Johnson Controls EUE17A, EBE17A, EUE15A, EBE12A, EUE12A Installation Manual

...
INSTALLATION MANUAL
®
ELECTRIC FURNACE
MODELS: EBE*/EUE* Downflow/Upflow
For Installation In:
2. Recreational Vehicles & Park Models
3. Modular Homes & Buildings
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ELECTRIC FURNACE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . .4
LIST OF FIGURES
Furnace Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Alcove & Closet Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Upflow Closet Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Duct Connector Depth (7990 Series) . . . . . . . . . . . . . . . . . . . . . . . . . .4
Duct Connector Dimensions (7990 Series) . . . . . . . . . . . . . . . . . . . . . 4
Recommended Floor Cut-out (7990 Series) . . . . . . . . . . . . . . . . . . . .4
Duct Connector Screw Attachment (7990 Series) . . . . . . . . . . . . . . . . 5
Duct Connector Tab Attachment (7990 Series) . . . . . . . . . . . . . . . . . .5
Installation of Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LIST OF TABLES
Duct Connector for Electric Furnaces . . . . . . . . . . . . . . . . . . . . . . . . .4
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
THERMOSTAT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
OPTIONAL AIR CONDITIONING ACCESSORIES . . . . . . . . . . . . . . 8
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Field Wiring Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
EBE10*/EUE10* Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
EBE12*/EUE12* Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
EBE15*/EUE15* Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
EBE17*/EUE17* Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
EBE20*/EUE20* Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
EBE23*/EUE23* Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
EBE/EUE Series Blower Performance . . . . . . . . . . . . . . . . . . . . . . . . 6
Physical and Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

SECTION I: GENERAL

The following list includes important facts and information regarding the EBE/EUE furnace and its packaging inclusions:
1. Furnace is rated at 240 volts, 60 Hz, single phase.
2. Filters are furnished with EBE model, and are the same for all EBE models - 16 x 20 x 1 in top and 20 x 20 x 1 in the louvered door. No filters are furnished with EUE models. External filter base and/or filter rack is needed for field installation.
3. Furnace size is the same for all models. See Figure 1.
4. Four-wire thermostat operation for heating and cooling.
5. Coil cavity built into furnace (coil shelf accessory required for EBE model).
6. All furnaces are equipped with an air conditioner blower and is A/C or Heat Pump ready (coil shelf accessory required for EBE model).
7. Holding strap furnished on top rear of furnace.
8. The EBE furnace is designed for downflow application, and the EUE furnace is designed for upflow application.
9. This furnace must not be operated without the front panel installed.
NOTICE
This furnace and its components listed on the A/C and Heat Pump equipment sticker are listed in combination as a system by Under­writer's Laboratories for the United States and Canada.
24”
SUB-BASE, IF USED, ADDS 7/8” MORE TO TOTAL HEIGHT AND 3/8” TO WIDTH.
THERMOSTAT WIRING ENTRY
FIELD WIRING ENTRY
J H
A
B
C
FIGURE 1: Furnace Dimensions
K
E
F
G
D
19-5/8”
M
L
51-5/8”
N
OPTIONAL BOTTOM FIELD WIRING ENTRY
A
B C
D
E F
G
H
J
K
L M
N
1-7/8”
2-5/8”
3-1/2”
1”
5-1/16”
5-1/2”
5-13/16”
1”
1-3/4”
7-13/16”
8-5/8”
9-7/16”
16-1/2”
A0552-001
Johnson Controls Ducted Systems 5396713-BIM-C-0319
5396713-BIM-C-0319

SECTION II: SAFETY

This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury. CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property dam­age.
!
WARNING
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified con­tractor, installer or service agency.
!
CAUTION
This product must be installed in strict compliance with the installa­tion instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
!
WARNING
FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
A fire or electrical hazard may result causing property damage, per­sonal injury or loss of life.
1. Install this electric furnace only in a location and position as speci­fied in SECTION III of these instructions.
2. Always install the electric furnace to operate within the electric fur­nace’s intended maximum outlet air temperature. Only connect the air handler to a duct system which has an external static pressure within the allowable range, as specified on the EBE/EUE rating plate.
3. When an electric furnace is installed so that supply ducts carry air circulated by the air handler to areas outside the space containing the air handler, the return air shall also be handled by duct(s) sealed to the air handler casing and terminating outside the space containing the air handler.
4. The electric furnace is not to be used for temporary heating of buildings or structures under construction.
5. The size of the unit should be based on an acceptable heat loss or gain calculation for the structure. ACCA, Manual J or other approved methods may be used.
SAFETY REQUIREMENTS
1. This electric furnace should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes.
2. Refer to the unit rating plate for the EBE/EUE model number, and then see the dimensions page of this instruction for supply air ple­num dimensions in Figure 3. The plenum must be installed accord­ing to the instructions.
3. Provide clearances from combustible materials as listed under Clearances to Combustibles.
4. Provide clearances for servicing ensuring that service access is allowed for electric furnace elements and blower.
5. Failure to carefully read and follow all instructions in this manual can result in electric furnace malfunction, death, personal injury and/or property damage.
6. Check the rating plate and power supply to be sure that the electri­cal characteristics match.
7. Electric furnace shall be installed so the electrical components are protected from water.
8. Installing and servicing heating/cooling equipment can be hazard­ous due to the electrical components. Only trained and qualified personnel should install, repair, or service heating/cooling equip­ment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating/cooling equipment, observe precautions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
9. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit. There are no shipping or spacer brackets which need to be removed.
Also check to be sure all accessories such as heater kits, suspension kits, and coils are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping.
CODES
The electric furnace must be installed in accordance with the following codes:
• Standard for the Installation of Air Conditioning and Ventilating Systems (NFPA 90A)
• Standard for the Installation of Warm Air Heating and Air Condi­tioning Systems (NFPA 90B)
• National Electric Code (NFPA 70)
• Canadian Electrical Code, Part I (CSA C22.1)
• All local codes (state/county/township).
NOTICE
All applicable codes take precedence over any recommendation made in these instructions.
2 Johnson Controls Ducted Systems
5396713-BIM-C-0319

SECTION III: UNIT INSTALLATION

LOCATION
Access for servicing is an important factor in the location of any furnace. Provide a minimum of 24” (61 cm) in front of the furnace for access to the heating elements and controls. This access may be provided by a closet door or by locating the furnace 24” (61 cm) from a facing wall or partition.
FURNACE CLEARANCE
This furnace is approved for zero (0) inch clearance to combustible material on all or any part of the furnace exterior and the inlet or outlet duct work except as stated below.
For furnaces installed in upflow application, there must be a minimum of 1” (2.54 cm) clearance from the bare surface of the outlet duct work for a distance of 3 feet (91.4 cm) from the supply air opening. This requirement is met if the duct is wrapped with an insulating material at least 1” thick and having an R-value of at least R-4.
RETURN AIR
In order for the furnace to work properly, a closet or alcove must have a certain total free area opening for return air.
For Heating Only Furnace
Minimum 200 sq. in (1290 sq. cm) free area opening. Use any return Grille with minimum 200 sq. in. free opening.
For up to 4 Ton AC & HP Applications (Standard Blower)
Minimum 250 sq. in. (1613 sq. cm) free area opening. The standard blower assembly supplied with the furnace is capable of handling up 4 Ton AC applications. Use any return grille with minimum 250 sq. in. (1613 sq. cm) free area opening.
For 5 Ton AC Applications (Accessory Blower)
Minimum 350 sq. in (2129 sq. cm) free area opening. Use 5 Ton AC blower accessory 3500-7901/A. Use any return grille with a minimum 350 sq. in. (2129 sq. cm) free area opening.
Location
For downflow applications, the return air opening can be located in a closet front door, or in a sidewall above the furnace casing, or in a lou­vered door on the furnace. If opening for the return air is located in the floor, side walls or closet door anywhere below furnace casing height, 6 inches minimum clearance must be provided on the furnace side where return is located to provide for proper air flow.
For Upflow installations, a closet that is 32 inches wide by 30 inches deep with a 30-inch wide door is necessary. This is not required if there is a return grille installed below furnace.
The return air opening can be located in a closet front door or a side­wall above the furnace casing, or in a louvered door on the furnace. If opening for the return air is located in the floor, side walls or closet door anywhere below furnace casing height, 6” (15.2 cm) minimum clearance must be provided on the furnace side where return is located to provide for proper air flow. See Figure 2. The 6” (15.2 cm) minimum clearance is not required if there is a return grille installed above the furnace height. This return grille cannot start more than three feet above the furnace height. If the louvers in the closet door have as much air flow area as the EB louvered furnace door, only 1” clearance is required.
There must be at least 2 feet of space available in front of furnace for
23” MIN.
20”
servicing the furnace when necessary.
A 6 inch clearance is required if the space
24” MIN.
between furnace and enclosure is used for return air.
20”
A0844-001
FIGURE 2: Alcove & Closet Clearances When installing furnace in a separate closet or room which is accessi-
ble only through an outside door, a minimum of 200 in
2
(1290 cm2) free opening for return air must be provided. The supply and return air must be ducted, securely attached and be sealed to the furnace casing if there are grilles in the outside door to the closet. Openings where ducts pass through walls, the floor or the ceiling must be sealed to prevent air leakage into or from closet and the living area.
NOTE:
Minimum required square
32”
inch opening dictates the height of the return air opening as discussed earlier in the section.
1-5/8” 2-3/8
MIN., MAX.
30”
Return air
25-1/2” OPENING WIDTH
pass through frame width.
30”
WIDE DOOR
CLOSET
A0877-001
FIGURE 3: Upflow Closet Clearances Provisions shall be made to permit the return of circulating air from all
rooms and living spaces, except the bathroom(s) to the circulating air supply inlet of the furnace. Failure to comply may cause improper heat­ing and may cause the furnace to cycle on the limit.
DUCT SYSTEM DESIGN
Electric furnace is designed to operate at a given static pressure. In order to assure proper air flow through the furnace, the distribution
system must be designed so that the static pressure external to the fur­nace does not exceed the static pressure rating shown on the furnace rating plate.
The number, size and placement of registers should be such that even distribution of heat is provided throughout the home.
Johnson Controls Ducted Systems 3
5396713-BIM-C-0319

SECTION IV: ELECTRIC FURNACE INSTALLATION

7900 SERIES DUCT CONNECTOR FOR EBE DOWN­FLOW
The duct connector is designed to eliminate a sub-base requirement. Table 1 provides the part number of the duct connector needed.
Provide adequate clearance for servicing.
1. Locate furnace conveniently away from wall facing or partitions to permit easy removal of components.
2. A six (6) inch space minimum should be maintained between the furnace and closet door when door is used for return air.
3. Two (2) feet of space must be available in front of furnace for future servicing (blower, element or furnace removal, etc.).
TABLE 1:
 - Indicates connector above or below could be used depending on tolerance  - Indicates connector above could be used depending on tolerance in floor  - Indicates connector below could be used depending on tolerance in floor to
DUCT CONNECTORS (7990 SERIES)
FIGURE 4: Duct Connector Depth (7990 Series) These duct connectors are for connecting the furnace to an under the
floor supply duct system. The furnace may be installed on combustible flooring without a separate sub-base.
Duct Connector for Electric Furnaces
FLOOR TO
DUCT DIMENSIONS
FINGERED
STYLE
TAB STYLE
1” (2.54 cm) 7990-6211 7990-6011
2” (5.1 cm) 7990-6221 7990-6021 3” (7.6 cm)
 
4” (10.2 cm) 7990-6241 7990-6041 5” (12.7 cm)
 
6” (15.2 cm) 7990-6261 7990-6061 7” (17.8 cm) 7990-6271 7990-6071 8” (20.3 cm) 7990-6281 7990-6081 9” (22.8 cm)
 
10” (25.4 cm) 7990-6301 7990-6101
11” (282 cm)
 
12” (30.5 cm) 7990-6321 7990-6121
13” (33 cm)
in floor to duct dimension. to duct dimension. duct dimension.
DUCT CONNECTOR
SUPPLY DUCT
DEPTH
 
FLOOR
SCREW
FLOOR JOIST
A0867-001
DUCT CONNECTORS FOR
SCREW ATTACHMENT
18-3/4
2-3/8
2-3/8
14
13
11
DUCT CONNECTORS FOR
TAB ATTACHMENT
18-3/4
14
13
DUCT CUTOUT DIMENSIONS
2-3/8
2-3/8
12
18-3/4
4-3/8
2-3/8
2-3/8
11
12
18-3/4
4-3/8
FIGURE 5: Duct Connector Dimensions (7990 Series)
CEILING CUT-OUT FOR ROOF JACK
FLOOR CUT-OUT FOR DUCT CONNECTOR
1-1/8
FLOOR
9-7/8
23-1/4
20-1/2
2-1/8
1-3/8
1
FUTURE REFRIGERANT LINE ENTRANCE
REAR WALL
MIN.
OF ENCLOSURE
2-3/4
6-3/8
15
15
3-1/4
9-3/4
20
FIGURE 6: Recommended Floor Cut-out (7990 Series)
See
Chart
.
A0868-001
See
Chart
A0869-001
FURNACE OUTLINE
OPTIONAL ELECTRIC ENTRANCE
A0875-001
4 Johnson Controls Ducted Systems
5396713-BIM-C-0319
INSTALLATION OF SCREW ATTACHMENT DUCT CONNECTOR (7990 SERIES)
1. Make floor cut out as shown in Figure 6.
2. Determine the depth of the floor cavity from the surface of the floor
to the top of the supply air duct and select the appropriate duct connector from the chart.
3. Place locating bracket (supplied with the duct connector) to the
back edge of the floor opening. See Figure 7.
LOCATOR BRACKET
NAILS, FLAT HEAD SCREWS, OR STAPLES
SCREWS
FLOOR
SUPPLY DUCT
FIGURE 7: Duct Connector Screw Attachment (7990 Series)
4. Apply a water based duct sealant to the 1/2” supply duct attach-
ment flange of the duct connector.
5. Determine which of the four positions the duct connector best cen-
ters over the supply duct and insert it through the floor cutout.
6. When properly aligned with the supply duct, secure the duct con-
nector to the floor with nails, flat head screws or staples.
7. Use screws as required to secure duct connector to supply duct.
8. Cut out the opening to the supply duct. If sealant was not used, the
installer should tape the mating flanges to provide a good air seal.
A0872-001
4. Determine which of the four positions the duct connector best cen­ters over the supply duct and insert it through the floor cutout.
5. Mark cut-out location on the supply duct and remove the duct con­nector.
6. Cut out the opening to the supply duct.
7. Bend tabs down through and back up under the supply duct.
8. Secure the duct connector to the floor with nails, flat head screws or staples.
The duct connector is designed for use on ducts down to 12" in width. When using the connector on smaller width ducts, there is not sufficient clearance to bend the tabs on two sides of the duct connector.
In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners. Holes for sheet metal screws are provided in three (3) tabs on each side of the duct connector. If more than 3 tabs need to be used to provide a more secure and air tight connection, the remaining tabs can also be fas­tened to the duct with screws after drilling the required screw holes.
INSTALLATION OF THE FURNACE
1. Remove the front panels and set the furnace onto the duct con­nector. Slide it back until the rear of the unit engages the locator bracket.
2. Secure the front of the furnace with two screws at the provided mounting holes. See Figure 9.
Secure Furnace to Floor with Two
Furnace Seated Against the Locator Bracket
.
Nails or Screws (Not Provided).
NOTICE
Duct sealant and tape must be classified as meeting HUD Standard
3280.715, U.L. Standard 181A.
INSTALLATION OF TAB ATTACHMENT DUCT CONNECTOR (7990 SERIES)
1. Make floor cut out as shown in Figure 6.
2. Determine the depth of the floor cavity from the surface of the floor to the top of the supply air duct and select the appropriate duct connector from the chart.
3. Place locating bracket (supplied with the duct connector) to the rear of the floor area for the furnace. See Figure 8.
LOCATOR BRACKET
NAILS, FLAT HEAD SCREWS, OR STAPLES
(Bend tabs under duct opening to secure to the supply duct.)
FLOOR
SUPPLY DUCT
FIGURE 8: Duct Connector Tab Attachment (7990 Series)
A0873-001
A0874-001
FIGURE 9: Installation of Furnace
3. Secure the top of the furnace to a structural member using screw through the strap at the top of the furnace. Strap may be moved to any of the holes located along the top back of the furnace. Installer may provide an equivalent method, such as screws through the casing side.
Johnson Controls Ducted Systems 5
5396713-BIM-C-0319
WIRING
Furnace wiring is complete except for the power supply and the thermo­stat wires. See wiring diagrams (Figures 13–18) for wire and fuse size. See Table 2 for ground wire sizes. Thermostat wires connect through side of furnace and should also be no smaller than 22 gauge. Power wires can enter through the side of the unit or through the auxiliary entrance, located in the bottom of the unit. (See Figure 1). When bring­ing wiring through the bottom of the furnace, cable connectors must be installed to hold wiring in place and to relieve any strain on the wiring. These connectors also serve as a seal between the furnace and the floor. Thus, additional sealing is not required.
Refer to the National Electrical Code, Canadian Electrical Code and local codes for wiring material requirements.
IMPORTANT
All installation on field wiring must be rated at 60ºC or higher.
Models for EBE/EUE15*, EBE/EUE17*, EBE/EUE20*, and EBE/ EUE23* may be connected to a single or dual branch circuit.
These units are shipped from the factory set up for dual power supply connections. For single power supply connections, jumper bars (P/N 3500-378P*) are required and are available from the factory. See Fig­ures 11 and 12.
NOTICE
The furnaces are equipped with either one or two 60 amp circuit breakers. These circuit breakers protect the wiring inside of the fur­nace in the event of a short circuit. Additionally, these breakers pro­vide a means of disconnecting the power to the unit. The circuit breakers in the furnace are not meant to protect the branch circuit wiring between the furnace and the home's breaker panel. General wire and breaker sizes are shown in Table 2. If sheathed cable is used, refer to National Electrical Code, Canadian Electrical Code and local codes for additional requirements concerning supply cir­cuit wiring. Electrical Data can be found in Table 4.
TABLE 2:
Single Branch Circuit Service 2 Leads + 1 Ground CKT #1
Nominal Circuit Load - Amps 43.8 50.5 63.8 70.4 83.8 93.8 Minimum Wire Size (90ºC) #8 #6 #4 #4 #3 #2 Minimum Wire Size (75ºC) #6 #6 #4 #3 #2 #1 Minimum Wire Size (60ºC) #6 #4 #3 #2 #1 #0 Ground Wire Size + #10 #8 #8 #8 #6 #6 Max. Fuse (or C.B.) - Amps 60 70 80 90 110 125 Dual Branch Circuit Service Branch Circuit Load - Amps 43.8 20.0 47.1 23.3 43.8 40.0 47.1 46.7 Branch Circuit Min. - Amps 54.8 25.0 58.9 29.1 54.8 50.0 58.9 58.4 Minimum Wire Size (90ºC) #8 #10 #6 #10 #8 #8 #6 #6 Minimum Wire Size (75ºC) #6 #10 #6 #10 #6 #8 #6 #6 Minimum Wire Size (60ºC) #6 #10 #4 #10 #6 #6 #4 #4
Ground Wire Size Max. Fuse (or C.B.) - Amps 60 30 60 30 60 50 60 60
NOTES:
1. Does Not require a Jumper.
2. Jumper provided for Single Branch Circuit Only.
3. Requires Jumper Bars (P/N 3500-378P).
4. Refer to National Electrical Code (NEC). Table 250-122 for Non-Sheathed Conductor Ground Wire.
TABLE 3:
Wiring Requirements
1
MODELS
4
EBE/EUE Series Blower Performance
Static Pressure (inches of w.c.)
CFM (STD. Air)
for all EBE/EUE Models
EBE10A
EUE10A
2
EBE12A
EUE12A
NOT
APPROVED
Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Hi
MH
M
ML
Lo
1607 1563 1515 1477 1434 1406 1377 1345 1390 1346 1298 1286 1253 1224 1201 1160 1241 1192 1151 1115 1097 1074 1032 1000 1099 1051 1002 979 949 912 872 855 1006 950 923 896 860 826 800 728
3
EBE15A
EUE15A
CKT #1 CKT #2 CKT #1 CKT #2 CKT #1 CKT #2 CKT #1 CKT #2
#10 #10 #10 #10 #10 #10 #10 #10
3
EBE17A
EUE17A
3
EBE20A
EUE20A
3
EBE23A
EUE23A
6 Johnson Controls Ducted Systems
5396713-BIM-C-0319
0
6
FFO
NO
N
O
F
FO
0
6
TABLE 4:
Physical and Electrical Data
1
MODEL NUMBER
D.O.E. Output
OUTPUT
60 Hz.,1 Phase
60 Hz.,1 Phase
CAPACITY
60 Hz.,1 Phase
Element Capacity
@ 240 VAC
240 VAC
230 VAC
220 VAC
2,3
EBE10A
EUE10A
3,4
EBE12A
EUE12A
5
EBE15A
EUE15A
BTU 34,000 39,000 51,000 56,000 67,000 77,000
kW 10.0 11.4 15.0 16.4 19.6 22.6
BTU 31,000 36,000 47,000 52,000 61,000 71,000
kW 9.1 10.6 13.8 15.2 17.9 20.8
BTU 29,000 33,000 43,000 48,000 57,000 65,000
kW 8.5 9.7 12.6 14.1 16.7 19.1 kW 9.6 11.2 14.4 16.0 19.2 21.6
Amps 40.0 46.7 60.0 66.7 80.0 90.0
Motor Amps @ 240 V. 4.0 Maximum
Circuit Load Amps
@ 240 V.
CKT 1 43.8 CKT 2 NA NA 20.0 23.3 40.0 46.7
50.5
5
Filter Size for EBE in top of unit only 16 x 20 x 1
Filter Size for EBE in louvered door only 20 x 20 x 1
Shipping Weights 83 84 85 86 84 86
NOTES:
1. Casing or Cabinet must be permanently grounded in accordance with N.E.C. or other applicable codes.
2. Does Not require a Jumper.
3. Approved for Single Branch Circuit Service Only.
4. Jumper provided for Single Branch Circuit Only.
5. Requires Jumper Bars (P/N 3500-378P).
!
WARNING
For personal safety be sure to turn the electrical power OFF at the household service box and at the furnace circuit breakers before attempting any service or maintenance operations. Homeowners should never perform any maintenance which requires opening electric box door.
Furnace is equipped with a protective shield over field wiring con­nection. When field wiring is completed, shield must be replaced to prevent hazard of electrical shock when using furnace disconnect. (See Figure 10.)
5
EBE17A
EUE17A
5
EBE20A
EUE20A
5
EBE23A
EUE23A
43.8 47.1 43.8 47.1
CIRCUIT BREAKERS
BLOWER
ELECTRIC PANEL
FIELD WIRING PROTECTIVE SHIELD
A0871-001
FIGURE 10: Field Wiring Shield
THERMOSTAT WIRES
3500-378P* JUMPER BARS (FOR SINGLE BRANCH CIRCUIT SERVICE)
NOTE:
As Shipped, the jumper bar assembly is set up for bottom entry. For side entry, the top lug can be removed and re-positioned, as shown, to provide proper wire bending clearances.
GROUND LUGS
A0345-001
TRANSFORMER
LIMIT SWITCHES
SEQUENCERS
CIRCUIT BREAKERS
FIGURE 11: Control Box
Johnson Controls Ducted Systems 7
5396713-BIM-C-0319

SECTION V: THERMOSTAT INSTALLATION

The adjustable heat anticipator in the thermostat is pre-set at 0.4 amps. This setting should be checked at the time of installation.
In some cases the thermostat may be a “self-setting” type in which case no amp setting is on the thermostat, eliminating the need for any field adjustment.
Thermostat should be located on an inside wall in an open area to more closely regulate average room air, preferably, where there is air move­ment back to furnace. Care should be used to locate thermostat away from hot air discharge openings, lights, etc. Locating height of thermo­stat is important. Thermostat should be located 52” to 66” (132 - 167.6 cm) above the floor. This is sometimes called the comfort zone.
If a condenser with its own Transformer shares a Heat/Cool Thermostat with this furnace, use a thermostat with isolating contacts to prevent interconnection of Class II 24 Volt Systems.
Cycle furnace using the thermostat to make sure it operates correctly. Maintenance and operating instructions are in the customer envelope
accompanying the furnace. Give the customer envelope to the home owner.
!
CAUTION
When using separate thermostats, a thermostat interlock system must be provided to prevent simultaneous operation of the furnace and air conditioner. Simultaneous operation can result in coach overheating, equipment damage and energy waste. (See Figures 13 through 18.)
Do not connect Yellow wire to thermostat until an outdoor unit is installed.

SECTION VI: OPTIONAL AIR CONDITIONING ACCESSORIES

!
WARNING
Failure to install this insulation and coil shelf kit could result in dam­age to equipment and/or personal injury. Liability and warranty from the manufacturer could also be void.
EBE Furnace Models
The EBE furnace is already equipped with a blower and control system for add-on air conditioning and heat pump. The coil shelf kit (3500-8981 for downflow coils up to 5 ton and 3500-8602 extension cabinet for any coils taller than 19-1/2”) must be installed when adding on remote air conditioning systems. With the 3500-8981 coil shelf installed in the EBE model, the coil cavity accepts coils no taller than 19-1/2”, no wider than 18-1/4” and no deeper than 20-1/2”.
EUE Furnace Models
No extension cabinet and coil shelf are needed for the EUE upflow fur­nace. The coil shelf is already installed in the EUE models. Like the above furnace models, the coil cavity accepts coils no taller than 19-1/2”, no wider than 18-1/4” and no deeper than 20-1/2”.
NOTICE
If the controls are located at the top of the unit, the furnace is an upflow furnace and the airflow is forced up through the furnace and into the airways.
HIGH PERFORMANCE BLOWER ACCESSORY PACKAGE
COOLING
THERMOSTAT
DOUBLE POLE
DOUBLE THROW SWITCH
TO
AIR CONDITIONER
FIGURE 12: Thermostat Wiring
HEATING
THERMOSTAT
TO
FURNACE
A0876-001
!
CAUTION
All areas around the line sets, drain hoses and other openings in the coil shelf should be sealed air tight. Use some moldable com­pound or caulking to seal the area. Failure to do so may result in loss of performance and premature compressor failure.
All electric furnaces are equipped with a blower and control system to add-on air conditioning and heat pumps to specified sizes. If the requirement is to achieve more air flow or cooling than specified, then the blower inside the furnace has to be replaced with an accessory blower package 3500-7901/*. This accessory blower package would deliver air conditioning up to 5-tons.
8 Johnson Controls Ducted Systems

SECTION VII: WIRING DIAGRAMS

ECM ELECTRIC FURNACE - 10kW
4
BLK (3)
ORG (4)
GRN(14)
YEL (6)
SEQUENCER
ELEMENTS
NOTE:
C
3
L
BLOWER
2
MOTOR
G
1
N
H2
H1
BRN
YEL
YEL
R
R
LIMIT
SWITCHES
ORG
L
L
HEAT
IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED. IT MUST BE REPLACED WITH TYPE 105
(HIGH)
(MED/HIGH)
(MED)
(LOW/MED)
(LOW)
ORG (4)
YEL(6)
BLK(3)
M3
M4
ORG
BLK(1)
BRN
.
YEL
LINE
LOAD
M1
M2
ORG
0
RELAY
C THERMOPLASTIC
5
4
3
2
1
GRN(12)
YEL(7)
YEL
1
8
4
2
6
YEL(13)
GRN (12)
WHT (10)
YEL(13)
WHT(11)
XFMR
RED(8)
ORG(5)
CIRCUIT #1
BREAKER
60 AMP
GND. LUG
ORG
REPLACE FILTER
WITH SAME SIZE
RED(9)
FUSE
3A
BLK(2)
WIRING MUST CONFORM TO LOCAL CODES
240 VAC.
60Hz
1 PHASE
HEAT/COOL
T'STAT
Y
G W
R
CONDENSING UNIT
CONTACTOR
LINE VOLTAGE
FIELD SUPPLY POWER LOW VOLTAGE FIELD INSTALLED CONTROL
240 VAC - 60 Hz - 1 PHASE
D.O.E. OUTPUT CAPACITY - BTU 34,000
MAX. MOTOR-FLA 3.8
SINGLE BRANCH CIRCUIT SERVICE
NOMINAL CIRCUIT LOAD-AMPS 43.8
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
C) COPPER #6
C) COPPER #6
2 LEADS +
1 GROUND
60
5396713-BIM-C-0319
WARNING
HIGH VOLTAGE
SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY. TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX, AND LOCK IT OUT.
DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT
OFF AT HOUSEHOLD SERVICE BOX. CHECK WITH A VOLTMETER
OR OTHER PROPER INSTRUMENT.
CAUTION
SERVICE CONNECTION COVER MUST BE INSTALLED.
IMPORTANT -
IF FILTERS ARE USED, CLEAN/REPLACE EACH SEASON
FIGURE 13: EBE10*/EUE10* Wiring Diagram
Johnson Controls Ducted Systems 9
- HAZARD OF ELECTRICAL SHOCK -
OR MORE OFTEN AS NEEDED.
5395383-UWD-B-1017
5396713-BIM-C-0319
4
BLK (3)
ORG (4)
GRN(14)
YEL (6)
SEQUENCER
ELEMENTS
NOTE:
C
3
L
BLOWER
2
MOTOR
G
1
N
YEL(6)
BLK(3)
BLK(1)
BRN
H2
M3
M4
H1
BRN
RED
YEL
R
R
LIMIT
SWITCHES
ORG
BLK
L
L
HEAT
IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED. IT MUST BE REPLACED WITH TYPE 105
C THERMOPLASTIC
ECM ELECTRIC FURNACE - 12kW
(MED/HIGH)
(LOW/MED)
ORG (4)
RED
M1
M2
(HIGH)
(MED)
(LOW)
ORG
LINE
LOAD
0
4
2
RELAY
5
4
3
2
1
GRN(12)
YEL(7)
YEL
1
8
6
GRN (12)
WHT (10)
YEL(13)
XFMR
YEL(13)
WHT(11)
ORG(5)
BLK
RED(8)
CIRCUIT #1
CIRCUIT #2
FUSE
3A
BLK(2)
WIRING MUST CONFORM TO LOCAL CODES
BREAKER
60 AMP
60 AMP
BREAKER
GND. LUG
REPLACE FILTER
WITH SAME SIZE
RED(9)
240 VAC.
1 PHASE
CONDENSING UNIT
CONTACTOR
LINE VOLTAGE
FIELD SUPPLY POWER LOW VOLTAGE FIELD INSTALLED CONTROL
60Hz
240 VAC - 60 Hz - 1 PHASE
D.O.E. OUTPUT CAPACITY - BTU 39,000
MAX. MOTOR-FLA 3.8
SINGLE BRANCH CIRCUIT SERVICE
NOMINAL CIRCUIT LOAD-AMPS 50.5
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
C) COPPER #6
C) COPPER #4
HEAT/COOL
T'STAT
Y
G W
R
2 LEADS +
1 GROUND
70
WARNING
HIGH VOLTAGE
SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY. TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX, AND LOCK IT OUT.
DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT
OFF AT HOUSEHOLD SERVICE BOX. CHECK WITH A VOLTMETER
OR OTHER PROPER INSTRUMENT.
CAUTION
SERVICE CONNECTION COVER MUST BE INSTALLED.
IMPORTANT -
IF FILTERS ARE USED, CLEAN/REPLACE EACH SEASON
FIGURE 14: EBE12*/EUE12* Wiring Diagram
10 Johnson Controls Ducted Systems
- HAZARD OF ELECTRICAL SHOCK -
OR MORE OFTEN AS NEEDED.
5395384-UWD-B-1017
4
BLK (3)
ORG (4)
GRN(14)
YEL (6)
RED
ELEMENTS
NOTE:
C
3
L
BLOWER
2
MOTOR
G
1
N
YEL(6)
BLK(3)
BLK(1)
SEQUENCER
RED
H3
BLK
WHT
H2
M5
M6
H1
BLK
YEL
YEL
R
R
R
LIMIT
SWITCHES
ORG
ORG
BLK
L
L
L
WHT
H4
HEAT
IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED. IT MUST BE REPLACED WITH TYPE 105
C THERMOPLASTIC
ECM ELECTRIC FURNACE - 15kW
LINE VOLTAGE FIELD SUPPLY POWER LOW VOLTAGE FIELD INSTALLED CONTROL
RED(9)
FUSE
3A
CIRCUIT 1
240 VAC.
60Hz
1 PHASE
DUAL BRANCH
CIRCUIT 2
240 VAC.
60Hz
1 PHASE
REQUIRES JUMPER BARS (P/N 3500-378/*)
(MED/HIGH)
(LOW/MED)
ORG (4)
M3
M4
BLK
(HIGH)
(MED)
(LOW)
M1
M2
0
RELAY
LINE
LOAD
4
2
5
3
2
1
GRN(12)
YEL(7)
YEL YEL
WHT
ORG
1
8
6
4
YEL(13)
ORG
YEL(13)
GRN (12)
WHT (10)
WHT(11)
XFMR
RED(8)
ORG(5)
CIRCUIT #1
BREAKER
CIRCUIT #2
BREAKER
BLK
BRN
0
4
2
RELAY
REPLACE FILTER
WITH SAME SIZE
BLK(2)
WIRING MUST CONFORM TO LOCAL CODES
GND
60 AMP
CIRCUIT SERVICE
60 AMP
GND
1
8
6
HEAT/COOL
T'STAT
Y
G W
R
CONDENSING UNIT
CONTACTOR
SINGLE BRANCH CIRCUIT SERVICE
CIRCUIT #1
BREAKER
60 AMP
60 AMP
CIRCUIT #2
BREAKER
GND. LUG
240 VAC.
60Hz
1 PHASE
240 VAC - 60 Hz - 1 PHASE
D.O.E. OUTPUT CAPACITY - BTU 51,000
MAX. MOTOR-FLA 3.8
SINGLE BRANCH CIRCUIT SERVICE
NOMINAL CIRCUIT LOAD-AMPS 63.8
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
DUAL BRANCH CIRCUIT SERVICE
BRANCH CKT. LOAD-AMPS 43.8 20.0
BRANCH CKT. MIN. AMPACITY 54.8 25.0
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
C) COPPER #4
C) COPPER #3
C) COPPER #6 #10
C) COPPER #6 #10
2 LEADS +
1 GROUND
80
4 LEADS + 2 GROUNDS CKT #1 CKT #2
60 30
5396713-BIM-C-0319
WARNING
HIGH VOLTAGE
SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY. TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX, AND LOCK IT OUT.
DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT
OFF AT HOUSEHOLD SERVICE BOX. CHECK WITH A VOLTMETER
OR OTHER PROPER INSTRUMENT.
CAUTION
SERVICE CONNECTION COVER MUST BE INSTALLED.
IMPORTANT -
IF FILTERS ARE USED, CLEAN/REPLACE EACH SEASON
FIGURE 15: EBE15*/EUE15* Wiring Diagram
Johnson Controls Ducted Systems 11
- HAZARD OF ELECTRICAL SHOCK -
OR MORE OFTEN AS NEEDED.
5395385-UWD-B-1017
5396713-BIM-C-0319
4
BLK (3)
ORG (4)
GRN(14)
YEL (6)
RED
ELEMENTS
NOTE:
C
3
L
BLOWER
2
MOTOR
G
1
N
YEL(6)
BLK(3)
BLK(1)
SEQUENCER
RED
H3
BLK
WHT
H2
M5
M6
H1
BLK
YEL
YEL
R
R
R
LIMIT
SWITCHES
ORG
ORG
BLK
L
L
L
WHT
H4
HEAT
IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED. IT MUST BE REPLACED WITH TYPE 105
C THERMOPLASTIC
ECM ELECTRIC FURNACE - 17kW
LINE VOLTAGE FIELD SUPPLY POWER LOW VOLTAGE FIELD INSTALLED CONTROL
RED(9)
FUSE
3A
CIRCUIT 1
240 VAC.
60Hz
1 PHASE
DUAL BRANCH
CIRCUIT SERVICE
CIRCUIT 2
240 VAC.
60Hz
1 PHASE
(MED/HIGH)
(LOW/MED)
ORG (4)
M3
M4
BLK
(HIGH)
(MED)
(LOW)
M1
M2
0
4
2
RELAY
LINE
LOAD
YEL(7)
YEL
WHT
8
6
5
4
3
2
1
GRN(12)
YEL
ORG
ORG
1
WHT (10)
GRN (12)
YEL(13)
XFMR
YEL(13)
WHT(11)
RED(8)
WIRING MUST CONFORM TO
CIRCUIT #1
BREAKER
CIRCUIT #2
BREAKER
BLK
BRN
0
4
2
RELAY
LOCAL CODES
60 AMP
60 AMP
1
8
6
ORG(5)
REPLACE FILTER
WITH SAME SIZE
BLK(2)
GND
GND
HEAT/COOL
T'STAT
Y
G W
R
CONDENSING UNIT
CONTACTOR
SINGLE BRANCH CIRCUIT SERVICE
CIRCUIT #1
BREAKER
60 AMP
60 AMP
CIRCUIT #2
BREAKER
GND. LUG
240 VAC.
60Hz
1 PHASE
240 VAC - 60 Hz - 1 PHASE
D.O.E. OUTPUT CAPACITY - BTU 56,000
MAX. MOTOR-FLA 3.8
SINGLE BRANCH CIRCUIT SERVICE
NOMINAL CIRCUIT LOAD-AMPS 70.4
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
DUAL BRANCH CIRCUIT SERVICE
BRANCH CKT. LOAD-AMPS 47.1 23.3
BRANCH CKT. MIN. AMPACITY 58.9 29.1
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
C) COPPER #3
C) COPPER #2
C) COPPER #6 #10
C) COPPER #4 #10
REQUIRES JUMPER BARS (P/N 3500-378/*)
2 LEADS +
1 GROUND
90
4 LEADS + 2 GROUNDS CKT #1 CKT #2
60 30
WARNING
HIGH VOLTAGE
SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY. TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX, AND LOCK IT OUT.
DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT
OFF AT HOUSEHOLD SERVICE BOX. CHECK WITH A VOLTMETER
OR OTHER PROPER INSTRUMENT.
CAUTION
SERVICE CONNECTION COVER MUST BE INSTALLED.
IMPORTANT -
IF FILTERS ARE USED, CLEAN/REPLACE EACH SEASON
FIGURE 16: EBE17*/EUE17* Wiring Diagram
12 Johnson Controls Ducted Systems
- HAZARD OF ELECTRICAL SHOCK -
OR MORE OFTEN AS NEEDED.
5395387-UWD-A-0717
4
RED
RED
NOTE:
BLK (3)
ORG (4)
GRN(14)
YEL (6)
ELEMENTS
C
3
L
BLOWER
2
MOTOR
G
1
N
YEL(6)
BLK(3)
BLK(1)
SEQUENCER
WHT
H4
H3
BLK
L
L
L
L
HEAT
M7
M8
YEL
SWITCHES
WHT
M5
M6
LIMIT
YEL
RED RED
H2
H1
BLK
ORG
R
ORG
R
BLK
R
BLK
R
IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED. IT MUST BE REPLACED WITH TYPE 105
C THERMOPLASTIC
ECM ELECTRIC FURNACE - 20kW
LINE VOLTAGE FIELD SUPPLY POWER LOW VOLTAGE FIELD INSTALLED CONTROL
RED(9)
FUSE
3A
CIRCUIT 1
240 VAC.
60Hz
1 PHASE
DUAL BRANCH
CIRCUIT SERVICE
CIRCUIT 2
240 VAC.
60Hz
1 PHASE
REQUIRES JUMPER BARS (P/N 3500-378/*)
(MED/HIGH)
(LOW/MED)
ORG (4)
M3
M4
BLK
(HIGH)
(MED)
(LOW)
M1 M2
0
RELAY
LINE
LOAD
4
2
2
1
GRN(12)
YEL(7)
YEL YEL
WHT
ORG
1
8
6
5
4
3
YEL(13)
ORG
YEL(13)
WHT (10)
GRN (12)
WHT(11)
XFMR
RED(8)
ORG(5)
CIRCUIT #1
BREAKER
BLK
CIRCUIT #2
BREAKER
BLK
BRN
0
4
2
RELAY
REPLACE FILTER
WITH SAME SIZE
BLK(2)
WIRING MUST CONFORM TO LOCAL CODES
GND
60 AMP
60 AMP
GND
1
8
6
HEAT/COOL
T'STAT
Y
G W
R
CONDENSING UNIT
CONTACTOR
SINGLE BRANCH CIRCUIT SERVICE
CIRCUIT #1
BREAKER
60 AMP
60 AMP
CIRCUIT #2
BREAKER
GND. LUG
240 VAC.
60Hz
1 PHASE
240 VAC - 60 Hz - 1 PHASE
D.O.E. OUTPUT CAPACITY - BTU 67,000
MAX. MOTOR-FLA 3.8
SINGLE BRANCH CIRCUIT SERVICE
NOMINAL CIRCUIT LOAD-AMPS 83.8
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
DUAL BRANCH CIRCUIT SERVICE
BRANCH CKT. LOAD-AMPS 43.8 40.0
BRANCH CKT. MIN. AMPACITY 54.8 50.0
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
C) COPPER #2
C) COPPER #1
C) COPPER #6 #8
C) COPPER #6 #6
2 LEADS +
1 GROUND
110
4 LEADS + 2 GROUNDS CKT #1 CKT #2
60 50
5396713-BIM-C-0319
WARNING
HIGH VOLTAGE
SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY. TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX, AND LOCK IT OUT.
DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT
OFF AT HOUSEHOLD SERVICE BOX. CHECK WITH A VOLTMETER
OR OTHER PROPER INSTRUMENT.
CAUTION
SERVICE CONNECTION COVER MUST BE INSTALLED.
IMPORTANT -
IF FILTERS ARE USED, CLEAN/REPLACE EACH SEASON
FIGURE 17: EBE20*/EUE20* Wiring Diagram
Johnson Controls Ducted Systems 13
- HAZARD OF ELECTRICAL SHOCK -
OR MORE OFTEN AS NEEDED.
5395388-UWD-A-0717
4
ORG (4)
RED
RED
NOTE:
BLK (3)
GRN(14)
YEL (6)
ELEMENTS
C
3
L
BLOWER
2
MOTOR
G
1
N
YEL(6)
BLK(3)
BLK(1)
SEQUENCER
WHT
H4
H3
BLK
L
L
L
L
HEAT
M7
M8
YEL
SWITCHES
WHT
M5
M6
LIMIT
YEL
RED
RED
H2
H1
BLK
ORG
R
ORG
R
BLK
R
BLK
R
IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED. IT MUST BE REPLACED WITH TYPE 105
C THERMOPLASTIC
ECM ELECTRIC FURNACE - 23kW
LINE VOLTAGE FIELD SUPPLY POWER LOW VOLTAGE FIELD INSTALLED CONTROL
RED(9)
FUSE
3A
CIRCUIT 1
240 VAC.
60Hz
1 PHASE
DUAL BRANCH
CIRCUIT SERVICE
CIRCUIT 2
240 VAC.
60Hz
1 PHASE
REQUIRES JUMPER BARS (P/N 3500-378/*)
(MED/HIGH)
(LOW/MED)
ORG (4)
M3
M4
BLK
(HIGH)
(MED)
(LOW)
M1 M2
0
4
2
RELAY
LINE
LOAD
WHT
8
6
5
4
3
2
1
GRN(12)
YEL(7)
YEL YEL
ORG
ORG
1
WHT (10)
GRN (12)
YEL(13)
XFMR
YEL(13)
WHT(11)
RED(8)
ORG(5)
CIRCUIT #1
BREAKER
BLK
CIRCUIT #2
BREAKER
BLK
BRN
0
8
4
2
6
RELAY
REPLACE FILTER
WITH SAME SIZE
BLK(2)
WIRING MUST CONFORM TO LOCAL CODES
GND
60 AMP
60 AMP
GND
1
HEAT/COOL
T'STAT
Y
G W
R
CONDENSING UNIT
CONTACTOR
SINGLE BRANCH CIRCUIT SERVICE
CIRCUIT #1
BREAKER
60 AMP
60 AMP
CIRCUIT #2
BREAKER
GND. LUG
240 VAC.
60Hz
1 PHASE
240 VAC - 60 Hz - 1 PHASE
D.O.E. OUTPUT CAPACITY - BTU 77,000
MAX. MOTOR-FLA 3.8
SINGLE BRANCH CIRCUIT SERVICE
NOMINAL CIRCUIT LOAD-AMPS 93.8
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
DUAL BRANCH CIRCUIT SERVICE
BRANCH CKT. LOAD-AMPS 47.1 46.7
BRANCH CKT. MIN. AMPACITY 58.9 58.4
WIRE SIZE (75
WIRE SIZE (60
MAX. FUSE SIZE (OR CB) - AMPS
C) COPPER #1
C) COPPER #0
C) COPPER #6 #6
C) COPPER #4 #4
2 LEADS +
1 GROUND
125
4 LEADS + 2 GROUNDS CKT #1 CKT #2
60 60
WARNING
HIGH VOLTAGE
SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY. TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX, AND LOCK IT OUT.
DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT
OFF AT HOUSEHOLD SERVICE BOX. CHECK WITH A VOLTMETER
OR OTHER PROPER INSTRUMENT.
CAUTION
SERVICE CONNECTION COVER MUST BE INSTALLED.
IMPORTANT -
IF FILTERS ARE USED, CLEAN/REPLACE EACH SEASON
FIGURE 18: EBE23*/EUE23* Wiring Diagram
Subject to change without notice. Published in U.S.A. 5396713-BIM-C-0319 Copyright © 2019 by Johnson Controls. All rights reserved. Supersedes: 5396713-BIM-B-0618
- HAZARD OF ELECTRICAL SHOCK -
OR MORE OFTEN AS NEEDED.
York International Corp.
5005 York Drive
Norman, OK 73069
5395389-UWD-A-0717
Loading...