The E-Link Gateway provides Johnson Controls® and
YORK® mechanical equipment, such as chillers and
rooftop units, with Building Automation System (BAS)
networking connectivity. It is designed with three active
serial ports: Port 1 and Port 4 are used for BAS
networking, Port 2 is reserved for connecting to the
equipment, and Port 3 provides access for auxiliary
monitoring and control.
To simplify the installation and setup, the E-Link
Gateway comes pre-configured with a series of chiller
and rooftop equipment profiles that you can choose by
selecting the correct DIP switch settings.
Several E-Link Gateway models are available for
connection to various types of input voltage and
equipment. For chillers using the OptiView™ or
Latitude Micro Panel, the E-Link Gateway consist s of a
single circuit board attached to four studs inside the
Micro Panel, using the accessory mounting kit. The
panel supplies 12 VDC input power, eliminating the
need for an external power supply.
For chillers using the IPU-II based Micro Panel, the
E-Link Gateway is installed inside the Micro Panel and
requires an additional transformer to supply power to
the E-Link Gateway. The transformer is included in the
E-Link IPU-II Installation Kit. (This kit is not available in
Europe. Use E-Link Gateway YK-ELNKE00-0.)
For other types of chillers, the E-Link Gateway is
packaged in its own enclosure. In addition to the E-Link
Gateway circuit board, a transformer is included inside
the enclosure that converts a 120- or 240-volt input to
24 VAC power.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
The E-Link Gateway is supplied as a circuit board that
can be installed directly into the equipment’s enclosure,
or can be supplied pre-mounted in an enclosure ready
for line voltage. Accessory mounting kits are used to
mount the E-link Gateway directly into OptiView
Latitude, and IPU-II based Micro Panels.
IMPORTANT: Do not install the E-Link Gateway
directly into an equipment’s enclosure without the
use of an approved installation kit.
E-Link Gateway Installation Instructions1
IMPORTANT: The E-Link Gateway is intended to
provide an input to equipment under normal
operating conditions. Use this E-Link Gateway only
as an operating control. Where failure or malfunction
of the E-Link Gateway could lead to personal injury
or property damage to the controlled equipment or
other property, additional precautions must be
designed into the control system. Incorporate and
maintain other devices, such as supervisory or
alarm systems or safety or limit controls, intended to
warn of or protect against failure or malfunction of
the E-Link Gateway.
Table 1: YORK Chiller Models (Current
Production)
Board
Number
031-02550BACnet®,
031-01095YORK Talk 2,
031-02478YORK Talk 2,
031-01065YORK Talk 2,
031-01730YORK Talk 3YN, OM RETROFITS,
031-02430YORK Talk 3YK, YT, YS, YR, YST,
331-02496BACnet®YPAL
YORK-003Modbus R T UYEWS-D1, YEAS,
1
Language
(Native)
Modbus®,
YORK Talk 2,
4,800 bits per
second (bps)
4,800 bps
4,800 bps
1,200 bps
Chiller Model
YCWL, YCUL, YCAL,
YLAA, YCRL, YLPA
YCAS, YCWS, YCRS
YCAV, YCIV, YVAA
YIA, YPC, YG, YB
CR
YD, YMC
YGAS
2
2
Table 2: E-Link Gateway Product Code Numbers
DescriptionProduct Code
Numbers
E-Link with Serial Outputs (BACnet
MS/TP, Modbus Remote Terminal Unit
[RTU], and N2)
E-Link with LONWORKS® as an OutputYK-ELNK101-0
E-Link with Serial Outputs in
1.Installing technician must verify board number in unit
prior to installation.
2.Software edition of YEWS-D1 (RHSYEWSD1) V1.08 or
later), YEAS (RHMASB V1.06 or later), YGAS
(RHMYGAS V1.03 or later) are supported.
E-Link Gateway Installation Instructions2
Mounting
!
FIG:Opti_Pnl
Figure 1: OptiView Micro Panel Connected to
E-Link Gateway
FIG:Opti_Pnl1
Figure 2: OptiView Micro Panel for YMC2
Connected to E-Link Gateway
WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies
before making electrical connections.
More than one disconnect or isolation
may be required to completely deenergize equipment. Contact with
components carrying hazardous voltage
can cause electric shock and may result
in severe personal injury or death.
OptiView Panel Installation
1. Attach the E-Link Gateway board to the studs
provided inside the chiller enclosure (Figure 1 or
Figure 2), using the four screws and washers
provided in the OptiView/Latitude installation kit.
2. Connect the communications cable (included with
the kit) from Port 2B on the E-Link Gateway to J2
on the OptiView Micro Panel. Ensure that wires are
connected according to Table 3.
3. Check for stray wire strands, which could cause
short circuits, and ensure all components are
secure.
4. Connect the BAS network to Port 1 (if the protocols
are transported by RS-485) or Port 4 (if the BAS
network is L
ONWORKS).
Note: For RS-485 2-wire operation, connect a 100
ohm 1 W resistor between COM and the E-Link
Gateway’s TB5 COM (see Figure 24).
5. Ensure jumper JP27 is set for RS-232 (see
Figure 20).
6. Connect the power harness (included with the kit)
from J2 on the E-Link Gateway to J21 on the
Optiview Micro Panel (see Figure 20).
The E-Link Gateway is now ready to be configured
using Quick Start; see the Commissioning a Standard
Applicationsection in this document.
Table 3: OptiView Wiring - E-Link Port 2B
E-Link Port 2B OptiView PortWire Color
RXGTXBlack
TXGRXRed
REFN/AShield/Drain
Table 4: BAS Wiring - E-Link Port 1
E-Link Port 1BASWire Color
++White
--Blue
REFREFBlack
E-Link Gateway Installation Instructions 3
IPU-II Panel Installation
Micro Boar
d
24 VAC
Transforme
r
Expansion
Nut
Expansion
Nut
Screw
Sheet
Metal
Screw
Resisto
r
Secondar
y
Powe
r
Wiring
Harness
Tie
Wrap
T
B5
TB 2
E-LIN
K
Transforme
r
Secondar
y
Ground
Communication
Wiring Harness
Com
Ground
T B 1
T B 5
The Resistor is used for BAS
RS485 2 Wire Connection.
Connect one end of the
Resistor to the COM o
f
TB5 (24 VAC) and the othe
r
to Port 1 COM.
Use this resistor only if the
BAS wiring utilizes a 2 Wire
communication trunk
Communication Wiring Harness:
Connect to Micro Board
TB1 as Follows:
Wire Color / Terminal
Red / +
Black / -
+
-
REFSHLD
TB 1 RS485
F
I
G
:
I
P
U
p
n
l
i
n
s
t
Terminal block location
for YCAL-D, YCAL-E, and YLAA.
Terminal block location
for YCAL-C, YCWL, and
Primary Powe
r
Wiring Harness
TB2
TB5
Y
CUL-C.
Figure 3: IPU-II Panel Installation (Installation Kit Not Available in Europe)
(Installation Kit Not Available in Europe)
1. Attach the E-Link Gateway board to the panel in
the upper right side of the enclosure using the four
expansion screws and nuts provided in the IPU-II
Panel Installation Kit (see Figure 3).
2. Attach the 24 VAC transformer to the panel to the
left of the E-Link board using two screws (see
Figure 3).
3. Connect the communications cable (included with
the kit) between the E-Link board and IPU-II Micro
board.
4. Connect the transformer to the terminal block.
5. Connect the transformer to E-Link. Secure the
wiring with tie-wraps.
6. Connect the resistor if the RS-485 2-wire operation
is required.
7. Connect the communications cable shielded
ground to the ground screw.
The E-Link Gateway is now ready to be configured
using Quick Start; see the Commissioning a Standard Application section in this document.
E-Link Gateway Installation Instructions4
Other Chiller Panel Installation
!
E-LINK
Enclosure
YORK Chiller
Micro Panel
Alternative
Mounting
Locations
FIG:MntEquip
Figure 4: Mounting on the Equipment
For all other applications, the E-Link Gateway includes
an optional enclosure. The optional enclosure does not
include communication cables due to the variety of
types and lengths that may be required.
3. Locate and remove the two plastic caps in the
bottom of the E-Link Gateway enclosure.
4. Mark an appropriate place on the enclosure for a
matching set of knock out holes. Mark and drill, or
punch, two holes in the Micro Panel.
IMPORTANT: Never install the E-Link Gateway
outside the confines of a building unless within
another enclosure rated IP 65/NEMA 4x or higher.
The E-Link Gateway can be mounted as a stand-alone
enclosure either on the outside surface of the chiller
Micro Panel (close coupled), or on a smooth surface
within close proximity of the chiller panel enclosure.
For mounting on a Micro Panel, the line voltage power
is supplied by a power source in the Micro Panel.
IMPORTANT: Make sure that the cover is securely
fastened to the enclosure and the internal ground
wire is attached before placing the Gateway in
operation. These steps help to minimize Radio
Frequency Interference (RFI) from being generated
and picked up.
Mounting on a Micro Panel
WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies
before making electrical connections.
More than one disconnect or isolation
may be required to completely
de-energize equipment. Contact with
components carrying hazardous voltage
can cause electric shock and may result
in severe personal injury or death.
5. Using two bulkhead pipe couplers, attach the
E-Link Gateway enclosure to the Micro Panel.
6. Complete wiring as described in the Applying Power section in this document.
IMPORTANT: Be careful not to damage the E-link
Gateway or Micro Panel’s circuit boards during the
installation. Protect all circuit boards from metal
chips, which may cause short circuits if left on the
boards at startup.
Note: Use of bulkhead pipe couplers provides
sufficient clearance to allow removal of the E-Link
Gateway cover.
IMPORTANT: When attaching the E-Link Gateway
to a Micro Panel, ensure the E-Link Gateway does
not impede access to other components.
To mount the E-Link Gateway on a Micro Panel:
1. Disconnect power to the chiller Micro Panel.
2. Make sure the E-link Gateway enclosure fits
properly and that no obstructions, such as internal
boards, switches, or external conduit, prevent
mounting or servicing of the panel. See Figure 4 for
examples of good mounting locations.
E-Link Gateway Installation Instructions 5
Wall Mounting
YORK Chiller
Micro Panel
Template for Mounting
on a Wall
Conduit
E-Link
Enclosure
FIG:WllMnt
Figure 5: Wall Mounting
!
!
To mount the E-Link Gateway on a wall:
IMPORTANT: When wall mounting, make sure
there is no interference with other components in the
near vicinity. Use appropriate conduit to connect the
power and communications wiring.
1. Check for proper clearances for the necessary
electrical and communications cable runs.
2. Ensure that power and communications wiring is in
compliance with all local, national, and regional
codes, and customer requirements.
3. Select a suitable location and mark the anchor
points. Ensure that the enclosure is level. See
Figure 5 for an example.
4. Drill the appropriate holes in accord an ce w ith th e
type of wall anchor used.
5. Install the enclosure on the wall.
IMPORTANT: Be careful not to damage the circuit
boards during installation.
6. Check that the mounting is secure and the wiring
connections are correct and tight. Check that no
loose wire strands or other metal objects that could
cause a short circuit are on the circuit board.
7. Complete wiring as described in the Applying Power section.
Applying Power
When using an enclosure type of E-Link Gateway,
power can be supplied from either a separate power
supply or the main terminal strip in the chiller panel.
Locate the power source within 0.9 m (3 ft) of the
E-Link Gateway, and protect it with a suitable fuse or
circuit breaker. Ensure th e power is supplied from a
dedicated source and not controlled by a programmed
switch.
If the enclosure is mounted on a wall, the wiring from
the power source to the E-Link Gateway must always
run in a suitable conduit. To obtain the best
Electromagnetic Interference (EMI) and
Electromagnetic Compatibility (EMC) performance,
ensure that the conduit is bonded to the metal of both
enclosures. Scraping the paint around the knockouts
usually helps provide a better electrical connection
between the joining parts.
WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies
before making electrical connections.
More than one disconnect or isolation
may be required to completely
de-energize equipment. Contact with
components carrying hazardous voltage
can cause electric shock and may result
in severe personal injury or death.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
E-Link Gateway Installation Instructions6
1. Connect a 1.29-1.02 mm (16-18 AWG) wire from a
reliable ground reference to the E-Link Gateway’s
incoming power ground lug. Do not remove the
existing wire that connects the ground lug to the
enclosure cover.
2. On 120 VAC applications, connect the Hot wire to
TB2 and the Neutral wire to TB1. Connect the
ground wire to a ground lug.
On 240 VAC applications, connect the Hot wire to
TB3 and the Neutral wire to TB1. Connect the
ground wire to a ground lug.
IMPORTANT: Use copper conductors only.
Make all wiring connections in accordance with
local, national, and regional regulations. Do not
exceed the E-Link Gateway’s electrical ratings.
1. Apply power and verify that the red power
FIG:PwrConn
Figure 6: Power Connection Shown as 120 VAC
Light-Emitting Diode (LED) on the IPU-II board is
on. Make sure the T-switch is set to OFF, and then
set the required Media Access Control (MAC)
address. Set the MAC address in accordance with
the system integrator to ensure that a unique
address is used. If any non-standard setup is
required, refer to the E-Link Commissioning and Troubleshooting Guide(LIT-12011238) for more
details.
Table 5: Allowable MAC Addresses
ProtocolMax Allowable Switch
Settable MAC
Addresses
BACnet MS/TP1 – 127
N21 – 127
Modbus RTU1 – 127
2. Based on the equipment to be integrated (see
Table 8) and the required BAS output protocol (see
Table 9), select the appropriate settings on
GROUP A and GROUP B switches. For equipment
points lists, refer to the Johnson Controls Portal
(Products and Services>Delivery>Products/
Service Field Support>Equipment
Integration>YORK Equipment Data Maps).
Commissioning a Standard Application
Once the E-Link Gateway has been mechanically and
electrically installed (that is, it has been located in its
enclosure, wired, and terminated appropriately), it may
be Quick Commissioned.
3. Press, hold a few seconds, then release the push
button shown in Figure 11. The status LED flashes
quickly. After the E-Link Gateway re-initializes, the
commissioning is complete.
4. When commissioning a
LONWORKS BAS output
protocol, disconnect the BAS network and cycle
the power on the E-Link Gateway to activate the
Quick St art and the
LONWORKS FTT10 ProtoCessor.
The ProtoCessor does not recognize the push
button as a trigger to reset and load the correct
conversion file. Wait a minimum of 10 minutes
before reconnecting the BAS network.
5. Check the E-Link Gateway’s LEDs. First, check the
ST ATUS LED; if the E-Link Gateway has no errors,
it flashes continuously (1/2 second on, 1/2 second
off). If the LED is not flashing continuously, see
Table 6 for possible reasons.
E-Link Gateway Installation Instructions 7
6. Place the equipment in remote oper at ing mod e to
accept commands from the E-Link Gateway. Refer
to the equipment installation literature for the
proper configuration settings.
Table 6: LED Status indication
Flash RateStatus LED Indication
LED OffNo database configuration is loaded, or no
1 FlashTerminal mode has been invoked (Switch
2 FlashesAn equipment to E-Link communications
3 FlashesA Quick Start has a configuration error.
LED OnNo errors with custom/field modified
Flashing
Continuously
input power is present.
T is on).
error has occurred.
application.
No errors with factory standard
application.
For all chillers that use the YORK T alk protocols, check
that the Port 2 communication LEDs, Red (TX) and
Green (RX), are flashing. This scenario indicates that
the chiller panel is being polled and is responding. See
Figure for the location of Port 2 communication LEDs.
What You Should Know before
Using Quick Starts
The E-Link is designed to use a set of predefined data
maps to associate equipment data with a set of fixed
BAS network variables. You are not able to make any
field changes to these data maps; attempting to do so
results in the automatic reversal of any edits that you
may have made. For any field patches, refer to your
local FSC (Field Support Center) for guidance.
The data maps used by the E-L i nk Gate way ar e based
on a collection of version controlled equipment point
lists, which are supplied by the equipment business for
the purpose of integrating equipment into BAS
networks. Unless noted otherwise, the equipment’s
data is available in these supported BAS protocols:
BACnet MS/TP, N2,
LONWORKS, and Modbus RTU.
The first release of the E-Link was positioned to
provide the equivalent functionality as offered by the
YORK MicroGateway. That release requires you to
reference point lists which are version J or earlier. All
subsequent E-link releases use point lists version K or
later.
Table 7: E-Link Releases
Firmware/Database RevisionPoint Lists
SSM4567 JCF0003BL.BINJ and earlier only
SSM4567 JCF0008BL.BINJ and earlier, or K
Quick Starts 1 through 16 all use the J version point
lists, whereas Quick Starts 17 through 33 use the K
version. The primary difference between the two
categories is that Quick Starts 1 through 16 have
limited network visible points. In this case, the available
points are those which were originally available at the
time when the MicroGateway was first released.
Quick Starts 17 and higher offer a much richer
equipment point compliment that is more reflective of
what the equipment currently makes available today.
These Quick Starts also create profiles that use more
descriptive BACnet point names, use engineering
units, and follow the BACnet Testing Laboratories™
(BTL) guidelines for compliance as a B-ASC contro ller.
In most cases, using a Quick Start that corresponds to
the equipment being integrated is sufficient to configure
the E-Link Gateway for operating on the BAS network;
however, in some circumstances, you will be required
to provide further customizing by connecting a laptop
computer onto Port 3 and then accessing the User
Reports (refer to the E-Link Gateway Commissioning and Troubleshooting Technical Bulletin [LIT-12011238]
for more information).
E-Link Gateway Installation Instructions8
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.