Johnson Controls FAC2612-1 Installation Manual

FAC2612-1 Advanced Application Field
Equipment Controller Installation Guide

Application

The FAC2612-1 Advanced Application Field Equipment Controller (FAC) is part of the Metasys® system Field Equipment Controller family. The FAC26 Series controllers run pre-engineered and user­programmed applications and provide the inputs and outputs required to monitor and control a wide variety of HVAC equipment.
FAC26 field controllers operate on an RS-485 BACnet® MS/TP Bus as BACnet Advanced Application Controllers (B-AACs) integrate into Johnson Controls® and third-party BACnet systems.
FAC26 controllers include an integral real-time clock, which enables the controllers to monitor and control schedules, calendars, and trends, and operate for extended periods of time as stand-alone controllers when offline from the system network.

Switchable communications protocols

By default, the Metasys system FEC Family Controllers and network sensors communicate using the standard BACnet protocol based on the ANSI/ ASHRAE 135-2008. The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building controls.
FEC, VMA16, and VMA18 are BTL-listed as BACnet Application Specific Controllers (B-ASCs). FAC Field Controllers and the VMA1930 Field Controller are BTL-listed as BACnet Advanced Application Controllers (B-AACs). The NS Series Sensors are BTL­listed as BACnet Smart Sensors (B-SSs).
Release 10.1 and later of the Controller Configuration Tool (CCT) can be used to switch the Field Bus communications protocol in supported FEC Family Field Controllers to be either the standard BACnet MS/TP or the N2 protocol. All new controllers use BACnet MS/TP as the default communications protocol. Switchable communications protocols in the MS/TP models provide a cost-effective upgrade and modernization path for customers with existing N2 controllers.
Part No. 24-10143-195 Rev. L
2019-10-18
The N2-capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers. The N2-capable FEC Family Controllers:
• have the input and output (I/O) quantities and characteristics of the FEC Family Controllers
• must be programmed with CCT
• support SA Bus devices
• support WRZ wireless sensors from the controller using the WRZ-7860 receiver (most models)
• are available in Buy American versions (most models)
• are listed for UL 864 UUKL/ORD-C100-13 UUKLC 10th Edition Smoke Control (some models). N2 is now supported as part of the Metasys 10th Edition listing for Smoke Control System Equipment. For details, refer to the Metasys System UL 864 10th
Edition UUKL/ORD-C100-13 UUKLC Smoke Control System Technical Bulletin (LIT-12012487).
The N2-capable controllers:
• do not support Zone Bus (for example, TMZ sensors and M100 actuators) or XT-Bus (System
91) devices (for example, XT, XTM, and XP modules)
• do not support a wireless connection to the N2 bus
• do not support NxE passthrough

North American emissions compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area
*2410143195L*
(barcode for factory use only)
MS-FAC2612-1
may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Observe these guidelines when installing a field controller
• Transport the controller in the original container to minimize vibration and shock damage.
• Verify that all parts shipped with the controller.
• Do not drop the controller or subject it to physical shock.

Parts included

• One field controller with removable terminal blocks
• One installation instructions sheet

Materials and special tools needed

• Three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
• One 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only)
• Small straight-blade screwdriver for securing wires in the terminal blocks
FAC2612-1 Advanced Application Field Equipment Controller Installation Guide2

FAC2612-1 physical features

Figure 1: FAC2612-1 physical features
Table 1: FAC2612-1 physical features
Physical feature: description and references
1 Configurable Output (COs) Terminal Blocks. See Table 2. 2 SPDT Relay Terminal Blocks. See Table 2. 3 Mounting Clips. See Figure 3. 4 SPST Relay Terminal Blocks. See Table 2.
24 VAC, Class 2 Supply Power Terminal Block. See Supply
5
power terminal block.
6 Cover Lift Tab
Field Controller (FC) Bus Terminal Block. See FC bus
7
terminal block.
Sensor Actuator (SA) Bus Terminal Block. See SA bus
8
terminal block.
Sensor Actuator (SA) Bus Port (RJ-12 6-pin Modular Jack).
9
See SA Bus port. Binary Input (BI) Terminal Blocks. Dry Contact Maintained
10
or Pulse Counter/Accumulator Mode. See Table 2. Universal Inputs (UI) Terminal Blocks. Can be defined as
Voltage Analog Input (0–10 VDC), Current Analog Input
11
(4–20 mA), Resistive Analog Inputs (0–600k ohm), or Dry Contact Binary Input. See Table 2.
Current Loop Mode DIP Switch Block for Universal Inputs that are defined as Current Analog Input (4–20 mA) in
12
the system software. See Setting the UI current loop DIP
switches.
Table 1: FAC2612-1 physical features
Physical feature: description and references
End-of-Line (EOL) Switch. See Setting the End-of-Line
13
(EOL) switch.
14 LED Status Indicators. See Table 8.
Field Controller (FC) Bus Port (RJ-12 6-pin Modular Jack).
15
See FC bus port. Device Address DIP Switch Block. See Setting the device
16
addresses.

Mounting

Observe these guidelines when mounting a field controller:
• Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
• Mount the controller horizontally on 35 mm DIN rail whenever possible.
• Mount the controller in the proper mounting position (Figure 2).
• Mount the controller on a hard, even surface whenever possible in wall-mount applications.
FAC2612-1 Advanced Application Field Equipment Controller Installation Guide 3
• Use shims or washers to mount the controller securely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions requirements in Table 10.
• Provide for sufficient space around the controller for cable and wire connections for easy cover removal and good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
• Do not mount the controller on surfaces prone to vibration, such as duct work.
• Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can interfere with controller communication.
Observe these additional guidelines when mounting a field controller in a panel or enclosure:
• Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller.
• Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller.
• Do not install the controller in an airtight enclosure.
1. Securely mount a 20 cm (8 in.) or longer section of 35 mm DIN rail horizontal and centered in the desired space so that the controller mounts in the horizontal position shown in Figure 2.
2. Pull the two bottom mounting clips outward from the controller to the extended position (Figure 3).
3. Hang the controller on the DIN rail by the hooks at the top of the (DIN rail) channel on the back of the controller (Figure 3), and position the controller snugly against the DIN rail.
4. Push the bottom mounting clips inward (up) to secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail.

Wall mount applications

To mount a field controller directly on a wall or other flat vertical surface:
1. Pull the two bottom mounting clips outward and ensure they are locked in the extended position as shown in Figure 3.
Figure 2: Field Controller mounting positions

DIN rail mount applications

Mounting the field controller horizontal on 35 mm DIN rail is the preferred mounting method. To mount a field controller on 35 mm DIN rail:
2. Mark the mounting hole locations on the wall using the dimensions in Figure 3 and one of the mount positions shown in Figure 2. Or hold the controller up to the wall or surface in a proper mount position and mark the hole locations through the mounting clips.
3. Drill holes in the wall or surface at the marked locations, and insert appropriate wall anchors in the holes (if necessary).
4. Hold the controller in place, and insert the screws through the mounting clips and into the holes (or anchors). Carefully tighten all of the screws.
Important: Do not overtighten the mounting screws. Overtightening the screws may damage the mounting clips.
FAC2612-1 Advanced Application Field Equipment Controller Installation Guide4

Mounting features and dimensions

Figure 3: Back of Controller showing extended mounting clips, DIN rail channel, and mounting dimensions, mm (in.)

Wiring

Warning
ATTENTION
Risque de dégâts matériels
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils for­mant un court-circuit ou connectés de façon incor­recte risquent d'endommager irrémédiablement l'équipement.
Important: Do not exceed the controller electrical ratings. Exceeding controller electrical ratings can result in permanent damage to the controller and void any warranty.
Important: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations.
Important: Electrostatic discharge can damage controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
For detailed information on configuring and wiring an MS/TP Bus, FC bus, and SA bus, refer to the MS/TP Communications Bus Technical Bulletin
(LIT-12011034).
Risk of Electric Shock
Disconnect the power supply before making electrical connections to avoid electric shock
Avertissement
Risque de décharge électrique
Débrancher l'alimentation avant de réaliser tout rac­cordement électrique afin d'éviter tout risque de décharge électrique.
CAUTION
Risk of Property Damage
Do not apply power to the system before checking all wiring connections. Short circuited or improperly con­nected wires may result in permanent damage to the equipment.

FAC terminal blocks and bus ports

See FAC2612-1 physical features for terminal block and bus port locations on the FAC2612-1 controller. Observe the following guidelines when wiring a controller.

Input and Output terminal blocks

On most field controller models, all of the input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are mounted on the top of the controller. See Table 2 for more information about I/O terminal functions, requirements, and ratings.

FC bus terminal block

The FC Bus terminal block is a blue, removable, 4­terminal plug that fits into a board-mounted jack.
Wire the removable FC bus terminal block plugs on the controller, and other controllers in a daisy-chain configuration using 3-wire twisted, shielded cable as shown in Figure 4. See Table 4 for more information.
FAC2612-1 Advanced Application Field Equipment Controller Installation Guide 5
Figure 4: FC bus terminal block wiring
Note: The FC bus Shield (SHLD) terminal is
isolated and can be used to connect (daisy chain) the shields for FC bus wiring.

SA bus terminal block

Note: The SA PWR terminal supplies 15 VDC. The SA PWR terminal can be used to connect (daisy chain) the 15 VDC power leads on the SA bus.

FC bus port

The FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for the Bluetooth® Commissioning Converter, or a ZFR/ZFR Pro Wireless Field Bus Router.
The FC bus port is connected internally to the FC bus terminal block. See Table 4 for more information. The FC bus port pin assignment is shown in Figure .
Figure 6: Pin number assignments for sensor, SA bus, and FC bus ports on Controllers
The SA Bus terminal block is a brown, removable, 4­terminal plug that fits into a board-mounted jack.
Wire the removable SA Bus terminal block plugs on the controller, and other SA bus devices in a daisy­chain configuration using 4-wire twisted, shielded cable as shown in Figure 5. See Table 4 for more information.
Figure 5: SA bus terminal block wiring

SA Bus port

The Sensor (SA Bus) port on the bottom of the controller (Figure 1) is an RJ-12, 6-position modular jack that provides a connection for the Bluetooth Commissioning Converter, the VAV Balancing Tool, specified network sensors, or other SA Bus devices with RJ-12 plugs.
A DIS1710 Local Controller Display also can be connected to the SA Bus port.
The Sensor port is connected internally to the SA bus terminal block. See Table 4 for more information. The Sensor Port pin assignment is shown in Figure 6.

Supply power terminal block

The 24 VAC supply power terminal block is a gray, removable, 3-terminal plug that fits into a board­mounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure . The middle terminal on the supply power terminal block is not
FAC2612-1 Advanced Application Field Equipment Controller Installation Guide6
used. See Table 4 for more information about the Supply Terminal Block.
Figure 7: 24 VAC supply power terminal block wiring
2. Connect the ZFR/ZFR Pro Wireless Field Bus Router to the FC bus port (RJ-12 modular jack) on the front of the controller.
3. Ensure that the controller's device address DIP switches are set to the correct device address. See Setting the device addresses.
4. Set DIP switch 128 to ON, which enables wireless operation on the controller.
For more information on the ZFR Pro Wireless Field Bus system, refer to the WNC1800/ZFR182x
Pro Series Wireless Field Bus System Product Bulletin (LIT-12012320).
For more information on the ZFR 1800 Wireless Field Bus system, refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin (LIT-12011336).
Terminal Wiring Guidelines, Functions, Ratings, and
Note: The supply power wire colors may be different on transformers from other manufacturers. Refer to the transformer manufacturer’s instructions and the project installation drawings for wiring details.
Important: Connect 24 VAC supply power to the field controller and all other network devices so that transformer phasing is uniform across the network devices. Powering network devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop problems. The field controller does not require an earth ground connection.

Wireless network applications

When configured for BACNet MS/TP communication, the controller can also be installed in a wireless application using a ZFR/ZFR Pro Wireless Field Bus Router. To configure a controller for use with the ZFR/ZFR Pro Series Wireless Field Bus system:
1. Wire the input/output terminals and SA bus.
Requirements

Input and Output wiring guidelines

Table 2 provides information and guidelines about the functions, ratings, and requirements for the controller input and output terminals; and references guidelines for determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in Table 2, observe these guidelines when wiring controller inputs and outputs:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All input and output cables, regardless of wire
size or number of wires, should consist of stranded, insulated, and twisted copper wires.
• Shielded cable is not required for input or output
cables.
• Shielded cable is recommended for input
and output cables that are exposed to high electromagnetic or radio frequency noise.
Note: In wireless network applications, do not connect any wires to the FC bus terminal block. (Connect the SA/FC terminal block on an IOM to an SA bus only).
FAC2612-1 Advanced Application Field Equipment Controller Installation Guide 7
• Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software setup. Cable runs over 30 m (100 ft) may require an offset in the input/output software setup.

FAC2612-1 I/O wiring ratings and requirements table

Table 2: Field Controller terminal blocks, functions, ratings, requirements, and cables
Terminal block label
UNIVERSAL
(Inputs)
BINARY
(Inputs)
Terminal label
+15 V
+5 V
INn
ICOMn
INn
ICOMn
Function, ratings, requirements
15 VDC Power Source for active (3-wire) input devices
connected to the Universal INn terminals. Provides 100 mA total current
5 VDC Power Source for active (3-wire) input devices connected to the Universal INn terminals.
Provides 40 mA total current.
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage Internal 75k ohm Pull-down
Analog Input - Current Mode (4–20 mA)
Internal 100 ohm load impedance
Note: A current loop fail-safe jumper can be positioned to maintain a closed 4 to 20 mA current loop, even when the power to the controller is interrupted or off. See
Setting the UI current loop DIP switches.
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V. 15k ohm pull up Qualified Sensors: 0–2k ohm potentiometer RTD (1k Nickel [ Johnson Controls sensor] 1k Platinum, and
A99B Silicon Temperature Sensor) Negative Temperature Coefficient (NTC) Sensor (10k Type L,
10k JCI Type II, 2.252k Type II)
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width Internal 12 V. 15k ohm pull up
Universal Input Common for all Universal Input terminals
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width Internal 18 V 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width (50 Hz at 50% duty cycle) Internal 18 V 3k ohm pull up
Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons, except the Configurable Output (CO) common (OCOMn) when the CO is defined as an Analog Output.
Determine wire size and maximum cable length
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power from the +15V terminal.
Same as (Universal) INn.
Note: Use 3-wire cable for devices that source power from the +5 V terminal.
See Guideline A in Table 3.
See Guideline B in Table 3.
See Guideline A in Table 3.
See Guideline A in Table 3.
Same as (Universal) INn
See Guideline A in Table 3.
FAC2612-1 Advanced Application Field Equipment Controller Installation Guide8
Loading...
+ 16 hidden pages