Johnson Controls Facility Explorer FX Series, Facility Explorer FX20, Facility Explorer FX60 Installation Instructions Manual

Page 1
Installation Instructions FX20/60 RS-232 Issue Date April 9, 2014
FX Supervisory Controllers RS-232 Card
Applications
The RS-232 option card provides RS-232 communications capability to the FX Supervisory Controllers. You can install up to two RS-232 option cards per FX Supervisory Controller. The port assignments are shown in Figure 1.
For related information on FX Supervisory Controllers mounting and wiring, refer to the
FX Supervisory Controllers Installation Instructions (Part No. 24-10174-77).
Figure 1: FX Supervisory Controllers
RS-232 Card
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.
Canada
This Class (A) digital apparatus meets all requirements of the Canadian Interference­Causing Equipment Regulations.
© 2014 Johnson Controls, Inc.
Part No. 24-10174-85, Rev.C
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
1
Page 2
Installation
Unpack the RS-232 option card and inspect the contents of the package for damaged or missing components. If the option card is damaged, notify the appropriate carrier and return any damaged components for repair or replacement.
Parts Included
Included in this package are the following items:
one RS-232 option card, along with
connector end plate
FX Supervisory Controllers RS-232 Card
Installation Instructions (Part No. 24-10174-85)
Special Tools Needed
To install the RS-232 card, use a number 2 Phillips screwdriver.
!
WARNING: Risk of Electric Shock. Disconnect the power supply before making electrical connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
Mounting
Mounting the RS-232 Card onto the FX Supervisory Controllers
Mount the RS-232 card in either of the option card slots on the FX Supervisory Controllers, as available.
To mount the RS-232 card onto the FX Supervisory Controllers:
1. If a station is running, stop it using the platform Application Director view.
2. Remove power from FX Supervisory Controller.
3. Remove the FX Supervisory Controller
cover. To do this, press in the four tabs on both ends of the FX Supervisory Controller and lift off the cover.
Note: If accessory modules are plugged into the FX Supervisory Controllers, you may need to slide them away from the unit to access the cover tabs.
4. If the battery and bracket is installed,
remove it by taking out the four screws holding the bracket in place. Set the screws aside for later.
5. Unplug the battery from the connector on
the FX Supervisory Controllers (Figure 2).
AVERTISSEMENT: Risque de décharge électrique. Débrancher l'alimentation avant
de réaliser tout branchement électrique. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.
IMPORTANT: Make sure to plug any option card into its connector properly (pins aligned).
IMPORTANT: Avoid hot plug-in or the removal of any option card from the FX Supervisory Controllers (or other accessory module). This means you must first remove power from the unit.
FX Supervisory
Con troll er
Figure 2: Removing the Battery Assembly
6. Remove the blanking end plate for the slot
you are installing the option card into. Retain the blanking end plate in case you want to remove the option card at a later date.
7. Carefully insert the pins of the RS-232
card into the socket of the appropriate option card slot. The mounting holes on the RS-232 card should line up with the standoffs on the FX Supervisory
2 FX Supervisory Controllers RS-232 Card Installation Instructions
Page 3
Controllers. If they do not line up, the connector is not properly aligned.
8. Press until the RS-232 card is completely seated.
9. Place the custom end plate that came with the RS-232 card over its connector (Figure 3).
Figure 3: Inserting the RS-232 Card
10. If you are installing or replacing the battery or bracket, plug the battery cable into the battery connector on the FX Supervisory Controller. See Figure 2 for the location.
11. Set the battery and bracket assembly back over the option card slots, with the mounting holes aligned with the standoffs.
12. Place the four screws through the battery bracket, end plates, and into the standoffs on the FX Supervisory Controller. Hand tighten these screws with a screwdriver.
Figure 4: Refastening the Screws
13. Replace the FX Supervisory Controller cover. If accessory modules were unplugged, plug them back into the FX Supervisory Controller as before, and secure.
14. Restore power to the controller and verify normal operation.
Wiring
The RS-232 card uses standard DB-9M plug and pinouts (it is identical to the RS-232 port on the FX Supervisory Controller base). To connect the FX Supervisory Controller RS-232 card with a Data Terminal Equipment (DTE) device, use a null modem cable with DB9 connector.
Table 1: RS-232 Card Port Assignments
FX20/FX30E/FX60/FX60E FX70
Up to 2 RS-232 cards supported Up to 2 RS-232 cards supported Option Slot 1 Option Slot 2 Option Slot 1 Option Slot 2 RS-232 =
COM3 RS-485 =
COM3, COM4 LON = LON1 RS-232 = COM3 LON = LON1 RS-232 = COM5 Wireless TEC =
COM1 Sedona =
COM3 Modem =
COM1 GPRS = COM3,
COM4
RS-232 = COM4 RS-232 = COM5 RS-232 = COM6
RS-232 = COM5 RS-485 = COM5,
COM6
RS-232 = COM3 NA NA
RS-232 = COM4 Sedona = COM5 RS-23 2 = COM6
RS-232 = COM3 Modem = COM3 RS-232 = COM5
RS-232 = COM5 GPRS = COM5,
COM6
RS-232 = COM7
RS-232 = COM7
FX Supervisory Controllers RS-232 Card Installation Instructions 3
Page 4
Table 2: COM Assignment for RS-232 Card in Option Slot 2
Pinout References Signal DB-9 Plug Pin
DB-9 Plug (Male)
DCD Data carrier
detect RXD Receive data 2 TXD Transmit data 3 DTR Data terminal
ready GND Ground 5 DSR Data set ready 6 RTS Request to send 7 CTS Clear to send 8 9
1
4
Repair Information
If the RS-232 option card fails to operate within its specifications, replace the unit. For a replacement option card, contact the nearest Johnson Controls® representative.
Operation
LEDs
Two LEDs are visible on the top of the RS-232 option card when the cover is removed from the FX Supervisory Controller. These LEDs are as follows:
RX (green): Receive. Indicates that the FX Supervisory Controller is receiving data from a device.
TX (yellow): Transmit. Indicates that the FX Supervisory Controller is transmitting a message to a device.
507 E. Michigan Street, Milwaukee, WI 53202
Johnson Controls® is a registered trademark of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.
4 FX Supervisory Controllers RS-232 Card Installation Instructions