The FAC3613 Advanced Application Field Equipment
Controller (FAC) is part of the Metasys® system
Field Equipment Controller family. The FAC36
Series controllers run pre-engineered and userprogrammed applications and provides the inputs
and outputs required to monitor and control a wide
variety of HVAC and other facility equipment.
FAC36 controllers operate on an RS-485 BACnet
MS/TP Bus as BACnet Advanced Application
Controllers (B-AACs) and integrate into Johnson
Controls® and third-party BACnet systems.
FAC36 field controllers include an integral real-time
clock, which enables the controllers to monitor
and control schedules, calendars, and trends, and
operate for extended periods of time as stand-alone
controllers when offline from the Metasys system
network.
Communications protocols
The FAC3613 field controllers can communicate
using BACnet MS/TP, N2, or wireless Zigbee. By
default, the FAC3613 field controllers communicate
using the standard BACnet MS/TP protocol. The
BACnet protocol is a standard for ANSI, ASHRAE, and
the International Standards Organization (ISO) for
building controls.
The FEC Family Controllers, including the FAC3613,
can be used as functional replacements for
legacy N2 controllers. The N2-capable MS/TP
field controller models provide a cost-effective
upgrade and modernization path for customers
with existing N2 controllers. For installation and
commissioning support, and tips for efficient and
safe replacement, refer to the Modernization Guidefor Legacy N2 Controllers (LIT-12012005) and the
controller-specific documentation. For information
about mapping N2 Objects in controllers with
switchable communications protocols, refer to the
N2 Compatibility Options chapter of the Controller Tool
Help (LIT-12011147).
To configure FAC3613 field controllers to
communicate using the N2 communications
protocol, see Configuring N2 Communications.
The FAC3613 field controller can also be installed in
a wireless application using a ZFR/ZFR Pro Wireless
Field Bus Router. To configure these controllers to
®
Controller Installation Guide
Part No. 24-11021-7 Rev. C
2019-10-18
communicate using the wireless communications
protocol, see Configuring Wireless Communications.
Fast persistence
The FAC3613 model has been significantly upgraded
and now includes a fast persistence feature that
allows you to retain data values at a configurable
interval, up to once per second. Persistence refers
to how often samples of data are stored locally. This
upgrade to the persistence feature ensures that
in the event of a problem, such as a loss of power,
more recent data can be retrieved up to the rate that
the data is persisted, minimizing the potential loss of
data. When power is restored, previously persisted
data, up to the rate of persistence, is still available
and accessible. When persistence is configured
for once per second, you risk losing only the most
recent one second of data before the power loss.
Persisting data may be essential for situations that
require greater data accuracy. This may include
certain methods of utility data collection and billing
Attributes that can be persisted in the FAC3613
include: Counter Input Present Value Attributes,
Binary Input, Binary Output, and Binary Value COS
Counts and Active Time Attributes, and PID/PRAC
tuning parameters.
North American emissions
compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment
is operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area
may cause harmful interference, in which case the
users will be required to correct the interference at
their own expense.
*24110217C*
(barcode for factory use only)
MS-FAC3613
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
• Do not drop the controller or subject it to physical
shock.
Parts included
• One field Controller. (Power and SA bus terminal
blocks are removable)
• One installation instructions sheet.
Installation
Observe the following guidelines when installing a
field controller:
• To minimize vibration and shock damage,
transport the controller in the original container.
• Verify that all parts shipped with the controller.
FAC3613 physical features
Figure 1: FAC3613 Physical Features
Materials and special tools needed
• Three fasteners appropriate for the mounting
surface (M4 screws or #8 screws)
• One 23 cm (9.125 in.) or longer piece of 35 mm
DIN rail and appropriate hardware for DIN rail
mount (only)
• Small straight-blade screwdriver for securing
wires in the terminal blocks
Table 1: Physical features
Physical feature: description and references
Analog Output (AO) Terminal Block: Can be defined as
1
Voltage Analog Output (0–10 VDC) or Current Analog
Output (4–20 mA) (see Table 2)
Device Address DIP Switch Block (see Setting the Device
2
Addresses)
3Mounting clip
FAC3613 Advanced Application Field Equipment Controller Installation Guide2
Table 1: Physical features
Physical feature: description and references
Binary Outputs (BO) Terminal Block: 24 VAC Triac (see
4
Table 2)
24 VAC, Class 2/SELV Supply Power Terminal Block (see
5
Supply power terminal block)
6Cover Lift Tab (One of Two)
7FC Bus Terminal Block (see FC bus terminal block )
Table 1: Physical features
Physical feature: description and references
8SA Bus Terminal Block (see SA bus terminal block)
Sensor Port: (SA Bus) RJ-12 6-Pin Modular Jack (see SA Bus
9
port )
Binary Input (BI) Terminal Block: Dry Contact Maintained
or Pulse Counter/Accumulator Mode (see Terminal wiring
10
guidelines, functions, ratings, and requirements
Universal Inputs (UI) Terminal Block: Can be defined as
Voltage Analog Input (0–10 VDC), Current Analog Input
11
(4–20 mA), Resistive Analog Inputs (0–600k ohms), or
Dry Contact Binary Input (see Input and Output wiring
guidelines)
End-of-Line (EOL) Switch (see Setting the End-of-Line
12
(EOL) switch)
13LED Status Indicators (see Table 7)
14FC Bus Port (RJ-12 6-pin Modular Jack)
Mounting
Observe the following guidelines when mounting a
field controller:
• Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied
enclosure.
Observe these additional guidelines when mounting
a field controller in a panel or enclosure:
• Mount the controller so that the enclosure walls
do not obstruct cover removal or ventilation
through the controller.
• Mount the controller so that the power
transformer and other devices do not radiate
excessive heat to the controller.
• Do not install the controller in an airtight
enclosure.
Figure 2: Controller Mounting Positions
• Mount the controller horizontally on 35 mm DIN
rail whenever possible.
• Mount the controller in the correct mounting
position (Figure 2).
• Whenever possible in wall-mount applications,
mount the controller on a hard, even surface.
• Use shims or washers to mount the controller
securely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive
vapors and observe the ambient conditions
requirements in Technical specifications.
• Provide sufficient space around the controller for
cable and wire connections, easy cover removal,
and good ventilation through the controller (50
mm [2 in.] minimum on the top, bottom, and
front of the controller).
• Do not mount the controller on surfaces prone to
vibration, such as ductwork.
• Do not mount the controller in areas where
electromagnetic emissions from other
devices or wiring can interfere with controller
communication.
Mounting Features and Dimensions
See Figure 3 for mounting dimensions in millimeters
and inches. Inches are listed in parenthesis. Figure
3 also illustrates the DIN rail channel and the
mounting clips in an extended position.
Figure 3: Back of Controller
FAC3613 Advanced Application Field Equipment Controller Installation Guide3
DIN Rail mount applications
Mounting the field controller horizontally on 35 mm
DIN rail is the preferred mounting method.
To mount a field controller on 35 mm DIN rail,
complete the following steps:
Important: Do not overtighten the mounting
screws. Overtightening the screws may
damage the mounting clips.
Wiring
1.Securely mount a 23 cm (9.125 in.) or longer
section of 35 mm DIN rail, horizontally and
centered in the desired space, so that the
controller mounts in the position shown in
Figure 2.
2.Pull the two bottom mounting clips outward
from the controller to the extended position
(Figure ).
3.Hang the controller on the DIN rail by the hooks
at the top of the (DIN rail) channel on the back
of the controller (Figure ), and position the
controller snugly against the DIN rail.
4.Push the bottom mounting clips inward (up) to
secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the
bottom mounting clips out to the extended position
and carefully lift the controller off the DIN rail.
Wall mount applications
To mount a field controller directly on a wall or
other flat vertical surface, complete the following
steps:
CAUTION
Risk of Electric Shock:
Disconnect the power supply before making electrical
connections to avoid electric shock
ATTENTION
Mise En Garde: Risque de décharge électrique
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de
décharge électrique.
CAUTION
Risk of Property Damage:
Do not apply power to the system before checking all
wiring connections. Short circuited or improperly connected wires may result in permanent damage to the
equipment.
1.Pull the two bottom mounting clips outward
and ensure they are locked in the extended
position.
2.Mark the mounting hole locations on the wall
in either the horizontal or vertical mounting
position. Or hold the controller up to the wall or
surface in a proper mount position and msark
the hole locations through the mounting clips.
3.Drill holes in the wall or surface at the marked
locations, and insert appropriate wall anchors
in the holes (if necessary).
4.Hold the controller in place, and insert the
screws through the mounting clips and into the
holes (or anchors). Carefully tighten all of the
screws.
FAC3613 Advanced Application Field Equipment Controller Installation Guide4
ATTENTION
Mise En Garde: Risque de dégâts matériels
Ne pas mettre le système sous tension avant d'avoir
vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement
l'équipement.
Important: Do not exceed the controller
electrical ratings. Exceeding controller electrical
ratings can result in permanent damage to the
controller and void any warranty.
Important: Use copper conductors only. Make
all wiring in accordance with local, national, and
regional regulations.
Important: Electrostatic discharge can
damage controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
Note: The FC bus Shield (SHLD) terminal is
isolated and can be used to connect (daisy
chain) the shields for FC bus wiring.
SA bus terminal block
For detailed information about configuring and
wiring an MS/TP bus, FC bus and SA bus, refer to
the MS/TP Communications Bus Technical Bulletin(LIT-12011034). For detailed information on wiring an
N2 network, refer to the
Terminal blocks and bus ports
See FAC3613 physical features for terminal block
and bus port locations on the FAC3613 controller.
Observe the following guidelines when wiring a
controller.
Input and Output terminal blocks
The fixed input terminal blocks are located on the
bottom of the controller, and the output terminal
blocks are located on the top of the controller. See
Table 2 for more information about I/O terminal
functions, requirements, and ratings.
FC bus terminal block
The FC Bus terminal block is a blue, removable, 4terminal plug that fits into a board-mounted jack.
Wire the removable FC bus terminal block plugs on
the controller, and other controllers in a daisy-chain
configuration using 3-wire twisted, shielded cable as
shown in Figure 4. For more information about the
FC Bus terminal function, requirements, and ratings,
see .
Figure 4: FC bus terminal block wiring
The SA Bus terminal block is a brown, removable, 4terminal plug that fits into a board-mounted jack.
Wire the removable SA Bus terminal block plugs on
the controller, and other SA bus devices in a daisychain configuration using 4-wire twisted, shielded
cable as shown in Figure 5. For more information
about the SA Bus terminal function, requirements,
and ratings, see .
Figure 5: SA bus terminal block wiring
Note: The SA PWR terminal supplies 15 VDC.
The SA PWR terminal can be used to connect
(daisy chain) the 15 VDC power leads on the SA
bus.
FC bus port
The FC bus port on the front of the controller is
an RJ-12, 6-position modular jack that provides
a connection for the Mobile Access Portal (MAP)
Gateway, the Bluetooth® Commissioning Converter,
or the ZFR/ZFR Pro Wireless Field Bus Router.
The FC bus port is connected internally to the FC bus
terminal block. For more information about the FC
Bus port functions, requirements, and ratings, see .
The FC bus port pin assignment is shown in Figure
6.
Note:
• When the is configured for N2 network
communication, the FC bus port is not used.
FAC3613 Advanced Application Field Equipment Controller Installation Guide5
• The MAP Gateway serves as a replacement
for the BTCVT, which is no longer available
for purchase, but continues to be supported.
Figure 6: Pin number assignments for sensor, SA
bus, and FC bus ports on Field Controllers
Figure 7: 24 VAC supply power terminal block
wiring
SA Bus port
The Sensor (SA Bus) port on the bottom of the
controller is an RJ-12, 6-position modular jack
that provides a connection for MAP Gateway, the
Bluetooth® Commissioning Converter (BTCVT), the
VAV Balancing Tool, specified network sensors, or
other SA Bus devices with RJ-12 plugs.
A DIS1710 Local Controller Display also can be
connected to the SA Bus port (but only on FEC
models without integral display and push buttons).
The Sensor port is connected internally to the SA
bus terminal block. For more information about the
Sensor port functions, requirements and ratings,
see . The Sensor Port pin assignment is shown in
Figure 6 (but only on FEC models without integral
display and push buttons).
Supply power terminal block
The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a boardmounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the
transformer to the HOT and COM terminals on the
terminal plug as shown in Figure 7. Do not use the
middle terminal on the supply power terminal block.
See for more information about the Supply Power
Terminal Block.
Note: The supply power wire colors may
be different on transformers from other
manufacturers. Refer to the transformer
manufacturer’s instructions and the project
installation drawings for wiring details.
Important: Connect 24 VAC supply power
to the field controller and all other network
devices so that transformer phasing is uniform
across the network devices. Powering network
devices with uniform 24 VAC supply power
phasing reduces noise, interference, and
ground loop problems. The field controller
does not require an earth ground connection.
Terminal wiring guidelines, functions,
ratings, and requirements
Input and Output wiring guidelines
Table 2 provides information and guidelines about
the functions, ratings, and requirements for the
controller input and output terminals. The table also
references guidelines for determining proper wire
sizes and cable lengths.
In addition to the wiring guidelines in Table 2,
observe these guidelines when you wire controller
inputs and outputs:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All input and output cables, regardless of wire
size or number of wires, should consist of
stranded, insulated, and twisted copper wires.
FAC3613 Advanced Application Field Equipment Controller Installation Guide6
• Shielded cable is not required for input or output
cables.
• Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software
setup. Cable runs over 30 m (100 ft) may require
• Shielded cable is recommended for input
an offset in the input/output software setup.
and output cables that are exposed to high
electromagnetic or radio frequency noise.
I/O Terminal blocks, ratings, and
requirements
Table 2: Terminal blocks, functions, ratings, requirements, and cables
Nickel [ Johnson Controls® sensor], 1k Platinum, and
A99B Silicon Temperature Sensor) Negative Temperature
Coefficient (NTC) Sensor
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V. 15k ohms pull-up
Universal Input Common for all Universal Input
terminals
Note: All Universal ICOMn terminals share a
common, which is isolated from all other commons,
except the SA bus common. One common screw
terminal point is provided for every two input screw
terminal points.
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width
Internal 18 V. 3k ohms pull-up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V. 3k ohms pull-up
Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons.
Determine wire size and
maximum cable length
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power
from the +15V terminal.
See Guideline A in Table 3.
See Guideline B in Table 3.
See Guideline A in Table 3.
See Guideline A in Table 3.
Same as (Universal) INn
See Guideline A in Table 3.
FAC3613 Advanced Application Field Equipment Controller Installation Guide7
Table 2: Terminal blocks, functions, ratings, requirements, and cables
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohms or more.
Note: The Analog Output (AO) operates in the
Voltage Mode when connected to devices with
impedances greater than 1,000 ohms. Devices that
OUTn
ANALOG
(Outputs)
OCOMn
OUTn
BINARY
(Output)
OCOMn
drop below 1,000 ohm may not operate as intended
for Voltage Mode applications.
Analog Output - Current Mode (4–20 mA)
Requires an external load between 0 and 300 ohms.
Note: The Analog Output (AO) operates in the
Current Mode when connected to devices with
impedances less than 300 ohms. Devices that
exceed below 300 ohms may not operate as
intended for Current Mode applications.
Analog Output Signal Common for all Analog OUT
terminals.
Note: All Analog Output Common terminals
(OCOMn) share a common, which is isolated from
all other commons. One common screw terminal
point is provided for every two output screw
terminal points.
Binary Output - 24 VAC Triac Class 2, 24 V, 500 mA
(External Power Source)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Binary Output Common (for OUTn terminal)
Note: Each Binary Output Common terminal
(OCOMn) is isolated from all other commons,
including other Binary Output Common terminals.
Determine wire size and
maximum cable length
See Guideline C in Table 3.
See Guideline C in Table 3.
Cable and wire length guidelines
The following table defines cable length guidelines
for the various wire sizes that may be used for
wiring low-voltage (<30 V) input and outputs.
Note: The required wire sizes and lengths
for high-voltage (>30 V) Relay Outputs are
determined by the load connected to the relay,
and local, national, or regional electrical codes.
FAC3613 Advanced Application Field Equipment Controller Installation Guide8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.