Johnson Controls HE-67xx Installation Guide

24-9591-5, Rev. B
Installation Instructions HE-67xx Issue Date March 2016
TRUERH Series
HE-67xx Surface-mount Duct Humidity/Temperature Sensors
nstallation
I
IMPORTANT: The HE-67xx Series Duct
Humidity/Temperature Sensor is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the humidity/temperature sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the humidity/temperature sensor.
IMPORTANT : Le HE-67xx Series Duct
Humidity/Temperature Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du humidity/temperature sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du humidity/temperature sensor.
© 2016 Johnson Controls, Inc. 1 Part No. 24-9591-5, Rev. B www.johnsoncontrols.com Code No. LIT-216521

Parts Included

HE-6700 sensor

Tools Needed

drill with 1/8 in. drill bit
1/4 in. nut driver
ocation Considerations
L
The sensor must be mounted inside a duct or economizer rooftop system.
Orientation: The sensor must be mounted on a flat surface in a vertical, upright position.
Placement: Mount the unit at least eight feet downstream from sources of heat or humidity and away from areas with no air flow.
Temperature Requirements: -20 to 140°F (-29 to 60°C)
IMPORTANT: To avoid damage to the sensor,
do not mount the HE-67xx in a location that is exposed to rain, snow, or direct sunlight, or in a location where high concentrations of corrosive vapors are present.
No. 6
Sheet Metal
Screws (2)
Duct
!
Sensor Terminal
Signal Designation
20 to 30 VAC at 50/60 Hz
Product Code
Description
M
ounting
To mount the HE-67xx:
1. Using the sensor as a template, mark the location of the two screws.
2. Use a drill with a 1/8 in. bit to drill two holes in the duct.
3. Attach the sensor to the duct using a 1/4 in. nut driver and two No. 6 sheet metal screws (not provided) as shown in Figure 1.
Note: Mount the sensor in an upright position.
Figure 1: HE-6700 Mounting
iring
W
IMPORTANT: All wiring connections must be
made in accordance with the National Electrical Code and all local regulations.
To wire the HE-67xx:
1. Route the wires from the controller to the HE-67xx. We recommend you use No. 18 AWG wire.
2. Connect the wires to the appropriate terminals of the wiring block. (See Table 1, and refer to the appropriate controller documentation.)
Table 1: HE-6700 Terminal Designations
T T OUT COM PWR
Temperature Temperature Relative Humidity Output Common Power: 14 to 30 VDC or
WARNING: Risk of Electric Shock.
Disconnect the power supply before making electrical connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
AVERTISSEMENT : Risque de décharge
électrique. Débrancher
l'alimentation avant de réaliser tout branchement électrique. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.
heckout
C
After installation and wiring are complete, apply power and make an operational check as shown in the appropriate controller documentation.
Refer to Table 2 for accessories available, and contact the nearest Johnson Controls representative.
Table 2: Accessories
Number
ACC-BRKT-100
ACC-CBL-100
For specifications on the product, refer to Table 3.
Mounting Bracket for mounting the sensor perpendicular to the duct;
3.25 H x 3.62 W x 0.75 in. D (83 x 92 x 19 mm)
Wiring Harness, 53 in. (1.3 m)
2 TRUERH Series HE-67xx Surface-mount Duct Humidity/Temperature Sensors Installation Instructions
Table 3: Specifications
European Single Point of Contact:
NA/SA Single Point of Contact:
APAC Single Point of Contact:
Building Efficiency
Product Power Requirements Current Draw Output Signal Humidity Transmitter
Temperature Sensor Accuracy at 70°F (21°C)
Ambient Operating Conditions
Survival Operating Conditions
Ambient Storage Conditions
Terminal Connections Acceptable Wire Gauge Dimensions (H x W x L) Shipping Weight
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
TRUERH Series HE-67xx Surface-mount Duct Humidity/Temperature Sensors
14 to 30 VDC or 20 to 30 VAC at 50/60 Hz, Class 2 3 mA with no load; 25 mA maximum 0 to 5 VDC, 1k ohm maximum load Accuracy: HE-67x2: ±2% RH for 20 to 80% RH at 77° F (25°C)
±4% RH for 10 to 20% and 80 to 90% RH at 77°F (25°C) HE-67x3: ±3% RH for 20 to 80% RH at 77° F (25°C)
±5% RH for 10 to 20% and 80 to 90% RH at 77°F (25°C) Temperature Coefficient: -0.1 to 0.05% RH/C at 41°F (5°C)
-0.07 to -0.21% RH/C at 149°F (65°C) HE-67Nx-0N0GS: ±0.34 F° (0.18C°); reference resistance of 1.0k ohms at 70°F (21°C)
HE-67Tx-0N0GS: ±0.9 F° (0.50C°); reference resistance of 2.25k ohms at 77°F (25°C) HE-67Yx-0N0GS: ±0.36 F° (0.20C°); reference resistance of 10.0k ohms at 77°F (25°C) Note: HE-67Tx-0N0GS and HE-67Yx-0N0GS: Resistance change is nonlinear with a negative temperature coefficient.
32 to 140°F (0 to 60°C) 0-100% RH, 85°F (29.4°C) maximum dew point
-20 to 140°F (-29 to 60°C); 0 to 100% RH, 85°F (29.4°C) maximum dew point
-40 to 140°F (-40 to 60°C) 0-100% RH, 85°F (29.4°C) maximum dew point
1/4 in. (6.35 mm) male spade 16 to 24 AWG wire (18 AWG wire recommended)
3.00 x 3.00 x 1.23 in. (76 x 76 x 31 mm)
0.50 lb (0.23 kg)
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
TRUERH Series HE-67xx Surface-mount Duct Humidity/Temperature Sensors Installation Instructions 3
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered tr ademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Loading...