Johnson Controls DPT 260 Catalog Page

NEW
MULTI-RANGE
LCD COMBO
Model DPT 260
Very Low Differential Multi-Configurable
Pressure Transducer
Unidirectional Ranges: 0.1 - 10 in. W.C.
Bidirectional Ranges: ±0.1 - 10 in. W.C.
Air or Non-Conducting Gas
Target Users
Service/Retrofit Friendly
Small Users - Inventory &
Installation Savings
Sub-Contractors - Quick
Installation
Flexible for Building
Specification Changes
Service Technicians -
Quick and Accurate Reconfigurations
Features
Standard 3 1/2 Digit LCD
SIMPLE 5 STEP SETUP -
ALL SLIDE SWITCH
OPERATION
etra Systems 260 pressure transducers sense differential or gauge (static)
S
pressure and convert this pressure difference to a proportional electrical out­put for either field selectable unidirectional or bidirectional pressure ranges. The 260 Series is offered with field selectable high level analog outputs of 1 to 5, 0 to 5, and 0 to 10 VDC, or 4 to 20 mA.
Used in Building Energy Management Systems, these transducers are capable of measuring pressures and flows with the performance necessary for proper building pressurization and air flow control.
The 260 Series transducers can be configured for air pressure ranges as low as 0.1 in. W.C. full
scale. Static standard accuracy is ±1.0% full
scale in normal ambient temperature en­vironments. The units are temperature
compsensated to within ±0.02%FS/
(0.036%FS/oC) for zero and span.
Model Unidirectional Bidirectional
MS1 0.1, 0.25, 0.5, 1.0 in. WC FS ±0.1, 0.25, 0.5, 1.0 in. WC FS MS2 1.0, 2.5, 5.0, 10 in. WC FS ±1.0, 2.5, 5.0, 10 in. WC FS
o
The Model 260 utilizes an all stainless steel micro-tig welded sensor. The tensioned stain­less steel diaphragm and insulated stainless steel electrode, positioned close to the diaphragm, form a variable capacitor. Positive pressure moves the diaphragm toward the electrode, increasing the capacitance. A decrease in pressure moves the diaphragm away from the electrode, decreasing the capacitance. The change in capacitance is detected and converted to a linear DC electrical signal by Setra’s custom ASIC tech­nology.
Optional Static Probe Designed with a Gasket to Seal Against the Duct.
F
Ranges
Field Selectable Multi-
Range
Field Selectable Multi-
Output
Fast Response Time
Simple 5-Step Setup - All
Slide Switch Operation
Field Accessible Push
Button Zero
Hinged Cover
External Mounting Tabs
Unregulated AC/DC
Operation
Microprocessor Based
Electronics - Guarantees Range to Range Performance
NIST Traceable
Fire Retardant Case
(UL 94 V-0 Approved)
Meets Conformance
Standards
ISO
9001: 2000
Certified
Performance Data
Thru All Field Selectable Ranges
Standard
*
Accuracy
RSS(at constant temp) ±1.0% FS
Non-Linearity, BFSL
±0.96% FS
Hysteresis 0.10% FS Non-Repeatability 0.05% FS
Thermal Effects**
Compensated Range °F (°C) 32 to 122 (0 to 50) Zero/Span Shift %FS/°F(°C) 0.02 (0.036)
Maximum Line Pressure 10 psi Long Term Stability (max) 0.5% FS/1 YR MS2 & MS4
1.0% FS/1 YR MS1 & MS3
Position Effect Zero Offset (%FS/G) 0.2% (Unit is factory calibrated at 0g effect in the vertical position.)
* RSS of Non-Linearity, Hysteresis, and Non-Repeatability. **Units calibrated at nominal 70˚F. Maximum thermal error computed from this datum.
NOTE: Setra quality standards are based on ANSI-Z540-1. The calibration of this product is NIST traceable.
Outline Drawings
4.75
120.7
4.25 108
Model 260 Specifications
Environmental Data
Temperature Operating
Physical Description
Case Fire-Retardant Glass Filled
Mounting Two External Screw Holes
Electrical Connection Removable Screw Terminal Block Pressure Fittings 3/16” O.D. Barbed Brass
Zero Push Button Weight (approx.) 8 ounces
Pressure Media
Typically air or similar non-conducting gases.
Specifications subject to change without notice.
U.S. Patent nos. 4093915; 4358814; 4434203; 6019002; 6014800. Other Patents Pending.
*
°F (°C) 32 to 122 (0 to 50)
Polyester (UL 94 V-0 Approved) Hinged Lid
Vertical Position
Pressure Fitting
0
150
O.862
21.8
Electrical Data (Voltage)
Circuit 3-Wire (Com, Exc, Out)
Protected from Miswiring Excitation 13 - 30 VDC/VAC Field Selectable Output*1 to 5, 0 to 5 or 0 to 10 VDC
**
Bidirectional Output at Zero Pressure: 1 to 5 VDC = 3 VDC
0 to 5 VDC = 2.5 VDC
0 to10 VDC = 5 VDC Output Impedance 500 ohms
*Calibrated into a 50K ohm load, operable into a 10K ohm load or greater. **Span (Full Scale) output factory set to within 1%.
Electrical Data (Current)
Circuit 2-Wire
Protected from Miswiring Excitation 24V (DC Only) Field Selectable Output Bidirectional Output at Zero Pressure: 12mA External Load 0 to 800 ohms Minimum supply voltage (VDC) = 13 Volts (at terminal) Maximum supply voltage (VDC) = 30 Volts (at terminal)
*Calibrated at factory with a 24 VDC loop supply voltage and a 250 ohm load.
**Span (Full Scale) output factory set to wtihin ±0.16mA.
*
4 to 20mA
**
**
.59
14.9
1.49
37.8
1.25
31.7 .63
15.9
1.3
31.8
4.15
105.4
Optional Static Probe Diagram
IN
1.03
26.3
.87 22
MM
ORDERING INFORMATION
Part Number Description
DPT260-MS1 0.1, 0.25, 0.5, 1.0 in. WC FS / ±0.1, 0.25, 0.5, 1.0 in. WC FS DPT260-MS2 1.0, 2.5, 5.0, 10 in. WC FS / ±1.0, 2.5, 5.0, 10 in. WC FS DPT260-MS1-SP 0.1, 0.25, 0.5, 1.0 in. WC FS / ±0.1, 0.25, 0.5, 1.0 in. WC FS with Static Probe DPT260-MS2-SP 1.0, 2.5, 5.0, 10 in. WC FS / ±1.0, 2.5, 5.0, 10 in. WC FS with Static Probe
.51
12.9
1.50
38.1
7.7 196
9.3
236.9
JCI260 Rev. A 12/05
While we provide application assistance on all Setra products, both personally and through our literature, it is the customer’s responsibility to determine the suitability of the product in the application.