Johnson Controls FMS-1655M Installation Instructions Manual

FMS-1655M
Room Pressure Monitor
Installation Instructions
LB-FMS1655M-S01 LB-FMS1655M-T01
LIT-12013119
January 2019
Application
These installation instructions guide the installer through the installation of the FMS-1655M Room Pressure Monitor. Please read these instructions thoroughly before beginning installation.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case users will be required to correct the interference at their own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
NOTICE
Risk of Property Damage. Ensure that the power source conforms to the requirements of the equipment. Failure to use a correct power source may result in permanent damage to the equipment.
NOTICE
Risque de dégâts matériels.
S’assurer que la source d’alimentation électrique est conforme aux spécications de l’équipement. L’utilisation d’une source
d’alimentation électrique inappropriée risque d’endommager irrémédiablement l’équipement.
IMPORTANT: The FMS-1655M Room Pressure Monitor must be wired to 24 VAC only. Wiring the unit to 110 VAC will cause
serious damange and void the warranty.
Use of the software that is in (or constitutes) this product or access to the cloud or hosted services applicable to this product, if any, is subject to applicable terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms. If you do not agree to be bound by such terms, you may return the unused product to your place of purchase.
1
FMS-1655M
FMS-1655M Room Pressure Monitor settings
This form should be completed during the initial conguration for each room pressure monitor. Be sure to congure the unit for either Positive, Negative, or both using the Isolation Mode Conguration setup procedure.
Room Name / Number
Unit Model Number and Serial Number (ESN)
Analog Output
Operating Mode (Direct or PID)
Analog Output Range (zero based or offset)
Analog Output Upper Limit (0-100%)
Analog Output Lower Limit (0-100%)
Analog Output Action (Direct or Reverse)
PID Constants
Proportional Constant (0.5-100%)
Integral Constant (0.0-100%)
Derivative Constant (0.0-100%)
Alarm Limits
Positive Isolation High Alarm Setpoint
Positive Isolation High Warning Setpoint
Positive Isolation Low Warning Setpoint
Positive Isolation Low Alarm Setpoint
Negative Isolation High Alarm Setpoint
Negative Isolation High Warning Setpoint
Negative Isolation Low Warning Setpoint
Negative Isolation Low Alarm Setpoint
Audible Alert
Operating Mode (audible or slient)
Delay Time Base (seconds or minutes)
Delay Setting (0-60)
Alarm Quiet Period Starting Hour (0-23)
Alarm Quiet Period Ending Hour (0-23)
Engineering Units
Inches of Water or Pascals
2
LIT-12013119
FMS-1655M
Table of contents
General ......................................................................................................................................................................................... 4
Specications ......................................................................................................................................................................... 4
Part Number Guide ................................................................................................................................................................ 5
Overview ................................................................................................................................................................................ 8
Mounting/Wiring .......................................................................................................................................................................... 9
Installation .............................................................................................................................................................................. 9
Remote sensor mounting procedure ...................................................................................................................................... 9
Display mounting procedure (surface mount) ...................................................................................................................... 10
Flush thin mount mounting procedure .................................................................................................................................. 11
Installation detail view .......................................................................................................................................................... 12
Basic programming ................................................................................................................................................................... 14
Main display screen.............................................................................................................................................................. 14
Conguring Room Pressure Monitor .................................................................................................................................... 14
Setting up alarm limits .......................................................................................................................................................... 14
Selecting displayed units ...................................................................................................................................................... 15
Conguring display options .................................................................................................................................................. 15
Adding password security .................................................................................................................................................... 16
Cleaning the display.................................................................................................................................................................. 17
Alarm setpoints ......................................................................................................................................................................... 18
Setup menu tree ........................................................................................................................................................................ 19
3
LIT-12013119
FMS-1655M

General

Specications
Electrical
Pressure Range ……………………………………………………………………………………………………………………… ±0.2500 “WC
Accuracy of Measurement ….....………………………………………………………………………………………………………… ±0.5% FS
*NIST Traceable / Individual certication available as option
Power Supply .....…… Class 2, 24VAC ±10%, 30VA universal 120/240 to 24 VAC, 60/50 Hz, step-down isolation transformer provided
Recommended Cable Type ....………………………………………………………………………………………...…………… Belden 1325A
Communications
BACnet® MS/TP Network……....……………………………………………………...………………Two-wire twisted pair, RS-485 signaling
Recommend Cable Type……...........…………………………………………………………………………………......…………Belden 3107A
Touchscreen User Interface
LCD Size ……………………………………………………………………………………………………………...……………… 3.2” diagonal
LCD Type ………………………………………...…………………………………………………………………......…………… Transmissive
Resolution …………………………………....………………………………………………………………………..………… 240 x 320 portrait
Viewing Area ….……………………………………………………………………………………………………...…… 50.60 mm x 66.80 mm Color Depth …………………………………………………………………………………………………………..……… 18-bit or 262K colors
Backlight Color …....………………………………………………………………………………………………...………………………… White
Luminous Intensity …………………………………………………………………………………………….…..……………… min 2500 cd/m2
FMS-1655M Monitor Surface Mount Enclosure …..………....……………………….………………………….………… 3”W x 5”H x 1.13”D
FMS-1655M Monitor Thin Mount Enclosure .............................................................................................................. 5”W x 8”H x 0.75”D
External Remote Sensor Housing ………………………….…………….……………………………………..………… 2.3”W x 4”H x 2.7”D Stainless Steel Cover Plate for Flow Tube ……………………………….……………………………………..……… 2.7”W x 4.5”H x 0.2”D Stainless Steel Cover Plate for Remote Sensor ………………………….……………………………………..……… 2.7”W x 4.5”H x 0.2”D
Surface Mount FMS-1655M Monitor with Power Supply ………………..……………………………….……...….....…… approx. wt. 3.7 lb.
Flush Thin Mount FMS-1655M Monitor with Power Supply ………………....…………………………………......……… approx. wt. 5.4 lb.
FMS-1655M Monitor Mounting Options ………………………………......……………………………………………...……… Surface, Flush
Flow Tube Cover Plate Mounting …………………………..........………………………………………………...………….… Surface, Flush
Remote Pressure Sensor Mounting ……………..............……………………………………………………………......…….………… Flush
Environmental
Operating Temperature …………………………...……………………………………....…………………………… 32° to 125° F Operating
Operating Humidity ………....……………………………………………………………......……………… 10% - 95% RH, Non-condensing
4
LIT-12013119
FMS-1655M

Part Number Guide

BRAND
LB = Johnson Controls
UNIT
FMS = Flow Monitor Station (FMS)
SERIES
1655M = BACnet Monitor
STYLE
S = Surface mount T = Thin flush mount
REMOTE SENSOR
01 = Standard remote sensor
- -
5
LIT-12013119
FMS-1655M
System Precautions
Warning
Failure to follow the wiring diagrams could result in damage to your equipment and could void your warranty. Under no circumstances should a single transformer be split between actuator and controller. Doing so will damage the actuator, the
transformer, the controller or all units. A single 120/24V 30Va transformer is required for the controller and a separate 120/24V
20Va transformer is required for the actuator. This equipment contains electrostatic sensitive components. To prevent possible
damage, take precautions to prevent electrostatic discharge when handling or servicing this equipment by wearing an
approved ESD grounding wrist strap connected to an earth ground source.
CORRECT
120/24VAC, 30Va Transformer Supplied by Johnson Controls
Controller
Actuator
FAST ACTING
ELECTRONIC ACTUATOR
CORRECT
120/24VAC, 20Va Third Party Transformer
6
LIT-12013119
FMS-1655M
System Precautions
Red / 24 VAC / 30VA
connected to the FMS
Only Class 2 wiring in this compartment.
Ground
}
Transformer 50/60 Hz
Blue
White
}
1 Amp Slow Blow
Fuse
}
Stepdown Isolation Transformer
Black
(provided with FMS-1655)
240 VAC 50/60 Hz
120 VAC 50/60 Hz
Note:
This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit
protected by a minimum 20A circuit breaker. This circuit breaker should be mounted in an approved electrical enclosure located
separately, but in close proximity to this product.
7
LIT-12013119
FMS-1655M

Overview

The Johnson Controls FMS-1655M Room Pressure Monitor is an ultra-sensitive instrument used to monitor differential pressure in hospital rooms, isolation rooms, surgical suites, laboratories, and clean rooms. This unit is capable of measuring and displaying differential air
pressures as low as 0.0001” WC (0.0249
Pa).
Key features of the FMS-1655M Monitor include:
• Full-color touchscreen display with programmable display options and
adjustable backlight
• Safety Halo™ edge lighting
Intuitive user interface that simplies
setup and conguration of unit
• Graphical display that indicates room status
• Audible and visual alarms
• Multi-level password protection
Zero calibration feature allows in-eld recalibration of zero pressure reading
• 2 factory-calibrated analog outputs, one for PID control and one for remote monitoring room DP
BACnet® BMS network comms port
The FMS-1655M Monitor is equipped
with a 3.2” full-color touchscreen display in portrait orientation (240 pixels by 320
pixels). The password-protected menu
tree is intuitive and simplies the setup and conguration of the unit. The menus
incorporate touch-based interfaces such as sliders, radio buttons, and dialog pop­ups to facilitate the ease-of-use of the FMS-1655M Monitor.
The display has a bright background
color that changes to indicate the three
different room statuses. The background
colors indicate “Normal” when pressure is within dened limits, “Warning” when pressure is nearing an out-of­limits condition, and “Alarm” when
pressure is outside dened acceptable
limits. The pressure ranges for these conditions are easily set by the user for
the specic installation. The background
color changes provide an at-a-glance conditions of the monitored room.
Alarm conditions may be dened by
the user, in terms of desired differential pressure settings for the room being monitored. When an alarm condition occurs, it may be annunciated in three user-denable ways:
1. On the display
2. With an audible alarm
3. Safety Halo™ edge lighting
4. Over the BMS network
The alarm will automatically reset when the unit has sensed that the room differential pressure has returned to proper limits. The user may easily mute the audible alarm by touching the Alarm Audible button at the bottom of the touchscreen display.
The FMS-1655M Monitor provides a single digital input that may be used for monitoring a door switch. The
conguration of the door switch input is congured for normally-closed
operation, and is active-high triggered. A SPDT magnetic door switch type is recommended for use with function.
The user may set up multiple multi-level passwords to prevent unauthorized or casual access to the FMS-1655M
Monitor conguration settings. Up to
ten passwords of up to eight digits may be programmed, with each having one of four associated access levels. Administrators and facility management personnel may have unrestricted access, while general staff may be assigned restricted access passwords which limit the functionality of the user menus.
Room pressure selection of Positive, Negative, or Neutral Isolation may be protected using limited access passwords, thereby eliminating the
need for keylock switches and keys. In
some locales, it is prohibitive to allow an isolation room controller to switch between positive and negative modes of isolation. To accommodate this situation, the FMS-1655M Monitor may
be congured at the factory for either
Positive- and Neutral-isolation modes only or Negative- and Neutral-isolation modes only.
The FMS-1655M Monitor isolation monitor is powered by a supplied universal 120/240 VAC to 24 VAC isolation power supply that is fused at the secondary with a 1-amp slow blow fuse. This powers both the touchscreen display along with the connected differential pressure sensor module.
A 10 ft. length of 4-conductor cable is provided with the FMS-1655M Monitor to interface the two modules. If the distance between the display and remote sensor
modules exceeds 10 ft, then this cable may be substituted with the required length of 4 conductor, dual twisted pair,
shield cable (Belden part no. 1325A).
The FMS-1655M Monitor includes a remotely mounted sensor for measuring the differential pressure of the monitored room or space. This remote sensor must be installed in the wall between the monitored isolation room and the adjoining corridor or anteroom. The front port (P1) must be oriented towards the isolation room and the rear port (P2) towards the corridor or anteroom. Please
see the illustration on pages 8-9 for more
details.
The FMS-1655M Monitor incorporates a PID output signal that may be used to control a damper actuator. The factory­calibrated analog signal is available as a voltage between 0-10VDC or 2-10VDC at the remote sensor connector. Refer to
page 12 and 13 for more information.
8
LIT-12013119
FMS-1655M

Mounting/Wiring

Installation

Remote sensor mounting procedure

1. Cut an opening in the wall of the isolation room to receive the supplied
single-gang “old work” low voltage mounting bracket (Figure 1) for the
remote sensor module. Nominal
dimensions for the cutout are 3.65” H x
2.15” W. Drill a 7/16” hole through the opposite wall for the ow tube.
2. Install the single-gang low voltage
mounting bracket in the cutout. Route a length of supplied ow tube through the mounting bracket and through the 7/16” hole in the opposite wall.
Separate the backplate from the
touchscreen display enclosure by turning the set screw at the bottom of
the display enclosure fully clockwise to release the backplate. Pull the backplate bottom out slightly to
clear the bottom edge of the display
enclosure and slide the backplate down
away from the tabs at the top of the enclosure. Disconnect either end of the
gray harness between the backplate
and display module by pushing down
on the locking tab, and then sliding the
connector out. Disconnect the interface cable from the display module by
removing the terminal block from the 4 pin connector CN3 on the display
module PC board.
5. The FMS-1655M Monitor has a factory-calibrated analog output and is available as voltage at the Vo terminal. The designated output (Vo) can be used to control a damper actuator to maintain a user set pressure setpoint when the FMS-1655M Monitor is used in a controller application.
6. Attach the pluggable connector to the mating header on the remote sensor
module. Attach the end of the ow tube to the barbed tting at back of sensor,
and then secure the remote sensor
module to the mounting bracket with two supplied 6-32 x ¾” screws.
7. Install the louvered cover plate onto
the installed sensor module using two supplied machine screws. On the opposite side of the wall (corridor side),
attach the end of the ow tube to the barbed tting of the ow tube mounting
plate.
8. Press the mounting plate into place, allowing the excess tube length to go into the wall space. Secure the mounting plate with the supplied screws and wall anchors.
9. Install a louvered cover plate onto the mounting plate using two supplied machine screws.
3. Conrm that the 4-conductor
interface cable between the remote sensor module and the touchscreen
display module has its red and black
conductors securely attached to the +V and GND terminals, respectively. Route the end of the interface cable
with the 3 and 4 pin connector down
the wall to the anticipated location of the touchscreen display module.
4. Using a suitable length of 2 conductor 20 AWG cable, connect the output of the universal isolated power supply module to the power input at the remote sensor module. The output of this power supply module is non­polarized, so the two red wire may be wired to power input terminals in either
orientation. Refer to page 12-13 for
power wiring details.
Fig 1. Single-gang, low-voltage mounting
bracket.
9
LIT-12013119
FMS-1655M

Display mounting procedure (surface mount)

1. Cut an opening in the wall adjacent to the door of the isolation room for installing the supplied single-gang “old
work” low voltage mounting bracket
(Figure 1) for the touchscreen display module. Nominal dimensions for the cutout are 3.65” H x 2.15” W.
2. Install the single-gang low voltage
mounting bracket in the cutout.
3. Pull the loose end of the interface
cable from the remote sensor module through the cutout in the drywall, and then through the hole in the center of
the display enclosure backplate (Figure
2).
4. Attach the backplate to the mounting
bracket with two 6-32 x ¾” screws,
carefully aligning it using the two
mounting slots on the backplate before
tightening.
Fig 2. Route interface cable through center
hold at display enclosure backplate.
5. Connect the loose end of the interface cable (4 pin) to the corresponding header at the top of the display module
circuit board (see Figure 3). Conrm all
4 conductors of the interface cable are securely attached at the terminal plugs. Re-connect gray harness between backplate and display module.
6. Reconnect the gray harness to the
backplate circuit board and attach the display enclosure to the backplate
by inserting the tabs at the top of the display into the corresponding
slots at the top of the backplate.
Secure the display enclosure to
the backplate by turning the slotted
setscrew at the bottom of the enclosure
counterclockwise until it is ush with
the enclosure bottom.
7. Finally, apply power to the monitoring system by applying line power to the power supply module. If the unit was shipped with the 24VDC wall adapter power supply, power up the system by plugging it into an available electrical receptacle, preferably located at a location above the ceiling tile directly above the surface mounted display
Fig 3a. Basic FMS Assembly with close up of
wall sensor connections.
Fig 3. Interface connected to 4-pin header at
top of display module.
10
LIT-12013119
FMS-1655M
Thin ush mount mounting
procedure
The FMS-1655M thin ush mount
model offers an attractive stainless steel faceplate with an ultra-thin enclosure
(less than ¾” thick) that may be installed
in any application where wall depth is
either unknown or extremely limited. New construction applications can take
advantage of the included wall box that may be installed during the rough-
in phase. For retrot applications not
requiring electrical conduit termination, the unit may be installed using the
retrot mounting plate that simpliesthe
installation process.
1. The FMS-1655M thin ush mount modeloffers an attractive stainless steel faceplate with an ultra-thin
enclosure (less than ¾” thick) that
may be installed in any application
where wall depth is either unknown or
extremely limited. New construction
applications can take advantage of the
included wall box that may be installed
during the rough-in phase. For retrot
applications not requiring electrical conduit termination, the unit may be
installed using the retrot mounting plate that simplies the installation
process.
2. If this is a new construction project and the wall box has been installed, you
may skip the next two steps. If this is a retrot application and existing drywall
is in place, then proceed with the next step to prepare the opening for the
FMS-1655M thin ush mount model.
3. Using the retrot mounting plate (see Figure 3b) as a template, trace the
inner outline ontothe drywall at the desired mounting location with a pencil
or marker. Also mark the location of the
two mounting holes on the drywall. Cut along the traced outline with a drywall
knife or saw, taking care not to make
the opening too large. Drill out the two holes to clear access to the mounting clip nuts. Remove the cut section of
drywall and discard. Be sure to brush
off any drywall dust or remnants from the inside surface of the opening to
ensure proper adhesion of the retrot
mounting plate.
4. Remove the paper backing from the
two adhesive strips on the retrot
mounting plate and insert it into the
cut opening of the drywall. The retrot
plate should be oriented such that the
corner notch is located at the lower left corner of the opening in the drywall, with the tabs bent towards you. Using
the four tabs on the retrot mounting
plate as alignment guides, press the mounting plate onto the inside surface
of the drywall opening rmly to ensure
maximum adhesion.
Fig 3b. Retrot Mounting Plate
5. The electrical connections must terminated before installing the stainless steel faceplate of the FMS­1655M. Run the 4-conductor, dual twisted pair, interface cable from the FMS1655M remote sensor to the FMS1655M display. Refer to the wiring diagram shown at end of this manual for details.
6. Terminate the interface cable originating from the remote sensor
at the 4-position terminal block CN3 on the back side of the FMS-1655M
display, ensuring proper electrical connections. Power connections should be terminated at +V and GND
of the CN3 terminal block and sensor comms at + & - terminals at CN3.
Insure proper polarity of the comms wiring is maintained between sensor and display.
7. For monitoring the FMS1655M over a BACnet MS/TP network, terminate the BACnet network cable at CN7 of
the FMS1655M display. Refer to wiring diagrams at end of this manual for details.
8. With the electrical connectionsproperly terminated, the stainless steel faceplate may be installed using
the two at head machine screws. For retrot applications where the mounting plate has been afxed to
the inside surface of the drywall, the two mounting screws thread into the clip nuts of the mounting plate. For those applications where the wall box
has been installed, the two mounting screws fasten the faceplate directly.
Fig 3c. Basic FMS1655M thin mount assembly
11
LIT-12013119
FMS-1655M
+ (RS485)
- (RS485)
GNDIN+VsIoVo
- Vin
+Vin

Installation detail view

Gasket
Louvered
Cover Plate
Remote Sensor Installation Detail
Stainless Steel Flow Tube Mounting Plate
To optional door switch
(with standard 24 VAC power supply)
(Side View)
Wall Section (cutaway view)
Optional Analog Output Damper Control
Stainless Steel Mounting Plate
Gasket
Louvered
Cover Plate
Corridor
Thin Silicone Caulking (apply around tube and between stainless steel plate and wall to seal unit penetration)
Flow Tube When Flow Tube mounting plate is located directly opposite the
sensor, ow tubing
must be cut as short as
possible to prevent kinks.
Note: To maintain sensor accuracy, Flow tube should
not exceed 36 inches.
Terminal For connection of transmitter to FMS-1655M Monitor
Orange wall bracket
to be installed
rst by using the
rotating clamps for secure wall attachment.
+ (RS485)
- (RS485)
GNDIN+VsIoVo
- Vin
+Vin
To FMS-1655M Monitor
Isolation Room
To Johnson Controls isolation transformer
12
LIT-12013119
FMS-1655M
Installation detail view
Stainless Steel Flow Tube Mounting Plate
Isolation Room
Gasket
Flow Tube When Flow Tube mounting plate is located directly opposite the
sensor, ow tubing
must be cut as short as
possible to prevent kinks.
Note: To maintain sensor accuracy, Flow tube
should not exceed 36
inches.
Terminal For connection of transmitter to FMS-1655M Monitor.
To FMS-1655M Monitor monitor
Optional Analog Output Damper Control
To optional door switch
+ (RS485)
- (RS485)
GNDIN+VsIoVo
Louvered Cover
Plate
- Vin
+Vin
Thin Silicone Caulking (apply around tube and between stainless steel plate and wall to seal unit penetration)
Corridor
To Johnson Controls isolation transformer
Wall Section (cutaway view)
Remote Sensor Installation Detail
(Bottom View)
13
Rotating clamps secure assembly to wall board
Gasket
Stainless Steel Mounting Plate
LIT-12013119
FMS-1655M

Basic programming

FMS-1655M Monitor basic programming
After the FMS-1655M Monitor unit has been properly installed, apply power to the unit. Upon power up, the Safety Halo™ status indication bezel will cycle through seven colors (red, green, blue, yellow, magenta, cyan, and white), followed by three action icons (normal,
caution, alarm), and nally, the Johnson
Controls splash screen indicating serial
numbers, rmware version numbers, and BACnet MAC address. This splash screen
remains displayed for approximately 10 seconds and disappears to reveal the main display screen. This splash screen can be redisplayed using the About this FMS option in the Diagnostics Menu.

Main display screen

All FMS-1655M Monitor units come shipped from the factory in the neutral isolation mode. The neutral isolation mode will be represented on a blue
background (Figure 4). Information
displayed on the main screen includes the following:
• Name of monitored room (up to 25 characters)
• Current isolation mode (positive, negative, or neutral)
• Current differential pressure reading in selected engineering units (default is “WC)
• Time and date
• Door Status (If door switch is used)
While in neutral isolation mode, the
background color of the main display
screen is blue. However, while in either positive or negative isolation modes, the
background color actively represents the
current status of the monitor. A green
background indicates that the current
differential pressure is within allowable limits of the desired setpoint.
Fig 4. Main display shows isolation mode, room
status and differential pressure.
A yellow background indicates one of two
conditions: 1) door to monitored space is open (if door switch is enabled), or 2) current differential pressure has drifted outside of the allowable limits of the desired setpoint and are in the caution range.
A red background indicates that the
current differential pressure has reached a critical condition and is outside of the allowable limits of the desired setpoint.
The FMS-1655M Monitor incorporates a full-color touchscreen and includes an extensive easy-to-use menu system
that allows the user to quickly setup
the monitor for immediate use. Also integrated into the FMS-1655M Monitor display are several hotspots that provide
quick access to various settings. Refer to page 17 for details on using these
hotspots as display settings shortcuts. Touching the screen anywhere other than
one of the reserved hotspots invokes
the menu system, unless one or more security passwords have been entered.
FMS-1655M Monitor may be congured
to start displaying the real-time differential pressure of the isolation room being monitored.

Setting up alarm limits

To determine the various setpoints at which the unit status changes from normal to warning, and from warning to
alarm, the alarm limits must be congured
accordingly.
Alarm limits are only in effect while the unit is in either positive or negative isolation mode, as the alarms are disabled while neutral isolation mode
is active.
In order to specify the alarm limits for positive or negative isolation mode, set the isolation mode accordingly by selecting the Room Setup option from the Unit Setup menu, and then select the Isolation Mode option from the Set Isolation Mode menu. Select the desired isolation mode from the resulting
conguration popup window and press “OK.”
Conguring Room Pressure
Monitor
Conguring the FMS-1655M Monitor
settings is extremely easy using the intuitive user menus integrated in the touchscreen display. Within minutes, the
14
LIT-12013119
FMS-1655M
0.100
main display, setting the system time and date, adjusting the display brightness, and setting the Safety HaloTM function. The Display Options menu item allows the
main display to be congured as required by the specic application. If desired, the
user may individually enable or disable the display of the isolation mode, room status, and the time/date at the bottom of the screen.
Fig 5. Enter high alarm setpoint for positive
isolation mode using keyboard popup.
To begin specifying the alarm and warning setpoints, select the Alarm Limits option from the System Setup menu. The user is prompted to sequentially enter the high alarm and warning limits, followed by the low warning and alarm limits, in that order. For example, if positive isolation mode was selected above, then the
conguration popup shown in Figure 5 will
be displayed, prompting the user to enter the positive isolation high alarm setpoint
using the keypad.
These limits should be specied to
identify the differential pressure range which is considered normal, as well as the range which indicates a warning condition, and the range which is considered critical and indicates an alarm condition.
The gure on page 14 shows the
relationship of these four alarm setpoints and how they relate to the normal operating differential pressure of the
monitored isolation room.
Conguring alarm buzzer
The FMS-1655M Monitor alarm resources provide support for both visual and audible alerts. The audible alert option on the System Setup menu allows the alarm
buzzer settings to be easily congured. Selecting this option invokes the conguration screen shown in Figure 6.
Fig 6. Alarm buzzer may be congured for
audible or silent mode.
The alarm buzzer may be selected for one of two modes of operation: audible or silent mode. If audible mode is selected,
a delay may be specied in seconds or
minutes. If silent mode is selected, then the alarm buzzer will not sound whenever the unit encounters an alarm condition. If audible mode is selected, the user may specify an alarm quiet period. This feature allows the audible alerts to be suppressed
between the specied hours every day,
thereby eliminating the potential for
nuisance alarms. Hospitals may take
advantage of this feature to minimize nuisance alarms during non-visiting hours in patient rooms.

Selecting displayed units

The FMS-1655M Monitor displays differential pressure readings in one of two units: inches of water column (in WC) or Pascals (Pa). Touching the differential pressure reading in the upper
LCD window of the display will invoke
the Select Engineering Units selection screen. If the engineering units selection is changed, the corresponding alarm setpoints are automatically converted to the newly selected units.
Conguring display options
The Display Setup menu provides
support for conguring all of the display
settings on the FMS-1655M Monitor.
Options are available for conguring the
The Safety Halo Setup Menu allows the user to disable or enable this function as well as setting the intensity of the Safety HaloTM brightness. A nightly auto-dim feature can be set to dim the Safety HaloTM brightness to a
user-set level at specied hours every
day.
The set time and date option on the Display Setup menu allows the user to specify the current time and date that may be displayed at the bottom of the main display. The FMS-1655M Monitor will maintain the time and date as long as the unit is not powered down. The time and
date can be synced to the network master clock when the FMS-1655M Monitor is connected to the BACnet network.
TM
option on the Display
15
LIT-12013119
FMS-1655M
The set brightness option on the Display Setup menu allows the intensity of the
display backlighting to be adjusted from
very dim to very bright. The brightness settings are saved in nonvolatile memory and remain in effect through a power cycle.

Adding password security

Access to the FMS-1655M Monitor menu system can be protected from unauthorized tampering through the multi-level security passwords. Up to ten individual passwords may be entered in
the system, each with a specic access
level. A password entry may be created by selecting the Passwords Setup option from the System Setup menu, and then selecting add password. The user is prompted to enter a minimum of four and up to eight numeric digits.
Once a password has been specied, the
user is prompted to specify one of four access levels: Unrestricted, Standard,
Basic, and Restricted. All password
entries are saved to non-volatile memory, and remain in effect through a power failure. In the event that a password has been forgotten, there is a factory-default
“back door” password that will provide
unrestricted access to the user menu system. Please consult with the factory for more information regarding this password.
Note: An unrestricted password must
be created rst before any restricted
passwords can be set. Resetting Sensor Zero Offset
The FMS-1655M Monitor’s remote sensor can have its zero offset reset to the factory calibrated default in the event the monitored pressure does not approach zero when the door to the monitored room is opened. Select the Reset Zero Offset option on the Diagnostics menu to begin the procedure. once the reading
stabilizes, click the OK button to proceed.
Exit to the main display and verify that the reading goes to zero. If not, repeat the above procedure.
Remote monitoring the FMS-1655M Monitor
The FMS-1655M Monitor provides native
support for BACnet® MS/TP protocol over
a RS-485 serial port located on the FMS­1655M Monitor user interface display at
CN7, a 3 pin pluggable terminal block at back of display (see page 19). The FMS-
1655M Monitor is able to communicate 11 points of information to the building management system. See page 18 for list
of BACnet® points. The network settings are easily congured by selecting the
Network Setup option from the Unit Setup menu. As an alternate means
of remote monitoring, a 4-20mA signal representing the room DP is available for connecting to a third party controller
on the BMS. It is located at the green terminal block on the remote sensor and labeled as “Io.”
PID output setup
The FMS-1655M Monitor has an analog output which can be used to control a damper actuator for closed loop control of the room differential pressure. This analog
output is present at the 9 pin connector on remote sensor and can be congured
for a 0-10Vdc or 2-10Vdc output through the touchscreen display menu. Go to PID
Output option in Room Setup of Unit Setup menu. Select PID Output Setup,
set operating mode, and output range.
Touch Finish to save settings and exit
back to PID Output Setup menu. If
necessary the PID loop parameters can
be changed by selecting the PID Loop
Setup option where the Proportional, Integral, & Derivative values can be tuned for the optimum control loop response. For most typical applications, PID factory
settings work well.
Editing setpoints
When the FMS-1655M Monitor is used as a controller, the target differential pressure setpoints can be set by selecting the Room Setup option in the Unit Setup menu. There the Edit Setpoint option can be selected and the setpoints for Positive, Negative, and Neutral isolation can be set as well as a deadband.
Diagnostic menu
The FMS-1655M monitor incorporates several troubleshooting tools. The Override PID Output option allows the analog output to be overridden and
locked while test and balance makes
adjustments to the Supply and Exhaust dampers. While in the overridden state,
the analog output is “disconnected” from
the PID control loop, if enabled. The Real-Time View option allows the user to see in real time the actual values for the Pressure, Setpoint, PID Output, and Door
Status. A software reset can be invoked
through the Reset Monitor option. It is recommended to perform this function after installation to insure that all user settings are properly stored to nonvolatile memory.
16
LIT-12013119
FMS-1655M

Cleaning the display

• The cloth may be used dry, or lightly dampened with a mild cleaner or ethanol.
Be sure the cloth is only lightly dampened, not wet. Never apply cleaner directly to touch panel surface; if cleaner is spilled onto
touch panel, soak it up immediately with absorbent cloth.
Cleaner must be neither acid nor alkali (neutral pH).
Wipe the surface gently; if there is a directional surface texture, wipe in the same direction as the texture.
Never use acidic or alkaline cleaners, or organic chemicals such as: paint thinner, acetone, tolulene, xylene, propyl or isopropyl
alchohol, or kerosene.
Tapping the current room name text brings up an
alphanumeric keyboard to quickly change the name of
the monitored room.
Tapping the Status line brings up the Isolation Mode
popup to quickly change the
monitored mode of isolation.
Tap anywhere else on the screen enters the Main Setup Menu if no password is stored. Otherwise, a password must be entered before the Main Setup Menu can be accessed.
Tapping the units brings up engineering units selection popup to
quickly change pressure
measurement units.
Tapping Time brings up the Time Entry popup to
quickly change the current
displayed time.
Tap ALARM AUDIBLE to
toggle mode of audible alarm. It automatically
reverts back to audible
mode when the alarm condition is removed.
Hot-Spot Features of FMS-1655M Monitor
Touchscreen Display
17
LIT-12013119
FMS-1655M

Alarm setpoints

18
LIT-12013119
FMS-1655M

Setup menu tree

19
LIT-12013119
FMS-1655M
20
LIT-12013119
FMS-1655M
Conguring display module settings
Options Dipswitch (S1) – internal use only
1. Graphics Chip Mode Selection OFF = Programming Mode ON = Run Mode
2. Touch Screen Calibration Mode OFF = Force calibration ON = Auto calibration
3. Reserved
4. Reserved
Options Dipswitch (S2) – mode conguration 1
1. Reserved Set to OFF ON = CMS-1655
2. Reserved Set to OFF ON = Enabled
3. Mode Select OFF = FMS-1655M/ CMS-1655 ON = HMS-1655
4. Operational Mode: OFF = Demo Mode ON = Run Mode
Pushbutton Switch (SW1): Reset Button
Pushbutton Switch (SW2): Reserved
BACnet® objects
The following table itemizes the list of points available for integration in a BMS. This table contains the objects for open BACnet®
integration.
Object
Instance
AI - 1 Analog Input 1 (default: Differential Pressure)
BI - 1 Digital Input 1 (Door Switch) Read-Only
AO - 1 Analog Output (PID 1 OUT) Read-Only
AV - 1 Setpoint (Differential Pressure Setpoint) Read/Write
AV - 2 Low Pressure Alarm Setpoint Read/Write
AV - 3 Low Pressure Warning Setpoint Read/Write
AV -4 High Pressure Warning Setpoint Read/Write
AV -5 High Pressure Alarm Setpoint Read/Write
AV - 6 Pressure Deadband Read/Write
MSO-1
MSO-2 Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
Isolation Mode: 1=positive, 2=negative,
3=neutral
Functional Description Read or
Write
Analog Inputs
Read-Only
Binary Inputs
Analog Outputs
Analog Values
Multistate Objects
Read/Write
21
LIT-12013119
FMS-1655M
FMS-1655M Monitor wiring guide
22
LIT-12013119
FMS-1655M
European Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
NA/SA Single Point of Contact:
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
APAC Single Point of Contact:
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 - CHINA
Building Technologies & Solutions
Headquarters: Milwaukee, Wisconsin, USA
Branch Officies: Principal Cities World-wide
Johnson Controls® is registered trademark of Johnson Controls.
© Copyright 2019 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited.
All other marks herein are the marks of their respective owners.
www.johnsoncontrols.com
Loading...