NEW
MULTI-RANGE
LCD COMBO
Model DPT 260
Very Low Differential Multi-Configurable
Pressure Transducer
Unidirectional Ranges: 0.1 - 10 in. W.C.
Bidirectional Ranges: ±0.1 - 10 in. W.C.
Air or Non-Conducting Gas
Target Users
● Service/Retrofit Friendly
● Small Users - Inventory &
Installation Savings
● Sub-Contractors - Quick
Installation
● Flexible for Building
Specification Changes
● Service Technicians -
Quick and Accurate
Reconfigurations
Features
■ Standard 3 1/2 Digit LCD
SIMPLE 5 STEP SETUP -
ALL SLIDE SWITCH
OPERATION
etra Systems 260 pressure transducers
sense differential or gauge (static)
S
pressure and convert this pressure
difference to a proportional electrical output for either field selectable unidirectional or
bidirectional pressure ranges. The 260 Series is
offered with field selectable high level analog
outputs of 1 to 5, 0 to 5, and 0 to 10 VDC, or
4 to 20 mA.
Used in Building Energy Management
Systems, these transducers are capable of
measuring pressures and flows with the
performance necessary for proper building
pressurization and air flow control.
The 260 Series transducers can be configured
for air pressure ranges as low as 0.1 in. W.C. full
scale. Static standard accuracy is ±1.0% full
scale in normal ambient temperature environments. The units are temperature
compsensated to within ±0.02%FS/
(0.036%FS/oC) for zero and span.
Model Unidirectional Bidirectional
MS1 0.1, 0.25, 0.5, 1.0 in. WC FS ±0.1, 0.25, 0.5, 1.0 in. WC FS
MS2 1.0, 2.5, 5.0, 10 in. WC FS ±1.0, 2.5, 5.0, 10 in. WC FS
o
The Model 260 utilizes an all stainless steel
micro-tig welded sensor. The tensioned stainless steel diaphragm and insulated stainless
steel electrode, positioned close to the
diaphragm, form a variable capacitor. Positive
pressure moves the diaphragm toward the
electrode, increasing the capacitance. A
decrease in pressure moves the diaphragm
away from the electrode, decreasing the
capacitance. The change in capacitance is
detected and converted to a linear DC
electrical signal by Setra’s custom ASIC technology.
Optional Static Probe Designed
with a Gasket to Seal Against the
Duct.
F
Ranges
■ Field Selectable Multi-
Range
■ Field Selectable Multi-
Output
■ Fast Response Time
■ Simple 5-Step Setup - All
Slide Switch Operation
■ Field Accessible Push
Button Zero
■ Hinged Cover
■ External Mounting Tabs
■ Unregulated AC/DC
Operation
■ Microprocessor Based
Electronics - Guarantees
Range to Range Performance
■ NIST Traceable
■ Fire Retardant Case
(UL 94 V-0 Approved)
■ Meets Conformance
Standards
ISO
9001:
2000
Certified
✓
Performance Data
Thru All Field Selectable Ranges
Standard
*
Accuracy
RSS(at constant temp) ±1.0% FS
Non-Linearity, BFSL
±0.96% FS
Hysteresis 0.10% FS
Non-Repeatability 0.05% FS
Thermal Effects**
Compensated Range °F (°C) 32 to 122 (0 to 50)
Zero/Span Shift %FS/°F(°C) 0.02 (0.036)
Maximum Line Pressure 10 psi
Long Term Stability (max) 0.5% FS/1 YR MS2 & MS4
1.0% FS/1 YR MS1 & MS3
Position Effect
Zero Offset (%FS/G) 0.2%
(Unit is factory calibrated at 0g effect in the vertical position.)
* RSS of Non-Linearity, Hysteresis, and Non-Repeatability.
**Units calibrated at nominal 70˚F. Maximum thermal error computed from
this datum.
NOTE: Setra quality standards are based on ANSI-Z540-1.
The calibration of this product is NIST traceable.
Outline Drawings
4.75
120.7
4.25
108
Model 260 Specifications
Environmental Data
Temperature
Operating
Physical Description
Case Fire-Retardant Glass Filled
Mounting Two External Screw Holes
Electrical Connection Removable Screw Terminal Block
Pressure Fittings 3/16” O.D. Barbed Brass
Zero Push Button
Weight (approx.) 8 ounces
Pressure Media
Typically air or similar non-conducting gases.
Specifications subject to change without notice.
U.S. Patent nos. 4093915; 4358814; 4434203; 6019002; 6014800.
Other Patents Pending.
*
°F (°C) 32 to 122 (0 to 50)
Polyester (UL 94 V-0 Approved)
Hinged Lid
Vertical Position
Pressure Fitting
0
150
O.862
21.8
Electrical Data (Voltage)
Circuit 3-Wire (Com, Exc, Out)
Protected from Miswiring
Excitation 13 - 30 VDC/VAC
Field Selectable Output*1 to 5, 0 to 5 or 0 to 10 VDC
**
Bidirectional Output at Zero
Pressure: 1 to 5 VDC = 3 VDC
0 to 5 VDC = 2.5 VDC
0 to10 VDC = 5 VDC
Output Impedance 500 ohms
*Calibrated into a 50K ohm load, operable into a 10K ohm load or greater.
**Span (Full Scale) output factory set to within 1%.
Electrical Data (Current)
Circuit 2-Wire
Protected from Miswiring
Excitation 24V (DC Only)
Field Selectable Output
Bidirectional Output at Zero
Pressure: 12mA
External Load 0 to 800 ohms
Minimum supply voltage (VDC) = 13 Volts (at terminal)
Maximum supply voltage (VDC) = 30 Volts (at terminal)
*Calibrated at factory with a 24 VDC loop supply voltage and a 250 ohm load.
**Span (Full Scale) output factory set to wtihin ±0.16mA.
*
4 to 20mA
**
**
.59
14.9
1.49
37.8
1.25
31.7
.63
15.9
1.3
31.8
4.15
105.4
Optional Static
Probe Diagram
IN
1.03
26.3
.87
22
MM
ORDERING INFORMATION
Part Number Description
DPT260-MS1 0.1, 0.25, 0.5, 1.0 in. WC FS / ±0.1, 0.25, 0.5, 1.0 in. WC FS
DPT260-MS2 1.0, 2.5, 5.0, 10 in. WC FS / ±1.0, 2.5, 5.0, 10 in. WC FS
DPT260-MS1-SP 0.1, 0.25, 0.5, 1.0 in. WC FS / ±0.1, 0.25, 0.5, 1.0 in. WC FS with Static Probe
DPT260-MS2-SP 1.0, 2.5, 5.0, 10 in. WC FS / ±1.0, 2.5, 5.0, 10 in. WC FS with Static Probe
.51
12.9
1.50
38.1
7.7
196
9.3
236.9
JCI260 Rev. A 12/05
While we provide application assistance on all Setra products, both personally and through our literature, it is the
customer’s responsibility to determine the suitability of the product in the application.