warmer/cooler temperature setpoint adjustment and temporary oc cu pancy override. The humidity sensor provides Relative Humidity (RH) accuracy of ±2% or ±3% RH and measures RH over the entire range of 0 to 100%.
A warmer/cooler dial is included on certain models for minor temperature adjustments from the setpoint. All models feature an occupancy override button that allows the user to override time-of-day scheduling when the space is occupied outside of the normal occupied hours schedule. The transmitter also includes DIP switches to enable or disable override and Light-Emitting Diode (LED) functions. In addition, all models feature a user-selectable 0 to 5 VDC or 0 to 10 VDC humidity output switch, and a power supply selection switch.
The HE-6800 Series Humidity Transmitters include screw terminal block terminations that provide flexibility for field wiring. All models include a 6-pin modular jack access port for connecting accessories to the Zone Bus. This feature allows a technician to commission or service the controller via the transmitter.
Part No. 24-10409-28, Rev. E
Issued February 2016

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case users will be required to correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Cau sing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
IMPORTANT: Use the HE-6800 Series Humidity Transmitter only to provide in put to equipment under normal operating conditions. Where failure or malfunction of the transmitter could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the transmitter.
HE-6800 Series Humidity Transmitters with TemperatureSensor
Installation Instructions
1

Installation

Special Tools Needed

A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls® T-4000-1 19 Allen-Head Adjustment Tool is required during installation.

Accessories

Installing the HE-6800 Series Humidity Transmitter on a wallbox requires accessory NS-WALLPLATE-0, ordered separately.

Mounting

Location Considerations

Locate the HE-6800 Series Humidity Transmitter:
on a partitioning interior wall, and approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (no heating and no cooling), or sources of electrical interference
Note: The HE-6800 Series Humidity Transmitter is shock and vibration resistant; however, be careful not to drop the unit or mount it where it could be exposed to excessive vibration.
The following ambient operating conditions apply:
Temperature: 32 to 131°F (0 to 55°C)
Humidity: 10 to 95% RH, noncondensing; 86°F (30°C) maximum dew point
To mount the transmitter to the wall:
2. Insert a blade screwdriver into the slot next to the security screw location, and then carefully pry the top edge of the transmitter assembly away from its mounting base and remove.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
3. Pull out approximately 6 in. (152 mm) of cable from the wall, and insert the cable through the hole in the mounting base.
4. Align the mounting base on the wall, and use the base as a template to mark the location of the two mounting holes on the surface.
Note: Make sure the mounting base is positioned correctly with the security screw located on the top edge of the base.
5. Secure the mounting base to the wall using the appropriate mounting hardware (field furnished).
6. Set DIP switches for the desired operation. See the
Internal Wiring Diagrams Adjustments sections for additional information.
7. Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the transmitter assembly , and rot ate the assembly onto its mounting base.
Note: Make sure the terminal block pins align with the holes in the terminal block.
8. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to tighten the security screw and fasten the network transmitter assembly to the mounting base.
and Setup and
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to loosen the security screw on the top of the unit.
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions
2

Wiring

Figure 1: Terminal Block Wiring Designations
(LED ON Mode [Factory Default] and Manual Override PB Enabled)
RT
D
1
Temperature
Sensor
2
Temperature
Sensor
Common
3
Setpoint
Common
4
Setpoint
Setpoint
5
24 VAC/ +15 VDC
1k Ohms
6
Common
7
Zone Bus
Manual
Override
Button
8
LED
LED
Internal wiring diagram with DIP switches set as shown on the right, LED Mode = ON and Manual Override push button enabled.
FIG:term_blck_LED
NO
12
3
9 RH Output 0–10 VDC
Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations.
Keep wires as short as possible to minimize sensor error. Each 2 50 ft (76 m) run of 18 AWG wire or 50 ft (15 m) of 24 AWG wire creates 1F° (0.56C°) error for a nickel sensor or 1.5F° (0.83C°) error for a platinum sensor due to wire resistance.
To maintain less than 1F° (0.56C°) error for nickel or
1.5F° (0.83C°) error for platinum, hold the total resistance of all sensor wiring below 3 ohm. When wiring the HE-6800, do not run low voltage wiring in the same conduit as line voltage wiring or other conductors supplying highly inductive loads.

Internal Wiring Diagrams

Internal wiring diagrams are shown in Figure 1 and Figure 2. Terminal block designations are shown in Figure 3. The terminals are identified in Table 1. See the Setup and Adjustments
section and Figure 4 for an explanation of the LED and Pushbutton (PB) modes. Make connections pairing the following wires:
sensor (Terminal 1 and Terminal 2)
setpoint (Terminal 3 and Terminal 4)
Zone Bus and Common (COM)
(Terminals 6 and 7)
Shielding is not required. If used, follow the system controller’s recommenda tio ns for gr ou nd in g th e shie ld .
Note: The Manual Override PB does not respond when the DIP switch positions are all down (LED mode NO PB, as shown in Figure 2 and Figure 4).
Manual Override is selected for either Terminals 1 and 6 to short sensor (with DIP switch set for LED Off) or Terminal 6 and Terminal 8 to short LED (with DIP switch set for LED On).
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions
3
.
Figure 2: Terminal Block Wiring Designations (LED OFF Mode and Manual Override PB Enabled)
RT
D
1
Temperature
Sensor
2
Temperature
Sensor
Common
3
Setpoint
Common
4
Setpoint
Setpoint
5
24 VAC/ +15 VDC
6
Common
7
Zone Bus
Manual
Override
Button
8
LED
LED
Internal wiring diagram with DIP switches set as shown on the right, LED Mode = OFF and Manual Override push button enabled.
FIG:term_blk_LED_OFF
Not Connected
NO
12
3
9 RH Output 0–10 VDC
Figure 3: Terminal Block Location and Wiring
FIG:term_b lk
Table 1: Terminal Block Wiring
Terminal Signal Designation
1 Temperature Sensor and Manual Override 2 Temperature Sensor Common
1. The +15 VDC power supply is used only when an HE-6800 Series Humidity Transmitter is connected to a VMA Controller.

Setup and Adjustments

3 Setpoint Common and LED Common 4 Setpoint 5
24 VAC (+15 VDC – VMA Only
1
)
6 Common (for Power, RH Output, Zone
Bus, or Manual Override)
7 Zone Bus 8 LED and Manual Override 9 RH Output (0 to 10 VDC)
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions

Controller Configuration DIP Switch and LED Mode

A DIP switch configures the HE-6800 for use with the desired controller by enabling or disabling the manual override PB and the LED. To change the controller mode, use the three position DIP switch located on the PCB. See Figure 4 and consult Table 2 to determine the controller compatibility.
4
For all transmitter models, the factory default
Figure 4: Controller Configuration
DIP Switch Positions
DIP switch in the default position.
KEY:
Switch is in up position (ON)
Switch is in down position (OFF)
Note: Read switch positions from left to right.
LED MODE
OFF
ON
NO PB
NO
12
3
REMOVING THE CIRCUIT
BOARD VOIDS WARRANTY
FIG:dip_switch
LED mode is LED Mode:ON. The DIP switch positions enable/disable the functions listed in Table 3
Risk of Property Damage.
Do not use switch settings other than those shown in Figure 4. Using other switch settings may cause incorrect controller operation or damage to the element, controller, [and/or] controlled equipment.
Risque de dégâts matériels.
Ne pas utiliser un paramétrage des commutateurs différent de celui-ci illustré à la Figure 4. L'utilisation d'autres paramètres de commutateurs risque de provoquer un fonctionnement incorrect du contrôleur ou d'endommager l'élément, le contrôleur [et/ou] l'équipement contrôlé.
Table 2: Controller Compatibility with LED Mode and PB
Types of HE-6800
All Models
LED Mode (Figure 4)
Features Enabled on HE-6800
LED Off
2
LED On Sensor,
No PB Room Sensor
Sensor and Manual Override
Manual Override, and LED
Only
AHU UNT1100 VAV1xx or
No Yes Yes Yes Yes
No No No Yes Yes
Yes Yes Yes Yes Yes
Features Recognized by Controller
VMA12
UNT1xx
Series
1
VMA14 Series
1
1. For these controllers, the LED appears brig hter when pressing the manual override PB.
2. Holding the manual override PB for more than 2 seconds may affect the sensor reading.
Table 3: LED Mode and Functions

Humidity Output and Power Supply Selection Switch

A 0 to 10 VDC or 0 to 5 VDC selector DIP switch enables you to change the output for % RH. The
LED Mode Functions Switch Positions
Enabled Disabled
OFF Sensor, PB LED Switch positions are down, up, and down. The LED remains off at all times. ON LED, Sensor,
PB
--- Switch positions are factory set up, down, and up. The controller determines the LED mode.
NO PB Sensor LED and PB Switch positions are all down. LED is off, and the PB does not function.
default factory setting is OFF (0 to 10 VDC output).
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions
5
The HE-6800 also features a power supply selection
Figure 5: Humidity Output and Power Supply
DIP Switch Positions
DIP switch in the default position.
KEY:
Switch is in up position (ON)
Switch is in down position (OFF)
NO
12
FIG:pwr_bst_ds
Switch 2
OFF = Low supply voltage operation ON = High supply voltage operation
Switch 1
OFF = 0–10 VDC output, corresponding to 0–100%RH ON = 0–5 VDC output, corre spo nding to 0–100%RH
DIP switch. If you are using the transmitter where supply voltage is 24 VAC or higher, set this switch to ON.
3. Check all supply voltage connections. See Figure 1, Figure 2, or Figure 3, if necessary.
4. Check the settings:
Verify that any scaling modifications, setpoint
adjustments, and overrides have been saved and downloaded to the controller.
Check the override status (Temporary
Occupancy mode vs. Unoccupied mode) at the controller.
Check the setpoint settings.
5. Confirm DIP switch positions if:
the LED remains on or is dim
the room sensor reading is outside of the
normal range for the space being sensed
Note: Make sure the DIP switch setting is correct for the controller used with the HE-6800.

Temperature Setpoint

Adjust the setpoint using the setpoint adjustment dial. Rotate clockwise to raise the temperature; rotate counterclockwise to lower the temperature.

Troubleshooting

HE-6800 Series Humidity Transmitters are recommended for use only with Johnson Controls
6. Replace the HE-6800 if the troubleshooting suggestions fail to remedy the problem.

Accessories

Contact the nearest Johnson Controls representative to order any of the parts listed in Table 4.
Note: Review the technical specifications of the accessories prior to their use in an application.
digital controllers. If the HE-6800 is not functioning properly, use the following procedure to identify the problem and determine a solution:
1. Check that the HE-6800 is mounted in a location indicative of the space temperature (for example, away from drafts or sunlight).
2. Verify that the wiring is correct.

Repair Information

Do not field repair the HE-6800 Series Humidity Transmitters. As with any electrica l device, keep the air vents clean and free from dust or obstruction. If an HE-6800 Series Humidity Transmitter fails to operate within its specifications, replace the unit. For a replacement transmitter, contact the nearest Johnson Controls representative.
Table 4: Optional Accessories
Product Code Number Description
ACC-INSL-0 ACC-INSL-1
NS-WALLPLATE-0 Adapts an HE-6800 Series Humidity Transmitter (3-3/16 x 3-3/16 in. [80 x 80 mm]) to a
T-4000-119 Allen-Head Adjustment Tool (30 per Bag)
1
1
Wallbox Mounting Pad (10 per Bag) Surface Mounting Pad (10 per Bag)
Standard 3-3/16 x 4-3/4 in. (80 x 120 mm) Wallbox
1. These foam pads help prevent drafts from entering the unit through the wall, and make installation easier when mounting on an uneven surface.
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions
6

Technical Specifications

HE-6800 Series Humidity Transmitters with Temperature Sensor (Part 1 of 2)

Power Requirements 4.5 to 7.5 mA at 14 to 30 VDC and 5K ohm Load, or 18 to 25 mA at 20 to 30 VAC
and 5K ohm Load
Terminations 9-Position Screw Clamp Terminal Block Wire Size 16 to 24 AWG (1.3 to 0.6 mm Diameter); 18 AWG (1.0 mm Diameter)
Temperature Measurement Range 32 to 131°F (0 to 55°C) Humidity
Measurement Range
Temperature Sensor
Humidity Sensor Type Capacitive Polymer Sensor Humidity
Element Accuracy
Setpoint Range Warmer/Cooler Temperature Sensor Time Constant 10 Minutes at 10 ft per Minute Manual Override Integral Momentary Pushbutton (DIP Switch Selectable) LED Green LED Indicates Three Modes of Operation (VMA12 and VMA14 Series
Ambient Operating Conditions 32 to 131°F (0 to 55°C), 10 to 95% RH Noncondensing;
Ambient Storage Conditions -40 to 140°F (-40 to 60°C), 5 to 95% RH Noncondensing;
Materials White Thermopla stic
Dimensions (H x W x D)
Shipping Weight 0.44 lb (0.20 kg)
Full Range 0 to 100% RH Calibrated Range 10 to 90% RH
Nickel (HE-68Nx Models)
Platinum (HE-68Px Models)
Nonlinear NTC, Thermistor, Type II (HE-686x Models)
HE-68x2 Models ±2% RH for 20 to 80% RH at 50 to 95°F (10 to 35°C);
HE-68x3 Models ±3% RH for 20 to 80% RH at 77°F (25°C);
HE-68xx-0 Models 3-3/16 x 3-3/16 x 1-5/16 in. (80 x 80 x 32 mm) HE-68xx-1 Models 3-3/16 x 3-3/16 x 1-7/16 in. (80 x 80 x 35 mm)
Recommended
Sensor Type 1,000 ohm Thin Film Nickel Coefficient Approximately 3 ohm per F° (5.4 ohm per C°) Reference
Resistance Accuracy ±0.3 4F° at 70°F (±0.18C° at 21°C) Sensor Type 1,000 ohm Thin Film Platinum Coefficient Approximately 2 ohm per F° (3.9 ohm per C°) Reference
Resistance Accuracy ±0.3 5F° at 70°F (±0.19C° at 21°C) Sensor Type 10,000 ohm NTC Thermistor Coefficient Nonlinear NTC, Johnson Controls Type II Reference
Resistance Accuracy ±0.9 F° (±0.5C°) at 32 to 15 8°F (0 to 70°C)
±4% RH for 10 to 20% RH and 80 to 90% RH at 50 to 95°F (10 to 35°C)
±6% RH for 10 to 20% RH and 80 to 90% at 77°F (25°C)
Controllers Only)
86°F (30°C) Maximum Dew Point
86°F (30°C) Maximum Dew Point
Protection: IP30 (EN 60529)
1,000 ohm at 70°F (0°C)
1,000 ohm at 32°F (0°C)
10,000 ohm at 77°F (25°C)
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions
7
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
HE-6800 Series Humidity Transmitters with Temperature Sensor (Part 2 of 2)
Compliance United States UL Listed, File E107041,
CCN PAZX, Under UL 916, Energy Management Equipment
Canada UL Listed, File E107041,
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance
Australia and New Zealand
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment
with the essential requirements and other relevant provisions of the EMC Directive, WEEE Directive, and RoHS Directive.
RCM, Australia/NZ Emissions Compliant
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
8
Loading...