f61s_low whole 1922340 9thcc:2-93 Electric Switches
F61 Series
Flow Switch (Low Flow Rate – SPDT)
f61kd.tif
F61KD-4
Description
For use on liquid lines using water, ethylene
glycol solutions, or other liquids not injurious
to the brass and phosphor bronze parts. The
SPDT contact switch is activated by a low flow
rate; however, it has a large flow capacity with
a minimum pressure drop.
Selection Chart
Code
Number
F61KD-3C 1/2 x 1/2 in. (13 x 13 m m) 1
F61KD-4C 3/4 x 3/4 in. (19 x 19 m m) 1
★
F61KD-8C 3/4 x 3/4 in. (19 x 19 mm) 1
F61MD-1C 1/2 x 1/2 in. (13 x 13 mm) 3R
★
F61MD-2C 3/4 x 3/4 in. (19 x 19 mm) 3R
Inlet and Outlet
Size Female NPT
Enclosure
Applications
Typical applications include:
• water purification and treatment systems
• booster pumps
• fast shutdown on high input boilers to guard
against circulation failure
• cooling systems for electronic tubes,
bearings, and compressors
Dimensions
Height: 5-1/32 in. (127 mm)
Width: 4 in. (102 mm)
Depth: 2-13/16 in. (71 mm)
To Order
Specify the code number from the following
selection chart.
Adjustment Range –
NEMA
Type
R to Y Closes
Flow Increase
Minimum 0.6 (2.27)
Maximum 1.1 (4.17)
Minimum 8.5 (32.2)
Maximum 9.0 (34.1)
Minimum 0.6 (2.27)
Maximum 1.1 (4.17)
Minimum 0.6 (2.27)
Maximum 1.1 (4.17)
GPM (L/Min)
R to Y Opens
Flow Decrease
Minimum 0.3 (1.14)
Maximum 0.9 (3.4)
Minimum 4.5 (17.1)
Maximum 6.3 (23.9)
Minimum 0.3 (1.14)
Maximum 0.9 (3.4)
Minimum 0.3 (1.14)
Maximum 0.9 (3.4)
Electrical Ratings
Motor Rat ings
VAC
Horsepower 1 1 1 –
AC Full Load Amp 16.0 8.8 8.0 –
AC Locked Rotor
Amp
Non-Inductive or
Resistance Load
Amp
Pilot Duty – 125 VA, 24/277 VAC
Maximum
Liquid Temp
250°F
(121°C)
120
208
VAC
240
VAC
Maximum
Pressure
150 psig
(1034 kPa)
VAC
96.0 52.8 48.0 –
16 16 16 16
Minimum
Liquid Temp
32°F
(0°C)
-20°F
(-29°C)
277
VAC
Liquid
▲
Universal Replacement ★ Non-Stock Item. Built to Order.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
1/1
© 12/01 Johnson Controls, Inc