Johnson Controls DSV60B-300B Installation Instructions Manual

MODEL DSV
AIR CONDITIONING UNITS
INSTALLATION INSTRUCTIONS Supersedes:145.29-IOM2 (812) Form 145.29-IOM2 (814)
MODEL DSV60B-300B
VERTICAL R-410A
AIR CONDITIONING UNITS
STYLE B
Issue Date:
August 25, 2014
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDLINES
This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and respon­sibilty of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard.
DANGER indicates an imminently haz­ardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially haz­ardous situation which, if not avoided, could result in death or serious injury.
All wiring must be in accordance with published specifications and must be performed ONLY by qualified service personnel. Johnson Controls will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this will void the manufacturers warranty and cause serious damage to prop­erty or injury to persons.
, oils,
FORM 145.29-IOM2 (814)
which it is situated, as well as sever personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized operating/service personnel. It is expected that this individual possesses independent training that will en­able them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.
CAUTION identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution. Usually and instruction will be given, together with a brief explanation.
NOTE is used to highlight additional in­formation which may be helpful to you.
2 JOHNSON CONTROLS
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls policy for continu­ous product improvement, the information contained in this document is subject to change without notice. While Johnson Controls makes no commitment to up­date or provide current information automatically to the manual owner, that information, if applicable, can be obtained by contacting the nearest Johnson Controls service office.
TABLE OF CONTENTS
Safety Symbols………………………………………………………… 2 Changeability of This Document…………………….……………….. 3
Nomenclature……………………………………….………………….. 4 Typical Installation Diagram…………………………..………………. 5 General Information……………………………………………………. 6
Pre-Installation Inspection of Equipment……………………………. 6 Installation -
Unit Mounting / Unit Weights…………..……………………………..7 Evaporator / Condenser Assembly…………….…………………… 7 Condensate Trap..…………………………………………………. 8 Ductwork………………………………………………………………. 9
Optional Accessories -
Variable Frequency Drive (VFD)………..……………………………9 Hot Gas Bypass (HGBP)……….…………….………………………10
Air Side Economizer…………….…………….………………………10 Discharge Plenum…………….……………..……..…………………11 Low Ambient Damper…………….…………..………………………12
Blower Discharge Conversion……..………………………………....13
Electrical Wiring / Electrical Data………………………………….. 13 Fan Performance Data……………………………………………….. 15
Motor and Pulley Data / Blower Speed Adjustment…………… 19
Start-Up and Operation………………………………………………. 21
Refrigerant Charges………………………………………………. 21 Pressure Switch Settings…………………………………………. 21
Microprocessor Controller……………………………………....…… 22
Operation……………………………….………………………….. 22
Microprocessor Flash Codes…………………………………….. 24 Maintenance/Service………………………………………………… 25 Appendix A: Unit Dimensional Drawings…………………………… 26 Appendix B: Typical Service Clearances……………………………36 Appendix C: Typical Wiring Schematics…………………………… 37
R-410A Service Procedures - Quick Reference Guide…………… 47
FORM 145.29-IOM2 (814)
It is the responsibility of operating/service personnel as to the applicability of these documents to the equipment in question. If there is any question in the mind of operating/service personnel as to the applicability of these documents, then, prior to working on the equipment, they should verify with the owner whether the equipment has been modified and if current literature is available.
JOHNSON CONTROLS 3
NOMENCLATURE
Product Category
DS =
Miscellaneous Options
A = None D = Condensate Overflow Switch
Product Indentifier
V = Vertical, Free Standing Heating Options
0 = None
Nominal Capacity
060 = 5 TON Refrigerant Circuit Options 096 = 8 TON Design Series A = None 120 = 10 TON
B= Current B = Hot Gas Bypass 144 = 12 TON 180 = 15 TON 240 = 20 TON
VOLTAGE Condenser Drive Options
300 = 25TON
2 = 208/230-60-3
1 = Std Motor & Drive
4 = 460-60-3
2 = High Static Drive
5 = 575-60-3
Control Options
M = Std Microprocessor Controls Outdoor Air-side Options
A = Std Air-Side coil C = Corrosion Protective Coating
ID Motor
1 = Std 2 = High Static Indoor Air-side Options 3 = Std cw VFD*
A = Std Air-Side coil
4 = High Static cw VFD* C = Corrosion Protective Coating
D = Stainless Steel Drain Pan F = Coated Coil w/ S-S Drain Pan
Supply Air Discharge Configuration
V= Top Ve rtical H=Front Horizontal
* VFD OPTION AVAILABLE ONLY ON 10 TONS AND UP
Integral Air-Cooled Packaged A/C, R-410A
1AAMV2HDS120
B
1,2312134,5,6891071116
0
A
14
15A17
1
FORM 145.29-IOM2 (814)
4 JOHNSON CONTROLS
DSV - TYPICAL INSTALLATION DIAGRAM
FORM 145.29-IOM2 (814)
JOHNSON CONTROLS 5
FORM 145.29-IOM2 (814)
GENERAL INFORMATION
All models 8 ~ 25 tons are shipped as separate condensing unit and evaporator section modules. The 5 ton models are shipped as factory-charged unitized packages. All models are designed for freestanding mounting on the floor, or on a field fabricated structural steel stand. All models can be ordered in either top or front fan discharge.
The 5 ton model utilizes a single compressor. All 8 through 25 ton models are dual compressor units with two independent refrigerant circuits. The 8 ~ 25 ton models require field connection and charging of the refrigerant circuits. The 8 ~ 25 ton models are shipped with a nitrogen holding charge only. Refer to ‘Start-Up and Operation’ section for charge information.
All units come standard with a microprocessor control board with safety controls and troubleshooting LED (refer to Microprocessor section).
Units will operate reliably at outdoor ambient down to 50F. In applications requiring operation below this temperature, a low ambient damper accessory is available. The damper installs on the condenser air discharge, and allows operation to 0 F ambient.
ONLY QUALIFIED PERSONNEL SHOULD PERFORM INSTALLATION AND SERVICE OF THIS EQUIPMENT.
PRE-INSTALLATION INSPECTION OF EQUIPMENT
All units are factory tested to ensure safe operation and quality assembly. Units are packaged and sealed on shipping skids and shipped in first class condition. Torn and broken packaging, scratched or dented panels should be reported to carrier immediately. Internal inspection of all units should be performed prior to installation. Remove all access doors and check for visual defects that can occur during transport. Any problems found internally should be reported to carrier and manufacturer immediately. Refrigerant circuit should be checked to ensure no leaks have occurred during shipment. Install gauge set to high and low pressure ports to confirm pressure has been maintained and no leaks have occurred during shipment. Repair any damage prior to installation to ensure safe operation.
See Appendix section for unit dimensional drawings.
Record any unit damage on the Bill of Lading and report to carrier and factory immediately. Shipping and handling damages are not warranty items.
RIGGING
PRIOR TO MOUNTING UNIT, CHECK INDIVIDUAL UNIT WEIGHTS (PAGE 10) AND VERIFY LIFTING CAPACITY OF LIFTING EQUIPMENT EXCEEDS WEIGHT OF UNITS BY SAFE MARGINS. FAILURE TO DO SO MAY RESULT IN UNIT DAMAGE, PERSONAL INJURY OR EVEN DEATH.
To ensure safe installation of the unit ensure the base of the unit is continuously supported.
DETERMINE THE ACTUAL CENTER OF GRAVITY OF THE UNIT BY PERFORM­ING A TEST LIFT. LIFTING AN UNBAL­ANCED UNIT CAN CAUSE PERSONAL INJURY OR EVEN DEATH.
INSTALLATION SITE
LOCK ALL ELECTRICAL POWER SUP­PLY SWITCHES IN THE OFF POSITION BEFORE INSTALLING THE UNIT. FAIL­URE TO DISCONNECT POWER SUPPLY MAY RESULT IN ELECTRICAL SHOCK OR EVEN DEATH.
Location - To ensure unit operates at maximum efficiencies, choose a dry indoor area where the temperature is controlled between 50F and 115F. Consideration of surrounding areas should be taken when choosing a location to install the unit. Common vibration and sound levels associated with commercial equipment may be objectionable to people or equipment.
Failure to allow adequate space between units, condenser intake and discharge may result in poor unit performance and possible unit failure.
Install thermostats, air supplies and returns so that each unit will operate only on individual unit control. To assure fast drainage of condensate run-off, unit
6 JOHNSON CONTROLS
FORM 145.29-IOM2 (814)
DSV Operating Weight (Lbs)
Unit
Operating Weight
(Condenser Only)
Shipping Weight
(Condenser Only)
DSV060B
920 (620)
980 (675)
DSV096B
1240 (810)
1290 (865)
DSV120B
1325 (860)
1385 (915)
DSV144B
1560 (980)
1645 (1035)
DSV180B
1655 (1030)
1740 (1090)
DSV240B
1875 (1210)
1960 (1270)
DSV300B
2480 (1400)
2600 (1450)
Corner Bracket
can be slightly pitched in the same direction as drain pan outlet.
UNIT MOUNTING
The 5 ton model is shipped as a fully assembled integral package. The 8 ~ 25 ton models are shipped in two pieces - a separate condensing unit and evaporator module - which are intended for assembly into a freestanding vertical package on site. The unit is not designed for remote condenser / evaporator installation and must be installed as a packaged system. Installation or modification of the unit that is not described in this manual is not factory recommended nor is it factory supported. User is responsible for any damage that as a result may occur.
Flanges for all duct connections, corner securing brackets, and refrigerant tubing couplings are shipped in the condensing section of the unit for field installation. Duct flanges for evaporator return are incorporated into the filter rack.
Floor mounted units should be secured on a solid, level pad or sturdy stand. The base of the unit should be approximately 6 inches higher than the lower edge of the wall opening. This height will allow the condenser air ducts to be pitched away from the unit, offering protection from rain water entering the base pan (refer to typical installation diagram on Page 4). The use of an isolating rubber sheet is recommended to reduce vibration and noise transmission. Ensure that the entire base is continuously supported. Unit may be pitched slightly to ensure efficient drainage of condensate.
Ensure that entire base is continuously supported. DO NOT support unit at corner points only!
EVAPORATOR / CONDENSER ASSEMBLY ASSEMBLY OF SPLIT UNITS (8 - 25 TON MODELS)
- Place the condensing section in the required location.
- Carefully position the evaporator section atop the condensing section. Align all sides, the evaporator motor wire routing hole, and the refrigerant line routing holes.
- Install the securing brackets at all four corners, on the evaporator/condenser separation joint.
Securing Corner Bracket
- Units are provided with couplings to mate refrigerant piping between condenser and evaporator section. Unit with Hot Gas Bypass option will be provided with additional copper couplings for the HGBP piping. Remove shipping bracket securing spun copper ends in the condenser, this can be discarded and is not required.
- Cut off spun copper ends on each refrigerant pipe in evaporator and condenser. Cut pipe to appropriate length to fit on couplings. Ensure circuit 1 from condenser connects to circuit 1 piping in evaporator, follow same procedure for circuit 2. Do not cross circuits.
- Follow common A/C service practices by brazing copper couplings to refrigerant pipe using a flow of nitrogen gas (max. 1 psi) through the refrigerant piping to minimize contamination to internal piping. Otherwise damage to unit refrigeration components may occur. Use the service gauge ports for this procedure to introduce nitrogen flow. Once complete pressure test with nitrogen (500 psig).
- Evacuate each circuit to at least 350 microns. If gauge pressure rises above 500 microns in one minute, evacuation is incomplete or the system has a leak.
- Charge circuit(s) to the value indicated on the unit
nameplate or see section ‘Start-Up and Operation’.
JOHNSON CONTROLS 7
FORM 145.29-IOM2 (814)
Evaporator connections, couplings included with unit
Condenser piping for coupling to evaporator
Condenser Securing Bracket
- Install bushing/clamp into evaporator wiring routing hole, and pull wires through into electrical control panel from evaporator. Connect motor leads to load terminals on contactor/overload relay.
Typical Piping Connections View (8/10 TON Model without HGBP Shown)
Do not cross circuits when brazing refrigerant piping between sections.
SEPARATION OF UNITS - (DSV060B MODEL)
If separation of units is required to pass through doorways, elevators. Unit is not designed and not certified to be installed as a remote condenser and evaporator.
- Reclaim the entire refrigerant charge from each compressor circuit.
- Disconnect the evaporator motor high voltage wires. Pull all wiring into the evaporator compartment. Remove bushing/clamp from routing hole for evaporator motor wiring.
- Cut and remove sections of all liquid and suction refrigerant lines. Make two cuts in each line, approximately 6 inches above and below the evaporator floor/condenser roof.
Use a TUBING CUTTER ONLY - do not use a hacksaw to cut refrigerant tubing otherwise serious damage can occur to refrigeration system!
- Remove corner securing brackets from the outside corners of the cabinet, at the joint line between the evaporator and condenser sections.
- Remove the evaporator section.
- Refer to ‘Assembly of Split Units’ for assembly instructions.
CONDENSATE TRAP
Unit requires a field installed external condensate trap otherwise without a trap condensate can be thrown into the air stream, cause water overflow resulting in unit and property damage. This system must be trapped according to a negative pressure (draw­through) system. Use dimensions given below. Adhere to local Codes for piping external trap and condensate.
Example: Trapping a system up to 2” External static pressure
A= (1” for each 1” of maximum negative static pressure)) + 1”
B= Half of A C= A + B + Pipe Diameter
Dimensions for trapping a negative pressure system
Example: Trapping a system up to 2” External static
pressure
A= (2”) + 1” B= A/2 C= A + B + 3/4” = 5-1/4”
8 JOHNSON CONTROLS
FORM 145.29-IOM2 (814)
DUCTWORK
When installing ductwork, adhere to local Codes. Minimize duct runs and avoid abrupt changes in direction where possible. Allow ample access space for servicing of the coils and changing of filters. Perform regular maintenance on ducts to increase unit life, maintain efficient operation, and reduce accumulation of explosive dust. Refer to blower performance charts, and engineer duct runs and accessory pressure drop so as not to exceed maximum external static values. Ensure continuous running condenser intake ambient air temperature do not exceed 115oF. The condenser exhaust should discharge into an open area to prevent short cycling of hot exhaust condenser air with the condenser intake.
Louver sizing guidelines
One of the key issues in obtaining optimum performance from indoor air-conditioners is the proper selection of the condenser intake and discharge louvers. Unlike outdoor air cooled units, which intake and discharge their cooling virtually unrestricted, indoor units must overcome the resistance of grilles or louvers at the outside wall - plus the restriction of any interconnecting ductwork.
Our indoor air cooled air-conditioners are designed to accommodate the external static pressure loss associated with properly sized louvers of the "storm proof” type. This type of louver typically has a free area approximately 40-45% of the actual louver size. To determine the free area required for any given unit, adhere to the following guidelines:
- Size condenser air intakes for 350-600 feet/minute nominal velocity (Maximum recommended 700 feet/minute)
- Size condenser air discharge for 1,200-1,500 feet /minute nominal velocity (Maximum recommended 1,700 feet/minute)
The use of louvers with higher velocities than above may be employed, at the discretion of the engineer/installer, provided that the total air pressure drop does not exceed the capability of the condenser fan and motor. The use of low restriction louvers with shallow blade angles can allow higher face velocities without excessive static pressure loss.
Exceeding the static pressure capability of the condenser fan will result in insufficient condenser air volume. This will cause a loss in system capacity, and may cause compressor shut-down during high ambient periods. (Installation of an oversize condenser motor/drive, where applicable, may be considered in such cases.)
(As a general rule, these velocities will require an intake louver sized approximately 1.25 to 1.5 times the dimensions of the duct connection on the unit, and a discharge louver sized approximately 1.5 to 2 times the duct connection dimensions.)
Use only louver sections that provide different deflection angles for air discharge and air intake, to ensure the unit does not short circuit. Protect
the unit from weather conditions (rain, snow) entering through the condenser air intake. All outdoor air
ducts should pitch away from the unit, toward the outside wall. Connect all ducts to unit with canvas
section duct connectors or choose another suitable noise and vibration absorbing device.
The Manufacturer will not accept any liability resulting from incorrect instal­lation of this equipment. Follow instal­lation instructions carefully.
VARIABLE FREQUENCY DRIVE (VFD)
Optional VFD controller for the evaporator fan is available on the 10 to 25 ton models. Mounted in the in the evaporator module section, the VFD allows the operator to set the duct static. The VFD will control the frequency (speed) of the evaporator fan motor in order to meet the desired supply duct static set point. For reliable unit operation unit must have a factory installed Hot Gas Bypass circuit on refrigeration circuit # 1.
The unit does not carry a failsafe circuit to bypass the VFD and run the evaporator fan in the event of a VFD malfunction.
VFD is factory mounted and wired. The installer must field provide and install two sensor tubing lines complete with static pressure probes. Installer is required to field wire fan power wiring between evaporator and condenser as a result of the unit being shipped factory split. The power wiring can be found inside the VFD enclosure, no extra power wiring is required – sufficient length is provided. The VFD option does not include a evaporator fan bypass circuit in case of microdrive failure. Microdrive will need to be replaced to re-activate unit. In case of VFD failure the evaporator fan will stop running however unit compressors will continue to run until a low pressure safety trip is activated.
JOHNSON CONTROLS 9
FORM 145.29-IOM2 (814)
Jumper set to 4-20mA
4-20mA Output from Transducer (–COM)
Transducer Power (+EXC)
Refer to separate ‘VFD Installation and Operation Manual’ for detailed installation and operation
instructions.
Do not run evaporator fan motor below 30Hz otherwise coil freeze-up and nuisance lock-outs may occur.
Building excessive ductwork pressure can cause damage to unit or personnel
VFD Input/Output
Note: Jumper is required between contacts 10 & 11
HOT GAS BYPASS (HGBP)
Optional HGBP on the lead compressor circuit (circuit #1) meters flow of compressor discharge hot gas to the system low side in order to balance the system capacity to the space load requirement. HGBP is factory installed using an adjustable hot gas regulator. The bypassed hot gas from the compressor is discharged to the evaporator inlet (i.e.: between the TX valve and distributor) via a Tee connection.
Adjusting HGBP set point
The desired coil suction pressure or coil temperature when the HGBP valve opens is selectable by adjusting the screw on the HGBP valve. To set the load run the unit and cool down the evaporator coil by either shutting the fans or by blocking the airflow until the suction pressure drops at least 5psi below the desired evaporator coil setpoint. The next step is to allow the pressure to be raised by the bypassed gas, the screw spring adjustment can be set until the HGBP valve closes at the desired set point.
The pressure of the evaporator coil is set to maintain an evaporator coil temperature above the point where frost and coil freeze up could form.
AIR SIDE ECONOMIZER
Optional air side economizer mixing box is designed to attach the return air side of the evaporator. Mixing comes with low-leakage opposed blade dampers. Economizer is used to provide ventilation and free cooling for the JCI DSV series of vertical air handlers.
Economizer setup is done through the LCD keypad display locating on the economizer control module mounted on the mixing box. Access to the mixing box is required.
The factory supplied economizer includes: economizer module, mixing box, actuator, enthalpy sensor, temperature sensor, dampers, and wiring harness. Refer to Appendix C for economizer electrical wiring schematics.
SEQUENCE OF OPERATION High enthalpy sequence
Enthalpy sensor should be located in the outdoor air duct. When the outside air enthalpy exceeds the enthalpy set-point, the economizer module Y1-In and Y1-Out terminals are closed and economizer will be forced into the minimum damper position setting. The
DSV unit’s microprocessor board will control
mechanical cooling requirements.
Low enthalpy sequence
When the outside air enthalpy is below the enthalpy set-point, economizer module Y1-In and Y1-Out terminals are opened and free cooling is activated.
The JCI unit’s microprocessor board turns off
compressor operation.
Damper Modulation
The temperature sensor should be located in the supply discharge air duct. Locating the sensor in the discharge air provides effective 'low-limit' sensing and control. The outside-air damper remains at minimum position if the discharge air temperature is below 500 F or 100 C. If the discharge air temperature is between 500 to 560 F (100 to 13.30 C) the outside air damper will modulate between minimum position and fully open. Above 560 F (13.30 C) the outside air damper will remain in the fully open position.
10 JOHNSON CONTROLS
FORM 145.29-IOM2 (814)
Plenum Dimensions (Inches)
MODEL
W
D
H
Side Grille
Front Grille
DSV060B
52
29
24
16x12 (2x)
32x12
DSV096B
71.5
32
24
20x18 (2x)
48x18
DSV120B
71.5
32
24
20x18 (2x)
48x18
Plenum Dimensions (Inches)
MODEL
W
D
H
Side Grille
Front Grille
DSV144B
82.5
34
28
24x20 (2x)
28x20 (2x)
DSV180B
82.5
34
28
24x20 (2x)
28x20 (2x)
DSV240B
90.5
34
28
24x20 (2x)
32x20 (2x)
A B C D E
DSV060B VASE-060B-1 49.00 27.75 24.00 40.00 14.00 DSV096B/120B VASE-120B-1 66.50 36.25 26.50 58.00 19.50 DSV144B/180B VASE-180B-1 78.00 35.75 28.50 70.00 19.50
DSV240B VASE-240B-1 86.00 41.25 34.00 78.00 25.00
DSV300B VASE-300B-1 104.00 45.00 34.00 90.00 25.00
MODEL
PART NO.
MIXING BOX
DAMPER
1
FINISHED PRODUCTS
SPOT WELD WELD
INSULATE
PAINTING
NONONONO
6.75
3.625
EDB
TOP VIEW
FRONT VIEW
4
(vertical) discharge evaporator blower configuration. Discharge plenum for 5 – 10 Ton model comes with single front grille and single side grilles. The 12 – 20 Ton models come with double front grilles and single side grilles.
Discharge plenum is constructed of heavy gauge sheet metal with supply grilles mounted on three side (front, left and right sides). Discharge plenum is secured to the unit using 4X corner brackets included with plenum.
Refer to separate ‘Air Side Economizer Installation and Operation Manual’ for more detailed installation
and operation instructions.
DISCHARGE PLENUM
Optional discharge plenum is available for field mounting to the top of evaporator for the 5-20 ton models. Discharge plenum is only compatible with top
JOHNSON CONTROLS 11
FORM 145.29-IOM2 (814)
MODEL PART NO. A B C
DSV060B VADK-060B-1 47.375" 5.0" 11.875"
DSV096B/120B VADK-120B-1 66.375" 5.0" 14.125" DSV144B/180B VADK-180B-1 77.5" 5.0" 14.125"
DSV240B VADK-240B-1 85.5" 5.0" 12.875"
DSV300B VADK-300B-1 103.5" 5.0" 12.875"
LOW AMBIENT DAMPER INSTALLATION
If unit operation is required at outdoor ambient below 50 F, the optional Low Ambient Damper kit should be installed to maintain acceptable condensing pressure.
The damper is installed directly onto the intake duct connection as illustrated. The damper position is determined by refrigerant pressure. A direct-coupled electric damper actuator motor drives the damper open or closed, depending on the output signal from a proportional pressure control module. A pressure transducer senses the high-side refrigerant pressure, through a service access port, located on the liquid refrigerant line leaving the condenser. The pressure controller, complete with terminal connection blocks for wiring, is attached to a field-installed mounting bracket. Appropriate mounting hardware for the pressure control module and the damper actuator motor are provided with the kit. A routing hole is provided in the condenser corner panel, near the actuator mounting location, to allow installation of the plenum-rated cable between the motor and the control module.
12 JOHNSON CONTROLS
On dual compressor units, the pressure transducer MUST be connected to the #1 circuit liquid line fitting. Connection to the second stage refrigerant circuit will result in system malfunction.
For detailed installation instructions, refer to the
supplementary ‘Low Ambient Damper Kit’
installation instructions.
FORM 145.29-IOM2 (814)
EVAPORATOR BLOWER DISCHARGE CONVERSION
All models can be factory ordered with either front or top fan discharge.
Procedure for converting the fan discharge is similar on all models. Original drive belts will need to be replaced, see ‘Drive Belt’ section for alternate belt information.
- Remove the panel attachment screws on the alternate location access panel. Remove the panel and set aside.
- Remove blower drive belt on all models with base mounted motors.
- Remove the panel attachments screws on the blower mounting panel. Do not remove fasteners securing blowers to panel! The blowers are to remain attached to the mounting panel at all times.
- Carefully remove the blower panel assembly from the evaporator cabinet. Do not allow blower housings to contact the evaporator coil during the removal. On some models, the housing(s) will have to be "rotated" to exit through the panel opening.
- Interchange the blower panel assembly with the position of the alternate access panel. Exercise care in locating the panel. Do not allow blower housings to contact the evaporator coil. Install the attachment screws and tighten securely.
- Install the blank access panel into the remaining evaporator opening. Fasten securely.
- Install new drive belts.
- Adjust drive belts to appropriate tension. Test run
blower and observe operation for unusual sounds or vibration.
ELECTRICAL WIRING
Follow local electrical codes when making electrical connections. Units are completely factory wired for normal supply voltages (ie.208-230, 460, 575V/3Ph/60Hz) Confirm unit specifications by checking unit data plate. All electrical components are accessible through an independent electrical panel located on the "front" face of the condensing section. The electrical control boxes are located behind outer access panels. The condenser section electrical cover is installed with wiring diagrams on the inside, which must be opened to be read.
Ensure evaporator motor rotation is correct upon unit start-up. Switch any two wires at contactor if blower rotation is not correct.
DISCONNECT AND LOCK OUT POWER WHEN SERVICING UNIT. UNIT MAY START AUTOMATICALLY IF POWER IS NOT DISCONNECTED. FAILURE TO DO SO MAY RESULT IN PERSONAL IN­JURY OR DEATH DUE TO ELECTRICAL SHOCK.
If canvas flexible joints are used on ductwork, install a ground wire to the ductwork as well.
IMPORTANT: All wiring must comply with applicable local and national codes (NEC). Type and location of disconnect switches must comply with all applicable codes.
For low voltage thermostat wiring, 18 gauge wire may be used for up to 50 feet lengths. Low voltage runs up to 125 feet require 16 gauge wire.
JOHNSON CONTROLS 13
FORM 145.29-IOM2 (814)
ELECTRICAL DATA - STANDARD EVAPORATOR MOTOR
MODEL #
VOLTAGE
COMPRESSOR
EVAP.
FAN
COND. FAN
MCA
MAX FUSE
/ CCT.
BKR. AMP
QTY RLA
LRA
HP
FLA
HP
FLA
DSV060B2
208-230/3/60
1 @ 16.0
110.0
1.00
3.1
1.50
4.5
27.60
40
DSV060B4
460/3/60
1 @ 7.8
52.0
1.00
1.5
1.50
2.2
13.45
20
DSV060B5
575/3/60
1 @ 5.7
38.9
1.00
1.2
1.50
1.8
10.13
15
DSV096B2
208-230/3/60
2 @ 15.3
83.0
1.00
3.1
2.00
5.8
43.33
50
DSV096B4
460/3/60
2 @ 6.2
41.0
1.00
1.5
2.00
2.9
18.35
20
DSV096B5
575/3/60
2 @ 4.8
33.0
1.00
1.2
2.00
2.3
14.30
15
DSV120B2
208-230/3/60
2 @ 16.0
110.0
1.50
4.5
3.00
8.5
49.00
60
DSV120B4
460/3/60
2 @ 7.8
52.0
1.50
2.2
3.00
4.2
23.95
30
DSV120B5
575/3/60
2 @ 5.7
38.9
1.50
1.8
3.00
3.4
18.03
20
DSV144B2
208-230/3/60
2 @ 19.0
123.0
2.00
5.8
3.00
8.5
57.05
70
DSV144B4
460/3/60
2 @ 9.7
62.0
2.00
2.9
3.00
4.2
28.93
35
DSV144B5
575/3/60
2 @ 7.4
50.0
2.00
2.3
3.00
3.4
22.35
25
DSV180B2
208-230/3/60
2 @ 23.2
164.0
3.00
8.5
5.00
14.0
74.70
90
DSV180B4
460/3/60
2 @ 11.2
75.0
3.00
4.2
5.00
6.6
36.00
45
DSV180B5
575/3/60
2 @ 7.9
54.0
3.00
3.4
5.00
5.3
26.48
30
DSV240B2
208-230/3/60
2 @ 30.1
225.0
5.00
14.0
7.50
19.4
101.13
125
DSV240B4
460/3/60
2 @ 16.7
114.0
5.00
6.6
7.50
9.7
53.88
70
DSV240B5
575/3/60
2 @ 12.2
80.0
5.00
5.3
7.50
7.8
40.55
50
DSV300B2
208-230/3/60
2 @ 34.0
240.0
7.50
20.4
10.00
25.0
121.90
150
DSV300B4
460/3/60
2 @ 16.0
140.0
7.50
9.7
10.00
12.5
58.20
70
DSV300B5
575/3/60
2 @ 12.9
107.6
7.50
7.8
10.00
10.0
46.83
50
ELECTRICAL DATA - OVERSIZED EVAPORATOR MOTOR
MODEL #
VOLTAGE
COMPRESSOR
EVAP.
FAN
COND. FAN
MCA
MAX FUSE
/ CCT.
BKR. AMP
QTY RLA
LRA
HP
FLA
HP
FLA
DSV060B2
208-230/3/60
1 @ 16.0
110.0
1.50
4.5
1.50
4.5
29.00
45
DSV060B4
460/3/60
1 @ 7.8
52.0
1.50
2.2
1.50
2.2
14.15
20
DSV060B5
575/3/60
1 @ 5.7
38.9
1.50
1.8
1.50
1.8
10.73
15
DSV096B2
208-230/3/60
2 @ 15.3
83.0
1.50
4.5
2.00
5.8
44.73
60
DSV096B4
460/3/60
2 @ 6.2
41.0
1.50
2.2
2.00
2.9
19.05
25
DSV096B5
575/3/60
2 @ 4.8
33.0
1.50
1.8
2.00
2.3
14.90
15
DSV120B2
208-230/3/60
2 @ 16.0
110.0
2.00
5.8
3.00
8.5
50.30
60
DSV120B4
460/3/60
2 @ 7.8
52.0
2.00
2.9
3.00
4.2
24.65
30
DSV120B5
575/3/60
2 @ 5.7
38.9
2.00
2.3
3.00
3.4
18.53
20
DSV144B2
208-230/3/60
2 @ 19.0
123.0
3.00
8.5
3.00
8.5
59.75
70
DSV144B4
460/3/60
2 @ 9.7
62.0
3.00
4.2
3.00
4.2
30.23
35
DSV144B5
575/3/60
2 @ 7.4
50.0
3.00
3.4
3.00
3.4
23.45
30
DSV180B2
208-230/3/60
2 @ 23.2
164.0
5.00
14.0
5.00
14.0
80.20
100
DSV180B4
460/3/60
2 @ 11.2
75.0
5.00
6.6
5.00
6.6
38.40
45
DSV180B5
575/3/60
2 @ 7.9
54.0
5.00
5.3
5.00
5.3
28.38
35
DSV240B2
208-230/3/60
2 @ 30.1
225.0
7.50
20.4
7.50
20.4
108.53
125
DSV240B4
460/3/60
2 @ 16.7
114.0
7.50
9.7
7.50
9.7
56.98
70
DSV240B5
575/3/60
2 @ 12.2
80.0
7.50
7.8
7.50
7.8
43.05
50
14 JOHNSON CONTROLS
FAN PERFORMANCE
SUPPLY AI R BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1600 408 0.13 555 0.29 652 0.38 739 0.45 819 0.54 893 0.63 963 0.71 1029 0.81
1800 459 0.20 600 0.39 689 0.48 770 0.58 846 0.66 917 0.76 984 0.86 1047 0.96
2000 510 0.25 647 0.51 729 0.61 806 0.71 877 0.81 944 0.92 1008 1.00 1069 1.14
2200 561 0.35 695 0.65 772 0.76 843 0.88 911 0.99 975 1.10 1036 1.23 1094 1.34
2400 612 0.45 745 0.83 816 0.95 883 1.07 947 1.19 1008 1.31 1066 1.44 ~ ~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
CONDENSER FAN PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3100 513 0.50 615 0.65 706 0.80 790 0.98 867 1.15 938 1.33 1006 1.50
Hi-Static Drive
Standard Factory Drive 1.5 HP
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.0
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive +1 .5 HP
OUTDOOR
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Standard Factory Drive + 1 HP
Field Supplied Low Static
Drive
SUPPLY AI R BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2600 496 0.28 605 0.40 701 0 .50 788 0.62 868 0.74 947 0.89 1016 1.04 1045 1.19 1075 1.35 1105 1.50
2900 514 0.36 618 0.48 710 0 .60 794 0.72 872 0.86 944 0.98 1017 1.12 1075 1.28 1128 1.42 ~ ~
3200 538 0.44 636 0.58 725 0 .70 806 0.84 881 0.98 952 1.12 1018 1.26 1081 1.42 ~ ~ ~ ~
3500 571 0.56 664 0.70 748 0 .84 826 0.98 898 1.14 967 1.28 1031 1.44 ~ ~ ~ ~ ~ ~
3800 613 0.70 700 0.86 779 1 .00 853 1.16 923 1.32 989 1.48 ~ ~ ~ ~ ~ ~ ~ ~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
CONDENSER FAN PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4400 478 0.60 560 0.78 634 0 .96 702 1.14 765 1.34 824 1.54 880 1.74
Standard Factory Drive + 2 HP
Optional Hi-Static Drive + 2 HP
OUTDOOR
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Optional Hi-Static Drive + 1.5 HP
Standard Factory Drive + 1 HP
Low Static
Drive
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
DSV060B
FORM 145.29-IOM2 (814)
DSV096B
JOHNSON CONTROLS 15
Loading...
+ 33 hidden pages