EM-4000 Series Meters
Installation and Operation Manual
This page intentionally left blank.
EM-4000 Series Meters Installation and Operation Manual
Published by:
Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
All rights reserved. No part of this publication may be reproduced or transmitted in
any form or by any means, electronic or mechanical, including photocopying, recording, or information storage or retrieval systems or any future forms of duplication, for
any purpose other than the purchaser's use, without the expressed written permission
of Johnson Controls, Inc.
Modbus® is a registered trademark of Schneider Electric, licensed to the Modbus
Organization, Inc.
EM-4000 Series Meters Installation and Operation Manual i
This page intentionally left blank.
EM-4000 Series Meters Installation and Operation Manual ii
Use of Product for Protection
Our products are not to be used for primary over-current protection. Any protection
feature in our products is to be used for alarm or secondary protection only.
Statement of Calibration
Our instruments are inspected and tested in accordance with specifications published
by Johnson Controls, Inc. The accuracy and a calibration of our instruments are traceable to the National Institute of Standards and Technology through equipment that is
calibrated at planned intervals by comparison to certified standards. For optimal
performance, Johnson Controls, Inc. recommends that any meter be verified for
accuracy on a yearly interval using NIST traceable accuracy standards.
Disclaimer
The information presented in this publication has been carefully checked for
reliability; however, no responsibility is assumed for inaccuracies. The information
contained in this document is subject to change without notice.
This symbol indicates that the operator must refer to an explanation in
the operating instructions. Please see Chapter 4 for important safety
information regarding installation and hookup of the EM-4000 meter.
Dans ce manuel, ce symbole indique que l’opérateur doit se référer à un important
AVERTISSEMENT ou une MISE EN GARDE dans les instructions opérationnelles. Veuillez consulter le chapitre 4 pour des informations importantes relatives à l’installation
et branchement du compteur.
The following safety symbols may be used on the meter itself:
Les symboles de sécurité suivante peuvent être utilisés sur le compteur même:
This symbol alerts you to the presence of high voltage, which can
cause dangerous electrical shock.
Ce symbole vous indique la présence d’une haute tension qui peut
provoquer une décharge électrique dangereuse.
This symbol indicates the field wiring terminal that must be connected
to earth ground before operating the meter, which protects against
electrical shock in case of a fault condition.
Ce symbole indique que la borne de pose des canalisations in-situ qui doit être
EM-4000 Series Meters Installation and Operation Manual iii
branchée dans la mise à terre avant de faire fonctionner le compteur qui est protégé
contre une décharge électrique ou un état défectueux.
This symbol indicates that the user must refer to this manual for
specific WARNING or CAUTION information to avoid personal injury or
damage to the product.
Ce symbole indique que l'utilisateur doit se référer à ce manuel pour AVERTISSEMENT
ou MISE EN GARDE l'information pour éviter toute blessure ou tout endommagement
du produit.
EM-4000 Series Meters Installation and Operation Manual iv
Table of Contents
Use of Product for Protection iii
Statement of Calibration iii
Disclaimer iii
1: Three-Phase Power Measurement 1-1
1.1: Three-Phase System Configurations 1-1
1.1.1: Wye Connection 1-1
1.1.2: Delta Connection 1-4
1.1.3: Blondel’s Theorem and Three Phase Measurement 1-6
Table of Contents
1.2: Power, Energy and Demand 1-8
1.3: Reactive Energy and Power Factor 1-12
1.4: Harmonic Distortion 1-14
1.5: Power Quality 1-17
2: Meter Overview and Specifications 2-1
2.1: EM-4000 Meter Overview 2-1
2.1.1: Voltage and Current Inputs 2-2
2.1.2: Ordering Information 2-3
2.1.4: Measured Values 2-5
2.1.5: Utility Peak Demand 2-6
2.2: Specifications 2-7
2.3: Compliance 2-12
2.4: Accuracy 2-13
3: Mechanical Installation 3-1
EM-4000 Series Meters Installation and Operation Manual TOC - 1
Table of Contents
3.1: Introduction 3-1
3.2: ANSI Installation Steps 3-3
3.3: DIN Installation Steps 3-4
4: Electrical Installation 4-1
4.1: Considerations When Installing Meters 4-1
4.2: CT Leads Terminated to Meter 4-4
4.3: CT Leads Pass Through (No Meter Termination) 4-6
4.4: Quick Connect Crimp-on Terminations 4-7
4.5: Voltage and Power Supply Connections 4-8
4.6: Ground Connections 4-8
4.7: Voltage Fuses 4-9
4.8: Electrical Connection Diagrams 4-10
5: Communication Installation 5-1
5.1: EM-4000 Series Meter Communication 5-1
5.1.1: IrDA Port (Com 1) 5-1
5.1.2: RS485 / KYZ Output (Com 2) 5-1
6: Using the EM-4000 Meter 6-1
6.1: Introduction 6-1
6.1.1: Understanding Meter Face Elements 6-1
6.1.2: Understanding Meter Face Buttons 6-2
6.2: Using the Front Panel 6-3
6.2.1: Understanding Startup and Default Displays 6-3
6.2.2: Using the Main Menu 6-4
EM-4000 Series Meters Installation and Operation Manual TOC - 2
Table of Contents
6.2.3: Using Reset Mode 6-5
6.2.4: Entering a Password 6-6
6.2.5: Using Configuration Mode 6-7
6.2.5.1: Configuring the Scroll Feature 6-9
6.2.5.2: Configuring CT Setting 6-10
6.2.5.3: Configuring PT Setting 6-11
6.2.5.4: Configuring Connection Setting 6-13
6.2.5.5: Configuring Communication Port Setting 6-13
B.5: Important Note Concerning the EM-4000 Meter's
Modbus® Map B-3
EM-4000 Series Meters Installation and Operation Manual TOC - 3
Table of Contents
B.5.1: Hex Representation B-3
B.6: Modbus® Register Map (MM-1 to MM-37) B-3
C: Using the USB to IrDA Adapter (CAB6490) C-1
C.1: Introduction C-1
C.2: Installation Procedures C-1
EM-4000 Series Meters Installation and Operation Manual TOC - 4
1: Three-Phase Power Measurement
1: Three-Phase Power Measurement
This introduction to three-phase power and power measurement is intended to
provide only a brief overview of the subject. The professional meter engineer or meter
technician should refer to more advanced documents such as the EEI Handbook for
Electricity Metering and the application standards for more in-depth and technical
coverage of the subject.
1.1: Three-Phase System Configurations
Three-phase power is most commonly used in situations where large amounts of
power will be used because it is a more effective way to transmit the power and
because it provides a smoother delivery of power to the end load. There are two
commonly used connections for three-phase power, a wye connection or a delta
connection. Each connection has several different manifestations in actual use.
When attempting to determine the type of connection in use, it is a good practice to
follow the circuit back to the transformer that is serving the circuit. It is often not
possible to conclusively determine the correct circuit connection simply by counting
the wires in the service or checking voltages. Checking the transformer connection
will provide conclusive evidence of the circuit connection and the relationships
between the phase voltages and ground.
1.1.1: Wye Connection
The wye connection is so called because when you look at the phase relationships and
the winding relationships between the phases it looks like a Y. Figure 1.1 depicts the
winding relationships for a wye-connected service. In a wye service the neutral (or
center point of the wye) is typically grounded. This leads to common voltages of 208/
120 and 480/277 (where the first number represents the phase-to-phase voltage and
the second number represents the phase-to-ground voltage).
EM-4000 Series Meters Installation and Operation Manual 1-1
1: Three-Phase Power Measurement
V
A
Phase 3
Phase 2
V
B
Figure 1.1: Three-phase Wye Winding
The three voltages are separated by 120o electrically. Under balanced load conditions
the currents are also separated by 120
conditions can cause the currents to depart from the ideal 120
V
C
N
Phase 1
o
. However, unbalanced loads and other
V
A
o
separation. Threephase voltages and currents are usually represented with a phasor diagram. A phasor
diagram for the typical connected voltages and currents is shown in Figure 1.2.
V
C
I
C
N
I
A
I
V
B
Figure 1.2: Phasor Diagram Showing Three-phase Voltages and Currents
B
EM-4000 Series Meters Installation and Operation Manual 1-2
1: Three-Phase Power Measurement
The phasor diagram shows the 120o angular separation between the phase voltages.
The phase-to-phase voltage in a balanced three-phase wye system is 1.732 times the
phase-to-neutral voltage. The center point of the wye is tied together and is typically
grounded. Table 1.1 shows the common voltages used in the United States for wyeconnected systems.
Phase to Ground VoltagePhase to Phase Voltage
120 volts208 volts
277 volts480 volts
2,400 volts4,160 volts
7,200 volts12,470 volts
7,620 volts13,200 volts
Table 1: Common Phase Voltages on Wye Services
Usually a wye-connected service will have four wires: three wires for the phases and
one for the neutral. The three-phase wires connect to the three phases (as shown in
Figure 1.1). The neutral wire is typically tied to the ground or center point of the wye.
In many industrial applications the facility will be fed with a four-wire wye service but
only three wires will be run to individual loads. The load is then often referred to as a
delta-connected load but the service to the facility is still a wye service; it contains
four wires if you trace the circuit back to its source (usually a transformer). In this
type of connection the phase to ground voltage will be the phase-to-ground voltage
indicated in Table 1, even though a neutral or ground wire is not physically present at
the load. The transformer is the best place to determine the circuit connection type
because this is a location where the voltage reference to ground can be conclusively
identified.
EM-4000 Series Meters Installation and Operation Manual 1-3
1.1.2: Delta Connection
V
A
V
B
Delta-connected services may be fed with either three wires or four wires. In a threephase delta service the load windings are connected from phase-to-phase rather than
from phase-to-ground. Figure 1.3 shows the physical load connections for a delta
service.
In this example of a delta service, three wires will transmit the power to the load. In a
true delta service, the phase-to-ground voltage will usually not be balanced because
the ground is not at the center of the delta.
Figure 1.4 shows the phasor relationships between voltage and current on a threephase delta circuit.
In many delta services, one corner of the delta is grounded. This means the phase to
ground voltage will be zero for one phase and will be full phase-to-phase voltage for
Phase 3
the other two phases. This is done for protective purposes.
EM-4000 Series Meters Installation and Operation Manual 1-4
1: Three-Phase Power Measurement
V
A
V
BC
Figure 1.4: Phasor Diagram, Three-Phase Voltages and Currents, Delta-Connected
Another common delta connection is the four-wire, grounded delta used for lighting
loads. In this connection the center point of one winding is grounded. On a 120/240
volt, four-wire, grounded delta service the phase-to-ground voltage would be 120
volts on two phases and 208 volts on the third phase. Figure 1.5 shows the phasor
diagram for the voltages in a three-phase, four-wire delta system.
V
I
C
I
B
V
AB
C
V
CA
I
A
V
CA
V
BC
Figure 1.5: Phasor Diagram Showing Three-phase Four-Wire Delta-Connected System
N
V
AB
V
B
EM-4000 Series Meters Installation and Operation Manual 1-5
1: Three-Phase Power Measurement
1.1.3: Blondel’s Theorem and Three Phase Measurement
In 1893 an engineer and mathematician named Andre E. Blondel set forth the first
scientific basis for polyphase metering. His theorem states:
If energy is supplied to any system of conductors through N wires, the total power in
the system is given by the algebraic sum of the readings of N wattmeters so arranged
that each of the N wires contains one current coil, the corresponding potential coil
being connected between that wire and some common point. If this common point is
on one of the N wires, the measurement may be made by the use of N-1 Wattmeters.
The theorem may be stated more simply, in modern language:
In a system of N conductors, N-1 meter elements will measure the power or energy
taken provided that all the potential coils have a common tie to the conductor in
which there is no current coil.
Three-phase power measurement is accomplished by measuring the three individual
phases and adding them together to obtain the total three phase value. In older analog meters, this measurement was accomplished using up to three separate elements.
Each element combined the single-phase voltage and current to produce a torque on
the meter disk. All three elements were arranged around the disk so that the disk was
subjected to the combined torque of the three elements. As a result the disk would
turn at a higher speed and register power supplied by each of the three wires.
According to Blondel's Theorem, it was possible to reduce the number of elements
under certain conditions. For example, a three-phase, three-wire delta system could
be correctly measured with two elements (two potential coils and two current coils) if
the potential coils were connected between the three phases with one phase in common.
In a three-phase, four-wire wye system it is necessary to use three elements. Three
voltage coils are connected between the three phases and the common neutral conductor. A current coil is required in each of the three phases.
In modern digital meters, Blondel's Theorem is still applied to obtain proper metering.
The difference in modern meters is that the digital meter measures each phase voltage and current and calculates the single-phase power for each phase. The meter
then sums the three phase powers to a single three-phase reading.
EM-4000 Series Meters Installation and Operation Manual 1-6
1: Three-Phase Power Measurement
Phase B
Phase C
Phase A
A
B
C
N
Node "n"
Some digital meters measure the individual phase power values one phase at a time.
This means the meter samples the voltage and current on one phase and calculates a
power value. Then it samples the second phase and calculates the power for the second phase. Finally, it samples the third phase and calculates that phase power. After
sampling all three phases, the meter adds the three readings to create the equivalent
three-phase power value. Using mathematical averaging techniques, this method can
derive a quite accurate measurement of three-phase power.
More advanced meters actually sample all three phases of voltage and current
simultaneously and calculate the individual phase and three-phase power values. The
advantage of simultaneous sampling is the reduction of error introduced due to the
difference in time when the samples were taken.
Figure 1.6: Three-Phase Wye Load Illustrating Kirchhoff’s Law and Blondel’s Theorem
Blondel's Theorem is a derivation that results from Kirchhoff's Law. Kirchhoff's Law
states that the sum of the currents into a node is zero. Another way of stating the
same thing is that the current into a node (connection point) must equal the current
out of the node. The law can be applied to measuring three-phase loads. Figure 1.6
shows a typical connection of a three-phase load applied to a three-phase, four-wire
service. Kirchhoff's Law holds that the sum of currents A, B, C and N must equal zero
or that the sum of currents into Node "n" must equal zero.
If we measure the currents in wires A, B and C, we then know the current in wire N by
Kirchhoff's Law and it is not necessary to measure it. This fact leads us to the
conclusion of Blondel's Theorem- that we only need to measure the power in three of
EM-4000 Series Meters Installation and Operation Manual 1-7
the four wires if they are connected by a common node. In the circuit of Figure 1.6 we
must measure the power flow in three wires. This will require three voltage coils and
three current coils (a three-element meter). Similar figures and conclusions could be
reached for other circuit configurations involving Delta-connected loads.
1.2: Power, Energy and Demand
It is quite common to exchange power, energy and demand without differentiating
between the three. Because this practice can lead to confusion, the differences
between these three measurements will be discussed.
Power is an instantaneous reading. The power reading provided by a meter is the
present flow of watts. Power is measured immediately just like current. In many
digital meters, the power value is actually measured and calculated over a one second
interval because it takes some amount of time to calculate the RMS values of voltage
1: Three-Phase Power Measurement
and current. But this time interval is kept small to preserve the instantaneous nature
of power.
Energy is always based on some time increment; it is the integration of power over a
defined time increment. Energy is an important value because almost all electric bills
are based, in part, on the amount of energy used.
Typically, electrical energy is measured in units of kilowatt-hours (kWh). A kilowatthour represents a constant load of one thousand watts (one kilowatt) for one hour.
Stated another way, if the power delivered (instantaneous watts) is measured as
1,000 watts and the load was served for a one hour time interval then the load would
have absorbed one kilowatt-hour of energy. A different load may have a constant
power requirement of 4,000 watts. If the load were served for one hour it would
absorb four kWh. If the load were served for 15 minutes it would absorb ¼ of that
total or one kWh.
Figure 1.7 shows a graph of power and the resulting energy that would be transmitted
as a result of the illustrated power values. For this illustration, it is assumed that the
power level is held constant for each minute when a measurement is taken. Each bar
in the graph will represent the power load for the one-minute increment of time. In
real life the power value moves almost constantly.
The data from Figure 1.7 is reproduced in Table 2 to illustrate the calculation of
energy. Since the time increment of the measurement is one minute and since we
EM-4000 Series Meters Installation and Operation Manual 1-8
1: Three-Phase Power Measurement
0
10
20
30
40
50
60
70
80
123456789 10 11 12 13 14 15
Time (minutes)
sttawolik
specified that the load is constant over that minute, we can convert the power reading
to an equivalent consumed energy reading by multiplying the power reading times 1/
60 (converting the time base from minutes to hours).
Figure 1.7: Power Use over Time
EM-4000 Series Meters Installation and Operation Manual 1-9
1: Three-Phase Power Measurement
Time
Interval
(minute)
Power
(kW)
Energy
(kWh)
Accumulated
1300.500.50
2500.831.33
3400.672.00
4550.922.92
5601.003.92
6601.004.92
7701.176.09
8701.177.26
9601.008.26
10701.179.43
11801.3310.76
12500.8312.42
13500.8312.42
Energy
(kWh)
14701.1713.59
15801.3314.92
Table 1.2: Power and Energy Relationship over Time
As in Table 1.2, the accumulated energy for the power load profile of Figure 1.7 is
14.92 kWh.
Demand is also a time-based value. The demand is the average rate of energy use
over time. The actual label for demand is kilowatt-hours/hour but this is normally
reduced to kilowatts. This makes it easy to confuse demand with power, but demand
is not an instantaneous value. To calculate demand it is necessary to accumulate the
energy readings (as illustrated in Figure 1.7) and adjust the energy reading to an
hourly value that constitutes the demand.
In the example, the accumulated energy is 14.92 kWh. But this measurement was
made over a 15-minute interval. To convert the reading to a demand value, it must be
normalized to a 60-minute interval. If the pattern were repeated for an additional
three 15-minute intervals the total energy would be four times the measured value or
EM-4000 Series Meters Installation and Operation Manual 1-10
1: Three-Phase Power Measurement
0
20
40
60
80
100
12345678
Intervals (15 mins.)
sruoh-ttawolik
59.68 kWh. The same process is applied to calculate the 15-minute demand value.
The demand value associated with the example load is 59.68 kWh/hr or 59.68 kWd.
Note that the peak instantaneous value of power is 80 kW, significantly more than the
demand value.
Figure 1.8 shows another example of energy and demand. In this case, each bar represents the energy consumed in a 15-minute interval. The energy use in each interval
typically falls between 50 and 70 kWh. However, during two intervals the energy rises
sharply and peaks at 100 kWh in interval number 7. This peak of usage will result in
setting a high demand reading. For each interval shown the demand value would be
four times the indicated energy reading. So interval 1 would have an associated
demand of 240 kWh/hr. Interval 7 will have a demand value of 400 kWh/hr. In the
data shown, this is the peak demand value and would be the number that would set
the demand charge on the utility bill.
As can be seen from this example, it is important to recognize the relationships
between power, energy and demand in order to control loads effectively or to monitor
use correctly.
EM-4000 Series Meters Installation and Operation Manual 1-11
Figure 1.8: Energy Use and Demand
1.3: Reactive Energy and Power Factor
V
I
I
R
I
X
0
The real power and energy measurements discussed in the previous section relate to
the quantities that are most used in electrical systems. But it is often not sufficient to
only measure real power and energy. Reactive power is a critical component of the
total power picture because almost all real-life applications have an impact on reactive power. Reactive power and power factor concepts relate to both load and generation applications. However, this discussion will be limited to analysis of reactive power
and power factor as they relate to loads. To simplify the discussion, generation will
not be considered.
Real power (and energy) is the component of power that is the combination of the
voltage and the value of corresponding current that is directly in phase with the voltage. However, in actual practice the total current is almost never in phase with the
voltage. Since the current is not in phase with the voltage, it is necessary to consider
1: Three-Phase Power Measurement
both the inphase component and the component that is at quadrature (angularly
rotated 90
o
or perpendicular) to the voltage. Figure 1.9 shows a single-phase voltage
and current and breaks the current into its in-phase and quadrature components.
Figure 1.9: Voltage and Complex Current
The voltage (V) and the total current (I) can be combined to calculate the apparent
power or VA. The voltage and the in-phase current (I
real power or watts. The voltage and the quadrature current (I
) are combined to produce the
R
) are combined to cal-
X
culate the reactive power.
The quadrature current may be lagging the voltage (as shown in Figure 1.9) or it may
lead the voltage. When the quadrature current lags the voltage the load is requiring
both real power (watts) and reactive power (VARs). When the quadrature current
EM-4000 Series Meters Installation and Operation Manual 1-12
1: Three-Phase Power Measurement
Displacement PFcos=
leads the voltage the load is requiring real power (watts) but is delivering reactive
power (VARs) back into the system; that is VARs are flowing in the opposite direction
of the real power flow.
Reactive power (VARs) is required in all power systems. Any equipment that uses
magnetization to operate requires VARs. Usually the magnitude of VARs is relatively
low compared to the real power quantities. Utilities have an interest in maintaining
VAR requirements at the customer to a low value in order to maximize the return on
plant invested to deliver energy. When lines are carrying VARs, they cannot carry as
many watts. So keeping the VAR content low allows a line to carry its full capacity of
watts. In order to encourage customers to keep VAR requirements low, some utilities
impose a penalty if the VAR content of the load rises above a specified value.
A common method of measuring reactive power requirements is power factor. Power
factor can be defined in two different ways. The more common method of calculating
power factor is the ratio of the real power to the apparent power. This relationship is
expressed in the following formula:
Total PF = real power / apparent power = watts/VA
This formula calculates a power factor quantity known as Total Power Factor. It is
called Total PF because it is based on the ratios of the power delivered. The delivered
power quantities will include the impacts of any existing harmonic content. If the voltage or current includes high levels of harmonic distortion the power values will be
affected. By calculating power factor from the power values, the power factor will
include the impact of harmonic distortion. In many cases this is the preferred method
of calculation because the entire impact of the actual voltage and current are
included.
A second type of power factor is Displacement Power Factor. Displacement PF is based
on the angular relationship between the voltage and current. Displacement power factor does not consider the magnitudes of voltage, current or power. It is solely based
on the phase angle differences. As a result, it does not include the impact of harmonic
distortion. Displacement power factor is calculated using the following equation:
EM-4000 Series Meters Installation and Operation Manual 1-13
where is the angle between the voltage and the current (see Fig. 1.9).
Time
Amps
– 1000
– 500
0
500
1000
In applications where the voltage and current are not distorted, the Total Power Factor
will equal the Displacement Power Factor. But if harmonic distortion is present, the
two power factors will not be equal.
1.4: Harmonic Distortion
Harmonic distortion is primarily the result of high concentrations of non-linear loads.
Devices such as computer power supplies, variable speed drives and fluorescent light
ballasts make current demands that do not match the sinusoidal waveform of AC
electricity. As a result, the current waveform feeding these loads is periodic but not
sinusoidal. Figure 1.10 shows a normal, sinusoidal current waveform. This example
has no distortion.
1: Three-Phase Power Measurement
Figure 1.10: Nondistorted Current Waveform
Figure 1.11 shows a current waveform with a slight amount of harmonic distortion.
The waveform is still periodic and is fluctuating at the normal 60 Hz frequency.
However, the waveform is not a smooth sinusoidal form as seen in Figure 1.10.
EM-4000 Series Meters Installation and Operation Manual 1-14
1: Three-Phase Power Measurement
–1000
–500
0
500
1000
t
)spma( tnerruC
a
2a
–1500
1500
Time
Amps
3rd harmonic
5th harmonic
7th harmonic
Total
fundamental
– 500
0
500
1000
Figure 1.11: Distorted Current Waveform
The distortion observed in Figure 1.11 can be modeled as the sum of several sinusoidal waveforms of frequencies that are multiples of the fundamental 60 Hz frequency.
This modeling is performed by mathematically disassembling the distorted waveform
into a collection of higher frequency waveforms.
These higher frequency waveforms are referred to as harmonics. Figure 1.12 shows
the content of the harmonic frequencies that make up the distortion portion of the
waveform in Figure 1.11.
Figure 1.12: Waveforms of the Harmonics
EM-4000 Series Meters Installation and Operation Manual 1-15
1: Three-Phase Power Measurement
The waveforms shown in Figure 1.12 are not smoothed but do provide an indication of
the impact of combining multiple harmonic frequencies together.
When harmonics are present it is important to remember that these quantities are
operating at higher frequencies. Therefore, they do not always respond in the same
manner as 60 Hz values.
Inductive and capacitive impedance are present in all power systems. We are accustomed to thinking about these impedances as they perform at 60 Hz. However, these
impedances are subject to frequency variation.
X
= jL and
L
= 1/jC
X
C
At 60 Hz, = 377; but at 300 Hz (5th harmonic) = 1,885. As frequency changes
impedance changes and system impedance characteristics that are normal at 60 Hz
may behave entirely differently in the presence of higher order harmonic waveforms.
Traditionally, the most common harmonics have been the low order, odd frequencies,
such as the 3rd, 5th, 7th, and 9th. However newer, non-linear loads are introducing
significant quantities of higher order harmonics.
Since much voltage monitoring and almost all current monitoring is performed using
instrument transformers, the higher order harmonics are often not visible. Instrument
transformers are designed to pass 60 Hz quantities with high accuracy. These devices,
when designed for accuracy at low frequency, do not pass high frequencies with high
accuracy; at frequencies above about 1200 Hz they pass almost no information. So
when instrument transformers are used, they effectively filter out higher frequency
harmonic distortion making it impossible to see.
However, when monitors can be connected directly to the measured circuit (such as
direct connection to a 480 volt bus) the user may often see higher order harmonic
distortion. An important rule in any harmonics study is to evaluate the type of equipment and connections before drawing a conclusion. Not being able to see harmonic
distortion is not the same as not having harmonic distortion.
It is common in advanced meters to perform a function commonly referred to as
waveform capture. Waveform capture is the ability of a meter to capture a present
picture of the voltage or current waveform for viewing and harmonic analysis.
EM-4000 Series Meters Installation and Operation Manual 1-16
Typically a waveform capture will be one or two cycles in duration and can be viewed
as the actual waveform, as a spectral view of the harmonic content, or a tabular view
showing the magnitude and phase shift of each harmonic value. Data collected with
waveform capture is typically not saved to memory. Waveform capture is a real-time
data collection event.
Waveform capture should not be confused with waveform recording that is used to
record multiple cycles of all voltage and current waveforms in response to a transient
condition.
1.5: Power Quality
Power quality can mean several different things. The terms "power quality" and
"power quality problem" have been applied to all types of conditions. A simple definition of "power quality problem" is any voltage, current or frequency deviation that
1: Three-Phase Power Measurement
results in mis-operation or failure of customer equipment or systems. The causes of
power quality problems vary widely and may originate in the customer equipment, in
an adjacent customer facility or with the utility.
In his book Power Quality Primer, Barry Kennedy provided information on different
types of power quality problems. Some of that information is summarized in Table
1.3.
EM-4000 Series Meters Installation and Operation Manual 1-17
1: Three-Phase Power Measurement
CauseDisturbance TypeSource
Impulse transientTransient voltage disturbance,
sub-cycle duration
Oscillatory
transient with decay
Transient voltage, sub-cycle
duration
Sag/swellRMS voltage, multiple cycle
duration
InterruptionsRMS voltage, multiple
seconds or longer duration
Under voltage/over voltageRMS voltage, steady state,
System protection
Circuit breakers
Fuses
Maintenance
Motor starting
Load variations
Load dropping
Intermittent loads
Motor starting
Arc furnaces
Non-linear loads
System resonance
Table 1.3: Typical Power Quality Problems and Sources
It is often assumed that power quality problems originate with the utility. While it is
true that many power quality problems can originate with the utility system, many
problems originate with customer equipment. Customer-caused problems may manifest themselves inside the customer location or they may be transported by the utility
system to another adjacent customer. Often, equipment that is sensitive to power
quality problems may in fact also be the cause of the problem.
If a power quality problem is suspected, it is generally wise to consult a power quality
professional for assistance in defining the cause and possible solutions to the
problem.
EM-4000 Series Meters Installation and Operation Manual 1-18
2: Meter Overview and Specifications
2: Meter Overview and Specifications
2.1: EM-4000 Meter Overview
The EM-4000 meter is a multifunction, data
logging, power and energy meter with waveform recording capability, designed to be
used in electrical substations, panel boards,
as a power meter for OEM equipment, and as
a primary revenue meter, due to its high performance measurement capability. The unit
provides multifunction measurement of all
electrical parameters and makes the data
available in multiple formats via display and
communication systems. The unit also has
data logging and load profiling to provide
historical data analysis.
The EM-4000 meter offers 2 MegaBytes of Flash memory. (Because the memory is
flash-based rather than NVRAM (non-volatile random-access memory), some sectors
are reserved for overhead, erase procedures, and spare sectors for long-term wear
reduction.) The unit provides you with up to four logs: three historical logs and a
sequence of events log.
The purposes of these features include historical load profiling, voltage analysis, and
recording power factor distribution. The EM-4000 meter’s real-time clock allows all
events to be time stamped.
The EM-4000 meter is designed with advanced measurement capabilities, allowing it
to achieve high performance accuracy. It is specified as a 0.2% class energy meter for
billing applications as well as a highly accurate panel indication meter. It supplies
0.001 Hz Frequency measurement which meets generating stations’ requirements.
The EM-4000 meter provides additional capabilities, including standard RS485,
Figure 2.1: EM-4000 meter
Modbus® protocol support, and an IrDA port for remote interrogation.
Features of the EM-4000 meter include:
• 0.2% Class revenue certifiable energy and demand metering
• Meets ANSI C12.20 (0.2%) and IEC 62053-22 (0.2%) classes
EM-4000 Series Meters Installation and Operation Manual
2-1
2: Meter Overview and Specifications
• Multifunction measurement including voltage, current, power, frequency, energy,
etc.
• Optional secondary Voltage display (see the EM Series Communicator Software
User Manual for instructions on setting up this feature)
• Percentage of Load bar for analog meter reading
• 0.001% Frequency measurement for Generating stations
• Interval energy logging
• Line frequency time synchronization
• Easy to use faceplate programming
• IrDA port for laptop PC remote read
• RS485 communication
• Transformer/Line Loss compensation (see the EM Series Communicator Software
User Manual for instructions on using this feature)
• CT/PT compensation (see the EM Series Communicator Software
instructions on using this feature)
2.1.1: Voltage and Current Inputs
Universal Voltage Inputs
Voltage inputs allow measurement up to Nominal 576VAC (Phase to Reference) and
721VAC (Phase to Phase). This insures proper meter safety when wiring directly to
high Voltage systems. The unit will perform to specification on 69 Volt, 120 Volt, 230
Volt, 277 Volt, and 347 Volt power systems.
NOTE: Higher Voltages require the use of potential transformers (PTs).
User Manual for
Current Inputs
The unit supports a 5 Amp secondary for current measurements.
The current inputs are only to be connected to external current transformers.
EM-4000 Series Meters Installation and Operation Manual
2-2
2: Meter Overview and Specifications
The EM-4000 Series meter’s current inputs use a unique dual input method:
Method 1: CT Pass Through:
The CT wire passes directly through the meter without any physical termination on
the meter. This insures that the meter cannot be a point of failure on the CT circuit.
This is preferable for utility users when sharing relay class CTs. No Burden is added to
the secondary CT circuit.
Method 2: Current “Gills”:
This unit additionally provides ultra-rugged termination pass through bars that allow
CT leads to be terminated on the meter. This, too, eliminates any possible point of
failure at the meter. This is a preferred technique for insuring that relay class CT
integrity is not compromised (the CT will not open in a fault condition).
2.1.2: Ordering Information
EM-4000 Series Meter Ordering chart
Product-
Series
EM-4
EM-4000
Series
Meter
Example:
EM-4460-05-AI00
which translates to an EM-4000 Series meter with Modbus® communication, 60Hz
system, 90-265VAC/100-370VDC Power Supply, 5A Secondary Class, and ANSI
Network
ProtocolFreq.
4
Modbus
50
50 H z
System
60
60 Hz
System
-Power
Supply
-0
90-265
VAC/
100-370
VDC
DI
Current
Class
5
5 Amp
S e c o n d a r y
Mounting00
AI
ANSI
Mounting
DIN
Mounting
-
mounting. The last two options do not pertain to the EM-4000 Series meter, so the
ordering code contains 0s for them.
EM-4000 Series Meters Installation and Operation Manual
The following chart lists components that can be ordered along with the EM-4000
meter.
EM-4000 Series Meters Installation and Operation Manual
2-4
2: Meter Overview and Specifications
2.1.4: Measured Values
The EM-4000 Series meter provides the following measured values all in real time
instantaneous. As the table below shows, some values are also available in average,
maximum and minimum.
Table 1:
Measured ValuesInstantaneousAvgMaxMin
Voltage L-NXXX
Voltage L-LXXX
Current per PhaseXXXX
Current NeutralXX XX
WATT(A,B,C,Tot.)XXXX
VAR (A,B,C,Tot.)XXXX
VA (A,B,C,Tot.)XXXX
PF (A,B,C,Tot.)XXXX
+Watt-Hour (A,B,C,Tot.)X
-Watt-Hour (A,B,C,Tot.)X
Watt-Hour NetX
+VAR-Hour (A,B,C,Tot.)X
-VAR-Hour (A,B,C,Tot.)X
VAR-Hour Net (A,B,C,Tot.)X
VA-Hour (A,B,C,Tot.)X
FrequencyXXX
Voltage AnglesX
Current AnglesX
% of Load BarX
Waveform ScopeX
EM-4000 Series Meters Installation and Operation Manual
2-5
2.1.5: Utility Peak Demand
The EM-4000 Series meter provides user-configured Block (Fixed) window or Rolling
window Demand modes. This feature lets the user set up a customized Demand profile. Block window Demand mode records the average demand for time intervals the
user defines (usually 5, 15 or 30 minutes). Rolling window Demand mode functions
like multiple, overlapping Block windows. The user defines the subintervals at which
an average of Demand is calculated. An example of Rolling window Demand mode
would be a 15-minute Demand block using 5-minute subintervals, thus providing a
new Demand reading every 5 minutes, based on the last 15 minutes.
Utility Demand features can be used to calculate Watt, VAR, VA and PF readings.
Voltage provides an instantaneous Max and Min reading which displays the highest
surge and lowest sag seen by the meter. All other parameters offer Max and Min
capability over the user-selectable averaging period.
2: Meter Overview and Specifications
EM-4000 Series Meters Installation and Operation Manual
2-6
2.2: Specifications
Power Supply
Range:Universal, (90 to 265)
Power Consumption:(5 to 10)VA, (3.5 to 7)W -
Voltage Inputs
(For Accuracy specifications, see Section 2.4.)
2: Meter Overview and Specifications
VAC @50/60Hz or (100 to 370)VDC
depending on the meter’s hardware
configuration
Absolute Maximum Range:Universal, Auto-ranging:
Phase to Reference (Va, Vb, Vc to
Vref): (20 to 576)VAC
Phase to Phase (Va to Vb, Vb to Vc,
Vc to Va): (0 to 721)VAC
Supported hookups:3 Element Wye, 2.5 Element Wye,
2 Element Delta, 4 Wire Delta
Input Impedance:1M Ohm/Phase
Burden: 0.36VA/Phase Max at 600 Volts;
0.014VA at 120 Volts
Pickup Voltage:20VAC
Connection:7 Pin 0.400” Pluggable Terminal
Block
AWG#12 -26/ (0.129 -3.31) mm
EM-4000 Series Meters Installation and Operation Manual
2-7
2
2: Meter Overview and Specifications
Fault Withstand:Meets IEEE C37.90.1
Reading:Programmable Full Scale to any PT
ratio
Current Inputs
(For Accuracy specifications, see Section 2.4.)
Class 10: 5A Nominal, 10A Maximum
Burden:0.005VA Per Phase Max at 11 Amps
Pickup Current:0.1% of Nominal (0.2% of Nominal
if using Current Only mode, that is,
there is no connection to the
Voltage inputs)
Connections: O Lug or U Lug electrical connec-
tion (Figure 4.1)
Pass through wire, 0.177” / 4.5mm
maximum diameter (Figure 4.2)
Quick connect, 0.25” male tab
(Figure 4.3)
Fault Withstand (at 23
Reading:Programmable Full Scale to any CT
o
C): 100A/10sec., 300A/3sec.,
500A/1sec.
ratio
Continuous Current Withstand:20 Amps for screw terminated or
pass through connections
EM-4000 Series Meters Installation and Operation Manual
2-8
2: Meter Overview and Specifications
KYZ/RS485 Port Specifications
RS485 Transceiver; meets or exceeds EIA/TIA-485 Standard
Type:Two-wire, half duplex
Min. input Impedance:96kΩ
Max. output current:±60mA
Wh Pulse
KYZ output contacts, and infrared LED light pulses through face plate (see Section 6.4
for Kh values):
Pulse Width:90ms
Full Scale Frequency:~3Hz
Contact type:Solid state – SPDT (NO – C – NC)
Relay type:Solid state
Peak switching voltage:DC ±350V
Continuous load current:120mA
Peak load current:350mA for 10ms
On resistance, max.:35Ω
Leakage current:1µA@350V
Isolation:AC 3750V
Reset state:(NC - C) Closed; (NO - C) Open
EM-4000 Series Meters Installation and Operation Manual
2-9
2: Meter Overview and Specifications
(De-energized state)
N
O
C
N
C
90ms90ms
][
3600
][
WattP
pulse
Watthour
Kh
sT
»
¼
º
«
¬
ª
LED
ON
LED
ON
LED
OFF
LED
OFF
LED
OFF
IR LED Light Pulses
Through face plate
N
O
C
N
C
N
O
C
N
C
N
O
C
N
C
N
O
C
N
C
N
O
C
N
C
KYZ output
Contact States
Through Backplate
P
[Watt] - Not a scaled value
K
h See Section 6-4 for values
Infrared LED:
Peak Spectral wavelength:940nm
Reset state:Off
Internal schematic:
Output timing:
EM-4000 Series Meters Installation and Operation Manual
2-10
Isolation
Environmental Rating
2: Meter Overview and Specifications
All Inputs and Outputs are galvanically isolated to 2500 VAC
Storage:(-20 to +70)
Operating:(-20 to +70)
o
C
o
C
Humidity:to 95% RH Non-condensing
Faceplate Rating:NEMA12 (Water Resistant), mount-
ing gasket included
Measurement Methods
Voltage, current:True RMS
Power:Sampling at over 400 samples per
cycle on all channels
Update Rate
Watts, VAR and VA:Every 6 cycles (e.g., 100ms @ 60
Hz)
All other parameters:Every 60 cycles (e.g., 1 s @ 60 Hz)
1 second for Current Only measurement, if reference Voltage is not
available
Communication
Standard:
1. RS485 port through backplate
2. IrDA port through faceplate
3. Energy pulse output through backplate and Infrared LED through faceplate
EM-4000 Series Meters Installation and Operation Manual
2-11
2: Meter Overview and Specifications
Protocols: Modbus® RTU, Modbus® ASCII,
DNP 3.0
Com Port Baud Rate:RS485 Only: 1200, 2400, 4800;
All Com Ports: 9600 to 57600 bps
Com Port Address: 001-247
Data Format:8 Bit, No Parity (RS485: also Even
or Odd Parity)
Mechanical Parameters
Dimensions: see Chapter 3.
Weight:2 pounds/ 0.9kg (ships in a 6”
/15.24cm cube container)
2.3: Compliance
• UL/cUL Listed
• CE (EN61326-1, FCC Part 15, Subpart B, Class A)
• IEC 62053-22 (0.2% Class)
• ANSI C12.20 (0.2% Accuracy)
• ANSI (IEEE) C37.90.1 Surge Withstand
• ANSI C62.41 (Burst)
• EN61000-6-2 Immunity for Industrial Environments: 2005
• EN61000-6-4 Emission Standards for Industrial Environments: 2007
• EN61326 EMC Requirements: 2006
EM-4000 Series Meters Installation and Operation Manual
2-12
2.4: Accuracy
(For full Range specifications see Section 2.2.)
2: Meter Overview and Specifications
EM-4000 Clock Accuracy:Max. +/-2 seconds per day at 25
For 23
o
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5A
(Class 10) nominal unit, accuracy as follows:
Table 2:
ParameterAccuracyAccuracy Input Range1
Voltage L-N [V]0.1% of reading(69 to 480)V
Voltage L-L [V]
Current Phase [A]
Current Neutral (calculated) [A]
Active Power Total [W]
Active Energy Total [Wh]
0.2% of reading
0.1% of reading
2% of Full Scale
0.2% of reading
0.2% of reading
2
1, 3
1
1, 2
1, 2
(120 to 600)V
(0.15 to 5) A
(0.15 to 5) A @ (45 to 65)
Hz
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
o
C
Reactive Power Total
[VAR]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
Reactive Energy Total
[VARh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
Apparent Power Total [VA]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Apparent Energy Total
[VAh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Power Factor
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Frequency [Hz]+/- 0.001 Hz(45 to 65) Hz
Load Bar
+/- 1 segment
1
(0.005 to 6) A
EM-4000 Series Meters Installation and Operation Manual
2-13
2: Meter Overview and Specifications
1
• For 2.5 element programmed units, degrade accuracy by an additional 0.5% of
reading.
• For 1A (Class 2) Nominal, degrade accuracy to 0.5% of reading for watts and
energy; all other values 2 times rated accuracy.
• For 1A (Class 2) Nominal, the input current range for accuracy specification is
20% of the values listed in the table.
2
For unbalanced Voltage inputs where at least one crosses the 150V auto-scale
threshold (for example, 120V/120V/208V system), degrade the accuracy to 0.4%
of reading.
3
With reference Voltage applied (VA, VB, or VC). Otherwise, degrade accuracy to
0.2%. See hookup diagrams 8, 9, and 10 in Chapter 4.
EM-4000 Series Meters Installation and Operation Manual
2-14
3: Mechanical Installation
0.06 [
0.15]
0.77 [1.95]
5.02 [12
.75]
Gasket
3.25[8.26]
4.85[12.32]
4.85 [12
.32]
0.95 [2.41]
3.1: Introduction
The EM-4000 meter can be installed using a standard ANSI C39.1 (4” round) or an
IEC 92mm DIN (square) form. In new installations, simply use existing DIN or ANSI
punches. For existing panels, pull out old analog meters and replace them with the
EM-4000 meter. See Chapter 4 for wiring diagrams.
NOTE: The drawings shown below and on the next page give you the meter dimensions in inches and centimeters [cm shown in brackets]. Tolerance is +/- 0.1” [.25
cm].
3: Mechanical Installation
Figure 3.1: Meter Front and Side Dimensions
EM-4000 Series Meters Installation and Operation Manual
3-1
3: Mechanical Installation
3.56 [9.04]
3.56 [9.04]
CM
CM
3Q
8v
v
Figure 3.2: Meter Back Dimensions
Figure 3.3: ANSI and DIN Cutout Dimensions
Recommended Tools for EM-4000 meter Installation:
• #2 Phillips screwdriver
• Small adjustable wrench
• Wire cutters
The EM-4000 meter is designed to withstand harsh environmental conditions; however it is recommended you install it in a dry location, free from dirt and corrosive
substances (see Environmental specifications in Chapter 2).
EM-4000 Series Meters Installation and Operation Manual
3-2
3.2: ANSI Installation Steps
ANSI Installation
ANSI Studs
4.0” Round form
1. Slide meter with Mounting Gasket into panel.
2. Secure from back of panel with flat washer, lock washer and nut on each threaded
rod. Use a small wrench to tighten. Do not overtighten. The maximum installation
torque is 0.4 Newton-Meter.
3: Mechanical Installation
Figure 3.4: ANSI Installation
EM-4000 Series Meters Installation and Operation Manual
3-3
3.3: DIN Installation Steps
DIN mounting
bracket
Top mounting
bracket groove
Bottom
mounting
bracket groove
DIN Mounting brackets
Remove (unscrew) ANSI studs
for DIN installation
DIN Installation
92mm Square
form
1. Slide meter with NEMA 12 Mounting Gasket into panel (remove ANSI Studs, if in
place).
2. From back of panel, slide 2 DIN Mounting Brackets into grooves in top and bottom
of meter housing. Snap into place.
3. Secure meter to panel by using a #2 Phillips screwdriver to tighten the screw on
each of the two mounting brackets. Do not overtighten: the maximum installation
torque is 0.4 Newton-Meter.
3: Mechanical Installation
Figure 3.5: DIN Installation
EM-4000 Series Meters Installation and Operation Manual
3-4
4: Electrical Installation
4: Electrical Installation
4.1: Considerations When Installing Meters
Installation of the EM-4000 meter must be performed only by qualified personnel who follow standard safety precautions during all procedures. Those personnel should have appropriate training and
experience with high Voltage devices. Appropriate safety gloves,
safety glasses and protective clothing are recommended.
During normal operation of the EM-4000 meter, dangerous Voltages flow through
many parts of the meter, including: Terminals and any connected CTs (Current Transformers) and PTs (Potential Transformers), all I/O Modules (Inputs and Outputs) and
their circuits.
All Primary and Secondary circuits can, at times, produce lethal Voltages and
currents. Avoid contact with any current-carrying surfaces.
Do not use the meter or any I/O Output device for primary protection or in
an energy-limiting capacity. The meter can only be used as secondary
protection.
Do not use the meter for applications where failure of the meter may cause harm or
death.
Do not use the meter for any application where there may be a risk of fire.
All meter terminals should be inaccessible after installation.
Do not apply more than the maximum Voltage the meter or any attached device can
withstand. Refer to meter and/or device labels and to the specifications for all devices
before applying voltages. Do not HIPOT/Dielectric test any Outputs, Inputs or Communications terminals.
Caution: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in
permanent damage to the equipment.
EM-4000 Series Meters Installation and Operation Manual
4-1
4: Electrical Installation
Johnson Controls recommends the use of Fuses for Voltage leads and power supply
and shorting blocks to prevent hazardous Voltage conditions or damage to CTs, if the
meter needs to be removed from service. CT grounding is optional, but recommended.
NOTE: The current inputs are only to be connected to external current transformers
provided by the installer. The CTs shall be Approved or Certified and rated for the
current of the meter used.
Caution: Risk of Property Damage.
Ensure that the power source conforms to the requirements of the
equipment. Failure to use a correct power source may result in permanent damage to the equipment.
L'installation des compteurs de EM-4000 Series doit être effectuée
seulement par un personnel qualifié qui suit les normes relatives aux
précautions de sécurité pendant toute la procédure. Le personnel
doit avoir la formation appropriée et l'expérience avec les appareils
de haute tension. Des gants de sécurité, des verres et des vête-
ments de protection appropriés sont recommandés.
AVERTISSEMENT! Pendant le fonctionnement normal du compteur EM-4000 Series
des tensions dangereuses suivant de nombreuses pièces, notamment, les bornes et
tous les transformateurs de courant branchés, les transformateurs de tension, toutes
les sorties, les entrées et leurs circuits. Tous les circuits secondaires et primaires
peuvent parfois produire des tensions de létal et des courants. Évitez le contact avec les surfaces sous tensions. Avant de faire un travail dans le compteur, assurez-vous d'éteindre l'alimentation et de mettre tous les circuits
branchés hors tension.
Ne pas utiliser les compteurs ou sorties d'appareil pour une protection primaire ou capacité de limite d'énergie. Le compteur peut seulement être
utilisé comme une protection secondaire.
Ne pas utiliser le compteur pour application dans laquelle une panne de compteur
peut causer la mort ou des blessures graves.
Ne pas utiliser le compteur ou pour toute application dans laquelle un risque
d'incendie est susceptible.
EM-4000 Series Meters Installation and Operation Manual
4-2
4: Electrical Installation
Toutes les bornes de compteur doivent être inaccessibles après l'installation.
Ne pas appliquer plus que la tension maximale que le compteur ou appareil relatif
peut résister. Référez-vous au compteur ou aux étiquettes de l'appareil et les spécifications de tous les appareils avant d'appliquer les tensions. Ne pas faire de test
HIPOT/diélectrique, une sortie, une entrée ou un terminal de réseau.
Les entrées actuelles doivent seulement être branchées aux transformateurs externes
actuels.
Johnson Controls recommande d'utiliser les fusibles pour les fils de tension et alimentations électriques, ainsi que des coupe-circuits pour prévenir les tensions dangereuses ou endommagements de transformateur de courant si l'unité EM-4000 Series
doit être enlevée du service. Un côté du transformateur de courant doit être mis à
terre.
NOTE: Les entrées actuelles doivent seulement être branchées dans le transformateur externe actuel par l'installateur. Le transformateur de courant doit être approuvé
ou certifié et déterminé pour le compteur actuel utilisé.
IMPORTANT!
IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED
BY THE MANUFACTURER, THE PROTECT I ON PROVIDED BY
THE EQUIPMENT MAY BE IMPAIRED.
• THERE IS NO REQUIRED PREVENTIVE MAINTENANCE OR INSPEC TION NECESSARY FOR SAFETY. HOWEVER, ANY REPAIR OR MAIN TENANCE SHOULD BE PERFORMED BY THE FACTORY.
DISCONNECT DEVICE: The following part is considered the equipment disconnect device. A SWITCH OR CIRCUIT-BREAKER SHALL BE
INCLUDED IN THE END-USE EQUIPMENT OR BUILDING INSTALLATION. THE SWITCH SHALL BE IN CLOSE PROXIMITY TO THE EQUIPMENT AND WITHIN EASY REACH OF THE OPERATOR. THE SWITCH
SHALL BE MARKED AS THE DISCONNECTING DEVICE FOR THE
EQUIPMENT.
EM-4000 Series Meters Installation and Operation Manual
4-3
4: Electrical Installation
IMPORTANT! SI L'ÉQUIPEMENT EST UTILISÉ D'UNE FAÇON
NON SPÉCIFIÉE PAR LE FABRICANT, LA PROTECTION FOURNIE PAR L'ÉQUIPEMENT PEUT ÊTRE ENDOMMAGÉE.
NOTE: Il N'Y A AUCUNE MAINTENANCE REQUISE POUR LA PRÉVENTION OU INSPEC-
TION NÉCESSAIRE POUR LA SÉCURITÉ. CEPENDANT, TOUTE RÉPARATION OU MAINTENANCE DEVRAIT ÊTRE RÉALISÉE PAR LE FABRICANT.
DÉBRANCHEMENT DE L'APPAREIL : la partie suivante est considérée l'appareil de débranchement de l'équipement.
UN INTERRUPTEUR OU UN DISJONCTEUR DEVRAIT ÊTRE INCLUS
DANS L'UTILISATION FINALE DE L'ÉQUIPEMENT OU L'INSTALLATION.
L'INTERRUPTEUR DOIT ÊTRE DANS UNE PROXIMITÉ PROCHE DE
L'ÉQUIPEMENT ET A LA PORTÉE DE L'OPÉRATEUR. L'INTERRUPTEUR DOIT AVOIR LA
MENTION DÉBRANCHEMENT DE L'APPAREIL POUR L'ÉQUIPEMENT.
4.2: CT Leads Terminated to Meter
The EM-4000 meter is designed to have current inputs wired in one of three ways.
Figure 4.1 shows the most typical connection where CT Leads are terminated to the
meter at the current gills. This connection uses nickel-plated brass studs (current
gills) with screws at each end. This connection allows the CT wires to be terminated
using either an “O” or a “U” lug. Tighten the screws with a #2 Phillips screwdriver. The
maximum installation torque is 0.7376 foot-pounds (1 Newton-Meter).
EM-4000 Series Meters Installation and Operation Manual
4-4
4: Electrical Installation
Current Gills
(nickel-plated
brass studs)
Other current connections are shown in figures 4.2 and 4.3. Voltage and RS485/KYZ
connections are shown in Figure 4.4.
Figure 4.1: CT Leads Terminated to Meter, #8 Screw for Lug Connection
Wiring Diagrams are shown in Section 4.8 of this chapter.
Communications connections are detailed in Chapter 5.
EM-4000 Series Meters Installation and Operation Manual
4-5
4: Electrical Installation
$5XJSFQBTTJOH
UISPVHINFUFS
$VSSFOUHJMMT
SFNPWFE
4.3: CT Leads Pass Through (No Meter Termination)
The second method allows the CT wires to pass through the CT inputs without terminating at the meter. In this case, remove the current gills and place the CT wire
directly through the CT opening. The opening accommodates up to 0.177” / 4.5mm
maximum diameter CT wire.
Figure 4.2: Pass Through Wire Electrical Connection
EM-4000 Series Meters Installation and Operation Manual
4-6
4.4: Quick Connect Crimp-on Terminations
Quick connect
crimp-on
terminations
For quick termination or for portable applications, 0.25” quick connect crimp-on
connectors can also be used
4: Electrical Installation
Figure 4.3: Quick Connect Electrical Connection
EM-4000 Series Meters Installation and Operation Manual
*The power supply voltage range is Universal, (90 to 265) VAC @50/60Hz or
(100 to 370)VDC.
4.6: Ground Connections
The meter’s Ground terminals should be connected directly to the installation’s
protective earth ground. Use AWG# 12/2.5 mm
WARNING: Risk of Electric Shock.
Ground the meter according to local, national, and regional regulations.
Failure to ground the meter may result in electric shock and severe
personal injury or death.
AVERTISSEMENT: Risque de décharge électrique.
Effectuer la mise à terre selon les règlements locaux, nationaux et régionaux. La non mise
à la terre du compteur peut provoquer une décharge électrique, des blessures graves ou
provoquer la mort.
Figure 4.4: Meter Connections
2
wire for this connection.
EM-4000 Series Meters Installation and Operation Manual
4-8
4.7: Voltage Fuses
Johnson Controls recommends the use of fuses on each of the sense voltages and on
the control power.
• Use a 0.1 Amp fuse on each voltage input.
• Use a 3 Amp Slow Blow fuse on the power supply.
4: Electrical Installation
EM-4000 Series Meters Installation and Operation Manual
4-9
4.8: Electrical Connection Diagrams
The following pages contain electrical connection diagrams for the EM-4000 meter.
Choose the diagram that best suits your application. Be sure to maintain the CT
polarity when wiring.
The diagrams are presented in the following order:
1. Three Phase, Four-Wire System Wye/Delta with Direct Voltage, 3 Element
a. Example of Dual-Phase Hookup
b. Example of Single Phase Hookup
2. Three Phase, Four-Wire System Wye with Direct Voltage, 2.5 Element
4: Electrical Installation
3. Three-Phase, Four-Wire Wye/Delta with PTs, 3 Element
4. Three-Phase, Four-Wire Wye with PTs, 2.5 Element
5. Three-Phase, Three-Wire Delta with Direct Voltage
6. Three-Phase, Three-Wire Delta with 2 PTs, 2 CTs
7. Three-Phase, Three-Wire Delta with 2 PTs, 3 CTs
8. Current Only Measurement (Three Phase)
9. Current Only Measurement (Dual Phase)
10.Current Only Measurement (Single Phase)
WARNING: Risk of Electric Shock.
Disconnect the power supply before making electrical connections.
Contact with components carrying hazardous voltage can cause electric shock
and may result in severe personal injury or death.
AVERTISSEMENT: Risque de décharge électrique.
Débranchez l’alimentation électrique avant de faire un branchement électrique. Le contact
avec des composants ayant des tensons importantes peut provoquer une décharge
électrique, des blessures personnelles graves ou la mort.
EM-4000 Series Meters Installation and Operation Manual
4-10
4: Electrical Installation
C
B
A
C
BA
1. Service: WYE/Delta, 4-Wire with No PTs, 3 CTs
LINE
N
A
B
C
CT
Shorting
Block
Earth Ground
lc
LO
Power
Supply
Connection
GND
FUSE
HI
HI
HI
lb
la
LO
LO
L(+)
N(-)
Vref
Va
Vb
Vc
L(+)
3A
N(-)
FUSES
3 x 0.1A
N
A
LOAD
B
C
Select: “ 3 EL WYE ” (3 Element Wye) from the EM-4000 meter’s front panel display
(see Chapter 6).
EM-4000 Series Meters Installation and Operation Manual
4-11
1a. Example of Dual Phase Hookup
LINE
C
B
A
N
4: Electrical Installation
N
A
LOAD
CT
Shorting
Block
Earth Ground
HI
HI
HI
lb
lc
LO
FUSES
2 x 0.1A
C
B
la
LO
LO
GND
L(+)
N(-)
Vref
Va
Vb
Vc
x
Power
Supply
Connection
FUSE
3A
L(+)
N(-)
Select: “ 3 EL WYE ” (3 Element Wye) from the EM-4000 meter’s Front Panel Display.
(See Chapter 6.)
EM-4000 Series Meters Installation and Operation Manual
4-12
1b. Example of Single Phase Hookup
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
x
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
x
FUSE
0.1A
FUSE
3A
C
C
B
B
A
A
N
N
4: Electrical Installation
Select: “ 3 EL WYE ” (3 Element Wye) from the EM-4000 meter’s Front Panel Display.
(See Chapter 6.)
EM-4000 Series Meters Installation and Operation Manual
4-13
4: Electrical Installation
C
B
A
2. Service: 2.5 Element WYE, 4-Wire with No PTs, 3 CTs
LINE
N
A
B
C
CT
Shorting
Block
Earth Ground
lc
LO
Power
Supply
Connection
GND
FUSE
HI
HI
HI
lb
la
LO
LO
L(+)
N(-)
Vref
Va
Vb
Vc
L(+)
3A
N(-)
FUSES
2 x 0.1A
N
A
LOAD
B
C
Select: “2.5 EL WYE” (2.5 Element Wye) from the EM-4000 meter’s front panel
display (see Chapter 6).
EM-4000 Series Meters Installation and Operation Manual
4-14
4: Electrical Installation
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSES
3 x 0.1A
FUSE
3A
C
C
B
B
A
A
N
N
C
BA
C
B
A
3. Service: WYE/Delta, 4-Wire with 3 PTs, 3 CTs
Select: “3 EL WYE” (3 Element Wye) from the EM-4000 meter’s front panel display
(see Chapter 6).
EM-4000 Series Meters Installation and Operation Manual
4-15
4: Electrical Installation
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSES
2 x 0.1A
FUSE
3A
C
C
B
B
A
A
N
N
C
B
A
4. Service: 2.5 Element WYE, 4-Wire with 2 PTs, 3 CTs
Select: “2.5 EL WYE” (2.5 Element Wye) from the EM-4000 meter’s front panel
display (see Chapter 6).
EM-4000 Series Meters Installation and Operation Manual
4-16
5. Service: Delta, 3-Wire with No PTs, 2 CTs
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSES
3 x 0.1A
FUSE
3A
C
C
B
B
A
A
C
BA
C
BA
Not connected to meter
4: Electrical Installation
Select: “2 CT DEL” (2 CT Delta) from the EM-4000 meter’s front panel display (see
Chapter 6).
EM-4000 Series Meters Installation and Operation Manual
4-17
6. Service: Delta, 3-Wire with 2 PTs, 2 CTs
C
BA
C
BA
Not connected to meter
LINE
B
A
C
CT
Shorting
Block
4: Electrical Installation
A
LOAD
B
C
Earth Ground
Earth Ground
lc
HI
LO
FUSES
2 x 0.1A
lb
Power
Supply
Connection
GND
FUSE
HI
HI
la
LO
LO
L(+)
N(-)
Vref
Va
Vb
Vc
L(+)
3A
N(-)
Select: “2 CT DEL” (2 CT Delta) from the EM-4000 meter’s front panel display (see
Chapter 6).
EM-4000 Series Meters Installation and Operation Manual
4-18
7. Service: Delta, 3-Wire with 2 PTs, 3 CTs
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSES
2 x 0.1A
FUSE
3A
C
C
B
B
A
A
C
BA
C
BA
Not connected to meter
4: Electrical Installation
Select: “2 CT DEL” (2 CT Delta) from the EM-4000 meter’s front panel display (see
Chapter 6).
NOTE: The third CT for hookup is optional, and is used only for Current
measurement.
EM-4000 Series Meters Installation and Operation Manual
4-19
4: Electrical Installation
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSE
3A
FUSE
0.1A
20VAC
Minimum
C
C
B
B
A
A
8. Service: Current Only Measurement (Three Phase)
Select: “3 EL WYE” (3 Element Wye) from the EM-4000 meter’s front panel display
(see Chapter 6.)
* This connection is not required, but is recommended for improved accuracy.
EM-4000 Series Meters Installation and Operation Manual
4-20
4: Electrical Installation
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSE
3A
FUSE
0.1A
20VAC
Minimum
B
B
A
A
9. Service: Current Only Measurement (Dual Phase)
Select: “3 EL WYE” (3 Element Wye) from the EM-4000 meter’s front panel display
(see Chapter 6).
* This connection is not required, but is recommended for improved accuracy.
EM-4000 Series Meters Installation and Operation Manual
4-21
4: Electrical Installation
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSE
3A
FUSE
0.1A
20VAC
Minimum
N
N
A
A
10. Service: Current Only Measurement (Single Phase)
Select: “3 EL WYE” (3 Element Wye) from the EM-4000 meter’s front panel display
(see Chapter 6).
* This connection is not required, but is recommended for improved accuracy.
NOTE: The diagram shows a connection to Phase A, but you can also connect to
Phase B or Phase C.
EM-4000 Series Meters Installation and Operation Manual
4-22
5: Communication Installation
5: Communication Installation
5.1: EM-4000 Series Meter Communication
The EM-4000 meter provides two independent Communication ports. The first port,
Com 1, is an optical IrDA port. The second port, Com 2, provides RS485
communication speaking Modbus® ASCII and Modbus® RTU protocols.
5.1.1: IrDA Port (Com 1)
The EM-4000 meter’s Com 1 IrDA port is on the face of the meter. The IrDA port
allows the unit to be read and programmed without the need of a communication
cable. Just point at the meter with an IrDA-equipped laptop PC to configure it.
NOTES:
• Settings for Com 1 (IrDA Port) are configured using the EM Series Communicator
Software.
• This port only communicates via Modbus® ASCII Protocol.
• Refer to Appendix D for instructions on using EIG’s USB to IrDA Adapter.
5.1.2: RS485 / KYZ Output (Com 2)
Com 2 provides a combination RS485 and an Energy Pulse Output (KYZ pulse).
See Chapter 2, Section 2.2 for the KYZ Output specifications; see Chapter 6, Section
6.4 for pulse constants.
EM-4000 Series Meters Installation and Operation Manual
Figure 5.1: EM-4000 Meter Back with RS485 Communication Installation
RS485 allows you to connect one or multiple EM-4000 meters to a PC or other device,
at either a local or remote site. All RS485 connections are viable for up to 4000 feet
(1219.20 meters).
120.00
120.00
120.00
EM-4000 meter
Figure 5.2: EM-4000 Meter Connected to a PC via RS485 bus
RS485
RS485/RS232
or RS485/USB
Converter
RS232
or USB
As shown in Figure 5.2, to connect an EM-4000 meter to a PC, you need to use either
an RS485 to RS232 or an RS485 to USB converter.
EM-4000 Series Meters Installation and Operation Manual
5-2
5: Communication Installation
MAX
MIN
VOLTS L-N
AMPS
%LOAD
120%-
PRG
%THD
LM2
LM1
90%-
60%-
30%-
VOLTS L-N
W/VAR/PF
VA/Hz
Wh
KILO
VARh
VAh
Wh Pulse
MEGA
A
B
C
MENU
ENTER
From other RS485 device
Connect :
•
(−) to (
−
)
•
(+) to (+)
•
Shield(SH) to Shield(SH)
EM-4000 meter RS485 connections
120
. 0
120 . 0
120 . 0
+
-
SH
+
-
SH
Figure 5.3 shows the detail of a 2-wire RS485 connection
Figure 5.3: 2-wire RS485 Connections to EM-4000 Meter
NOTES:
For All RS485 Connections:
• Use a shielded twisted pair cable and ground the shield, preferably at one location
only.
• Establish point-to-point configurations for each device on a RS485 bus: connect (+)
terminals to (+) terminals; connect (-) terminals to (-) terminals.
• You may connect up to 31 meters on a single bus using RS485. Before assembling
the bus, each meter must have a unique address: refer to the EM Series Communi-cator Software User Manual for instructions.
• Protect cables from sources of electrical noise.
• Avoid both “Star” and “Tee” connections (see Figure 5.5).
• No more than two cables should be connected at any one point on an RS485 net-
work, whether the connections are for devices, converters, or terminal strips.
• Include all segments when calculating the total cable length of a network. If you are
not using an RS485 repeater, the maximum length for cable connecting all devices
is 4000 feet (1219.20 meters).
• Connect shield to RS485 Master and individual devices as shown in Figure 5.4. You
may also connect the shield to earth-ground at one point.
• Termination Resistors (RT) may be needed on both ends for longer length transmis-
sion lines. However, since the meter has some level of termination internally,
EM-4000 Series Meters Installation and Operation Manual
Termination Resistors may not be needed. When they are used, the value of the
Termination Resistors is determined by the electrical parameters of the cable.
Figure 5.4 shows a representation of an RS485 Daisy Chain connection.
Figure 5.4: RS485 Daisy Chain Connection
R
+ - SH
Earth Connection, preferably at
sin
le location
Slave device 1
+ - SH
Long stub results “T” connection that can cause
interference
EM-4000 Series Meters Installation and Operation Manual
5-4
6: Using the EM-4000 Meter
MAX
MIN
VOLTS L-N
AMPS
%LOAD
120%-
PRG
%THD
LM2
LM1
90%-
60%-
30%-
VOLTS L-N
W/VAR/PF
VA/Hz
Wh
KILO
VARh
VAh
Wh Pulse
MEGA
A
B
C
MENU
ENTER
IrDA
0000
0.659
IrDA Com
Port
Reading
Type
Indicator
Parameter
Designator
Watt-hour
Test P ul se
Scaling
Factor
% of Load
Bar
6.1: Introduction
You can use the Elements and Buttons on the EM-4000 meter’s face to view meter
readings, reset and/or configure the meter, and perform related functions. The following sections explain the Elements and Buttons and detail their use.
6.1.1: Understanding Meter Face Elements
6: Using the EM-4000 Meter
The meter face features the following elements:
• Reading type indicator: e.g., Max
• Parameter designator: e.g., Volts L-N
• Watt-hour test pulse: Energy pulse output to test accuracy
• Scaling factor: Kilo or Mega multiplier of displayed readings
• % of Load bar: Graphic Display of Amps as % of the load (see Section 6.3 for
additional information)
• IrDA Communication port: Com 1 port for wireless communication
Figure 6.1: Face Plate with Elements
EM-4000 Series Meters Installation and Operation Manual
6-1
6.1.2: Understanding Meter Face Buttons
MAX
MIN
VOLTS L-N
AMPS
%LOAD
120%-
PRG
%THD
LM2
LM1
90%-
60%-
30%-
VOLTS L-N
W/VAR/PF
VA/Hz
Wh
KILO
VARh
VAh
Wh Pulse
MEGA
A
B
C
MENU
ENTER
IrDA
0000
0.659
Menu Enter
Down Right
6: Using the EM-4000 Meter
Figure 6.2: Faceplate with Buttons
The meter face has Menu, Enter, Down and Right buttons, which let you perform
the following functions:
• View meter information
• Enter display modes
• Configure parameters (may be Password protected)
• Perform resets (may be Password protected)
• Perform LED Checks
• Change settings
• View parameter values
• Scroll parameter values
• View Limit states
EM-4000 Series Meters Installation and Operation Manual
6-2
6.2: Using the Front Panel
You can access four modes using the EM-4000 meter’s front panel buttons:
• Operating mode (Default)
• Reset mode
• Configuration mode
• Information mode - Information mode displays a sequence of screens that show
model information, such as Frequency, Amps, V-Switch, etc.
Use the Menu, Enter, Down and Right buttons to navigate through each mode and
its related screens.
NOTES:
6: Using the EM-4000 Meter
• See Appendix A for the display’s Navigation maps.
• The meter can also be configured using software; see the EM Series Communicator
Software User Manual for instructions.
6.2.1: Understanding Startup and Default Displays
Upon powering up, the meter displays a sequence of screens:
• Lamp Test screen where all LEDs are lit
• Lamp Test screen where all digits are lit
• Firmware screen showing the build number
• Error screen (if an error exists)
After startup, if auto-scrolling is enabled, the EM-4000 meter scrolls the parameter
readings on the right side of the front panel. The Kilo or Mega LED lights, showing the
scale for the Wh, VARh and VAh readings. Figure 6.3 shows an example of a Wh
reading.
EM-4000 Series Meters Installation and Operation Manual
6-3
6: Using the EM-4000 Meter
MAX
MIN
VOLTS L-N
AMPS
%LOAD
120%-
PRG
%THD
LM2
LM1
90%-
60%-
30%-
VOLTS L-N
W/VAR/PF
VA/Hz
Wh
KILO
VARh
VAh
Wh Pulse
MEGA
A
B
C
MENU
ENTER
IrDA
0000
0.659
A
B
C
-
-
-
MENUENTER
A
B
C
-
-
-
MENUENTER
A
B
C
-
-
-
MENUENTER
Figure 6.3: Display Showing Watt-hour Reading
The EM-4000 meter continues to provide scrolling readings until one of the buttons on
the front panel is pressed, causing the meter to enter one of the other Modes.
6.2.2: Using the Main Menu
1. Press the Menu button. The Main Menu screen appears.
• The Reset: Demand mode (rStd) appears in the A window. Use the Down button to
scroll, causing the Reset: Energy (rStE), Configuration (CFG), Operating (OPr), and
Information (InFo) modes to move to the A window.
• The mode that is currently flashing in the A window is the “Active” mode, which
means it is the mode that can be configured.
For example: Press Down Twice - CFG moves to A window. Press Down Twice - OPr moves to
A window.
EM-4000 Series Meters Installation and Operation Manual
6-4
2. Press the Enter button from the Main Menu to view the Parameters screen for the
A
B
C
-
-
-
MENUENTER
A
B
C
-
MENUENTER
A
B
C
-
-
-
MENUENTER
A
B
C
-
-
-
MENUENTER
mode that is currently active.
6.2.3: Using Reset Mode
Reset Mode has two options:
• Reset: Demand (rStd): resets the Max and Min values
• Reset: Energy (rStE): resets the energy accumulator fields
1. Press the Enter button while
either rStd or rStE is in the A window. The Reset Demand No or
Reset Energy No screen appears.
• If you press the Enter button
6: Using the EM-4000 Meter
-
-
again, the Main Menu appears,
with the next mode in the A
window. (The Down button
does not affect this screen.)
• If you press the Right button,
the Reset Demand YES or
Reset Energy YES screen
appears. Press Enter to perform a reset.
NOTE: If Password protection is enabled for reset, you must enter the four digit
password before you can reset the meter. (See the EM Series Communicator Software User Manual for information on Password protection.) To enter a password, follow the
instructions in Section 6.2.4.
CAUTION! Reset Demand YES resets all Max and Min values.
2. Once you have performed a reset, the screen displays either “rSt dMd donE” or
“rSt EnEr donE”and then resumes auto-scrolling parameters.
EM-4000 Series Meters Installation and Operation Manual
6-5
6.2.4: Entering a Password
A
B
C
-
MENUENTER
A
B
C
-
MENUENTER
PASS
12__
A
B
C
-
MENUENTER
If Password Protection has been enabled in the software for reset and/or configuration
(see the EM Series Communicator Software User Manual for more information), a
screen appears requesting a password when you try to reset the meter and/or configure settings through the front panel.
• PASS appears in the A window and 4 dashes appear in the B window; the left-most
dash is flashing.
1. Press the Down button to scroll numbers from 0 to 9 for the flashing dash. When
the correct number appears for that dash, use the Right button to move to the
next dash.
Example: The left screen, below, shows four dashes. The right screen shows the
display after the first two digits of the password have been entered.
6: Using the EM-4000 Meter
-
-
2. When all 4 digits of the password have been selected, press the Enter button.
• If you are in Reset mode and you enter the correct password, “rSt dMd donE” or
“rSt EnEr donE”appears and the screen resumes auto-scrolling parameters.
• If you are in Configuration mode and you enter the correct password, the display
returns to the screen that required a password.
• If you enter an incorrect Password, “PASS ----
FAIL” appears and:
• The previous screen is redisplayed, if you
are in Reset mode.
• The previous Operating mode screen is
-
-
-
-
redisplayed, if you are in Configuration
mode.
EM-4000 Series Meters Installation and Operation Manual
6-6
6.2.5: Using Configuration Mode
A
B
C
-
MENUENTER
A
B
C
-
MENUENTER
Configuration mode follows Reset: Energy on the Main Menu.
To access Configuration mode:
1. Press the Menu button while the meter is auto-scrolling parameters.
2. Press the Down button until the Configuration mode option (CFG) is in the A
window.
3. Press the Enter button. The configuration Parameters screen appears.
4. Press the Down button to scroll through the configuration parameters: Scroll
(SCrL), CT, PT, Connection (Cnct) and Port. The parameter currently ‘Active,” i.e.,
configurable, flashes in the A window.
6: Using the EM-4000 Meter
5. Press the Enter button to access the Setting screen for the currently active param-
eter.
NOTE: You can use the Enter button to scroll through all of the configuration
parameters and their Setting screens, in order.
-
-
Press Enter when CFG is in A window - Parameter screen appears Press Down- Press Enter when
Parameter you want is in A window
-
-
6. The parameter screen appears, showing the current settings. To change the
settings:
• Use either the Down button or the Right button to select an option.
EM-4000 Series Meters Installation and Operation Manual
6-7
6: Using the EM-4000 Meter
A
B
C
-
MENUENTER
A
B
C
-
MENUENTER
A
B
C
-
MENUENTER
• To enter a number value, use the Down button to select the number value for a
digit and the Right button to move to the next digit.
NOTE: When you try to change the current setting and Password protection is
enabled for the meter, the Password screen appears. See Section 6.2.4 for instructions on entering a password.
7. Once you have entered the new setting, press the Menu button twice.
8. The Store ALL YES screen appears. You can either:
• Press the Enter button to save the new setting.
• Press the Right button to access the Store ALL no screen; then press the Enter
button to cancel the Save.
9. If you have saved the settings, the Store ALL done screen appears and the meter
resets.
-
-
Press the Enter button to save Press the Enter button to The settings have been
the settings. Press the Right Cancel the Save. saved.
button for Stor All no screen.
-
-
-
-
EM-4000 Series Meters Installation and Operation Manual
6-8
6.2.5.1: Configuring the Scroll Feature
A
B
C
-
MENUENTER
A
B
C
-
-
-
MENUENTER
When in auto-scrolling mode, the meter performs a scrolling display, showing each
parameter for 7 seconds, with a 1 second pause between parameters. The parameters
that the meter displays are determined by the following conditions:
• They have been selected through software (see the EM Series Communicator Soft-ware User Manual for instructions).
6: Using the EM-4000 Meter
• They are enabled by the installed V-Switch
TM
on V-Switch
keys).
TM
key (see Section 2.1.3 for information
To enable or disable auto-scrolling:
1. Press the Enter button when SCrl is in the A window.
The Scroll YES screen appears.
2. Press either the Right or Down button if you want to
access the Scroll no screen. To return to the Scroll
YES screen, press either button.
3. Press the Enter button on either the Scroll YES
screen (to enable auto-scrolling) or the Scroll no
screen (to disable auto-scrolling).
4. The CT- n screen appears (this is the next Configuration mode parameter).
-
-
NOTES:
• To exit the screen without changing scrolling options, press the Menu button.
• To return to the Main Menu screen, press the Menu button twice.
• To return to the scrolling (or non-scrolling) parameters display, press the Menu
button three times.
EM-4000 Series Meters Installation and Operation Manual
6-9
6.2.5.2: Configuring CT Setting
The CT Setting has three parts: Ct-n (numerator), Ct-d (denominator), and Ct-S
(scaling).
1. Press the Enter button when Ct is in the A window. The Ct-n screen appears. You
can either:
• Change the value for the CT numerator.
• Access one of the other CT screens by pressing the Enter button: press Enter
once to access the Ct-d screen, twice to access the Ct-S screen.
NOTE: The Ct-d screen is preset to a 5 Amp value at the factory and cannot be
changed.
a. To change the value for the CT numerator:
6: Using the EM-4000 Meter
From the Ct-n screen:
• Use the Down button to select the number value for a digit.
• Use the Right button to move to the next digit.
b. To change the value for CT scaling:
From the Ct-S screen, use the Right button or the Down button to choose the
scaling you want. The Ct-S setting can be 1, 10, or 100.
NOTE: If you are prompted to enter a password, refer to Section 6.2.4 for instructions on doing so.
2. When the new setting is entered, press the Menu button twice.
3. The Store ALL YES screen appears. Press Enter to save the new CT setting.
Example CT Settings:
200/5 Amps: Set the Ct-n value for 200 and the Ct-S value for 1.
800/5 Amps: Set the Ct-n value for 800 and the Ct-S value for 1.
2,000/5 Amps: Set the Ct-n value for 2000 and the Ct-S value for 1.
10,000/5 Amps: Set the Ct-n value for 1000 and the Ct-S value for 10.
EM-4000 Series Meters Installation and Operation Manual
6-10
6: Using the EM-4000 Meter
A
B
C
-
-
-
MENUENTER
A
B
C
-
MENUENTER
A
B
C
-
-
-
MENUENTER
A
B
C
-
-
-
MENUENTER
NOTES:
• The value for Amps is a product of the Ct-n value and the Ct-S value.
• Ct-n and Ct-S are dictated by primary current; Ct-d is secondary current.
-
-
Press Enter Use buttons to set Ct-n Ct-d cannot be changed Use buttons to select
scaling
6.2.5.3: Configuring PT Setting
The PT Setting has three parts: Pt-n (numerator), Pt-d (denominator), and Pt-S (scaling).
1. Press the Enter button when Pt is in the A window. The PT-n screen appears. You
can either:
• Change the value for the PT numerator.
• Access one of the other PT screens by pressing the Enter button: press Enter
once to access the Pt-d screen, twice to access the Pt-S screen.
a. To change the value for the PT numerator or denominator:
From the Pt-n or Pt-d screen:
• Use the Down button to select the number value for a digit.
• Use the Right button to move to the next digit.
b. To change the value for the PT scaling:
From the Pt-S screen, use the Right button or the Down button to choose the
scaling you want. The Pt-S setting can be 1, 10, 100, or 1000.
NOTE: If you are prompted to enter a password, refer to Section 6.2.4 for instructions on doing so.
EM-4000 Series Meters Installation and Operation Manual
6-11
6: Using the EM-4000 Meter
A
B
C
-
MENUENTER
A
B
C
-
-
-
MENUENTER
A
B
C
-
MENUENTER
2. When the new setting is entered, press the Menu button twice.
3. The STOR ALL YES screen appears. Press Enter to save the new PT setting.
Example PT Settings:
277/277 Volts: Pt-n value is 277, Pt-d value is 277, Pt-S value is 1.
14,400/120 Volts: Pt-n value is 1440, Pt-d value is 120, Pt-S value is 10.
138,000/69 Volts: Pt-n value is 1380, Pt-d value is 69, Pt-S value is 100.
345,000/115 Volts: Pt-n value is 3450, Pt-d value is 115, Pt-S value is 100.
345,000/69 Volts: Pt-n value is 345, Pt-d value is 69, Pt-S value is 1000.
NOTE: Pt-n and Pt-S are dictated by primary voltage; Pt-d is secondary voltage.
-
-
Use buttons to set Pt-n Use buttons to set Pt-d Use buttons to select scaling
-
-
EM-4000 Series Meters Installation and Operation Manual
6-12
6.2.5.4: Configuring Connection Setting
A
B
C
-
MENUENTER
1. Press the Enter button when Cnct is in the A window. The Cnct screen appears.
2. Press the Right button or Down button to select a configuration. The choices are:
• 3 Element Wye (3 EL WYE)
• 2.5 Element Wye (2.5EL WYE)
• 2 CT Delta (2 Ct dEL)
NOTE: If you are prompted to enter a password, refer to Section 6.2.4 for instructions on doing so.
3. When you have made your selection, press the Menu button twice.
6: Using the EM-4000 Meter
4. The STOR ALL YES screen appears. Press Enter to save the setting.
-
-
Use buttons to select configuration
6.2.5.5: Configuring Communication Port Setting
Port configuration consists of: Address (a three digit number), Baud Rate (9600;
19200; 38400; or 57600), and Protocol (Modbus® RTU or Modbus® ASCII).
1. Press the Enter button when POrt is in the A window. The Adr (address) screen
appears. You can either:
• Enter the address.
• Access one of the other Port screens by pressing the Enter button: press Enter
once to access the bAUd screen (Baud Rate), twice to access the Prot screen
(Protocol).
EM-4000 Series Meters Installation and Operation Manual
6-13
6: Using the EM-4000 Meter
A
B
C
-
-
-
MENUENTER
A
B
C
-
MENUENTER
A
B
C
-
-
-
MENUENTER
a. To enter the Address:
From the Adr screen:
• Use the Down button to select the number value for a digit.
• Use the Right button to move to the next digit.
b. To select the Baud Rate:
From the bAUd screen, use the Right button or the Down button to select the
setting you want.
c. To select the Protocol:
From the Prot screen, press the Right button or the Down button to select the
setting you want.
NOTE: If you are prompted to enter a password, refer to Section 6.2.4 for instructions on doing so.
2. When you have finished making your selections, press the Menu button twice.
3. The STOR ALL YES screen appears. Press Enter to save the settings.
-
-
Use buttons to enter Address Use buttons to select Baud Rate Use buttons to select Protocol
EM-4000 Series Meters Installation and Operation Manual
6-14
6.2.6: Using Operating Mode
Operating mode is the EM-4000 meter’s default mode, that is, the standard front
panel display. After starting up, the meter automatically scrolls through the parameter
screens, if scrolling is enabled. Each parameter is shown for 7 seconds, with a 1 second pause between parameters. Scrolling is suspended for 3 minutes after any button
is pressed.
1. Press the Down button to scroll all the parameters in Operating mode. The
currently “Active,” i.e., displayed, parameter has the Indicator light next to it, on
the right face of the meter.
2. Press the Right button to view additional readings for that parameter. The table
below shows possible readings for Operating Mode. Sheet 2 in Appendix A shows
the Operating mode Navigation map.
6: Using the EM-4000 Meter
NOTE: Readings or groups of readings are skipped if not applicable to the meter type
or hookup, or if they are disabled in the programmable settings.
OPERATING MODE PARAMETER READINGS
POSSIBLE READINGS
VOLTS L-NVOLTS_LNVOLTS_LN_
MAX
VOLTS L-LVOLTS_LLVOLTS_LL_MAXVOLTS_LL_MIN
AMPSAMPSAMPS_NEUTRALAMPS_MAXAMPS_MINAMPS_THD
W/VAR/PFW_VAR_PFW_VAR_PF_MA
X_POS
VA/HzVA_FREQVA_FREQ_MAXVA_FREQ_MIN
WhKWH_RECKWH_DELKWH_NETKWH_TOT
VARhKVARH_POSKVARH_NEGKVARH_NETKVARH_TOT
VAhKVAH
VOLTS_LN_
MIN
W_VAR_PF_MIN
_POS
VOLTS_LN_
THD
W_VAR_PF_
MIN_NEG
EM-4000 Series Meters Installation and Operation Manual
6-15
6.3: Understanding the % of Load Bar
0000
-
-
-
A
B
C
MENUENTER
MAX
MIN
LM1
LM2
%THD
PRG
VOLTS L-N
VOLTS L-L
AMPS
WNARP
VA/Hz
lrDA
Wh
VARh
VAh
120%-
90%-
60%-
30%-
%LOAD
MEGA
KILO
Wh Pulse
10
The 10-segment LED bar graph at the bottom left of the EM-4000 meter’s front panel
provides a graphic representation of Amps. The segments light according to the load,
as shown in the table below.
When the load is over 120% of Full Load, all segments flash “On” (1.5 secs) and “Off”
(0.5 secs).
SegmentsLoad >= % Full Load
noneno load
11%
1-215%
1-330%
1-445%
6: Using the EM-4000 Meter
1-560%
1-672%
1-784%
1-896%
1-9108%
1-10120%
All Blink>120%
The % of Load bar can be programmed through EM Series Communicator Software see the EM Series Communicator Software User Manual for instructions.
1
EM-4000 Series Meters Installation and Operation Manual
To be certified for revenue metering, power providers and utility companies must
verify that the billing energy meter performs to the stated accuracy. To confirm the
meter’s performance and calibration, power providers use field test standards to
ensure that the unit’s energy measurements are correct. Since the EM-4000 meter is
a traceable revenue meter, it contains a utility grade test pulse that can be used to
gate an accuracy standard. This is an essential feature required of all billing grade
meters.
• Refer to Figure 6.5 for an example of how this process works.
• Refer to Table 6.1 for the Wh/Pulse constants for accuracy testing.
Figure 6.4: Watt-hour Test Pulse
EM-4000 Series Meters Installation and Operation Manual
6-17
6: Using the EM-4000 Meter
-
-
-
A
B
C
MENU ENTER
MAX
MIN
LM1
LM2
%THD
PRG
VOLTS L-N
VOLTS L-L
AMPS
WNARP
VA/Hz
lrDA
Wh
VARh
VAh
120%-
90%-
60%-
30%-
%LOAD
MEGA
KILO
Wh Pulse
Comparator
Energy
Standard
Error
Results
Test PulsesEnergy Pulses
Figure 6.5: Using the Watt-hour Test Pulse
Input Voltage LevelEM-4000 Meter
Below 150V 0.500017776
Above 150V 2.000071103
Table 6.1: Infrared & KYZ Pulse Constants for Accuracy Testing - Kh Watt-hour per pulse
NOTES:
• Minimum pulse width is 90 milliseconds.
• Refer to Chapter 2, Section 2.2, for Wh Pulse specifications.
EM-4000 Series Meters Installation and Operation Manual
6-18
7: Data Logging
7.1: Overview
The EM-4000 meter has 2 MB of flash memory for data logging. The meter can log
historical trends, and sequence of events. In addition, the meter has a real-time clock
that allows all events to be time-stamped when they occur.
7.2: Available Logs
The following logs are available for the EM-4000 meter.
• Historical logs: The EM-4000 meter has three Historical logs. Each log can be independently programmed with individual trending profiles, that is, each can be used
to measure different values. You can program up to 64 parameters per log. You
also have the ability to allocate available system resources between the three logs,
7: Data Logging
to increase or decrease the size of the individual historical logs. See the EM Series Communicator Software User Manual for additional information and instructions.
• System Events log: In order to protect critical billing information, the EM-4000
meter records and logs the following information with a timestamp:
• Demand resets
• Password requests
• System startup
• Energy resets
• Log resets
• Log reads
• Programmable settings changes
All of the EM-4000 meter logs can be viewed through the Log Viewer. Refer to the EM Series Communicator Software User Manual for additional information and instructions regarding logs and the Log Viewer.
EM-4000 Series Meters Installation and Operation Manual
7-1
7: Data Logging
This page intentionally left blank.
EM-4000 Series Meters Installation and Operation Manual
7-2
A: EM-4000 Meter Navigation Maps
A: EM-4000 Meter Navigation Maps
A.1: Introduction
You can configure the EM-4000 meter and perform related tasks using the buttons on
the meter face. Chapter 6 contains a description of the buttons on the meter face and
instructions for programming the meter using them. The meter can also be programmed using software (see the EM Series Communicator Software User Manual).
A.2: Navigation Maps (Sheets 1 to 4)
The EM-4000 meter’s Navigation maps begin on the next page. The maps show in
detail how to move from one screen to another and from one Display mode to another
using the buttons on the face of the meter. All Display modes automatically return to
Operating mode after 10 minutes with no user activity.
EM-4000 Meter Navigation Map Titles:
• Main Menu screens (Sheet 1)
• Operating mode screens (Sheets 2)
• Reset mode screens (Sheet 3)
• Configuration mode screens (Sheet 4)
EM-4000 Series Meters Installation and Operation Manual
A-1
MAIN MENU Screen
MAIN MENU:
RSTD (blinking)
RSTE
CFG
DOWN
DOWN
MAIN MENU screen scrolls through 5 choices,
showing 3 at a time. The top choice is always the
"active" one, which is indicated by blinking the legend.
MAIN MENU:
CFG (blinking)
INFO
OPR
MAIN MENU:
OPR (blinking)
RSTD
RSTE
CONFIGURATION MODE
grid of meter settings screens with
password-protected edit capability.
See sheet 5
OPERATING MODE
grid of meter data screens.
See sheets 2 & 3
ENTER
STARTUP
sequence run once at meter startup:
2 lamp test screens, hardware information
screen, firmware version screen,
(conditional) error screens
sequence completed
RESET DEMAND MODE
sequence of screens to get password, if
required, and reset max/min data.
See sheet 4
single screen
all screens
for a display
mode
button
group of
screens
MENU
ENTER
DOWN, RIGHT
Navigation:
Editing:
Returns to previous menu from any screen in any mode
Indicates acceptance of the current screen and advances to the
next one
Navigation and edit buttons
No digits or legends are blinking. On a menu, down advances
to the next menu selection, right does nothing. In a grid of
screens, down advances to the next row, right advances to the
next column. Rows, columns, and menus all navigate circularly.
A digit or legend is blinking to indicate that it is eligible for
change. When a digit is blinking, down increases the digit
value, right moves to the next digit. When a legend is blinking,
either button advances to the next choice legend.
action taken
10 minutes
with no
user activity
Configuration Mode is not
available during a
Programmable Settings
update via a COM port.
MAIN MENU:
RSTE (blinking)
CFG
INFO
DOWN
ENTER
ENTER
ENTER
DOWN
RESET ENERGY MODE
sequence of screens to get password, if
required, and reset energy accumulators.
See sheet 4
MENU
MENU
MENU
MENU
10 minutes with no user activity
SYMBOLSBUTTONS
MAIN MENU:
INFO (blinking)
OPR
RSTD
DOWN
INFORMATION
sequence of screens to show model
information, same as STARTUP except
lamp tests omitted.
MENU
ENTER
sequence
completed
Reset Energy Mode is not available for SHVA120, SHAA5, or SHWA300.
Main Menu Screens (Sheet 1)
A: EM-4000 Meter Navigation Maps
EM-4000 Series Meters Installation and Operation Manual
A-2
A: EM-4000 Meter Navigation Maps
EM-4000 Series Meters Installation and Operation Manual
A-3
RESET_MM_NO:
RST
DMD
no (blinking)
is password required?
RIGHTRIGHT
ENTER
is password
correct?
ENTER
2 sec
RIGHTDOWN
RESET_MM_YES:
RST
DMD
yes (blinking)
reset all max &
min values
RESET_MM_CONFIRM:
RST
DMD
DONE
RESET_ENTER_PW:
PASS
#### (one # blinking)
make next digit
blink
increment
blinking digit
from MAIN MENU
(RSTD selected)
MENU
(from any
reset mode
screen)
RESET_PW_FAIL:
PASS
####
FAIL
no
ENTER
2 sec.
to previous operating
mode screen
to Main Menu
see sheet 1
see sheet 2
RESET_ENERGY_NO:
RST
ENER
no (blinking)
is password required?
RIGHTRIGHT
ENTER
RESET_ENERGY_YES:
RST
ENER
yes (blinking)
from MAIN MENU
(RSTE selected)
no
reset all max &
min values
RESET_ENERGY_CONFIRM:
RST
ENER
DONE
2 sec.
to previous operating
mode screen
see sheet 2 or3
which reset?energy
which reset?
demand
energy
yes
yes
no
demand
ENTER
yes
Thispath not available for
SHVA120, SHAA5, SHWA300
Reset Mode Screens (Sheet 3)
A: EM-4000 Meter Navigation Maps
EM-4000 Series Meters Installation and Operation Manual
A-4
See Note 1
first DOWN or RIGHT in view
access (if password required)
CFG_ENTER_PW:
PASS
### (one # blinking)
is password
correct?
ENTER
CONFIG_MENU:
SCRL (blinking)
CT
PT
CONFIG_MENU:
CT (blinking)
PT
CNCT
DOWN
CONFIG_MENU:
PT (blinking)
CNCT
PORT
DOWN
CONFIG_MENU:
CNCT (blinking)
PORT
PASS
2
DOWN
CONFIG_MENU:
PORT (blinking)
PASS
2
SCRL
DOWN
CONFIG_MENU:
PASS
2
(blinking)
SCRL
CT
DOWN
2
DOWN
SCROLL_EDIT:
SCRL
yes or no
(choice blinking if edit)
CTD_SHOW:
CT-D
1 or 5
PTN_EDIT:
PT-N
####
(one # blinking if edit)
PTD_EDIT:
PT-D
####
(one # blinking if edit)
CONNECT_EDIT:
CNCT
1 of 3 choices
(choice blinking if edit)
ADDRESS_EDIT:
ADR
###
(one # blinking if edit)
BAUD_EDIT:
BAUD
##.#
(choice blinking if edit)
PROTOCOL_EDIT:
PROT
1 of 3 choices
(choice blinking if edit)
PASSWORD_EDIT:
PASS
#### (one # blinking)
MENU
CONFIG_MENU screen
scrolls through 6 choices,
showing 3 at a time. The
top choice is always the
"active" one, indicated by
blinking the legend.
PT_MULT_EDIT:
PT-S
1 or 10 or 100 or 1000
(choice blinking if edit)
to the originating
EDIT screen
any changes?
SAVE_NO:
STOR
ALL?
no (blinking)
RIGHTRIGHT
ENTER
SAVE_YES:
STOR
ALL?
yes (blinking)
no
yes
save new
configuration
MENU
SAVE_CONFIRM:
STOR
ALL
DONE
2 sec.
reboot
ENTER
ENTER
CT_MULT_EDIT:
CT-S
1 or 10 or 100
(choice blinking if edit)
CTN_EDIT:
CT-N
####
(one # blinking if edit)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTERENTER
DOWN
RIGHT
DOWN
RIGHT
DOWN or
RIGHT
DOWN or
RIGHT
RIGHT
DOWN or
RIGHT
3
ENTER
DOWN or
RIGHT
DOWN or
RIGHT
RIGHT
DOWN or
RIGHT
ENTER
2
ENTER
DOWN
RIGHT
ENTER
DOWN
RIGHT
blink
next
digit
increment
blinking
digit
yes
Notes:
1. Initial access is view-only. View access shows the existing settings. At the
first attempt to change a setting (DOWN or RIGHT pressed), password is
requested (if enabled) and access changes to edit. Edit ac cess blinks the digit
or list choice eligible for change and lights the PRG LED.
2. Skip over password edit screen and menu selection if access is view-only
or if password is disabled.
3. Scroll setting may be changed with view or edit access.
4. ENTER accepts an edit; MENU abandons it.
ENTER
CNCT choices:
3 EL WYE,
2 CT DEL,
2.5EL WYE
PROT choices:
MOD RTU,
MOD ASCI,
DNP
See Note 1
increment
blinking
digit
toggle
scroll
setting
increment
blinking
digit
show
next
choice
blink
next
digit
blink
next
digit
show
next
choice
blink
next
digit
show
next
choice
show
next
choice
blink
next
digit
show
next
choice
blink
next
digit
increment
blinking
digit
increment
blinking
digit
DOWN
DOWN
increment
blinking
digit
MENU
MENU
MENU
MENU
2
MENU
MENU
ENTER
MENU
MENU
(per row of the originating screen)
no
to Main Menu
see sheet 1
see sheet 2 or 3
to previous operating
mode screen
Configuration Mode Screens (Sheet 4)
EM-4000 Series Meters Installation and Operation Manual
A: EM-4000 Meter Navigation Maps
A-5
A: EM-4000 Meter Navigation Maps
This page intentionally left blank.
EM-4000 Series Meters Installation and Operation Manual
A-6
B: Modbus Map and Retrieving Logs
B: Modbus® Map and Retrieving Logs
B.1: Introduction
The Modbus® Map for the EM-4000 meter gives details and information about the
possible readings of the meter and its programming. The EM-4000 meter can be
programmed using the buttons on the face of the meter (Chapter 6), or by using
software. For a programming details see the EM Series Communicator Software User Manual.
B.2: Modbus® Register Map Sections
The EM-4000 meter's Modbus® Register map includes the following sections:
Fixed Data Section, Registers 1- 47, details the meter's Fixed Information.
Meter Data Section, Registers 1000 - 12031, details the meter's Readings, including
Primary Readings, Energy Block, Demand Block, Phase Angle Block, Status Block,
THD Block, Minimum and Maximum in Regular and Time Stamp Blocks, Option Card
Blocks, and Accumulators. Operating mode readings are described in Section 6.2.6.
Commands Section, Registers 20000 - 26011, details the meter's Resets Block,
Programming Block, Other Commands Block and Encryption Block.
Programmable Settings Section, Registers 30000 - 33575, details all the setups you
can program to configure your meter.