Johnson Controls E-Link Installation Manual

E-Link Gateway
Installation Instructions
Part No. 24-10404-9, Rev. D
Issued November 2, 2011
Supersedes April 29, 2011

Applications

The E-Link Gateway provides Johnson Controls® and YORK® mechanical equipment, such as chillers and rooftop units, with Building Automation System (BAS) networking connectivity. It is designed with three active serial ports: Port 1 and Port 4 are used for BAS networking, Port 2 is reserved for connecting to the equipment, and Port 3 provides access for auxiliary monitoring and control.
To simplify the installation and setup, the E-Link Gateway comes pre-configured with a series of chiller and rooftop equipment profiles that you can choose by selecting the correct DIP switch settings.
Several E-Link Gateway models are available for connection to various types of input voltage and equipment. For chillers using the OptiView™ or Latitude Micro Panel, the E-Link Gateway consist s of a single circuit board attached to four studs inside the Micro Panel, using the accessory mounting kit. The panel supplies 12 VDC input power, eliminating the need for an external power supply.
For chillers using the IPU-II based Micro Panel, the E-Link Gateway is installed inside the Micro Panel and requires an additional transformer to supply power to the E-Link Gateway. The transformer is included in the E-Link IPU-II Installation Kit. (This kit is not available in Europe. Use E-Link Gateway YK-ELNKE00-0.)
For other types of chillers, the E-Link Gateway is packaged in its own enclosure. In addition to the E-Link Gateway circuit board, a transformer is included inside the enclosure that converts a 120- or 240-volt input to 24 VAC power.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

The E-Link Gateway is supplied as a circuit board that can be installed directly into the equipment’s enclosure, or can be supplied pre-mounted in an enclosure ready for line voltage. Accessory mounting kits are used to mount the E-link Gateway directly into OptiView
Latitude, and IPU-II based Micro Panels.
IMPORTANT: Do not install the E-Link Gateway directly into an equipment’s enclosure without the use of an approved installation kit.
E-Link Gateway Installation Instructions 1
IMPORTANT: The E-Link Gateway is intended to provide an input to equipment under normal operating conditions. Use this E-Link Gateway only as an operating control. Where failure or malfunction of the E-Link Gateway could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the E-Link Gateway.
Table 1: YORK Chiller Models (Current
Production)
Board Number
031-02550 BACnet®,
031-01095 YORK Talk 2,
031-02478 YORK Talk 2,
031-01065 YORK Talk 2,
031-01730 YORK Talk 3 YN, OM RETROFITS,
031-02430 YORK Talk 3 YK, YT, YS, YR, YST,
331-02496 BACnet® YPAL YORK-003 Modbus R T U YEWS-D1, YEAS,
1
Language (Native)
Modbus®, YORK Talk 2, 4,800 bits per
second (bps)
4,800 bps
4,800 bps
1,200 bps
Chiller Model
YCWL, YCUL, YCAL, YLAA, YCRL, YLPA
YCAS, YCWS, YCRS
YCAV, YCIV, YVAA
YIA, YPC, YG, YB
CR
YD, YMC
YGAS
2
2
Table 2: E-Link Gateway Product Code Numbers
Description Product Code
Numbers
E-Link with Serial Outputs (BACnet MS/TP, Modbus Remote Terminal Unit [RTU], and N2)
E-Link with LONWORKS® as an Output YK-ELNK101-0 E-Link with Serial Outputs in
Enclosure E-Link with L
Enclosure E-Link OptiView/Latitude Panel
Installation Kit E-Link IPU-II Panel Installation Kit
(not available in Europe)
ONWORKS Output in
YK-ELNK100-0
YK-ELNKE00-0
YK-ELNKE01-0
YK-ELNKOLK-0
YK-ELNKSTK-0
1. Installing technician must verify board number in unit prior to installation.
2. Software edition of YEWS-D1 (RHSYEWSD1) V1.08 or later), YEAS (RHMASB V1.06 or later), YGAS (RHMYGAS V1.03 or later) are supported.
E-Link Gateway Installation Instructions2

Mounting

!
FIG:Opti_Pnl
Figure 1: OptiView Micro Panel Connected to
E-Link Gateway
FIG:Opti_Pnl1
Figure 2: OptiView Micro Panel for YMC2
Connected to E-Link Gateway
WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de­energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.

OptiView Panel Installation

1. Attach the E-Link Gateway board to the studs provided inside the chiller enclosure (Figure 1 or Figure 2), using the four screws and washers provided in the OptiView/Latitude installation kit.
2. Connect the communications cable (included with the kit) from Port 2B on the E-Link Gateway to J2 on the OptiView Micro Panel. Ensure that wires are connected according to Table 3.
3. Check for stray wire strands, which could cause short circuits, and ensure all components are secure.
4. Connect the BAS network to Port 1 (if the protocols are transported by RS-485) or Port 4 (if the BAS network is L
ONWORKS).
Note: For RS-485 2-wire operation, connect a 100 ohm 1 W resistor between COM and the E-Link Gateway’s TB5 COM (see Figure 24).
5. Ensure jumper JP27 is set for RS-232 (see Figure 20).
6. Connect the power harness (included with the kit) from J2 on the E-Link Gateway to J21 on the Optiview Micro Panel (see Figure 20).
The E-Link Gateway is now ready to be configured using Quick Start; see the Commissioning a Standard
Application section in this document. Table 3: OptiView Wiring - E-Link Port 2B
E-Link Port 2B OptiView Port Wire Color
RX GTX Black TX GRX Red REF N/A Shield/Drain
Table 4: BAS Wiring - E-Link Port 1
E-Link Port 1 BAS Wire Color
++White
--Blue REF REF Black
E-Link Gateway Installation Instructions 3
IPU-II Panel Installation
Micro Boar
d
24 VAC
Transforme
r
Expansion
Nut
Expansion
Nut
Screw
Sheet Metal
Screw
Resisto
r
Secondar
y
Powe
r
Wiring
Harness
Tie
Wrap
T
B5
TB 2
E-LIN
K
Transforme
r
Secondar
y
Ground
Communication
Wiring Harness
Com
Ground
T B 1
T B 5
The Resistor is used for BAS
RS485 2 Wire Connection.
Connect one end of the
Resistor to the COM o
f
TB5 (24 VAC) and the othe
r
to Port 1 COM.
Use this resistor only if the
BAS wiring utilizes a 2 Wire
communication trunk
Communication Wiring Harness:
Connect to Micro Board
TB1 as Follows:
Wire Color / Terminal
Red / +
Black / -
+
-
REFSHLD
TB 1 RS485
F
I
G
:
I
P
U
p
n
l
i
n
s
t
Terminal block location for YCAL-D, YCAL-E, and YLAA.
Terminal block location for YCAL-C, YCWL, and
Primary Powe
r
Wiring Harness
TB2
TB5
Y
CUL-C.
Figure 3: IPU-II Panel Installation (Installation Kit Not Available in Europe)
(Installation Kit Not Available in Europe)
1. Attach the E-Link Gateway board to the panel in the upper right side of the enclosure using the four expansion screws and nuts provided in the IPU-II Panel Installation Kit (see Figure 3).
2. Attach the 24 VAC transformer to the panel to the left of the E-Link board using two screws (see Figure 3).
3. Connect the communications cable (included with the kit) between the E-Link board and IPU-II Micro board.
4. Connect the transformer to the terminal block.
5. Connect the transformer to E-Link. Secure the wiring with tie-wraps.
6. Connect the resistor if the RS-485 2-wire operation is required.
7. Connect the communications cable shielded ground to the ground screw.
The E-Link Gateway is now ready to be configured using Quick Start; see the Commissioning a Standard Application section in this document.
E-Link Gateway Installation Instructions4

Other Chiller Panel Installation

!
E-LINK
Enclosure
YORK Chiller
Micro Panel
Alternative
Mounting Locations
FIG:MntEquip
Figure 4: Mounting on the Equipment
For all other applications, the E-Link Gateway includes an optional enclosure. The optional enclosure does not include communication cables due to the variety of types and lengths that may be required.
3. Locate and remove the two plastic caps in the bottom of the E-Link Gateway enclosure.
4. Mark an appropriate place on the enclosure for a matching set of knock out holes. Mark and drill, or punch, two holes in the Micro Panel.
IMPORTANT: Never install the E-Link Gateway outside the confines of a building unless within another enclosure rated IP 65/NEMA 4x or higher.
The E-Link Gateway can be mounted as a stand-alone enclosure either on the outside surface of the chiller Micro Panel (close coupled), or on a smooth surface within close proximity of the chiller panel enclosure.
For mounting on a Micro Panel, the line voltage power is supplied by a power source in the Micro Panel.
IMPORTANT: Make sure that the cover is securely fastened to the enclosure and the internal ground wire is attached before placing the Gateway in operation. These steps help to minimize Radio Frequency Interference (RFI) from being generated and picked up.

Mounting on a Micro Panel

WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
5. Using two bulkhead pipe couplers, attach the E-Link Gateway enclosure to the Micro Panel.
6. Complete wiring as described in the Applying Power section in this document.
IMPORTANT: Be careful not to damage the E-link Gateway or Micro Panel’s circuit boards during the installation. Protect all circuit boards from metal chips, which may cause short circuits if left on the boards at startup.
Note: Use of bulkhead pipe couplers provides sufficient clearance to allow removal of the E-Link Gateway cover.
IMPORTANT: When attaching the E-Link Gateway to a Micro Panel, ensure the E-Link Gateway does not impede access to other components.
To mount the E-Link Gateway on a Micro Panel:
1. Disconnect power to the chiller Micro Panel.
2. Make sure the E-link Gateway enclosure fits properly and that no obstructions, such as internal boards, switches, or external conduit, prevent mounting or servicing of the panel. See Figure 4 for examples of good mounting locations.
E-Link Gateway Installation Instructions 5

Wall Mounting

YORK Chiller
Micro Panel
Template for Mounting
on a Wall
Conduit
E-Link
Enclosure
FIG:WllMnt
Figure 5: Wall Mounting
!
!
To mount the E-Link Gateway on a wall:
IMPORTANT: When wall mounting, make sure there is no interference with other components in the near vicinity. Use appropriate conduit to connect the power and communications wiring.
1. Check for proper clearances for the necessary electrical and communications cable runs.
2. Ensure that power and communications wiring is in compliance with all local, national, and regional codes, and customer requirements.
3. Select a suitable location and mark the anchor points. Ensure that the enclosure is level. See Figure 5 for an example.
4. Drill the appropriate holes in accord an ce w ith th e type of wall anchor used.
5. Install the enclosure on the wall.
IMPORTANT: Be careful not to damage the circuit boards during installation.
6. Check that the mounting is secure and the wiring connections are correct and tight. Check that no loose wire strands or other metal objects that could cause a short circuit are on the circuit board.
7. Complete wiring as described in the Applying Power section.

Applying Power

When using an enclosure type of E-Link Gateway, power can be supplied from either a separate power supply or the main terminal strip in the chiller panel. Locate the power source within 0.9 m (3 ft) of the E-Link Gateway, and protect it with a suitable fuse or circuit breaker. Ensure th e power is supplied from a dedicated source and not controlled by a programmed switch.
If the enclosure is mounted on a wall, the wiring from the power source to the E-Link Gateway must always run in a suitable conduit. To obtain the best Electromagnetic Interference (EMI) and Electromagnetic Compatibility (EMC) performance, ensure that the conduit is bonded to the metal of both enclosures. Scraping the paint around the knockouts usually helps provide a better electrical connection between the joining parts.
WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
E-Link Gateway Installation Instructions6
1. Connect a 1.29-1.02 mm (16-18 AWG) wire from a reliable ground reference to the E-Link Gateway’s incoming power ground lug. Do not remove the existing wire that connects the ground lug to the enclosure cover.
2. On 120 VAC applications, connect the Hot wire to TB2 and the Neutral wire to TB1. Connect the ground wire to a ground lug.
On 240 VAC applications, connect the Hot wire to TB3 and the Neutral wire to TB1. Connect the ground wire to a ground lug.
IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the E-Link Gateway’s electrical ratings.
1. Apply power and verify that the red power
FIG:PwrConn
Figure 6: Power Connection Shown as 120 VAC
Light-Emitting Diode (LED) on the IPU-II board is on. Make sure the T-switch is set to OFF, and then set the required Media Access Control (MAC) address. Set the MAC address in accordance with the system integrator to ensure that a unique address is used. If any non-standard setup is required, refer to the E-Link Commissioning and Troubleshooting Guide (LIT-12011238) for more details.
Table 5: Allowable MAC Addresses
Protocol Max Allowable Switch
Settable MAC Addresses
BACnet MS/TP 1 – 127 N2 1 – 127 Modbus RTU 1 – 127
2. Based on the equipment to be integrated (see Table 8) and the required BAS output protocol (see Table 9), select the appropriate settings on GROUP A and GROUP B switches. For equipment points lists, refer to the Johnson Controls Portal
(Products and Services>Delivery>Products/ Service Field Support>Equipment Integration>YORK Equipment Data Maps).

Commissioning a Standard Application

Once the E-Link Gateway has been mechanically and electrically installed (that is, it has been located in its enclosure, wired, and terminated appropriately), it may be Quick Commissioned.
3. Press, hold a few seconds, then release the push button shown in Figure 11. The status LED flashes quickly. After the E-Link Gateway re-initializes, the commissioning is complete.
4. When commissioning a
LONWORKS BAS output
protocol, disconnect the BAS network and cycle the power on the E-Link Gateway to activate the Quick St art and the
LONWORKS FTT10 ProtoCessor.
The ProtoCessor does not recognize the push button as a trigger to reset and load the correct conversion file. Wait a minimum of 10 minutes before reconnecting the BAS network.
5. Check the E-Link Gateway’s LEDs. First, check the ST ATUS LED; if the E-Link Gateway has no errors, it flashes continuously (1/2 second on, 1/2 second off). If the LED is not flashing continuously, see Table 6 for possible reasons.
E-Link Gateway Installation Instructions 7
6. Place the equipment in remote oper at ing mod e to accept commands from the E-Link Gateway. Refer to the equipment installation literature for the proper configuration settings.
Table 6: LED Status indication
Flash Rate Status LED Indication
LED Off No database configuration is loaded, or no
1 Flash Terminal mode has been invoked (Switch
2 Flashes An equipment to E-Link communications
3 Flashes A Quick Start has a configuration error. LED On No errors with custom/field modified
Flashing Continuously
input power is present.
T is on).
error has occurred.
application. No errors with factory standard
application.
For all chillers that use the YORK T alk protocols, check that the Port 2 communication LEDs, Red (TX) and Green (RX), are flashing. This scenario indicates that the chiller panel is being polled and is responding. See Figure for the location of Port 2 communication LEDs.

What You Should Know before Using Quick Starts

The E-Link is designed to use a set of predefined data maps to associate equipment data with a set of fixed BAS network variables. You are not able to make any field changes to these data maps; attempting to do so results in the automatic reversal of any edits that you may have made. For any field patches, refer to your local FSC (Field Support Center) for guidance.
The data maps used by the E-L i nk Gate way ar e based on a collection of version controlled equipment point lists, which are supplied by the equipment business for the purpose of integrating equipment into BAS networks. Unless noted otherwise, the equipment’s data is available in these supported BAS protocols: BACnet MS/TP, N2,
LONWORKS, and Modbus RTU.
The first release of the E-Link was positioned to provide the equivalent functionality as offered by the YORK MicroGateway. That release requires you to reference point lists which are version J or earlier. All subsequent E-link releases use point lists version K or later.
Table 7: E-Link Releases
Firmware/Database Revision Point Lists
SSM4567 JCF0003BL.BIN J and earlier only SSM4567 JCF0008BL.BIN J and earlier, or K
Quick Starts 1 through 16 all use the J version point lists, whereas Quick Starts 17 through 33 use the K version. The primary difference between the two categories is that Quick Starts 1 through 16 have limited network visible points. In this case, the available points are those which were originally available at the time when the MicroGateway was first released.
Quick Starts 17 and higher offer a much richer equipment point compliment that is more reflective of what the equipment currently makes available today. These Quick Starts also create profiles that use more descriptive BACnet point names, use engineering units, and follow the BACnet Testing Laboratories™ (BTL) guidelines for compliance as a B-ASC contro ller.
In most cases, using a Quick Start that corresponds to the equipment being integrated is sufficient to configure the E-Link Gateway for operating on the BAS network; however, in some circumstances, you will be required to provide further customizing by connecting a laptop computer onto Port 3 and then accessing the User Reports (refer to the E-Link Gateway Commissioning and Troubleshooting Technical Bulletin [LIT-12011238] for more information).
E-Link Gateway Installation Instructions8
Loading...
+ 18 hidden pages