Johnson Controls FX-PCG1621 Series, FX-PCG16 Series, FX-PCG1611 Series, FX-PCG16 Installation Instructions Manual

FX-PCG16 General Purpose Programmable Controller Installation Instructions
FX-PCG1611-x, FX-PCG1621-x
Refer to the QuickLIT website for the most up-to-date version of this document.
Part No. 24-10143-152, Rev. G
Issued April 2016

Application

The FX-PCG16 controller is part of the Facility Explorer Controller FX-PCG family. The FX-PCG16 controller runs pre-engineered and user-programmed applications and provides the inputs and outputs required to monitor and control a wide variety of HVAC equipment.
The FX-PCG controllers operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus as BACnet Application Specific Controllers (B-ASC) and integrate
into Johnson Controls® and third-party BACnet systems.
With Release 10.1, you can use the FX-PCT software to switch the FX-PCG to use the N2 protocol.
The FX-PCG16 controller is available with or without an integral LCD and push button user interface.

Switchable Communications Protocols

By default, the FX-PC family controllers and network
sensors communicate using the standard BACnet
protocol, based on the ANSI/ASHRAE 135-2004.
The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building controls.
The N2-capable FX-PC controllers can be used as functional replacements for legacy N2 controllers. The N2-capable FX-PC controllers:
have the I/O quantities and characteristics of the FX-PC family controllers
must be programmed with FX-PCT, which has programming capabilities that are similar (but not identical) to HVACPro, GX9100, GPL, and other legacy tools
support SA Bus devices
support FX-WRZ wireless sensors from the controller using the FX-WRZ7860 receiver when configured for BACnet MS/TP communication
The N2-capable FX-PC controllers:
do not support Zone Bus (for example, TMZ sensors and M100 actuators)
do not support pass through in the commissioning mode
do not support remote downloading or commissioning using BACnet routing
do not support wireless connection to the N2 bus
FX-PCG, FX-PCX, and FX-PCV controllers are BTL­tested and listed as BACnet Application Specific Controllers (B-ASCs). FX-PCA field controllers are BTL-listed as BACnet Advanced Application Controllers (B-AACs). The NS Series Sensors are BTL-listed as BACnet Smart Sensors (B-SSs).
Release 10.1 of FX-PCT and later can be used to switch the Field Bus communications protocol in FX-PC Controllers to be either the standard BACnet Master-Slave/Token-Passing (MS/TP) or the N2 protocol. BACnet MS/TP is the default communications protocol for all new controllers. Switchable communications protocols provide a cost-effective upgrade and modernization path for customers with existing N2 controllers. The Modernization Guide for Legacy N2 Controllers (LIT-12012045) and the controller-specific documentation provide installation and commissioning support and include tips for efficient and safe replacement. Refer to the N2 Compatibility Options chapter of the Controller Tool Help (LIT-12011147) for information about mapping N2 Objects in controllers with switchable communications protocols.
1FX-PCG16 General Purpose Programmable Controller Installation Instructions

North American Emissions Compliance

Mounting

Observe these guidelines when mounting an FX-PCG:

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.
Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
Mount the controller horizontally on 35 mm DIN rail whenever possible.
Mount the controller in the proper mounting position (Figure 1).
Mount the controller on a hard, even surface whenever possible in wall-mount applications.
Use shims or washers to mount the controller securely and evenly on the mounting surface.
Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions requirements in Table 10.
Provide for sufficient space around the controller for cable and wire connections for easy cover removal and good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
Do not mount the controller on surfaces prone to vibration, such as duct work.
Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can interfere with controller communication.

Installation

Observe these guidelines when installing an FX-PCG:
Transport the controller in the original container to minimize vibration and shock damage.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical shock.

Parts Included

one FX-PCG16 with removable terminal blocks
one installation instructions sheet

Materials and Special Tools Needed

three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
one 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only)
small straight-blade screwdriver for securing wires in the terminal blocks
Observe these additional guidelines when mounting a controller in a panel or enclosure:
Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller.
Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller.
Do not install the controller in an airtight enclosure.
Figure 1: FX-PCG Mounting Positions
2FX-PCG16 General Purpose Programmable Controller Installation Instructions

DIN Rail Mount Applications

Mounting the controller horizontal on 35 mm DIN rail is the preferred mounting method.
To mount an FX-PCG on 35 mm DIN rail:
1. Securely mount a 20 cm (8 in.) or longer section of 35 mm DIN rail horizontal and centered in the desired space so that the controller mounts in the horizontal position shown in Figure 1.
2. Pull the two bottom mounting clips outward from the controller to the extended position (Figure 2).
3. Hang the controller on the DIN rail by the hooks at the top of the (DIN rail) channel on the back of the controller (Figure 2), and position the controller snugly against the DIN rail.
4. Push the bottom mounting clips inward (up) to secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail.

Wall Mount Applications

To mount an FX-PCG directly on a wall or other flat vertical surface:
3. Drill holes in the wall or surface at the locations marked in Figure 2, and insert appropriate wall anchors in all of the mounting holes (if necessary).
4. Hold the controller in place, and insert the screws through the mounting clips and into the holes (or anchors). Carefully tighten all of the screws.
Important: Do not overtighten the mounting screws.
Overtightening the screws may damage the mounting clips.
Figure 2: Back of Controller Showing Extended
Mounting Clips, DIN Rail Channel, and Mounting
Dimensions, mm (in.)
1. Pull the two bottom mounting clips outward and ensure they are locked in the extended position as shown in Figure 2.
2. Mark the three mounting hole locations on the wall using the dimensions in Figure 2 and one of the mount positions shown in Figure 1. Or hold the controller up to the wall or surface in a proper mount position and mark the hole locations through the mounting clips.
3FX-PCG16 General Purpose Programmable Controller Installation Instructions
Figure 3: FX-PCG16 Physical Features
Table 1: FX-PCG Physical Features Callouts and Descriptions
Physical Feature: Description and ReferencesCallout
1
2
4
5
6
7
8
9
Binary Output (BO) Source Power Selection Jumpers (See Binary Output (BO) Source Power Selection Jumpers)
Device Address DIP Switch Block (See Figure 9)
Mounting Clip3
Configurable Output (CO) Terminal Blocks (See Table 3)
24 VAC, Class 2 Supply Power Terminal Block (See Supply Power Terminal Block)
Cover Lift Tab (One of Two) (See Figure 3)
Display Navigation Buttons (See Setting Up an Integral or Local Display)
Note: Not available on all FX-PCG models.
LCD Display Area (See Setting Up an Integral or Local Display)
Note: Not available on all FX-PCG models.
FC Bus Terminal Block (See FC Bus Terminal Block)
4FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 1: FX-PCG Physical Features Callouts and Descriptions
Physical Feature: Description and ReferencesCallout
10
11
12
13
14
15
16
Sensor Actuator (SA) Bus Terminal Block (See SA Bus Terminal Block)
Sensor Port (Sensor Actuator [SA] Bus, RJ-12 6-pin Modular Jack) (See Figure 6)
Binary Inputs (BIs) Terminal Block (See Table 3)
Universal Inputs (UIs) Terminal Blocks (See Table 3)
LED Status Indicators (See Table 8)
Field Controller (FC) Bus Port (RJ-12 6-pin Modular Jack) (See Figure 6)
Binary Output (BO) Terminal Block (See Table 3)
Terminal Wiring Guidelines, Functions, Ratings, and
Important: Electrostatic discharge can damage
Requirements

Wiring

Observe the following guidelines when wiring a controller:
Risk of Electric Shock: Disconnect the power supply before making electrical connections to avoid electric shock.
Mise En Garde: Risque de décharge électrique:
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
For detailed information on configuring and wiring an MS/TP Bus, FC bus, and SA bus, refer to the FX-PC
Series Controllers MS/TP Communications Bus Technical Bulletin (LIT-12011670) or to the MS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908).
For detailed information on wiring an N2 bus, refer to the N2 Communications Bus Technical Bulletin (LIT-636018).

FX-PCG Terminal Blocks and Bus Ports

See Figure 3 for terminal block and bus port locations on the FX-PCG controller. Observe the following guidelines when wiring a controller.
controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
Risk of Property Damage: Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
Mise En Garde: Risque de dégâts matériels: Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
Important: Do not exceed the controller electrical
ratings. Exceeding controller electrical ratings can result in permanent damage to the controller and void any warranty.
Important: Use copper conductors only. Make all wiring
in accordance with local, national, and regional regulations.
Input and Output Terminal Blocks
All of the fixed input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are mounted on the top of the controller. See Table 3 for more information about I/O terminal functions, requirements, and ratings.
FC Bus Terminal Block
The FC Bus terminal block is a blue, removable, 4-terminal plug that fits into a board-mounted jack.
Wire the removable FC bus terminal block plugs on the controller, and other controllers in a daisy-chain configuration using 3-wire twisted, shielded cable as shown in Figure 4. See Table 5 for more information.
5FX-PCG16 General Purpose Programmable Controller Installation Instructions
Figure 4: FC Bus Terminal Block Wiring
Note: The FC bus Shield (SHLD) terminal is isolated
and can be used to connect (daisy chain) the shields for FC bus wiring.
SA Bus Terminal Block
The SA Bus terminal block is a brown, removable, 4-terminal plug that fits into a board-mounted jack.
Note: The SA PWR terminal supplies 15 VDC. The SA
PWR terminal can be used to connect (daisy chain) the 15 VDC power leads on the SA bus.
FC Bus Port
The FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for
the FX-BTCVT Bluetooth® Commissioning Converter, ZFR-USBHA-0 ZigBee® wireless dongle, or FX-ZFR1811
Wireless Field Bus Router.
The FC bus port is connected internally to the FC bus terminal block. See Table 5 for more information. The FC bus Port pin assignment is shown in Figure 6. Note: When an FX-PCG is configured for N2 network
communication, the FC bus port is not used.
Figure 6: Pin Number Assignments for Sensor, SA
Bus, and FC Bus Ports on Controllers
Wire the removable SA Bus terminal block plugs on the controller and other SA Bus devices in a daisy-chain configuration using 4-wire twisted, shielded cable as shown in Figure 5. See Table 5 for more information.
Figure 5: SA Bus Terminal Block Wiring
Sensor Port
The Sensor (SA Bus) port on the bottom of the controller (Figure 3) is an RJ-12, 6-position modular jack that provides a connection for the Bluetooth Commissioning Converter, the VAV box Balancing Tool, specified network sensors, or other SA Bus devices with RJ-12 plugs.
When the FX-PCG is configured for N2 communication, the SA Bus port must be used to download and commission the controller.
An FX-DIS1710 Local Controller Display also can be connected to the SA Bus port (but only on FX-PCG models without integral display and push buttons).
The Sensor port is connected internally to the SA bus terminal block. See Table 5 for more information. The Sensor Port pin assignment is shown in Figure 6.
6FX-PCG16 General Purpose Programmable Controller Installation Instructions
Supply Power Terminal Block
The 24 VAC supply power terminal block is a gray, removable, 3-terminal plug that fits into a board-mounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7. The middle terminal on the supply power terminal block is not used. See Table 5 for more information about the Supply Terminal Block.
Figure 7: 24 VAC Supply Power Terminal Block Wiring
Note: The supply power wire colors may be different on
transformers from other manufacturers. Refer to the transformer manufacturer’s instructions and the project installation drawings for wiring details.
Important: Connect 24 VAC supply power to the
controller and all other network devices so that transformer phasing is uniform across the network devices. Powering network devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop problems. The controller does not require an earth ground connection.

Wireless Network Applications

When configured for BACnet MS/TP communication, the controller can also be installed in a wireless application using an FX-ZFR1811 Series Wireless Field Bus Router.
To configure a controller for use with the FX-ZFR1811 Series Wireless Field Bus system:
1. Wire the input/output terminals and SA bus.
Note: In wireless network applications, do not
connect any wires to the FC Bus terminal block. (Connect the SA/FC terminal block on an FX-PCX to an SA bus only.)
2. Connect the FX-ZFR1811 Wireless Field Bus Router to the FC bus port (RJ-12 modular jack) on the front of the controller.
3. Ensure that the controller's device address DIP switches are set to the correct device address. See
Setting the Device Addresses.
4. Set DIP switch 128 to ON, which enables wireless operation on the controller.
For more information on installing a controller in a wireless configuration, refer to the FX-ZFR1811
Wireless Field Bus Router Installation Instructions (Part No. 24-10325-29).
7FX-PCG16 General Purpose Programmable Controller Installation Instructions

Termination Diagrams

A set of termination diagrams provides details for wiring inputs and outputs to the controllers. See the figures in this section for the applicable termination diagrams.
Table 2: Termination Details
Type of Field Device
Input/Output
UITemperature Sensor
UIVoltage Input - External
Source
UIVoltage Input - Internal
Source
Termination DiagramsType of
(Self-Powered)
Source (Isolated)
Source (2 wire)
UIVoltage Input
UICurrent Input - External
UICurrent Input - Internal
8FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 2: Termination Details
Type of Field Device
Input/Output
UICurrent Input - Internal
Source (3 wire)
UICurrent Input - External
Source (in Loop)
UIFeedback from EPP-1000
Termination DiagramsType of
Actuator (External Source)
Actuator (Internal Source)
UI or BIDry Contact (Binary Input)
CO0–20 VDC Output to
CO0–10 VDC Output to
9FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 2: Termination Details
Type of Field Device
Input/Output
CO24 VAC Triac Output
(Switch Low, External Source)
COIncremental Control to
Actuator (Switch Low, Externally Sourced)
CO
Termination DiagramsType of
Actuator (Switch High, Externally Sourced)
(Switch Low, Externally Sourced)
(Switch High, Externally Sourced)
COIncremental Control to
BO24 VAC Binary Output
BO24 VAC Binary Output
10FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 2: Termination Details
Type of Field Device
Input/Output
BOIncremental Control to
Actuator (Switch Low, Externally Sourced)
BO
Termination DiagramsType of
Jack (Fixed Address = 199)
SA BusNetwork Stat with Phone
11FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 2: Termination Details
Type of Field Device
Input/Output
SA BusNetwork Stat with
Terminals Addressable
SA BusNetwork Stat with
Terminals (Fixed Address = 199)
Termination DiagramsType of
12FX-PCG16 General Purpose Programmable Controller Installation Instructions

Input and Output Wiring Guidelines

Table 3 provides information and guidelines about the
functions, ratings, and requirements for the controller input and output terminals; and references guidelines for determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in Table 3, observe these guidelines when wiring controller inputs and
Shielded cable is not required for input or output cables.
Shielded cable is recommended for input and output cables that are exposed to high electromagnetic or radio frequency noise.
Inputs/outputs with cables less than 30 m (100 ft) typically do not require an offset in the software setup. Cable runs over 30 m (100 ft) may require an offset in the input/output software setup.
outputs:
Run all low-voltage wiring and cables separate from high-voltage wiring.
All input and output cables, regardless of wire size or number of wires, should consist of stranded, insulated, and twisted copper wires.
Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block Label
(Inputs)
Label
+15 VUNIVERSAL
INn
ICOMn
Function, Ratings, RequirementsTerminal
15 VDC Power Source for active (3-wire) input devices
connected to the Universal INn terminals.
Provides 100 mA total current
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage
Internal 75k ohm Pull-down
Analog Input - Current Mode (4–20 mA)
Internal 100 ohm load impedance
Note: Current loop jumpers are fail-safe to maintain a closed 4 to 20 mA current loop, even when the power to the controller is interrupted or off. See Universal Input
Current Loop Jumpers.
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V. 15k ohm pull up
Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[Johnson Controls® sensor], 1k Platinum, and A99B Silicon
Temperature Sensor) Negative Temperature Coefficient (NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k Type II)
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V. 15k ohm pull up
Universal Input Common for all Universal Input terminals
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
Determine Wire Size and Maximum Cable Length
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power from the +15V terminal.
See Guideline A in Table 4.
See Guideline B in Table 4.
See Guideline A in Table 4.
See Guideline A in Table 4.
Same as (Universal) INn
13FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block Label
BINARY
(Inputs)
BINARY
(Output)
Power Selection Jumper positioned to External (EXT) power.
BINARY
(Output)
Power Selection Jumper positioned to Internal (INT) power.
Label
INn
ICOMn
OUTn
OCOMn
OUTn
OCOMn
Function, Ratings, RequirementsTerminal
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width
Internal 18 V. 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V. 3k ohm pull up
Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common, which
is isolated from all other commons, except the Configurable Output (CO) common (OCOMn) when the CO is defined as an Analog Output.
Binary Output - 24 VAC Triac (External Power Source)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Binary Output Common (for OUTn terminal)
Note: Each Binary Output Common terminal (OCOMn) is
isolated from all other commons, including other Binary Output Common terminals.
Binary Output - 24 VAC Triac (Internal Power Source)
Model FX-PCG1611-0: Sources internal 24 VAC power
(24~ COM).
Model FX-PCG1611-1: Sources internal 24 VAC power (24~ HOT).
Binary Output - 24 VAC Triac (Internal Power Source)
Model FX-PCG1611-0: Connects OCOMn to 24~ HOT
when activated.
Model FX-PCG1611-1: Connects OCOMn to 24~ COM when activated.
Internal Power Source:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Determine Wire Size and Maximum Cable Length
See Guideline A in Table 4.
See Guideline C in Table 4.
See Guideline C in Table 4.
14FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block Label
CONFIGURABLE
(Outputs)
Label
OUTn
OCOMn
Function, Ratings, RequirementsTerminal
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
Binary Output - 24 VAC Triac (External Power Source only)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Analog Output Signal Common All Configurable Outputs (COs) defined as Analog Outputs (AOs) share a common, which is isolated from all other commons except the Binary Input common.
Binary Output Signal Common All Configurable Outputs (COs) defined as Binary Outputs are isolated from all other commons, including other CO commons.
Determine Wire Size and Maximum Cable Length
See Guideline A in Table 4.
See Guideline C in Table 4.
Same as (Configurable) OUTn.

Cable and Wire Length Guidelines

Table 4 defines cable length guidelines for the various
wire sizes that may be used for wiring low-voltage (<30V) input and outputs.
Table 4: Cable Length Guidelines for Recommended Wire Sizes for Low-Voltage (<30V) Inputs and Outputs
Wire Size/Gauge and TypeGuideline
Length and Type
A
B
C
1.5 mm2(18 AWG) stranded copper
1.5 mm2(18 AWG) stranded copper
See Figure 8 to select wire size/gauge. Use stranded copper wire
457 m (1,500 ft) twisted wire
297 m (975 ft) twisted wire0.8 mm (20 AWG) stranded copper
183 m (600 ft) twisted wire0.6 mm (22 AWG) stranded copper
107 m (350 ft) twisted wireN/A (24 AWG) stranded copper
229 m (750 ft) twisted wire
137 m (450 ft) twisted wire0.8 mm (20 AWG) stranded copper
91 m (300 ft) twisted wire0.6 mm (22 AWG) stranded copper
61 m (200 ft) twisted wireN/A (24 AWG) stranded copper
See Figure 8 to determine cable length. Use twisted wire cable.
AssumptionsMaximum Cable
100 mV maximum voltage drop
Depending on cable and the connected input or output device, you may have to define an offset in the setup software for the input or output point.
100 mV maximum voltage drop
Depending on cable and the connected input or output device, you may have to define an offset in the setup software for the input or output point.
N/A
15FX-PCG16 General Purpose Programmable Controller Installation Instructions

Maximum Cable Length versus Load Current

Figure 8: Maximum Wire Length for Low-Voltage (<30V) Inputs and Outputs by Current and Wire Size
Use Figure 8 to estimate the maximum cable length relative to the wire size and the load current (in mA) when wiring inputs and outputs.
Note: Figure 8 applies to low-voltage (<30V) inputs and
outputs only.

SA/FC Bus and Supply Power Wiring Guidelines

Table 5 provides information about the functions, ratings,
and requirements for the communication bus and supply power terminals; and guidelines for wire sizes, cable types, and cable lengths when wiring the controller's communication buses and supply power.
In addition to the guidelines in Table 5, observe these guidelines when wiring an SA or FC bus and the 24 VAC supply power:
Run all low-voltage wiring and cables separate from high-voltage wiring.
All SA and FC bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire.
Shielded cable is strongly recommended for all SA and FC bus cables.
Refer to the FX-PC Series Controllers MS/TP
Communications Bus Technical Bulletin (LIT-12011670) or to the MS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908) for detailed information about wire
size and cable length requirements for the SA and FC buses.
16FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block/Port
Labels
Recommended Cable TypeFunction, Electrical Ratings/RequirementsTerminal
Label
FC BUS
FC BUS
(Port)
SA BUS
Sensor
1
FC Bus Communications+
-
Signal Reference (Common) for Bus communicationsCOM
Isolated terminal (optional shield drain connection)SHLD
or
1
RJ-12 6-Position Modular Connector provides:
FC Bus Communications
FC Bus Signal Reference and 15 VDC Common
15 VDC, 180 mA, Power for Bluetooth Commissioning Converter or ZFR1811 Wireless Router
1
SA Bus Communications+
-
SA Bus Signal Reference and 15 VDC CommonCOM
SA PWR
15 VDC Supply Power for Devices on the SA Bus
(Maximum total current draw for SA Bus is 240 mA.)
1
Sensor
RJ-12 6-Position Modular Connector provides:
SA Bus Communications
SA Bus Signal Reference and 15 VDC Common
15 VDC Power for devices on the SA bus and Wireless Commissioning Converter
HOT24~
24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24 VAC)
COM
24 VAC Power Supply Common (Isolated from all other
Common terminals on controller)
35 VA
0.6 mm (22 AWG) stranded, 3-wire twisted, shielded cable recommended
Bluetooth Commissioning Converter retractable cable or 24 AWG 3-pair CAT 3 Cable <30.5 m (100 ft)
0.6 mm (22 AWG) stranded, 4-wire (2 twisted-pairs), shielded cable recommended.
Note: The + and - wire are one twisted pair, and the COM and SA PWR are the second twisted pair of wires.
24 AWG 3-pair CAT3 cable <30.5 m (100 ft)
0.8 mm to 1.5 mm
2
(18 AWG) 2-wire
1 The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the FX-PC Series Controllers MS/TP Communications Bus Technical Bulletin (LIT-12011670) or to the MS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908). For more information about N2 bus communications, refer to the N2 Communications Bus Technical Bulletin (LIT-636018).
17FX-PCG16 General Purpose Programmable Controller Installation Instructions

Setup and Adjustments

Setting the Device Addresses

FX-PCG controllers are master devices on MS/TP (SA or FC) buses. Before operating FX-PCG controllers on a bus, you must set a valid and unique device address for each controller on the bus. You set a controller's device address by setting the positions of the switches on the DIP switch block at the top of the controller (Figure
3). Consult the appropriate Communication Technical
Bulletin to find valid addresses for these controllers.
Figure 9: Device Address DIP Switch Block Set to
Address 21
Note: FX-PCG ship with switch 128 ON and the
remaining address switches off rendering the controllers wired slave devices, which do not operate on MS/TP buses, but will not interfere with bus operation. Set a valid and unique device address on the controller before applying power to the controller on the bus.
1. Set all of the switches on the address DIP switch block (128 through 1) to off.
2. Set one or more of the seven address switches (64 though 1) to ON, so that the sum of the switch numbers set to ON equals the intended device address. See Table 6 for valid device addresses.
Set the highest number switch that is less than or equal to the intended device address to ON. Then continue setting lower numbered switches until the total equals the intended address. For example, if the intended device address is 21, set switch 16 to ON first, then set switch 4 ON, followed by switch 1 (16+4+1= 21). See Figure 9.
3. Set switch 128 to ON only for controllers on an FX-ZFR Series Wireless Field Bus application. For all hard-wired SA and FC bus applications, ensure that switch 128 is set to Off.
Note: Do not connect a controller with switch 128
set to ON to an active (hard-wired) SA or FC bus. When a controller with switch 128 set to ON and a device address from 4 to 127 is connected to a wired field bus, the entire field bus is rendered inoperable until the controller is disconnected or switch 128 is set to Off.
Refer to the FX-ZFR Series Wireless Field Bus System Technical Bulletin (LIT-12011660) for more information on device addresses in wireless applications.
4. Set a unique and sequential device address for each of the controllers connected on the SA or FC bus starting with device address 4.
To ensure the best bus performance, set sequential device addresses with no gaps in the device address range (4, 5, 6, 7, 8, 9, and so on). The controllers do not need to be physically connected on the bus in their numerical device address order.
5. Write each FX-PCG's device address on the white label below the DIP switch block on the controller's cover.
Table 6 describes the FC bus and SA bus devices
addresses for Johnson Controls® MS/TP
communications bus applications.
Refer to the FX-PC Series Controllers MS/TP
Communications Bus Technical Bulletin (LIT-12011670) or MS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908) for
more information on controller device addresses and how to set them on MS/TP buses.
Refer to the Modernization Guide for Legacy N2 Controllers (LIT-12012005) for more information on controller device addresses and how to set them on N2 buses.
Table 6: SA/FC Bus Device Address Descriptions for MS/TP Controllers
Use on DescriptionDevice
Address
0
(Switch 128 Off)
1 to 3
(Switch 128 Off)
Reserved for FC Bus Supervisory Controller (not for use on FX-PC controllers).
Reserved for peripheral devices (not for use on FX-PC controllers).
18FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 6: SA/FC Bus Device Address Descriptions for MS/TP Controllers
Use on DescriptionDevice
Address
4 to 127
(Switch 128 Off)
0 to 3
(Switch 128 ON)
4 to 127
(Switch 128 ON)
Used for MS/TP master devices (FX-PC controllers) that are hardwired to an SA Bus or FC Bus.
Reserved addresses for wired slave devices (not for use on FX-PC controllers).
Note: FX-PCG controllers ship with switch 128 ON and the remaining address switches off rendering the controllers wired slave devices, which do not operate on MS/TP buses.
Valid for MS/TP Master controllers on wireless
FC Buses only.
Note: Do not connect a controller with switch
128 ON to an active (hard-wired) SA or FC bus. When a controller with switch 128 ON and a device address from 4 to 127 is connected to a wired field bus, the entire field bus is rendered inoperable until the controller is disconnected or switch 128 is set to Off.
19FX-PCG16 General Purpose Programmable Controller Installation Instructions

Removing the Controller Cover

Important: Electrostatic discharge can damage
controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
Important: Disconnect all power sources to the
controller before removing the cover and changing the position of any jumper or the EOL switch on the controller. Failure to disconnect power before changing a jumper or EOL switch position can result in damage to the controller and void any warranties.
The controller cover is held in place by four plastic latches that extend from the base and snap into slots on the inside of the housing cover.
To remove the controller cover:
1. Place your fingernails under the two cover lift tabs (Figure 3) on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches.
2. Pivot the top of the cover further to release it from the lower two latches.
3. Replace the cover by placing it squarely over the base, and then gently and evenly push the cover on to the latches until they snap into the latched position.
Figure 10: FX-PCG with Cover Removed Showing
EOL Switch and Jumper Positions
Figure 11: End-of-Line Switch Positions
To set the EOL switch on a controller:
1. Determine the physical location of the controller on the FC bus.
2. Determine if the controller must be set as a terminating device on the bus.
Note: Refer to the FX-PC Series Controllers MS/TP
Communications Bus Technical Bulletin (LIT-12011670) or to the MS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908) for detailed
information about EOL termination rules and EOL switch settings on FC buses.
Refer to the N2 Communications Bus Technical Bulletin (LIT-636018) for detailed information about EOL termination rules and EOL switch settings on N2 buses.
3. If the controller is a terminating device on the bus, set the EOL switch to ON. If the controller is not a terminating device on the bus, set the EOL switch to Off.

Setting the End-of-Line (EOL) Switch

Each controller has an EOL switch, which, when set to ON, sets the controller as a terminating device on the bus. See Figure 10 for the EOL switch location. The default EOL switch position is Off.
When an FX-PC controller is connected to power with its EOL switch set to ON, the amber EOL LED on the controller cover is lit.
20FX-PCG16 General Purpose Programmable Controller Installation Instructions

Setting the Input and Output Jumpers

Binary Output (BO) Source Power Selection Jumpers

Universal Input Current Loop Jumpers

The Universal Input (UI) current loop fail-safe jumpers are on the circuit board under the controller cover near the UI terminals (Figure 10). When a UI is defined (in the system software) as a 4-20 mA Analog Input and the UI’s current loop jumper is in the Disabled (default) position (Figure 13), the 4-20 mA current loop circuit opens whenever power to the controller is interrupted or off.
Risk of Electric Shock: Disconnect supply power to the controller before attempting to adjust the Binary Output Source Power Selection Jumpers. Failure to disconnect the supply power may result in electric shock.
Mise En Garde: Risque de décharge électrique:
Débrancher l'alimentation de l'controller avant tout réglage du Binary Output Source Power Selection Jumpers. Le non-respect de cette précaution risque de provoquer une décharge électrique.
Important: Do not connect an external power source
to a BO when the BO power source jumper is in the internal power (INT) position. Connecting external power to a BO that sources internal power can damage the controller and void any warranties.
The BO source power selection jumpers determine whether a BO provides internal power (sourced from the controller) to the output load (INT position) or requires an external power source (EXT position) for the output load. Figure 12 shows an example of a controller BOs and the associated power selection jumpers to the right of the BOs terminal block.
Figure 12: Example Binary Outputs and the
Associated Source Power Jumper Positions
Figure 13: Current Loop Jumper Positions
Setting the current loop jumper to the Enabled position (Figure 13) connects an internal 100 ohm resistor across the UI terminals, which maintains the 4-20 mA current loop circuit even when power to the controller is interrupted or off.
Important: Current Loop jumpers must be in the
Disabled (default) position for all UIs that are not set up to operate as 4-20 mA analog inputs.
Table 7 identifies the current loop jumpers associated
with each UI on the FX-PCG16 controller.
Table 7: FX-PCG16 UI Inputs and Jumper Labels
Jumper Label on Circuit BoardUniversal Input
Label
J74IN1
J73IN2

Setting Up an Integral or Local Display

FX-PCG1621 models have an integral LCD and push button user interface that allows you to set up and monitor the FX-PCG, the FX-PCG I/O points, and the modules and I/O points connected on the SA bus. FX-PCG1611 models do not have an integral display, but can be connected to an FX-DIS1710 Local Controller Display. For detailed information on setting up and operating either an integral user interface or a remotely connected FX-DIS1710 display, refer to the FX-DIS1710 Local Controller Display Technical Bulletin (LIT-12011666).
21FX-PCG16 General Purpose Programmable Controller Installation Instructions

Commissioning Controllers

You commission FX-PCG controllers with the FX-PCT
software, either via a Bluetooth®Wireless Commissioning Converter, a ZigBee® wireless dongle, or in BACnet
Router mode when connected to a Facility Explorer Supervisory Controller. Refer to the Controller Tool Help (LIT-12011147) for detailed information on commissioning controllers.
Table 8: Status LEDs and Descriptions of LED States
LED ColorLED Label
State
On SteadyGreenPOWER
Off SteadyRedFAULT
Blink - 2 HzGreenSA BUS
Blink - 2 HzGreenFC BUS
AmberEOL
Off (Except on terminating devices)
Description of LED StatesNormal LED
Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse is open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download required, if controller is in Boot mode, or a firmware mismatch exists between the FX-PCG and the FX-ZFR1811 Wireless Field Bus Router.
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (auto baud in progress)
On Steady = Communication lost, waiting to join communication ring
On Steady = EOL switch in ON position
Off Steady = EOL switch in Off position

Troubleshooting Controllers

Observe the Status LEDs on the front of the controller and see Table 8 to troubleshoot the controller. To troubleshoot an integral or local controller display, refer to the FX-DIS1710 Local Controller Display Technical Bulletin (LIT-12011666).

Repair Information

If a controller fails to operate within its specifications, replace the controller. For a replacement controller,
contact your Johnson Controls® representative.
22FX-PCG16 General Purpose Programmable Controller Installation Instructions

Accessories

Table 9: Accessories Ordering Information
DescriptionProduct Code Number
Bluetooth Commissioning Converter, with Bluetooth® TechnologyFX-BTCVT-1
Local Controller Display (for use with FX-PCG1611 model only)FX-DIS1710-0
Wireless Field Bus RouterFX-ZFR1811-0
Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall PlugTP-2420
Y65T31-0
ZFR-USBHA-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in. Primary Leads and Secondary Screw Terminals, Class 2
Note: Additional Y6x-x Series transformers are also available. Refer to the Series Y63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755) for more
information.
Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosureAS-XFR050-0
Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk PackAP-TBK4SA-0
Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk PackAP-TBK4FC-0
Replacement Power Terminal Blocks, 3-Position, Gray, Bulk PackAP-TBK3PW-0
USB Dongle with ZigBee® Driver provides a wireless connection through FX-PCT
to allow wireless commissioning of the wirelessly enabled FX-PCG, FX-PCA, FX-PCX, and FX-PCV field controllers. Also allows use of the FX-ZFR Checkout Tool (FX-ZCT) in FX-PCT. Note: The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle. For additional information on the ZFR-USBHA-0 ZigBee dongle, refer to the FX-ZFR
Series Wireless Field Bus System Technical Bulletin (LIT-12011660) or FX-ZFR Series Wireless Field Bus System Quick Reference Guide (LIT-12011696).
See Table 9 for controller accessories ordering information.

Technical Specifications

Table 10: FX-PCG Technical Specifications
Product Code Numbers
Supply Voltage
Power Consumption
Ambient Conditions
Controller Addressing for BACnet MS/TP
FX-PCG16x1-x General Purpose Programmable Controller
Controller
FX-PCG1621-0-x Controller with Display and Push-button User Interface
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
14 VA maximum for FX-PCG1611 only
20 VA maximum for FX-PCG1621 (with integral display) only
Note: VA rating does not include any power supplied to the peripheral devices connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can consume up to 12 VA for each BO or CO; for a possible total consumption of an additional 84 VA (maximum).
Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage: -40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and 128–255 are reserved and not valid controller addresses.)
DIP switch set; valid control device addresses 1-255Controller Addressing for N2
23FX-PCG16 General Purpose Programmable Controller Installation Instructions
Table 10: FX-PCG Technical Specifications
Communications Bus
Input and Output Capabilities
Analog Input/Analog Output Resolution and Accuracy
Terminations
Mounting
Housing
Dimensions(Height x Width x Depth)
Compliance
RS-485: selectable BACnet MS/TP or N2
3-wire FC bus between the supervisory controller and other controllers
4-wire SA bus between controller, network sensors and other sensor/actuator devices, includes a lead to source 15 VDC supply power (from controller) to bus devices.
N2 Open Protocol:
N2/FC Bus: 1.5 mm (18 AWG) standard 3-wire, twisted, shielded cable recommended between the supervisory controller and field controllers
H8SX/166xR Renesas® 32-bit microcontrollerProcessor
640 KB flash memory and 128 KB RAMMemory
2 - Universal Inputs: Defined as 0-10 VDC, 4-20 mA, 0-600k ohm, or Binary Dry Contact
2 - Binary Input: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal or external source power)
4 - Configurable Outputs: Defined as 0-10 VDC or 24 VAC/DC Field-Effect Transistor (FET) BO
Input: 16-bit resolution
Output: 16-bit resolution, +/- 200 mV accuracy in 0-10 VDC applications
Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal
Blocks
SA/FC Bus Port: RJ-12 6-Pin Modular Jacks
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface with three integral mounting clips on controller
Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum Rated
Protection Class: IP20 (IEC529)
150 x 164 x 53 mm (5-7/8 x 6-1/2 x 2-1/8 in.) including terminals and mounting clips Note: Mounting space requires an additional 50 mm (2 in.) space on top, bottom and front face of controller for easy cover removal, ventilation and wire terminations.
0.4 kg (0.9 lb)Weight
United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment
Industry Canada Compliant, ICES-003
Europe: Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
BACnet International: BACnet Testing Laboratories (BTL) Protocol Revision 4
Listed BACnet Application Specific Controller (B-ASC)
24FX-PCG16 General Purpose Programmable Controller Installation Instructions
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable
for damages resulting from misapplication or misuse of its products.
APAC Single Point of Contact:NA/SA Single Point of Contact:European Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
507 E. Michigan Street, Milwaukee, WI 53202
Johnson Controls®is a registered trademark of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners.© 2016 Johnson Controls, Inc.
Building Efficiency
www.johnsoncontrols.comPublished in U.S.A.
25FX-PCG16 General Purpose Programmable Controller Installation Instructions
Loading...