Johnson Controls FAC3613 Installation Manual

FAC3613 Advanced Application Field Equipment

Application

The FAC3613 Advanced Application Field Equipment Controller (FAC) is part of the Metasys® system Field Equipment Controller family. The FAC36 Series controllers run pre-engineered and user­programmed applications and provides the inputs and outputs required to monitor and control a wide variety of HVAC and other facility equipment.
FAC36 controllers operate on an RS-485 BACnet MS/TP Bus as BACnet Advanced Application Controllers (B-AACs) and integrate into Johnson Controls® and third-party BACnet systems.
FAC36 field controllers include an integral real-time clock, which enables the controllers to monitor and control schedules, calendars, and trends, and operate for extended periods of time as stand-alone controllers when offline from the Metasys system network.

Communications protocols

The FAC3613 field controllers can communicate using BACnet MS/TP, N2, or wireless Zigbee. By default, the FAC3613 field controllers communicate using the standard BACnet MS/TP protocol. The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building controls.
The FEC Family Controllers, including the FAC3613, can be used as functional replacements for legacy N2 controllers. The N2-capable MS/TP field controller models provide a cost-effective upgrade and modernization path for customers with existing N2 controllers. For installation and commissioning support, and tips for efficient and safe replacement, refer to the Modernization Guide for Legacy N2 Controllers (LIT-12012005) and the controller-specific documentation. For information about mapping N2 Objects in controllers with switchable communications protocols, refer to the
N2 Compatibility Options chapter of the Controller Tool Help (LIT-12011147).
To configure FAC3613 field controllers to communicate using the N2 communications protocol, see Configuring N2 Communications.
The FAC3613 field controller can also be installed in a wireless application using a ZFR/ZFR Pro Wireless Field Bus Router. To configure these controllers to
®
Controller Installation Guide
Part No. 24-11021-7 Rev. C
2019-10-18
communicate using the wireless communications protocol, see Configuring Wireless Communications.

Fast persistence

The FAC3613 model has been significantly upgraded and now includes a fast persistence feature that allows you to retain data values at a configurable interval, up to once per second. Persistence refers to how often samples of data are stored locally. This upgrade to the persistence feature ensures that in the event of a problem, such as a loss of power, more recent data can be retrieved up to the rate that the data is persisted, minimizing the potential loss of data. When power is restored, previously persisted data, up to the rate of persistence, is still available and accessible. When persistence is configured for once per second, you risk losing only the most recent one second of data before the power loss. Persisting data may be essential for situations that require greater data accuracy. This may include certain methods of utility data collection and billing
Attributes that can be persisted in the FAC3613 include: Counter Input Present Value Attributes, Binary Input, Binary Output, and Binary Value COS Counts and Active Time Attributes, and PID/PRAC tuning parameters.

North American emissions compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.
*24110217C*
(barcode for factory use only)
MS-FAC3613

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
• Do not drop the controller or subject it to physical shock.

Parts included

• One field Controller. (Power and SA bus terminal blocks are removable)
• One installation instructions sheet.

Installation

Observe the following guidelines when installing a field controller:
• To minimize vibration and shock damage, transport the controller in the original container.
• Verify that all parts shipped with the controller.

FAC3613 physical features

Figure 1: FAC3613 Physical Features

Materials and special tools needed

• Three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
• One 23 cm (9.125 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only)
• Small straight-blade screwdriver for securing wires in the terminal blocks
Table 1: Physical features
Physical feature: description and references
Analog Output (AO) Terminal Block: Can be defined as
1
Voltage Analog Output (0–10 VDC) or Current Analog Output (4–20 mA) (see Table 2)
Device Address DIP Switch Block (see Setting the Device
2
Addresses)
3 Mounting clip
FAC3613 Advanced Application Field Equipment Controller Installation Guide2
Table 1: Physical features
Physical feature: description and references
Binary Outputs (BO) Terminal Block: 24 VAC Triac (see
4
Table 2) 24 VAC, Class 2/SELV Supply Power Terminal Block (see
5
Supply power terminal block)
6 Cover Lift Tab (One of Two) 7 FC Bus Terminal Block (see FC bus terminal block )
Table 1: Physical features
Physical feature: description and references
8 SA Bus Terminal Block (see SA bus terminal block)
Sensor Port: (SA Bus) RJ-12 6-Pin Modular Jack (see SA Bus
9
port )
Binary Input (BI) Terminal Block: Dry Contact Maintained or Pulse Counter/Accumulator Mode (see Terminal wiring
10
guidelines, functions, ratings, and requirements
Universal Inputs (UI) Terminal Block: Can be defined as Voltage Analog Input (0–10 VDC), Current Analog Input
11
(4–20 mA), Resistive Analog Inputs (0–600k ohms), or Dry Contact Binary Input (see Input and Output wiring
guidelines)
End-of-Line (EOL) Switch (see Setting the End-of-Line
12
(EOL) switch)
13 LED Status Indicators (see Table 7) 14 FC Bus Port (RJ-12 6-pin Modular Jack)

Mounting

Observe the following guidelines when mounting a field controller:
• Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.
Observe these additional guidelines when mounting a field controller in a panel or enclosure:
• Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller.
• Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller.
• Do not install the controller in an airtight enclosure.
Figure 2: Controller Mounting Positions
• Mount the controller horizontally on 35 mm DIN rail whenever possible.
• Mount the controller in the correct mounting position (Figure 2).
• Whenever possible in wall-mount applications, mount the controller on a hard, even surface.
• Use shims or washers to mount the controller securely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive vapors and observe the ambient conditions requirements in Technical specifications.
• Provide sufficient space around the controller for cable and wire connections, easy cover removal, and good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
• Do not mount the controller on surfaces prone to vibration, such as ductwork.
• Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can interfere with controller communication.

Mounting Features and Dimensions

See Figure 3 for mounting dimensions in millimeters and inches. Inches are listed in parenthesis. Figure 3 also illustrates the DIN rail channel and the mounting clips in an extended position.
Figure 3: Back of Controller
FAC3613 Advanced Application Field Equipment Controller Installation Guide 3

DIN Rail mount applications

Mounting the field controller horizontally on 35 mm DIN rail is the preferred mounting method. To mount a field controller on 35 mm DIN rail, complete the following steps:
Important: Do not overtighten the mounting screws. Overtightening the screws may damage the mounting clips.

Wiring

1. Securely mount a 23 cm (9.125 in.) or longer
section of 35 mm DIN rail, horizontally and centered in the desired space, so that the controller mounts in the position shown in Figure 2.
2. Pull the two bottom mounting clips outward
from the controller to the extended position (Figure ).
3. Hang the controller on the DIN rail by the hooks
at the top of the (DIN rail) channel on the back of the controller (Figure ), and position the controller snugly against the DIN rail.
4. Push the bottom mounting clips inward (up) to
secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail.

Wall mount applications

To mount a field controller directly on a wall or other flat vertical surface, complete the following steps:
CAUTION
Risk of Electric Shock:
Disconnect the power supply before making electrical connections to avoid electric shock
ATTENTION
Mise En Garde: Risque de décharge électrique
Débrancher l'alimentation avant de réaliser tout rac­cordement électrique afin d'éviter tout risque de décharge électrique.
CAUTION
Risk of Property Damage:
Do not apply power to the system before checking all wiring connections. Short circuited or improperly con­nected wires may result in permanent damage to the equipment.
1. Pull the two bottom mounting clips outward
and ensure they are locked in the extended position.
2. Mark the mounting hole locations on the wall
in either the horizontal or vertical mounting position. Or hold the controller up to the wall or surface in a proper mount position and msark the hole locations through the mounting clips.
3. Drill holes in the wall or surface at the marked
locations, and insert appropriate wall anchors in the holes (if necessary).
4. Hold the controller in place, and insert the
screws through the mounting clips and into the holes (or anchors). Carefully tighten all of the screws.
FAC3613 Advanced Application Field Equipment Controller Installation Guide4
ATTENTION
Mise En Garde: Risque de dégâts matériels
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils for­mant un court-circuit ou connectés de façon incor­recte risquent d'endommager irrémédiablement l'équipement.
Important: Do not exceed the controller electrical ratings. Exceeding controller electrical ratings can result in permanent damage to the controller and void any warranty.
Important: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations.
Important: Electrostatic discharge can damage controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
Note: The FC bus Shield (SHLD) terminal is isolated and can be used to connect (daisy chain) the shields for FC bus wiring.

SA bus terminal block

For detailed information about configuring and wiring an MS/TP bus, FC bus and SA bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034). For detailed information on wiring an N2 network, refer to the

Terminal blocks and bus ports

See FAC3613 physical features for terminal block and bus port locations on the FAC3613 controller. Observe the following guidelines when wiring a controller.

Input and Output terminal blocks

The fixed input terminal blocks are located on the bottom of the controller, and the output terminal blocks are located on the top of the controller. See Table 2 for more information about I/O terminal functions, requirements, and ratings.

FC bus terminal block

The FC Bus terminal block is a blue, removable, 4­terminal plug that fits into a board-mounted jack.
Wire the removable FC bus terminal block plugs on the controller, and other controllers in a daisy-chain configuration using 3-wire twisted, shielded cable as shown in Figure 4. For more information about the FC Bus terminal function, requirements, and ratings, see .
Figure 4: FC bus terminal block wiring
The SA Bus terminal block is a brown, removable, 4­terminal plug that fits into a board-mounted jack.
Wire the removable SA Bus terminal block plugs on the controller, and other SA bus devices in a daisy­chain configuration using 4-wire twisted, shielded cable as shown in Figure 5. For more information about the SA Bus terminal function, requirements, and ratings, see .
Figure 5: SA bus terminal block wiring
Note: The SA PWR terminal supplies 15 VDC.
The SA PWR terminal can be used to connect (daisy chain) the 15 VDC power leads on the SA bus.

FC bus port

The FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for the Mobile Access Portal (MAP) Gateway, the Bluetooth® Commissioning Converter, or the ZFR/ZFR Pro Wireless Field Bus Router.
The FC bus port is connected internally to the FC bus terminal block. For more information about the FC Bus port functions, requirements, and ratings, see . The FC bus port pin assignment is shown in Figure
6.
Note:
• When the is configured for N2 network communication, the FC bus port is not used.
FAC3613 Advanced Application Field Equipment Controller Installation Guide 5
• The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.
Figure 6: Pin number assignments for sensor, SA bus, and FC bus ports on Field Controllers
Figure 7: 24 VAC supply power terminal block wiring

SA Bus port

The Sensor (SA Bus) port on the bottom of the controller is an RJ-12, 6-position modular jack that provides a connection for MAP Gateway, the Bluetooth® Commissioning Converter (BTCVT), the VAV Balancing Tool, specified network sensors, or other SA Bus devices with RJ-12 plugs.
A DIS1710 Local Controller Display also can be connected to the SA Bus port (but only on FEC models without integral display and push buttons).
The Sensor port is connected internally to the SA bus terminal block. For more information about the Sensor port functions, requirements and ratings, see . The Sensor Port pin assignment is shown in Figure 6 (but only on FEC models without integral display and push buttons).

Supply power terminal block

The 24 VAC supply power terminal block is a gray, removable, 3-terminal plug that fits into a board­mounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7. Do not use the middle terminal on the supply power terminal block. See for more information about the Supply Power Terminal Block.
Note: The supply power wire colors may be different on transformers from other manufacturers. Refer to the transformer manufacturer’s instructions and the project installation drawings for wiring details.
Important: Connect 24 VAC supply power to the field controller and all other network devices so that transformer phasing is uniform across the network devices. Powering network devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop problems. The field controller does not require an earth ground connection.

Terminal wiring guidelines, functions, ratings, and requirements

Input and Output wiring guidelines

Table 2 provides information and guidelines about the functions, ratings, and requirements for the controller input and output terminals. The table also references guidelines for determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in Table 2, observe these guidelines when you wire controller inputs and outputs:
• Run all low-voltage wiring and cables separate from high-voltage wiring.
• All input and output cables, regardless of wire size or number of wires, should consist of stranded, insulated, and twisted copper wires.
FAC3613 Advanced Application Field Equipment Controller Installation Guide6
• Shielded cable is not required for input or output cables.
• Inputs/outputs with cables less than 30 m (100 ft) typically do not require an offset in the software setup. Cable runs over 30 m (100 ft) may require
• Shielded cable is recommended for input
an offset in the input/output software setup.
and output cables that are exposed to high electromagnetic or radio frequency noise.
I/O Terminal blocks, ratings, and requirements
Table 2: Terminal blocks, functions, ratings, requirements, and cables
Terminal block label Terminal label Function, ratings, requirements
15 VDC Power Source for active (3-wire) input devices
+15 V
INn
UNIVERSAL
(Inputs)
ICOMn
INn
BINARY
(Inputs)
ICOMn
connected to the Universal INn terminals. Provides 100 mA total current
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage Internal 75k ohms pull-down
Analog Input - Current Mode (4–20 mA)
Internal 100 ohms load impedance. See Setting the Input
Jumpers.
Note: A current loop fail-safe jumper must be in the Enable position to maintain a closed 4 to 20 mA current loop. See UI current loop jumpers.
Analog Input - Resistive Mode (60–600k ohms)
Internal 12 V. 15k ohms pull-up Qualified Sensors: 0–2k ohms potentiometer, RTD (1k
Nickel [ Johnson Controls® sensor], 1k Platinum, and A99B Silicon Temperature Sensor) Negative Temperature Coefficient (NTC) Sensor
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width Internal 12 V. 15k ohms pull-up
Universal Input Common for all Universal Input terminals
Note: All Universal ICOMn terminals share a common, which is isolated from all other commons, except the SA bus common. One common screw terminal point is provided for every two input screw terminal points.
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width Internal 18 V. 3k ohms pull-up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width (50 Hz at 50% duty cycle) Internal 18 V. 3k ohms pull-up
Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons.
Determine wire size and maximum cable length
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power from the +15V terminal.
See Guideline A in Table 3.
See Guideline B in Table 3.
See Guideline A in Table 3.
See Guideline A in Table 3.
Same as (Universal) INn
See Guideline A in Table 3.
FAC3613 Advanced Application Field Equipment Controller Installation Guide 7
Table 2: Terminal blocks, functions, ratings, requirements, and cables
Terminal block label Terminal label Function, ratings, requirements
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage 10 mA maximum output current Required an external load of 1,000 ohms or more.
Note: The Analog Output (AO) operates in the Voltage Mode when connected to devices with impedances greater than 1,000 ohms. Devices that
OUTn
ANALOG
(Outputs)
OCOMn
OUTn
BINARY
(Output)
OCOMn
drop below 1,000 ohm may not operate as intended for Voltage Mode applications.
Analog Output - Current Mode (4–20 mA)
Requires an external load between 0 and 300 ohms.
Note: The Analog Output (AO) operates in the Current Mode when connected to devices with impedances less than 300 ohms. Devices that exceed below 300 ohms may not operate as intended for Current Mode applications.
Analog Output Signal Common for all Analog OUT terminals.
Note: All Analog Output Common terminals (OCOMn) share a common, which is isolated from all other commons. One common screw terminal point is provided for every two output screw terminal points.
Binary Output - 24 VAC Triac Class 2, 24 V, 500 mA (External Power Source)
Connects OUTn to OCOMn when activated. External Power Source Requirements: 30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle 40 mA minimum load current
Binary Output Common (for OUTn terminal)
Note: Each Binary Output Common terminal
(OCOMn) is isolated from all other commons, including other Binary Output Common terminals.
Determine wire size and maximum cable length
See Guideline C in Table 3.
See Guideline C in Table 3.

Cable and wire length guidelines

The following table defines cable length guidelines for the various wire sizes that may be used for wiring low-voltage (<30 V) input and outputs.
Note: The required wire sizes and lengths for high-voltage (>30 V) Relay Outputs are determined by the load connected to the relay, and local, national, or regional electrical codes.
FAC3613 Advanced Application Field Equipment Controller Installation Guide8
Table 3: Cable length guidelines for recommended wire sizes for low-voltage (<30 V) Inputs and Outputs
Wire size/Gauge and type
1.0 mm (18 AWG) stranded copper 457 m (1,500 ft) twisted wire
0.8 mm (20 AWG) stranded copper 297 m (975 ft) twisted wire
A
B
C
0.6 mm (22 AWG) stranded copper 183 m (600 ft) twisted wire
0.5 mm (24 AWG) stranded copper 107 m (350 ft) twisted wire
1.0 mm (18 AWG) stranded copper 229 m (750 ft) twisted wire
0.8 mm (20 AWG) stranded copper 137 m (450 ft) twisted wire
0.6 mm (22 AWG) stranded copper 91 m (300 ft) twisted wire
0.5 mm (24 AWG) stranded copper 61 m (200 ft) twisted wire
See Figure 8 to select wire size/gauge. Use stranded copper wire
Maximum cable length and type
See Figure 8 to determine cable length. Use twisted wire cable.
Assumptions
100 mV maximum voltage drop Depending on cable and the
connected input or output device, you may have to define an offset in the setup software for the input or output point.
100 mV maximum voltage drop Depending on cable and the
connected input or output device, you may have to define an offset in the setup software for the input or output point.
N/A

Maximum cable length versus load current

Use Figure 8 to estimate the maximum cable length relative to the wire size and the load current (in mA) when wiring inputs and outputs.
Note: Figure 8 applies to low-voltage (<30 V) inputs and outputs only.
Figure 8: Maximum wire length for low-voltage (<30 V) Inputs and Outputs by current and wire size

Communications bus and supply power wiring guidelines

The provides information about the functions, ratings, and requirements for the communication bus and supply power terminals. The table also
provides guidelines for wire sizes, cable types, and cable lengths for when you wire the controller's communication buses and supply power.
Important: Refer to the N2 Modernization Guide for Legacy N2 Controllers for guidelines when
using this device on an N2 bus.
In addition, observe these guidelines when you wire an SA bus and the 24 VAC supply power:
• Run all low-voltage wiring and cables separate from high-voltage wiring.
• All SA bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire.
• Shielded cable is strongly recommended for all SA bus cables.
• Refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034) for detailed information regarding wire size and cable length requirements for SA buses.
Communications bus and supply power terminal block
Note: The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For more information, refer to the MS/TP Communications
Bus Technical Bulletin (LIT-12011034).
FAC3613 Advanced Application Field Equipment Controller Installation Guide 9
Table 4: Communications bus and supply power terminal blocks, functions, ratings, requirements, and cables
Terminal block/ Port label
FC BUS
FC BUS
(Port)
SA BUS
Sensor
(Port)
24~
Terminal labels Function, electrical ratings/Requirements Recommended cable type
+
-
COM
SHLD
+
­COM SA Bus Signal Reference and 15 VDC Common
SA PWR
SENSOR
HOT
COM
FC Bus Communications
Signal Reference (Common) for Bus communications
Isolated terminal (optional shield drain connection )
RJ-12 6-Position Modular Connector provides: FC Bus Communications FC Bus Signal Reference and 15 VDC Common 15 VDC, 180 mA, Power for Bluetooth
Commissioning Converter
SA Bus Communications
15 VDC Supply Power for Devices on the SA Bus (Maximum total current draw for SA Bus is 240
mA.)
RJ-12 6-Position Modular Connector provides: SA Bus Communications SA Bus Signal Reference and 15 VDC Common 15 VDC Power for devices on the SA bus and
Bluetooth Commissioning Converter
24 VAC Power Supply - Hot
Supply 20–30 VAC (Nominal 24 VAC) 24 VAC Power Supply Common (Isolated from
all other Common terminals on controller) 14 VA
0.6 mm (22 AWG) stranded, 3-wire twisted, shielded cable recommended
Bluetooth Commissioning Converter retractable cable or 24 AWG 3-pair CAT 3 cable or above.
0.6 mm (22 AWG) stranded, 4-wire (2 twisted-pairs), shielded cable recommended.
Note: The + and - wire are one twisted pair, and the COM and SA PWR are the second twisted pair of wires.
24 AWG 3-pair CAT3 cable <30.5 m (100 ft)
0.8 mm to 1.0 mm (18 AWG) 2-wire
FAC3613 Advanced Application Field Equipment Controller Installation Guide10

Termination diagrams

A set of Johnson Controls termination diagrams provides details for wiring inputs and outputs to the
Table 5: Termination details
Type of field device
Type of Input/ Output
Termination diagrams
controllers. See the figures in this section for the applicable termination diagrams.
Temperature Sensor
Voltage Input ­External Source
Voltage Input ­Internal Source
UI
UI
UI
Voltage Input (Self-Powered)
UI
FAC3613 Advanced Application Field Equipment Controller Installation Guide 11
Table 5: Termination details
Type of field device
Current Input ­External Source (Isolated)
Current Input ­Internal Source (2­wire)
Type of Input/ Output
UI
UI
Termination diagrams
Current Input ­Internal Source (3 wire)
Current Input ­External Source (in Loop)
Feedback from EPP-1000
UI
UI
UI
FAC3613 Advanced Application Field Equipment Controller Installation Guide12
Table 5: Termination details
Type of field device
Type of Input/ Output
Termination diagrams
Dry Contact (Binary Input)
0–10 VDC Output to Actuator (External Source)
0–10 VDC Output to Actuator (Internal Source)
UI or BI
CO or AO
CO or AO
Current Output CO or AO
24 VAC Triac Output (Switch Low, External Source)
CO or AO
FAC3613 Advanced Application Field Equipment Controller Installation Guide 13
Table 5: Termination details
Type of field device
Type of Input/ Output
Termination diagrams
Analog Output (Current)
4–20 mA Output to Actuator
4–20 mA Output to Actuator
AO
AO
AO
Incremental Control to Actuator (Switch Low, Externally Sourced)
24 VAC Binary Output (Switch Low, Externally Sourced)
FAC3613 Advanced Application Field Equipment Controller Installation Guide14
BO
BO
Table 5: Termination details
Type of field device
24 VAC Binary Output (Switch High, Externally Sourced)
Incremental Control to Actuator (Switch High, Externally Sourced)
Type of Input/ Output
BO
BO
Termination diagrams
Network Stat with Phone Jack (Fixed Address = 199)
Network Stat with Terminals Addressable
SA Bus
Note: The bottom jack (J2) on the TE-700 and TE-6x00 Series Sensors is not usable as a zone bus or an SAB connection.
SA Bus
FAC3613 Advanced Application Field Equipment Controller Installation Guide 15
Table 5: Termination details
Type of field device
Network Stat with Terminals (Fixed Address = 199)
Type of Input/ Output
SA Bus
Termination diagrams

Setup and Adjustments

Configuring N2 Communications

N2-capable controllers support the full range of possible N2 device addresses provided by the N2 protocol standard (1-254). To configure a controller to communicate using the N2 protocol, complete the following steps:
1. Disconnect the 24 VAC supply from the controller.
2. Set the address switches to the desired N2 address. For details about setting a device address, see Setting the device address.
3. Reconnect the 24 VAC supply to the controller.
4. Using an SA bus connection, download the firmware and controller application file configured for N2 to the controller.

Switching the Communications Protocol from N2 to MS/TP

For N2 sites that are converting to BACnet MS/TP, you can switch the communications protocol of N2­configured MS/TP controllers back to BACnet MS/TP. To switch controller operating in N2 mode back into BACnet MS/TP mode, complete the following steps:
1. Disconnect the 24 VAC supply from the controller.
2. Set the address switches to the desired BACnet MS/TP address. For details about setting a device address, see Setting the device address.
3. Ensure the DIP switch 128 is set to OFF.
4. Reconnect the 24 VAC supply to the controller.
5. Using an SA Bus connection, download a controller application file configured for BACnet MS/TP to the controller.

Configuring Wireless Communications

To configure a controller for use with the ZFR/ZFR Pro Series Wireless Field Bus system, complete the following steps:
1. Disconnect the 24 VAC supply from the controller.
2. Wire the input/output terminals and SA bus.
Note: In wireless network applications, do not connect any wires to the FC bus terminal block. (Connect the SA/FC terminal block on an IOM to an SA bus only.)
3. Important: Before the controller is powered on, connect the ZFR/ZFR Pro Wireless Field Bus Router to the FC bus port (RJ-12 modular jack) on the front of the controller.
FAC3613 Advanced Application Field Equipment Controller Installation Guide16
4. Ensure that the controller's device address DIP switches are set to the correct device address. For details about setting a device address, see
Setting the device address.
For more information about device addresses in wireless applications, refer to the WNC1800/ZFR182x
Pro Series Wireless Field Bus System Technical Bulletin (LIT-12012356) or the ZFR1800 Series Wireless Field Bus System Technical Bulletin (LIT-12011295).
5. Reconnect the 24 VAC supply to the controller.
Figure 9: Device address DIP switch block set to address 21
For more information about the ZFR Pro Wireless Field Bus system, refer to the WNC1800/ZFR182x
Pro Series Wireless Field Bus System Product Bulletin (LIT-12012320).
For more information about the ZFR 1800 Wireless Field Bus system, refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin (LIT-12011336).

Setting the device address

Metasys field controllers are master devices on an MS/TP (SA or FC) bus. Before you operate field controllers on a bus, you must set a valid and unique device address for each controller on the bus. You set a field controller's device address by setting the positions of the switches on the DIP switch block at the top of the controller. Device addresses 4 through 127 are the valid addresses for these controllers on an MS/TP FC Bus.
Device Address Use on Description
0 (Switch 128 Off)
1-3 (Switch 128 Off)
4 to 127 (Switch 128 Off)
The DIP switch block has eight switches numbered 128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1 are device address switches. Switch 128 must be set to OFF for all hard-wired SA and FC bus applications.
Reserved for FC Bus Supervisory Controller(not for use on field controllers).
Reserved for peripheral devices (not for use on field controllers).
Used for MSTP master devices (field controllers) that are hardwired to an SA bus or FC bus.
Note: Metasys field controllers ship with switch 128 ON and the remainining adress switches off rendering the controllers wired subordinate devices, which do not operate on MS/TP buses, but do not interfere with bus operation. Set a valid and unique device address on the controller before applying power to the controller on the bus.
To set the device addresses on the controllers, complete the following steps:
1. Set all of the switches on the address DIP switch block (128 through 1) to OFF.
2. Set one or more of the seven address switches (64 though 1) to ON, so that the sum of the switch numbers set to ON equals the intended device address. Set the highest number switch that is less than or equal to the intended device address to ON. Then continue setting lower numbered switches until the total equals the intended address. For example, if the intended device address is 21, set switch 16 to ON first, then set switch 4 ON, followed by switch 1 (16+4+1= 21). See Figure 9.See for valid device addresses.
3. Set a unique and sequential device address for each of the controllers connected on the SA or FC bus starting with device address 4. To ensure the best bus performance, set sequential device addresses with no gaps in the device address range (4, 5, 6, 7, 8, 9, and so on). The controllers do not need to be physically connected on the bus in their numerical device address order.
4. Write each controller's device address on the white label below the DIP switch block on the controller's cover.
FAC3613 Advanced Application Field Equipment Controller Installation Guide 17
The following table describes the FC bus and SA bus devices addresses for Johnson Controls® MS/TP controllers communications bus applications. Refer to the MS/TP Communications Bus Technical Bul- letin (LIT-12011034) for more information on con­troller device addresses and how to set them on MS/TP buses.
The controller cover is held in place by four plastic latches that extend from the base and snap into slots on the inside of the housing cover.
To remove the controller cover, complete the following steps:

Removing the Controller cover

Important: Electrostatic discharge can damage controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
Important: Disconnect all power sources to the controller before you remove the cover and change the position of any jumper on the controller. Failure to disconnect power before changing a jumper can result in damage to the controller and void any warranties.
Figure 10: Cover removed showing EOL switch and jumper positions
1. Place your fingertips under the two cover lift tabs (FAC3613 physical features ) on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches.
2. Pivot the top of the cover further to release it from the lower two latches.
3. Replace the cover by placing it squarely over the base, and then gently and evenly push the cover on to the latches until they snap into the latched position.

Setting the End-of-Line (EOL) switch

Each controller has an EOL switch, which, when set to ON, sets the controller as a terminating device on the bus. The default EOL switch position is OFF.
FAC3613 Advanced Application Field Equipment Controller Installation Guide18
Figure 11: End-of-Line switch positions
To set the EOL switch on a field controller, complete the following steps:
1. Determine the physical location of the field controller on the FC bus.
2. Determine if the controller must be set as a terminating device on the bus.
Note: For detailed information regarding EOL termination rules and EOL switch settings on FC buses, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
3. If the controller is a terminating device on the FC bus, set the EOL switch to ON. If the controller is not a terminating device on the bus, set the EOL switch to Off.
When a controller is connected to power with its EOL switch set to ON, the amber EOL LED on the controller cover is lit.

Setting the Input Jumpers

CAUTION
Risk of Electric Shock:
Disconnect supply power to the controller before at­tempting to adjust the Binary Output Source Power Selection Jumpers. Failure to disconnect the supply power may result in electric shock.
ATTENTION
Risque de décharge électrique
Débrancher l'alimentation de l'controller avant tout réglage du Binary Output Source Power Selection Jumpers. Le non-respect de cette précaution risque de provoquer une décharge électrique.
Figure 12: Current loop jumper positions
Set the current loop jumper to the Enabled position (Figure 12) to connect an internal 100 ohms resistor across the UI terminals, which maintains the 4–20 mA current loop circuit even when power to the controller is interrupted or off.
Important: Current loop jumpers must be in the Disabled (default) position for all UIs that are not set up to operate as 4–20 mA analog inputs.
The following table identifies the current loop switches associated with each UI on the controller.
Table 6: FAC3613 UI Inputs and jumper labels
Universal Input label Jumper label on circuit board IN1 J5 IN2 J6 IN3 J7 IN4 J8 IN5 J9 IN6 J10 IN7 J11 IN8 J12

Setting up a local display

UI current loop jumpers

The UI current loop fail-safe jumper pins are located on the circuit board under the controller cover near the UI terminals.
FAC3613 Advanced Application Field Equipment Controller Installation Guide 19
The FAC3613 model does not have an integral display, but you can connect the controller to a DIS1710 Local Controller Display. For detailed information about setting up and operating either an integral user interface or a remotely connected DIS1710 display, refer to the

Input/Output Wiring Validation

The FAC3613 controllers ship with a default state that can assist in validating the wiring of the input and output terminals prior to download of an application file. When the controller is powered on in this state, the Fault LED will flash in a pattern of two quick blinks and then a long pause (see Table 7 ).
To make use of this feature, ensure the DIP switches are set to the desired address and wire the input and output terminals. Apply power to the FAC controller and connect to the device with either a MAP Gateway or MS-DIS1710-0 Local Display to view the points in the controller. The FAC controller will report an Operational status even though there is no true application loaded. CCT will not be able to commission or upload the device as a result until a true application is downloaded. The application name displayed will be the address of the controller followed by the model of the controller and “Default State”.
For example, a FAC3613 controller whose DIP switches are set to 8 would have the default state application name of “8-FAC3613 Default State”.
The default state creates I/O points for all connections on the input and output terminals. It assumes all Universal Inputs (UIs) are Nickel temperature sensors. The default state also takes input from a Network Sensor at address 199. If there is no connected Network Sensor, the startup of this default state will be delayed by 30 seconds as the controller attempts to establish connection with the sensor.
software licensing portal, and are loaded and licensed on the computer/server that is running CCT.
For additional information about the firmware package files, refer to the CCT Installation Instructions (LIT-12011259).

Troubleshooting Controllers

Observe the Status LEDs on the front of the field controller and see the table below to troubleshoot the controller. To troubleshoot an integral or local controller display, refer to the DIS1710 Local Controller Display Technical Bulletin (LIT-12011270).

Commissioning Controllers

You commission BACnet MS/TP controllers with the (Controller Configuration Tool ) CCT software. The controller can be connected using NxE Passthru, Bluetooth (using BTCVT), or through MAP 4.2+/ BACnet Router (Mobile Access Portal (MAP) Gateway at version 4.2 or above). Refer to Controller Tool Help (LIT-12011147) for detailed information on commissioning field controllers. Beginning at CCT Release 13, the firmware package files are orderable separately; they are not included with CCT. They are obtained from the Metasys software licensing portal, and are loaded and licensed on the computer/server that is running CCT. .
Note: The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.

Firmware Package File

The MS-FCP-0 equipment controller firmware package files are required for CCT to configure and commission the controllers. The firmware package files also allow you to upgrade an existing controller to the latest firmware release available for that controller.
Beginning at CCT Release 13, the firmware package files are orderable separately; they are not included with CCT. They are obtained from the Metasys
FAC3613 Advanced Application Field Equipment Controller Installation Guide20

LED status and states

Table 7: Status LEDs and description of LED states
LED label LED color Normal LED state Description of LED states
Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse is
POWER Green On Steady
FAULT Red Off Steady
SA BUS Green Blink - 2 Hz
FC BUS Green Blink - 2 Hz
Off (Except on
EOL Amber
terminating devices)
open. Check Output wiring for short circuits and cycle power to controller. On Steady = Power Connected
2 blinks followed by long pause = Controller powered on in default state. For more information about this default state, see Input/Output Wiring Validation.
Off Steady = No Faults On Steady = Device Fault; no application loaded; Main Code download required,
if controller is in Boot mode or a firmware mismatch exists between the and the ZFR1811 Wireless Field Bus Router..
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported) On Steady = Communication lost, waiting to join communication ring
Blink - 2 Hz = Data Transmission (normal communication) Off Steady = No Data Transmission (auto baud in progress) On Steady = Communication lost, waiting to join communication ring
On Steady = EOL switch in ON position Off Steady = EOL switch in Off position

Repair information

If controller fails to operate within its specifications, replace the controller. For a replacement controller, contact your Johnson Controls representative.
FAC3613 Advanced Application Field Equipment Controller Installation Guide 21

Accessories ordering information

Table 8: Accessories Ordering Information
Product Code Number Description
IOM Series Controllers
Mobile Access Portal (MAP) Gateway
TL-CCT-0 Metasys Controller Configuration Tool (CCT) Software MS-FCP-0 Metasys Equipment Controller Firmware Package Files for CCT MS-DIS1710-0 Local Controller Display NS Series Network
Sensors TP-2420 Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
Y65T31-0
AS-XFR050-0
AS-CBLTSTAT-0 Cable adapter for connecting to 8-pin TE-6700 Series sensors AP-TBK4SA-0 Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10 AP-TBK4FC-0 Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10 AP-TBK3PW-0 Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack of 10 WNC1800/ZFR182x
Pro Wireless field Bus System
ZFR1800 Series Wireless Field Bus System
WRZ Series Wireless Room Sensors
Refer to the Metasys® System Field Equipment Controllers and Related Products Product Bulletin (LIT-12011042) for a complete list of available IOM Series Controllers.
Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the appropriate product for your region.
Note: The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.
Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specific sensor model descriptions.
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in. Primary Leads and Secondary Screw Terminals, Class 2
Note: Additional Y6x-x Series transformers are also available. Refer to the Series Y63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755)
for more information.Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure for more information.
This system is used for installations that support BACnet/IP but can also coexist with the ZFR1800 Series when installed under the same supervisor (i.e., network engine). Refer to the WNC1800/ZFR182x Pro Series Wireless Field Bus System Product Bulletin (LIT-12012320) for a list of available products.
This system is used for installations that only support BACnet MS/TP. Refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin (LIT-12011336) for a list of available products.
Refer to the WRZ Series Wireless Room Sensors Product Bulletin (LIT-12000653) for specific sensor model descriptions.
FAC3613 Advanced Application Field Equipment Controller Installation Guide22

Technical specifications

Table 9: FAC3613 Advanced Application Field Equipment Controller
Product Code Numbers MS-FAC3613-0 Advanced Application Field Equipment Controller with Fast Persistence
Power Requirement
Power Consumption
Power Source
Ambient Conditions
Controller Addressing for BACnet MS/TP
Controller Addressing for N2 DIP switch set; valid control device addresses 1-254
Communications Bus
Processor RX631 32-Bit Renesas® microcontroller Memory 16 MB flash memory and 8 MB RAM
Real-Time Clock Backup Power Supply
Input and Output Capabilities
Analog Input/Analog Output Resolution and Accuracy
Terminations
Mounting
Housing
Dimensions (Height x Width x Depth)
Weight 0.5 kg (1.1 lb)
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
14 VA maximum
Note: The VA rating does not include any power supplied to the peripheral devices connected to binary outputs (BOs) or configurable outputs (COs), which can consume up to 12 VA for each BO or CO; for a possible total consumption of an additional 72 VA (maximum).
+15 VDC power source terminals provide 100 mA total current. Quantity 2 located in Universal IN terminals - for active (3-wire) input devices
Operating: 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing Storage: -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and 128–255 are reserved and not valid controller addresses.)
Selectable N2 or BACnet® MS/TP, RS-485:
3-wire FC Bus between the supervisory controller and field controllers 4-wire SA Bus between field controller, network sensors and other sensor/actuator
devices, includes a lead to source 15 VDC supply power (from field controller) to bus devices.
Super capacitor maintains power to the onboard real-time clock for a minimum of 72 hours when supply power to the controller is disconnected.
8 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohms, or Binary Dry Contact 6 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator
Mode
6 - Binary Outputs: Defined as 24 VAC Triac (external power source only) 6 - Analog Outputs: Defined as 0–10 VDC or 4–20 mA
Input: 15-bit resolution Output: 15-bit resolution, +/- 200 mV accuracy in 0–10 VDC applications
Input/Output: Fixed Screw Terminal Blocks SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks SA/FC Bus Port: RJ-12 6-Pin Modular Jacks
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface with three integral mounting clips on controller
Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing Protection Class: IP20 (IEC529)
150 mm x 220 mm x 57.5 mm (5-7/8 in. x 8-3/4 in. x 2-3/8 in.) including terminals and mounting clips
Note: Mounting space requires an additional 50 mm (2 in.) space on top, bottom, and front face of controller for easy cover removal, ventilation, and wire terminations.
FAC3613 Advanced Application Field Equipment Controller Installation Guide 23
Table 9: FAC3613 Advanced Application Field Equipment Controller
Compliance
United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No. 205, Signal Equipment Industry Canada Compliant, ICES-003
Europe: Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant BACnet International: BACnet Testing Laboratories™ (BTL) Protocol Revision 15 Listed
and Certified BACnet Advanced Application Controller (B-AAC), based on the ANSI/ASHRAE 135-2016
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.

Product warranty

This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty.

Single point of contact

APAC Europe NA/SA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 32 CHANGJIJANG RD NEW DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
For more contact information, refer to www.johnsoncontrols.com/locations.
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice.
www.johnsoncontrols.com
Loading...