Since 1915, Johnson Controls has provided
high-quality dampers that fit customer size and
application requirements. Continuing the legacy, a
fire-and-leakage-rated damper for dynamic life safety
smoke management and fire-resistant systems, that
meets new UL leakage-testing procedures, is now
offered.
•
UL File No. R11172
•
CSFM3230-0554:128
•
1-1/2 Hour Fire Rating
•
Class II leakage resistance
These UL/cUL leakage-rated FS-1300 Combination
Fire/Smoke Dampers are listed under
UL Standard 555, fifth edition, dated May 31, 1995,
and under UL Standard 555S, second edition, dated
November 1993, including all paragraphs effective
May 1995 and California State Fire Marshal listed.
Damper and Actuator Product Guide 268.1
Fire/Smoke Section
Product Bulletin FS-1300
Issue Date 0499
All FS-1300 Combination Fire/Smoke Dampers include
2-position electric or pneumatic actuators that have
been tested and approved as a matched set rated for
350°F temperature degradation
.
Features and Benefits
❑
High-Torque Spring
❑
3-Year Warranty on
Materials and Workmanship
❑
Dual Linkage Standard
❑
Sensor Temperature
Combinations of 165°F and
250°F (74°C and 121°C) or
212°F and 350°F (100°C and
177°C)
❑
16-Gauge Galvanized Steel
Blades
Ensures closure during dynamic airflow and
acts as the latch with additional torque to keep
blades closed
Confidence of company standing behind
product
Ensures complete rotation of all blades
Combinations of heat-sensing devices to meet
job requirements
One blade profile provides the correct product
performance
The FS-1300 Combination Fire/Smoke Damper is
designed to meet design specifications requiring one
damper to provide both a 1-1/2 hour fire rating and a
Class II leakage-rating at 350°F.
The FS-1300 Combination Fire/Smoke Damper is
tested according to UL Standard 555 for dampers
intended for use in HVAC duct systems passing
through fire-resistive partitions, and UL Standard 555S
for dampers that are used in HVAC smoke systems.
When multiple assemblies incorporate individual
sections operated by their own closure mechanism or
actuator, each individual section is to be operated at
the maximum specified airflow for the multiple
assembly, with all other sections closed.
The FS-1300 Combination Fire/Smoke Damper must be
installed in accordance with the Standard
and
SMACNA Fire Damper Guide
duct passes through a required fire barrier. The blades,
when closed, shall be within the plane of the fire barrier
(wall or floor).
The standard FS-1300 Combination Fire/Smoke
Damper includes a 24-inch-long, 18-gauge galvanized
steel sleeve, 165°F primary heat sensor, 250°F fusible
link, actuator, and dual linkage.
212°F primary heat sensor and 350°F fusible link are
optional.
Single-section dampers are approved for the following:
, at the point where a
NFPA-90A
Figure 3: Floor/Ceiling Mounting
FS-1300 Combination Fire/Smoke Leakage-rated
Dampers, up to 32 inches wide x 36 inches high, are
rated for mounting in cement floors or ceilings.
aintenance
M
Johnson Controls FS-1300 Dampers have no
components that require routine scheduled maintenance.
uide Specification
G
Furnish and install Johnson Controls FS-1300
dynamically tested, multi-blade, 1-1/2 hour fire-rated
and Class II leakage-rated dampers, approved under
UL Standard 555 and UL Standard 555S, dated
May 1995 and California State Fire Marshal listed.
Figure 2: Wall Mounting
FS-1300 Combination Fire/Smoke Dampers, up to
32 inches wide x 48 inches high, are rated for
mounting in masonry or metal stud gypsum wallboard
fire-rated walls.
to remove power to an electric or pneumatic actuator
and to close the damper blades for smoke protection.
Fusible Link
either 250°F or 350°F shall be used to close the
damper blades and lock them closed for fire protection.
Frames
galvanized sheet steel, with concealed linkage in both
side channels to provide positive blade motion and
eliminate noise and friction within the airstream.
Compressible spring stainless steel side seals and
bronze bearings shall be provided.
Blades
galvanized steel, and blade width not exceeding
8 inches. Blades shall have 3/8-inch square steel
zinc-plated pins.
heat sensor shall respond at 165°F or 212°F
with high-torque spring releasing at
are to be constructed of formed, 13-gauge
are to be constructed with 16-gauge
Page 3
peration
O
After installation, when power (electric or pneumatic) is
applied to the actuator, the damper blades will be
driven to the open position by the actuator.
When the primary temperature sensor detects heat, it
breaks power to the actuator, closing the damper
blades through the spring-return mechanism of the
actuator. The damper is now in the smoke protection
mode (damper closed via actuator).
If the air temperature reaches the fusible link
temperature (secondary temperature sensor), the link
fuses. The damper linkage disengages from the
actuator, allowing the blades to close by a torsion
spring. The damper is now in fire protection mode
(damper closed via torsion spring) and further
operation is not possible.
onstruction
C
w
o
l
f
r
i
Sleeve
A
Table 1: Damper Construction
ComponentDescription
Frame
Blades
Linkage
Blade Pin
Bearings
Side Seal
Blade Seal
Sleeve
Angles
Notes: The sleeve is designed for use with standard
breakaway connectors.
Mounting angles are provided with the damper. The
side containing factory-installed hardware has an
angle mounted as a guide for remaining angles on
that side.
13-gauge galvanized steel,
mechanically joined
16-gauge galvanized steel
1/8 inch rolled steel, zinc plated,
concealed in both channels of the frame
3/8 inch square steel, zinc plated
Oil-impregnated bronze
Self-compensating stainless steel
Stainless steel with extruded silicone
18-gauge galvanized sheet metal,
24-inches-long standard
16-gauge galvanized steel,
1.5 inch x 1.5 inch
Jackshaft
Linkage
Factory-installed
Angle
Primary
Temp erature
Sensor
Fusible Link
and Spring
Actuator
Figure 4: Damper Components
abeling
L
All damper assemblies include an identification label,
which provides the following information:
All actuators are factory mounted and tested with the
damper prior to shipment.
Electric
FS-1300 Combination Fire/Smoke Dampers are
available with Johnson Controls UL Listed/
CSA Certified electric actuators; 120 VAC actuator is
standard. Other actuator options are available.
Table 2: Electric Actuator
Code NumberDescriptionMaximum
Damper
Area
DMPR-S60024
DMPR-S60024S
DMPR-S60120
DMPR-S60120S
Note:Maximum size and area limitations are determined
by UL testing. Future testing may include additional
actuators, or expand present limits.
For more detailed information on the electric actuator,
refer to the
High Temperature Electric Actuator for
Smoke Dampers Submittal Data
Actuator Product Guide (FAN 268.1
3. Enter width and height of damper.
Note:To find actual damper size, multiply the
nominal size by 0.99479.
4. Enter options required.
Width
7
Figure 6: Mounting Dimensions with
Pneumatic Actuator, inches
FS-1300 Combination Fire/Smoke Dampers include
opposed 16-gauge blades, bronze bearings, side
seals, and dual linkage.
Example
:
TOVLE-200 x 200X is a combination
fire/smoke damper that has 16-gauge blades, opposed
blade operation, dual linkage, bronze bearings,
high-temperature blade seals, and side seals. Its
dimensions are 20 inches wide x 20 inches high, with a
24-inch-long sleeve, 24 VAC electric actuator, 165°F
primary heat sensor, and 250°F fusible link. (Unless
otherwise ordered, the system defaults to a
24-inch-long sleeve.)
Minimum: 15 x 14
Maximum: 32 x 48
Maximum: 32 x 36
*Maximum Flow is the velocity against which the actuator listed in Table 9 will be able to operate the damper to the fully
closed position and provide the rated leakage in the marked direction of airflow.
**Maximum SP is the static pressure against which the actuator listed in Table 9 will be able to operate the damper from
the fully closed position in the marked direction of airflow.
Wall or FloorTOVLP,
WallTOVHP28008DS-3153-2
Floor
Maximum
SP, in. WG**
Actuator, Tested as
Matched Set with
Damper (350°F)
Table 10: FS-1300 Dynamic Rating - Fire Mode
Width x Height, in.MountingOrdering CodeMaximum
Flow, fpm*
Minimum: 15 x 14
Maximum: 32 x 48
Maximum: 32 x 36
Note:Table 10 information is based on a 20 psi minimum supply pressure for pneumatic actuators.
When multiple assemblies incorporate individual
sections operated by their own closure mechanism or
actuator, each individual section is to be operated at
the maximum specified airflow for the multiple
Wall or FloorTOVLE, TOVHE,
WallTOVLP, TOVHP35008Jackshaft Spring
Floor
Table 11: UL Leakage-rated
Classifications
ClassStatic Pressure (SP), inches Water
assembly with all other sections closed.
II
Note: The ratings in Table 11 are valid in either direction of
All technical information is compiled from test data, corrected to standard temperature and pressure conditions,
determined using instrumentation and procedures in accordance with AMCA Standard for Test Methods for
Louvers, Dampers, and Shutters No. 500-89.
For application at conditions beyond these specifications, consult the loc al Johnson Controls office. Johnson Controls, Inc. shall not be liable
for damages resulting from misapplication or misuse of its products .
eturn Policy
R
All Johnson Controls Dampers are built to order, just in time and cannot be returned due to customer ordering
errors. All dampers are backed by a 3-year warranty, which covers defects in materials or workmanship. Refer to
terms and conditions of sale for specifics.
At Johnson Controls, delivering environmentally sound products and services is part of our corporate-wide
commitment to continuous improvement. We do this by reducing raw material consumption, recycling, eliminating
the use of toxins, and conserving and preserving natural resources. We believe that what is good for the
environment and the safety and health of all people is good for Johnson Controls. And we never forget that clean
water, air, and land is everyone’s business.
Controls Groupwww.johnsoncontrols.com
507 E. Michigan Street
P.O. Box 423Damper and Actuator Product Guide
Milwaukee, WI 53201Printed in U.S.A.