Indicates a hazardous situation that, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related
(for example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions
thoroughly and follow all warnings or cautions included in all manuals that
accompanied the product and are attached to the unit. Refer back to these
instructions as needed.
●This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be
qualied according to local, state and national building and safety codes and regulations. Incorrect
installation could cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance
requirements are specied, the appropriate measures should be taken during installation to guard
against possible damage or injury that might occur in an earthquake if the unit is not installed
correctly, injuries may occur due to a falling unit.
●Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and,
where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited
for electrical operation purposes. Keep a wet cloth and a re extinguisher nearby during brazing. Use
care in handling, rigging, and setting of bulky equipment.
●When transporting, be careful when picking up, moving and mounting these units. Although the
unit may be packed using plastic straps, do not use them for transporting the unit from one location
to another. Do not stand on or put any material on the unit. Get a partner to help, and bend with
your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum ns on the air
conditioner can cut ngers, so wear protective gloves.
●Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features,
disengagement, and interlocks must be in place and functioning correctly before the equipment is
put into operation. If these devices are improperly adjusted or tampered with in any way, a serious
accident can occur. Never bypass or jump-out any safety device or switch.
●Johnson Controls will not assume any liability for injuries or damage caused by not following steps
outlined or described in this manual. Unauthorized modications to Johnson Controls products are
prohibited as they…
◦May create hazards which could result in death, serious injury or equipment damage. ◦Will void product warranties. ◦May invalidate product regulatory certications.◦May violate OSHA standards.
TC-16005-rev.2
i
Take the following precautions to reduce the risk of property damage.
●Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during
installation work. Foreign matter could damage internal components or cause blockages.
●If air lters are required on this unit, do not operate the unit without the air lter set in place. If the air
lter is not installed, dust may accumulate and breakdown may result.
●Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules
attach themselves to the surface of the heat exchanger, the nned surfaces will repel water. As a
result, any amount of drainage moisture condensate can overow from the condensate pan and could
run inside of the electrical box, possibly causing electrical failures.
●When installing the unit in a hospital or other facility where electromagnetic waves are generated
from nearby medical and/or electronic devices, be prepared for noise and electronic interference
Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the
electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment,
and radio communications equipment may cause the unit to malfunction. The operation of the unit
may also adversely affect these same devices. Install the unit at least 10 ft. (approximately 3m) away
from such devices.
●When a wireless controller is used, locate at a distance of at least 3.3 ft. (approximately 1m) between
the indoor unit and electric lighting. If not, the receiver part of the unit may have difculty receiving
operation commands.
●Do not install the unit in any location where animals and plants can come into direct contact with the
outlet air stream. Exposure could adversely affect the animals and plants.
●Do not install the unit with any downward slope to the side of the condensate pipe. If you do, you may
have drain water owing back which may cause leaks.
●Be sure the condensate hose discharges water properly. If connected incorrectly, it may cause leaks.
●Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in
restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant
features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These
specialized oil-resistant units can be ordered for such applications. However, in places where large
quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used.
These products should not be installed in such locations.
●If the wired controller is installed in a location where electromagnetic radiation is generated, make
sure that the wired controller is shielded and cables are sleeved inside conduit tubing.
●If there is a source of electrical interference near the power source, install noise suppression
equipment (lter).
●During the test run, check the unit’s operation temperature. If the unit is used in an environment
where the temperature exceeds the operation boundary, it may cause severe damage. Check the
operational temperature boundary in the manual. If there is no specied temperature, use the unit
within the operational temperature boundary of 32 to 104°F (0 to 40°C).
●Read installation and appropriate user manuals for connection with PC or peripheral devices. If a
warning window appears on the PC, the product stops, does not work properly or works intermittently,
immediately stop using the equipment.
ii
TC-16005-rev.2
Installation Precautions
To reduce the risk of serious injury or death, the following installation
precautions must be followed.
●When installing the unit into…
◦A wall: Make sure the wall is strong enough to hold the unit’s weight. It may be necessary to
construct a strong wood or metal frame to provide added support.
◦A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
cause dripping and water damage to wall and oors.
◦Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
◦An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable wind bafe.
◦A snowy area: Install the outdoor unit on a raised platform that is higher than drifting snow.
Provide snow protection hood.
●If the remote sensors are not used with this controller, then do not install this controller…
◦in a room where there is no thermostat.◦where the unit is exposed to direct sunshine or direct light.◦where the unit will be in close proximity to a heat source.◦where hot/cold air from the outdoors, or a draft from elsewhere (such as air vents, diffusers or
grilles) can affect air circulation.
◦in areas with poor air circulation and ventilation.
●Do not install the unit in the following places. Doing so can result in an explosion, re, deformation,
corrosion, or product failure.
◦Explosive or ammable atmosphere.◦Where re, oil, steam, or powder can directly enter the unit, such as in close proximity or directly
above a kitchen stove.
◦Where oil (including machinery oil) may be present.◦Where corrosive gases such as chlorine, bromine, or sulde can accumulate, such as near a hot
tub or hot spring.
◦Where dense, salt-laden airow is heavy, such as in coastal regions.◦Where the air quality is of high acidity.◦Where harmful gases can be generated from decomposition.
●Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive
gases may be present. If you do, toxic gases can seep into breathable air spaces and can cause
respiratory injuries. If the condensate pipe is installed incorrectly, water leakage and damage to the
ceiling, oor, furniture, or other possessions may result. If condensate piping becomes clogged,
moisture can back up and can drip from the indoor unit. Do not install the indoor unit where such
dripping can cause moisture damage or uneven locations: Use a raised concrete pad or concrete
blocks to provide a solid, level foundation for the unit to prevent water damage and abnormal
vibration.
●Before performing any brazing work, be sure that there are no ammable materials or open ames
nearby.
●Perform a test run to ensure normal operation. Safety guards, shields, barriers, covers, and protective
devices must be in place while the compressor/unit is operating. During the test run, keep ngers and
clothing away from any moving parts.
●Clean up the site when nished, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being installed.
●During transportation, do not allow the backrest of the forklift make contact with the unit, otherwise,
it may cause damage to the heat exchanger and also may cause injury when stopped or started
suddenly.
●Remove gas inside the closing pipe when the brazing work is performed. If the brazing ller metal is
melted with remaining gas inside, the pipes will be blown off and it may cause injury.
●Be sure to use nitrogen gas for an airtight test. If other gases such as oxygen gas, acetylene gas or
uorocarbon gas are accidentally used, it may cause explosion or gas intoxication.
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use
and maintenance of the unit to the customer according to the information in all manuals that came with the
system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
TC-16005-rev.2
iii
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
●As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
Controls uses only refrigerants that have been approved for use in the unit’s intended home country
or market. Johnson Controls distributors similarly are only authorized to provide refrigerants that
have been approved for use in the countries or markets they serve. The refrigerant used in this unit
is identied on the unit’s faceplate and/or in the associated manuals. Any additions of refrigerant into
this unit must comply with the country’s requirements with regard to refrigerant use and should be
obtained from Johnson Controls distributors. Use of any non-approved refrigerant substitutes will void
the warranty and will increase the potential risk of injury or death.
●If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum
allowable concentration in the event that refrigerant gases should escape. The installation should
meet the requirements in ASHRAE Standards 15 and 34. If refrigerant gas has leaked during the
installation work, ventilate the room immediately.
●Check the design pressure for this product is 601 psi (4.15MPa). The pressure of the refrigerant
R410A is 1.4 times higher than that of the refrigerant R22. Therefore, the refrigerant piping for
R410A shall be thicker than that for R22. Make sure to use the specied refrigerant piping. If not, the
refrigerant piping may rapture due to an excessive refrigerant pressure. Besides, pay attention to
the piping thickness when using copper refrigerant piping. The thickness of copper refrigerant piping
differs depending on its material.
●The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
as moisture, oxide lm, (or fat). Perform the installation work with care to prevent moisture, dust, or
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the cycle
from such parts as expansion valve and the operation may be unavailable.
●To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the
sizes of the charging connections have been changed from R407C type and R22 type. It is necessary
to prepare the appropriate tools before performing installation work.
●Use refrigerant pipes and joints which are approved for use with R410A.
●A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is
under pressure and never open pressurized system parts.
●Before installation is complete, make sure that the refrigerant leak test has been performed. If
refrigerant gases escape into the air, turn OFF the main switch, extinguish any open ames and
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
should leak and come into contact with open ames, toxic gas could be generated. Also, because the
uorocarbons are heavier than air, they settle to the oor, which could cause asphyxiation.
●When installing the unit, and connecting refrigerant piping, keep all piping runs as short as
possible, and make sure to securely connect the refrigerant piping before the compressor starts
operating. If the refrigerant piping is not connected and the compressor activates with the stop
valve opened, the refrigerant cycle will become subjected to extremely high pressure, which can
cause an explosion or re.
●Tighten the are nut with a torque wrench in the specied manner. Do not apply excessive force to the
are nut when tightening. If you do, the are nut can crack and refrigerant leakage may occur.
●When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the
compressor stops.
●When pipes are removed out from under the piping cover, after the insulation work is completed,
cover the gap between the piping cover and pipes by a packing (eld-supplied). If the gap is not
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
●Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
valve ies out due to refrigerant pressure. At the test run, fully open the gas and liquid valves,
otherwise, these devices will be damaged. (It is closed before shipment.)
●If the arrangement for outdoor units is incorrect, it may cause owback of the refrigerant and result in
failure of the outdoor unit.
●The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15
o
.
iv
TC-16005-rev.2
Electrical Precautions
Take the following precautions to reduce the risk of electric shock, re or
explosion resulting in serious injury or death.
●Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram
and these instructions when wiring. Improper connections and inadequate grounding can cause
serious injury or death.
●Perform all electrical work in strict accordance with this installation and maintenance manual and all
the relevant regulatory standards.
●Before servicing, open and tag all disconnect switches. Never assume electrical power is
disconnected. Check with meter and equipment.
●Only use electrical protection equipment and tools suited for this installation.
●Insulate a wired controller against moisture and temperature extremes.
●Use specied cables between units.
●The new air conditioner may not function normally in the following instances:
◦If electrical power for the new air conditioner is supplied from the same transformer as the
external equipment* referred to below.
◦If the power source cables for this external equipment* and the new air conditioner unit are
located in close proximity to each other.
external equipment*: (Example): A lift, container crane, rectier for electric railway, inverter
power device, arc furnace, electric furnace, large-sized induction motor and large-sized
switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply
cables for the packaged air conditioner due to a rapid change in power consumption of the device
and an activation of a switch.
Check eld regulations and standards before performing electrical work in order to protect the
power supply for the new air conditioner unit.
●Communication cabling shall be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper.
Shielded cable must be considered for applications and routing in areas of high EMI and other
sources of potentially excessive electrical noise to reduce the potential for communication errors.
When shielded cabling is applied, proper bonding and termination of the cable shield is required
as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be
considered per application and local code requirements.
●The polarity of the input terminals is important, so be sure to match the polarity when using contacts
that have polarity.
●Use an exclusive power supply for the air conditioner at the unit’s rated voltage.
●Highly dangerous electrical voltages may be used in this system. Carefully refer to the wiring diagram
and these instructions when wiring. Improper connections and inadequate grounding can cause
serious injury or death.
●Before installing the controller or remote devices, ensure that the indoor and outdoor unit operation
has been stopped. Further, be sure to wait at least ve minutes before turning off the main power
switch to the indoor or outdoor units. Otherwise, water leakage or electrical breakdown may result.
●Do not open the service cover or access panel to the indoor or outdoor units without turning OFF the
main power supply. Before connecting or servicing the controller or cables to indoor or outdoor units,
open and tag all disconnect switches. Never assume electrical power is disconnected. Check with a
meter and equipment.
●This equipment can be installed with a Ground Fault Circuit Breaker (GFCI), which is a recognized
measure for added protection to a properly grounded unit. Install appropriate sized breakers / fuses
/ overcurrent protection switches, and wiring in accordance with local, state and NEC codes and
requirements. The equipment installer is responsible for understanding and abiding by applicable
codes and requirements.
TC-16005-rev.2
v
- CONTENTS -
IMPORTANT NOTICE AND SAFETY SUMMARY ......................................................................................... i
1. Introduction ................................................................................................................................................ i
2. Important Safety Instructions ..................................................................................................................... i
1. General Information (Features) .................................................................................................................. 1-1
2. DOAS (Dedicated Outdoor Air System) Type ............................................................................................ 2-1
2.1 Unit Nomenclature ............................................................................................................................. 2-1
2.3 General Data ..................................................................................................................................... 2-2
2.4 Dimensional Data .............................................................................................................................. 2-3
2.6 Component Data ............................................................................................................................... 2-6
2.7 Operation Space ............................................................................................................................... 2-7
2.8 Fan Performance ............................................................................................................................... 2-8
2.9 Electrical Data ................................................................................................................................... 2-9
2.10 Sound Data ....................................................................................................................................... 2-10
2.11 Control System .................................................................................................................................. 2-11
2.11.1 Refrigerant System .................................................................................................................. 2-11
2.11.2 Operating Temperature Range ................................................................................................ 2-12
2.11.3 Control Temperature ................................................................................................................ 2-13
2.11.4 Standard Operation Sequence ................................................................................................ 2-14
2.11.5 Safety and Control Device Setting ........................................................................................... 2-16
3. Optional Parts ............................................................................................................................................ 3-1
3.1 Line Up .............................................................................................................................................. 3-1
3.6 Relay and 3 Pin Connector Kit: PSC-5RA ......................................................................................... 3-14
4. Selection Data ............................................................................................................................................ 4-1
Johnson Controls proudly introduces new Variable Refrigerant Flow (VRF) air conditioners, a highly-efcient
and reliable air-conditioning system. Recently, increased numbers of buildings are requiring "Intelligent"
facilities that include communication networks, ofce automation, and a comfortable environment. In
particular, a comfortable environment is becoming more of a year-around requirement in ofce buildings.
The VRF multi-split system air conditioner meets these requirements. The proven combination of the scroll
compressor and inverter provides the best air conditioning for small and medium ofce buildings.
■ VRF System
Johnson Controls has developed the VRF system with its customers in mind.
This system, which is unique in the world, allows the interconnection of indoor units for all our VRF air
conditioners.
This system provides the consumer with greater exibility for installation, which means that the airconditioning systems will integrate better within complex facility structures.
■ Comfortable Air Conditioning Environment
Fresh air intake is realized while suppressing the air conditioning load by cooling or heating outdoor air.
■ Two Control Mode
Depend on the installation environment and the purpose of use, the DOAS control system can be chosen
from two options.
< Indoor Temperature Control >
In this mode, the control system bring the room atmosphere temperature closer to the set point
temperature of the wired controller, using a temperature sensor (remote sensor or thermistor in the
wired controller) mounted in the room.
[Advantage]
When using an indoor temperature sensor, the system will be able to control the temperature in
collaboration with other indoor units.
DOAS
Indoor Unit
Intake
OutletOutlet
Outlet
Remote Sensor
(Accessory)
Wired
Controller
(Optional Part)
Intake
(Outdoor
Temperature Set Point Range of Wired Controller: Cooling . 66
o
F (19oC) ~ 86oF (30oC)
Heating . 62oF (17oC) ~ 86oF (30oC)
TC-16005-rev.2
1-1
FEATURES
Unit Undersurface
Air)
Exhaust
Outdoor Unit
< Outlet Air Temperature Control >
In this mode, the control system bring the outlet temperature closer to the setting temperature of the
wired controller, using an outlet air thermistor in the unit.
[Advantage]
When it is set introduce outdoor air, the system enable intake of fresh air without impacting the room
temperature.
DOAS
Outlet Air
Thermistor
Outdoor Unit
for DOAS Unit
Indoor Unit
OutletOutlet
Outlet
Intake
Temperature Set Point Range of Wired Controller: Cooling . 56
Wired
Controller
(Optional Part)
o
F (13oC) ~ 77oF (25oC)
Intake
(Outdoor
Heating . 66oF (19oC) ~ 86oF (30oC)
■ Constant Air Volume Mode
Constant air volume mode is available for the unit in order to keep the air velocity constant during defrosting
or hot start operation.
Even when combined with a ventilation fan, air supply and exhaust are balanced by this constant air volume
mode. (Settings are available using the optional function setting in the wired controller.)
NOTE:
During the defrosting operation and start of the heating operation, airow temperature will be decreased.
Carefully consider the installation location and direction of the air outlet.
Note that, when the air outlet temperature is 19.4
o
F (-7oC) or less, heating operation is stopped.
■ Flexible Layout when Using a Drain Pump
Max. Drain-Up Length
DOAS Unit
23-5/8 inches (600mm)
■ High External Static Pressure
Flexible duct installation due to the high external static pressure capability.
1-2
TC-16005-rev.2
■ Operation Range
Outdoor Air Intake Temperature [oF DB (oC DB)]
FEATURES
19.4
(-7)23(-5)
Heating Operation
Available Range
32
(0)
41
(5)
50
(10)
Fan
Operation
59
(15)
68
(20)
Cooling Operation
Available Range
77
(25)
(30)
86
95
(35)
104
(40)
109.4
(43)
NOTES:
1. The above gure shows the sensed temperature of inlet air thermistor for the DOAS unit.
o
2. When the outdoor air intake temperature is 32
F DB (0oC DB) or less, the heating operation is started for
freeze protection of the heat exchanger.
However, when the condition is such that the heating operation is not available, the operation is stopped.
o
3. When the outdoor air intake temperature is 19.4
F DB (-7oC DB) or less, the heating operation is stopped for
protection of the heat exchanger from freezing and/or a cold draft.
In addition, even when it is within the operation range, the operation might be stopped for unit protection.
o
4. During the heating operation, when the outdoor air intake temperature is 59
F DB (15oC DB) or more, the
operation is changed to fan operation.
5. When starting the heating operation or defrosting operation, the fan function is stopped by setting the optional
function setting in the wired controller. Constant air volume mode is available in order to keep the air speed
constant. (If it is in abnormal condition, the fan function will stop.) Refer to the Service Manual for details.
o
6. During cooling operation, when the outdoor air intake temperature is 68
is changed to fan operation.
When the outdoor air intake temperature is 109.4
o
F DB (43oC DB) or more, the fan operation can continue,
though the alarm might be stopped by increasing pressure due to being out of operation range.
In addition, when the outdoor air intake temperature is high (approx. 104
(approx. 73.4
o
F DB (23oC DB) or less) the cooling operation and the fan operation might be alternated for unit
Indoor Unit Type
Model(H,Y)DOA096B21S
Indoor Unit Power Supply
Outlet Air Temperature Control *1
Nominal Cooling CapacityBtu/h
(kW)
Nominal Heating CapacityBtu/h
(kW)
Indoor Temperature Control *2
Nominal Cooling CapacityBtu/h
(kW)
Nominal Heating CapacityBtu/h
(kW)
Sound Pressure Level *3
(Overall A Scale) (208/230V)
Outer Dimensions
Heightin. (mm)19-1/8 (486)
Widthin. (mm)50 (1270)
Depthin. (mm)44-1/8 (1120)
Net Weightlbs (kg)247 (112)
Refrigerant
Indoor Fan
Airflow Rate cfm
External Pressure (208/230V)
High Pressurein.W.G (Pa)1.06/1.24 (265/310)
Standard in.W.G (Pa)
Motor Nominal OutputW402 (201 x 2 pcs)
Min Circuit AmpsA4.3
Maximum Fuse AmpsA15
Connections
Refrigerant Piping
Liquid Linein. (mm)3/8 (9.52)
Gas Linein. (mm)7/8 (22.20)
Condensate DrainVP25
ODin. (mm)1-1/4 (32)
IDin. (mm)1 (25)
dB
m3/min
AC 1Phase, 208/230V, 60Hz
DOAS
96,000
(28.2)
60,000
(17.6)
96,000
(28.2)
83,600
(24.5)
50/51
R410A
1236
(35.0)
-
Brazed
NOTES:
*1. Outlet Air Temperature Control
A control system to bring the outlet temperature closer to the set point temperature of the wired controller, using an outlet
air thermistor of the unit.
Nominal capacity (outlet air temperature control) is based on combination with VRF system and following conditions:
Outdoor Temperature: 91°F DB (33.0°C DB) Outdoor Temperature: 32°F DB (0°C DB)
82°F WB (28.0°C WB) 27°F WB (-2.9°C WB)
Discharge Set Temperature: 61°F DB (16.0°C DB) Discharge Set Temperature: 72°F DB (22.0°C DB)
Piping Length: 24.6 ft. (7.5m) Piping Lift: 0 ft. (0m)
*2. Indoor Temperature Control
A control system to bring the room atmosphere temperature closer to the set point temperature of the wired controller,
using a temperature sensor (remote sensor or thermistor in wired controller) mounted to any place in the room.
Nominal capacity (indoor temperature control) is based on combination with VRF system and following conditions:
Outdoor Temperature: 91°F DB (33.0°C DB) Outdoor Temperature: 32°F DB (0°C DB)
82°F WB (28.0°C WB) 27°F WB (-2.9°C WB)
Indoor Temperature: 81°F DB (27.0°C DB) Indoor Temperature: 68°F DB (20.0°C DB)
Piping Length: 24.6 ft. (7.5m) Piping Lift: 0 ft. (0m)
*3. The sound pressure level is based on the following conditions.
4.9 ft. (1.5m) beneath the units.
The above data is measured in an anechoic chamber so that reected sound should be taken into consideration in the
eld.
2-2
TC-16005-rev.2
2.4 Dimensional Data
Model: (H,Y)DOA096B21S (Produced in 2017 or earlier)
DOAS
Unit: inch (mm)
TC-16005-rev.2
2-3
DOAS
Model: (H,Y)DOA096B21S (Produced in 2018 or later)
Unit: inch (mm)
2-4
TC-16005-rev.2
2.5 Structure
44-1/8 (1120)
1-1/8 (28)
Model: (H,Y)DOA096B21S
DOAS
Unit: inch (mm)
19-1/8 (486)
5
10
7/8 (23)
1412
9
2
8
15
4
20
19
18
13
50 (1270)
3
1
11
16
17
7
6
TC-16005-rev.2
2-5
DOAS
(
)
(
)
2.6 Component Data
Indoor Heat Exchanger and Fan
Model(H,Y)DOA096B21S
Heat Exchanger TypeMulti-Pass Cross Finned Tube
TubeMaterial
Outer Diameter
Rows
Number of Tube/Coil
FinMaterial
Pitchin. (mm)1/16 (1.6)
Maximum Operating Pressure
Total Face Area6.48
Number of Coil/Unit1
Indoor FanMulti-Blade Centrifugal Fan
Number/Unit
Outer Diameter
Nominal Airflowcfm
(Hi)
Indoor Fan MotorDrip-Proof Type Enclosure
Starting Method
Nominal OutputW
Quantity
Insulation Class (*)
in. (mm)
psi (MPa)601 (4.15)
2
ft
2
m
in.
(mm)
m3/min.
PSC (Permanent Split Capacitor)
Copper Tube
1/4 (7.0)
4
108
Aluminum
(0.61)
2
8-15/16
(227)
1236
(35.0)
201
2
F
NOTE:
(*) The insulation class means the heat resistant grade of the insulation material based on the IEC standard.
Refer to the IEC 60085 for more information.
2-6
TC-16005-rev.2
2.7 Operation Space
Min. 39-3/
Model: (H,Y)DOA096B21S
Min. 23-5/8
[600]
[1000]
Min. 39-3/8
8
[1000]
Electrical Control Box
Service Access Door
(Min. 23-5/8 [600]
5-7/8 to 7-7/8
[150 to 200]
Min. 31-1/2
[800]
DOAS
Unit: inch [mm]
If the ceiling board can not be detected
for servicing, prepare a service access door below
the indoor unit for removing the indoor unit.
TC-16005-rev.2
2-7
DOAS
2.8 Fan Performance
2-8
TC-16005-rev.2
2.9 Electrical Data
DOAS
Model
Unit Main PowerApplicable VoltagePower Supply
VOLPH HZ MaximumMinimumMCAMFAOPTFLA
(H,Y)DOA096B21S208/2301602531884.315
VOL: Rated Unit Power Supply Voltage (V)
PH: Phase
HZ: Frequency (Hz)
MCA: Maximum Circuit Ampacity (A)
MFA: Maximum Fuse Ampacity (A)
OPT: Rated Motor Output (kW)
FLA: Full Load Ampacity (A)
NOTE:
Power supply voltage should be satised with the following.
Supply Voltage: Rated Voltage within ±10%
Starting Voltage: Rated Voltage within -15%
Operating Voltage: Rated Voltage within ±10%
Indoor
Fan Motor
0.402
(Motor 2 pcs)
Unit
3.4
TC-16005-rev.2
2-9
DOAS
2.10 Sound Data
NOTES:
1. The sound pressure level is based on the following:
Measurement Point: 4.9 ft. (1.5m) beneath the unit.
2. The above data is measured in an anechoic chamber therefor reected sound should be taken into consideration in
the eld.
2-10
TC-16005-rev.2
2.11 Control System
2.11.1 Refrigerant System
Model: (H,Y)DOA096B21S
DOAS
MarkPart Name
1
Heat Exchanger
2
Distributor
3
Strainer
4
Electronic Expansion Valve
ModelDistributor
(H,Y)DOA096B21S9 Pass
TC-16005-rev.2
2-11
(A) Gas Pipe
Connection
7/8
f
(22.2)
(B) Liquid Pipe
Connection
3/8
f
(9.52)
Unit: inch (mm)
(C) OD×T(D) OD×T
1×t0.063
f
(25.4×1.6)
1/2×t0.039
f
(12.7×1.0)
DOAS
19.4
(Outdoor Air Temp.)
2.11.2 Operating Temperature Range
o
F [
o
C] WB)
89.6
[32]
Relative Humidity: 90%RH
Cooling
(Outdoor Air Temp.)
Blowing
50
[10]
59
[15]
Inlet Air Temp. Dry Bulb (
Relative Humidity: 30%RH
68
[20]
o
F [oC] DB)
Relative Humidity: 20%RH
86
( )
[30]92[33.5]
104
[40]
109
[43]
[-7]
Inlet Air Temp. Wet Bulb (
Heating
32
[0]
NOTES:
1. The above gure shows the sensed temperature of inlet air thermistor for the DOAS unit.
o
2. When the outdoor air intake temperature is 32
F DB (0oC DB) or less, the heating operation is started for
freeze protection of the heat exchanger.
However, when the condition is such that the heating operation is not available, the operation is stopped.
o
3. When the outdoor air intake temperature is 19.4
F DB (-7oC DB) or less, the heating operation is stopped for
protection of the heat exchanger from freezing and/or a cold draft.
In addition, even when it is within the operation range, the operation might be stopped for unit protection.
o
4. During the heating operation, when the outdoor air intake temperature is 59
F DB (15oC DB) or more, the
operation is changed to fan operation.
5. When starting the heating operation or defrosting operation, the fan function is stopped though by setting the
optional function setting in the wired controller. Constant air volume mode is available in order to keep the air
speed constant. (If it is in an abnormal condition, the fan function will stop) Refer to the Service Manual for
details.
o
6. During cooling operation, when the outdoor air intake temperature is 68
is changed to fan operation.
When the outdoor air intake temperature is 109.4
o
F DB (43oC DB) or more, the fan operation can continue,
though the alarm might be stopped by increasing pressure due to being out of operation range.
In addition, when the outdoor air intake temperature is high (approx. 104
(approx. 73.4
o
F DB (23oC DB) or less) the cooling operation and the fan operation might be alternated for unit
F DB (20oC DB) or less, the operation
o
F DB (40oC DB) or more) or low
protection.
2-12
TC-16005-rev.2
2.11.3 Control Temperature
< Indoor Temperature Control >
CoolingHeating
Set Point Temperature
Range
for Wired Controller
[Inlet Temp.] > [Setting Temp.] +2oF (+1oC)
Thermo-ON
[Detected Indoor Temp.] < [Setting Temp.]
Thermo-OFF
[Inlet Temp.]: Sensed Temperature of Inlet Air Thermistor
[Setting Temp.]: Set Point Temperature of Wired Controller
[Detected Indoor Temp.]: Sensed Temperature of Remote Sensor or Thermistor for Wired Controller
< Outlet Air Temperature Control >
o
66
F (19oC) ~ 86oF (30oC)62oF (17oC) ~ 86oF (30oC)
[Inlet Temp.] < [Setting Temp.] -2oF (-1oC)
and
[Inlet Temp.] > 70
o
F (21oC)
o
20
F (-7oC) < [Inlet Temp.] < 58oF (14oC)
and
[Detected Indoor Temp.] > [Setting Temp.]
and
[Inlet Temp.] < [Setting Temp.]
or
[Inlet Temp.] < 68
o
F (20oC)
[Inlet Temp.] > [Setting Temp.]
[Inlet Temp.] > 59
and
or
o
F (15oC)
DOAS
CoolingHeating
Set Point Temperature
Range
o
56
F (13oC) ~ 77oF (25oC)66oF (19oC) ~ 86oF (30oC)
for Wired Controller
[Inlet Temp.] > [Setting Temp.] +2oF (+1oC)
Thermo-ON
[Inlet Temp.] > 70
and
o
F (21oC)
[Inlet Temp.] < [Setting Temp.] -2oF (-1oC)
Thermo-OFF
[Inlet Temp.] < 68
or
o
F (20oC)
[Inlet Temp.]: Sensed Temperature of Inlet Air Thermistor
[Setting Temp.]: Set Point Temperature of Wired Controller
[Inlet Temp.] < [Setting Temp.] -2oF (-1oC)
o
20
F (-7oC) < [Inlet Temp.] < 58oF (14oC)
and
[Inlet Temp.] > [Setting Temp.] +2oF (+1oC)
or
[Inlet Temp.] > 59
o
F (15oC)
TC-16005-rev.2
2-13
DOAS
(*) Refer to (2) below “Freeze Protection Control” for details.
(*) Refer to (2) below “Freeze Protection Control” for details.
2.11.4 Standard Operation Sequence
(1) Control Flowchart
DOAS inlet air is outdoor air.
As long as DOAS outdoor air inlet temperature does not reach the setting temperature of the controller,
thermo-OFF is not available and the operation is continued.
In addition, outdoor airow directly into the indoor unit during thermo-OFF.
NOTE:
Thermo-ON: The outdoor unit and some indoor units are running.
Thermo-OFF: The outdoor unit and some indoor units stay on, but do not run.
■ Cooling Operation
Cooling Operation
o
F (20oC)
Outdoor
Air Inlet
Temp.
< 68
< 71.6oF (22oC)
Compressor: OFF
Outdoor
Air Inlet
Temp.
Compressor: ON
■ Heating Operation
Heating Operation
Outdoor
Air Inlet
Temp.
o
> 68
F (20oC)
o
> 71.6
F (22oC)
> Set Temp.
< Set Temp.
> 59oF (15oC)
> 55.4oF (13oC)
Outdoor
Air Inlet
Temp.
o
F (0oC)
< 32
Compressor: OFF
> 32oF (0oC)
Forced Heating Control
(*)
o
< 59
F (15oC)
o
< 55.4
F (13oC)
Outdoor
Air Inlet
Temp.
o
> 32
F (0oC)
< 19.4oF (-7oC)
Compressor: ON
2-14
< 32
o
F (0oC)
Forced Heating Control or
Forced Stop Control
Forced Stop Control 1
(*)
(*)
TC-16005-rev.2
(2) Freeze Protection Control
I.U. : Indoor Unit
I.U. : Indoor Unit
DOAS operates the forced heating operation for freeze protection of the heat exchanger if the outdoor
air inlet temperature is 32oF (0oC) or less during the cooling or airow operation.
However, the operation is stopped if the outdoor air inlet temperature is 19.4oF (-7oC) or less, or the
temperature in the circuit is decreased.
In addition, the operation is stopped when the condition is not available for the heating operation.
(The operation connected DOAS and other indoor units, etc.)
Forced Heating Control
No
Operation
Yes
DOAS
Forced
Heating
Operation
> 32oF (0oC)
Outdoor
Air Inlet
Temp.
Forced Heating Operation: ONForced Heating Operation: OFF
3.12Computerized Central Controller Software / AdapterCCCS01 / CCCA01
Optional Parts
Model Name
Refer to the Engineering Manual of Control for details of item 3.7 to 3.12.
TC-16005-rev.2
3-1
OPTIONAL PARTS
Indoor Unit
Indoor Unit
3.2 Seismic Suspension Bracket: SSB-IDH-01
Replace the original suspension bracket to this seismic suspension bracket to prevent destruction or damage
to the ducted indoor unit during earthquake by improving its strength.
After conrming the ducted indoor unit model, install the seismic suspension bracket according to the
following procedures. Install the seismic suspension bracket securely with the screws that are attached to
the unit. If you don’t tighten the screws well enough, the unit may fall over.
(1) Remove two M6 screws securing the original suspension bracket and remove the original suspension
bracket.
Original Suspension Bracket
M6 Screws
(2) Attach the seismic suspension bracket to indoor unit and secure the seismic suspension bracket by
reusing two of the screws removed from the unit.
Seismic Suspension Bracket
M6 Screws
(3) Perform the same work at the other three bracket locations. (Total four places)
3-2
TC-16005-rev.2
3.3 Infrared (IR) Receiver Kit: CWDIRK01
This IR receiver kit is installed with the wall mount to use with the wireless controller.
3.3.1 Specications
ModelCWDIRK01
OPTIONAL PARTS
Outer Dimension
< W × H × D >
3.3.2 Dimensions
3-9/16 × 4-3/4 × 1-1/8 inch
(90 × 120 × 28 mm)
3-9/16 [90]
EMERGENCY
RUN
DEF
FILTER
TIMER
COOL
HEAT
4-3/4 [120]
IR Receiver Part
Unit: inch [mm]
1-1/8 [28]
3.3.3 Applicable Models
ModelCWDIRK01
Applicable Indoor Unit Model
Applicable Wireless ControllerCIR01
Accessory Cable
(about 16.4ft [5m])
To Terminal Block (A, B)
in Electrical Control Box
of Indoor Unit
General-Purpose
(Ducted and Wall Mount Type)
TC-16005-rev.2
3-3
OPTIONAL PARTS
3.3.4 Accessories / Options
No.AccessoryQtyRemarks
1
2
3
4
5
IR Receiver Kit
CWDIRK01
Cable Band 1For Clamping Cable
Securing Screw4For Installing IR Receiver Kit
Securing Screw2For Fixing Cable Clamp
Cable Clamp2For Clamping Cable
1With Connecting Cable
3.3.5 Installation
● Turn OFF the power supply completely before setting the DIP switch, installation work, and electrical
wiring work for the IR receiver kit. If not, it may cause an electric shock.
● Perform securely the installation work referring to this manual. If the installation is not completed
correctly, the IR receiver kit may fall and cause injury.
● Do not install the IR receiver kit where ammable gases may generate or enter. It may cause heat
generation or a re.
● Correctly perform the electrical wiring work. If electrical work is not completed correctly, heat generation
at the connection, a re or an electric shock may occur.
● Make sure that the electrical wires are securely xed so that no external force affects the terminal
connections of the wiring. Not doing so may cause heat generation or a re.
● When the IR receiver kit is installed near ambient lighting, it may not receive a signal from the wireless
controller. Therefore, pay particular attention to the installation position of the IR receiver kit.
● Do not run the connecting cable for the IR receiver kit and the power supply cable (208/230V) in
parallel. It may cause a malfunction of the IR receiver kit.
● To ensure correct performance, read this manual together with the “Installation and Maintenance
Manual” for the indoor unit and the wireless controller. Forward this information to the building owner
and request that they maintain all the equipment manuals.
● CWDIRK01 is for a general-purpose IR receiver kit. It is applied for ducted, cassette, wall mount,
ceiling-suspended, and oor type indoor units.
3-4
TC-16005-rev.2
OPTIONAL PARTS
IR Receiver Ki
pprox. 1/4 inch (6mm))
Securing Screw
(Accessory)
Two Securing Screws (M4, Field-Supplied)
1
Perform the installation work for the IR receiver kit while the indoor unit is being installed.
2
Turn OFF the power supply for the indoor unit if the IR receiver kit is attached after the indoor unit is
installed.
3 Install the IR receiver kit using the length of
connecting cable (accessory).
The cable length is approximately 17 ft. (5m).
4
Open the cover of the IR receiver kit.
Push the slotted screwdriver with a tip width of
approximately 1/4 inch (6mm) into the slot of the
IR receiver kit cover and rotate it to open the
cover as shown in the gure at the right.
5
Mount the IR receiver kit onto the wall or the ceiling surface as shown below.
Slot
t
Mounting Bracket
Slotted Screwdriver
(Tip Width:
A
Rotate
Push and rotate.
Situation A
(1) Secure the bracket.
Secure the bracket with four
accessory securing screws.
Situation B
(1) Prepare the eld-supplied switch box (JIS
Box). (JIS C8340)
Any of the following Switch Boxes
can be utilized.
1. Switch Box for One Switch
(Without Cover)
2. Small Switch Box for One Switch
(Without Cover)
3. Switch Box for One Switch
(With Cover)
Metal Conduit
(larger than I.D. φ13/16 inch (φ20mm)
TC-16005-rev.2
3-5
OPTIONAL PARTS
Cable
(M4, Field-Supplied)
(2) Select the connecting cable outlet direction
and cut out one of the knock-out holes on
the cover.
Select the connecting
cable outlet direction
and cut out of the
knock-out holes ( ).
(3) Lead the connecting cable through the
knock-out hole.
Connecting
Cable
Cover
(2) Run the connecting cable into the metal
conduit.
The connecting cable should
not be exposed. Lead it through
the metal conduit in the wall.
Connecting
(3) Secure the bracket.
Connecting Cable
(4) Attach the IR receiver kit.
Do not pinch the cable between the bracket and the IR receiver kit cover when attaching the IR
receiver kit. Attach the IR receiver kit cover following these directions.
Secure the tabs of the cover
into the slots on the left side
of the bracket.
Situation ASituation B
Mounting Bracket
Do not loosen the connecting
cable for the IR receiver kit.
Otherwise, it may become
pinched between the two
components causing a
malfunction of the indoor unit.
Hook the left side
of the cover to the
mounting bracket.
Push the right side
of the cover onto
the bracket.
Cover
Mounting Bracket
Click sound is heard
when the cover is
completely hooked
onto the bracket.
Cover
Hook the left side of
the cover to the mounting
bracket. Push the right
side of the cover onto
the bracket.
Securing Screw
Click sound is heard
when the cover is
completely hooked
onto the bracket.
3-6
TC-16005-rev.2
OPTIONAL PARTS
Insert the connecting
Switch Cover
PCB
Switch Cover
PCB2
Electrical Box
Cover
Ground Wiring Connection
for IR Receiver Kit
Terminal Block for Power Supply (TB1)
Ground Wiring Connection
for IR Receiver Kit
3.3.6 Electrical Wiring
The terminal block (TB2) for the controller cable is located as shown in the gure below. Connect the
connecting cable for the IR receiver kit to terminals A and B at TB2. (There is no polarity between terminals
A and B.) The details for wiring methods can be found in the “Installation and Maintenance Manual” for the
indoor unit.
The following wiring method is an example for wall mount indoor units
NOTE:
After running the connecting cable, clamp the extra length of the connecting cable using the accessory cable
band and place it in the electrical box.
cable from the rear
side of indoor unit.
TIWM006 - 012B21STIWM015 - 030B21S
Terminal Block for
Power Supply (TB1)
A 12
Connecting Cable
Screw for
Terminal Block for
Controller Cable (TB2)
Fix the wires with
cable clamp.
AB1
Connecting Cable
Terminal Block for
Controller Cable (TB2)
Screw for
3.3.7 Setting DIP Switches on Indoor Unit Side
Instructions for setting DIP switches for other indoor units can be found in the Installation and Maintenance
Manual for indoor units. The following DIP switch setting is an example for wall mount indoor units.
1
The factory setting of SW2 before shipment is “Wireless”. When using an IR receiver kit (CWDIRK01), set
the SW2 to “Wired”. If not doing so, the operation is not available.
2
Turn OFF the power supply of the indoor and outdoor units completely before setting the DIP switch.
If not turning off the power, the setting becomes invalid.
3
The positions of the DIP switches are shown below.
Open the switch cover. After the DIP switch is set, re-attach the switch cover. The details for setting DIP
switches for an indoor unit can be found in the Installation and Maintenance Manual for indoor units.
Turn OFF the power supply completely before setting the DIP switch for an IR receiver kit.
Not doing so may cause an electric shock.
1
The following switches are on the IR receiver kit.
NOTE:
When the case is closed, pay particular attention to the outlet position for connecting cable.
bracket.
(2) Remove two securing
screws to open the case.
“COOL” Button
EMERGENCY
RUN
DEF
FILTER
TIMER
2
Emergency Operation Setting
COOL
HEAT
“HEAT” Button
DIP Switch (DSW1)
(Factory Setting)
Outlet for
Connecting Cable
ON
341256
“COOL” and “HEAT” switches are used for emergency operation when the batteries for the wireless
controller are low.
(1) Switch “COOL”: Press “COOL” so that the cooling operation is started.
Press “COOL” again so that the cooling operation is stopped.
(2) Switch “HEAT”: Press “HEAT” so that the heating operation is started.
Press “HEAT” again so that the heating operation is stopped.
NOTE:
During an emergency operation, a yellow light “
” ashes (0.5 second ON/0.5 second OFF).
The temperature setpoint and the fan speed for the cooling/heating operation are the same as before
starting an emergency operation.
3
The DIP switch (DSW1) is for the optional function selection. If the optional function selection is required,
set the DIP switch as follows.
Optional Function
Main/Sub SettingOXXXXX
Identifying of
Indoor Unit
Invalidity of
Emergency Operation
DIP Switch Setting (DSW1)
123456
Details
Change main (OFF setting)/ sub (ON setting) wireless
controller for a two-wireless controller system.
XOXXXX
It functions as B Mode (identication of indoor unit) of
the wireless controller when it is “ON”.
XXXOXXThe switches for emergency operation are invalid.
O: ON
X: OFF
Review the following optional function settings when a function for the IR receiver kit is selected from the
wireless controller or the centralized controller.
● The optional functions “Cooling Lower Limit for Setting Temperature” and “Heating Upper Limit for Setting
Temperature” are not available with the wireless controller.
● The optional function setting “Fixing of Setting Temperature” is not available. When the operation mode is
changed from the wireless controller, the indicated temperature on the wireless controller becomes the set
temperature of the wired controller.
3-8
TC-16005-rev.2
t
Wireless Controller
3.3.9 Identifying Indoor Units Installed in a Side-by-Side Operation
Turn OFF the power supply completely before setting the DIP switch for the IR receiver kit.
Not doing so can cause an electric shock.
OPTIONAL PARTS
When two indoor units are installed side by side,
the commands from the wireless controller may
Indoor Unit
A
Indoor Unit
B
be received by both indoor units. The function,
“Identifying of Indoor Units Installed Side by Side”
enables operation of the individual unit correctly
without interfering with the other unit’s operation.
IR Receiver
Kit A
IR Receiver
Kit B
As shown in the gure at the right, the IR receiver
kit of A and B are set side by side. In this instance,
unit B is set as “Identifying Indoor Units Installed
Side by Side”.
NOTE:
This function setting is required at the receiver side.
"Identified"
It should be set according to the Installation Manual
for indoor units. Contact your distributor for details.
Setting of Identifying of Indoor Units Installed Side by Side
1
IR Receiver Kit Setting
Set the Number 2 pin of the IR receiver kit DIP switch (DSW1) at the “Identied” Unit B “ON” side.
2
Wireless Controller
Set the wireless controller according to the Installation and Maintenance Manual for the Wireless
Controller.
"Identified"
IR Receiver Ki
Cancellation of Identifying of Indoor Units Installed Side by Side
1
IR Receiver Kit Setting
Set the Number 2 pin of the IR receiver kit DIP switch (DSW1) “OFF” side for cancellation.
2
Wireless Controller
Cancel the wireless controller setting according to the Installation and Maintenance Manual for the
Wireless Controller.
TC-16005-rev.2
3-9
OPTIONAL PARTS
Wireless Controller
Indoor Unit
Standard
Standard Indoor Unit or
Standard
t
Wireless Controller
Control Cable
between
Indoor Units
Operation of Multiple Units
3.3.10 Simultaneous Operation
● Turn OFF the power supply completely before setting the DIP switch and electrical wiring work for the
IR receiver kit. Not doing so can cause an electric shock.
● Accurately perform the electrical wiring work. If the electrical work is not completed correctly, heat
generation at the connection, a re, or an electric shock may occur.
● Make sure that the electrical wires are adequately clamped with a cable clamp and not in a manner that
applies too much external force to the terminal connections of the wirings. If done correctly, the result
could cause heat generation or a re.
● Do not run the connecting cable for IR receiver kit and the power supply cable (208/230V) in parallel.
It may cause a malfunction of the IR receiver kit.
Up to 16 indoor units can be simultaneously
controlled using one wireless controller.
When multiple indoor units are installed in a large
Indoor Unit
(Address setting
is required.)
room, all the indoor units can be controlled to start/
stop with only one wireless controller.
NOTE:
Do not apply a simultaneous operation for the indoor
units installed separately in different rooms.
Some units may be left without turning OFF the
power supply.
Control Example of Simultaneous
(Example of 4-way cassette type indoor units.)
Installation of IR Receiver Kit
In an instance of simultaneous operation of multiple (up to 16 ) indoor units by the wireless controller, install
the IR receiver kit only to the unit to be operated. Other units should be the standard units without the IR
receiver kit. If multiple IR receiver kits are required to be installed, two IR receiver kits are the maximum.
with IR Receiver Kit
Indoor Unit
Indoor Unit
Indoor Unit with IR Receiver Kit
3-10
Should be Standard Indoor Units
Available to Install IR Receiver Ki
TC-16005-rev.2
Electrical Wiring Connecting and Setting
Unit Number Setting
Max. 63 units are available for setting.
Power Supply Cable 208/230V
1
Connection between Indoor Units
Perform the connection work as shown below.
OPTIONAL PARTS
Power
Supply
Cable
TB
L
1
TB
1
L2N
2
AB12
TB
1
TB
2
L1L2NL
AB12
TB
1L2
1
TB
2
AB12
N
(208/230V)
Control Cable
(No Polarity)
Indoor Unit No.1Indoor Unit No.2Indoor Unit No.3
Connecting Cable
IR Receiver Kit
(Accessory)
For twin, triple or quad combinations,
a communication cable for the wireless
controller is not required.
Wired Controller Cable
Use the field-supplied communication cable (AWG18)
for the wired controller cable. The total length
should be within 1640ft (500m). If the total length
is less than 98ft (30m), AWG22 cables can be used.
2
Do not run the connected wireless controller cable and the power supply cable (208/230V) in parallel in
the indoor units.
Stabilize the cable with cable bands. Along with the wiring outside the indoor units, the control cables
should not run with the power supply cable (208/230V). Keep a separation of more than 12 inches (30cm)
or run the cable through a grounded metal conduit.
3
Unit Number Setting
The indoor unit numbers are set by the auto-address function. Therefore, an indoor unit number setting
is not required. If the indoor unit number is xed, set the unit number of all indoor units respectively and
serially. It is recommended that the unit number settings begin with “1”. The setting is set not to overlap
the unit number.
DSW6 (Tens Digit)RSW1 (Units Digit)
Setting
ON
1 2 3 4 5 6
Factory setting for DSW6 and RSW1 were set to "0".
OFF
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.: Set for No. 16 Unit
DSW6RSW1
ON
1 2 3 4 5 6
Set No.1 pin ON.
OFF
Set at "6".
TC-16005-rev.2
3-11
OPTIONAL PARTS
Alarm
3 5
)
These signals are repeated until the alarm is reset.
3.3.11 Test Run by Wireless Controller (CIR01)
After all installations are completed, a test run should be performed.
(1) Perform the test run according to the Installation Manual of the wireless controller.
(2) The test run from the wireless controller switch takes two hours to complete.
NOTE:
For the wall mount indoor units, if the TIMER indicator (green) is ashing (0.5 second ON/0.5 second
OFF) after two hours, an alarm may occur. Operate the indoor unit ,and check for abnormality.
3.3.12 Alarm Indication
● If a malfunction occurs, such as safety device actuation, during the test run or the normal
operation, “RUN” (red light) ashes (0.5 second ON / 0.5 second OFF).
● The alarm codes are indicated by the number of LED ashes of “DEF” (green light) and “FILTER” (yellow
light).
The rst LED light is green. The number of times this LED ashes (0.5 second ON and
OFF) will tell you the “DEF” Alarm Code.
The second LED light is yellow. The number of times this LED ashes (0.5 second ON and
OFF) will tell you the “FILTER” Alarm Code.
Example
"FILTER" (yellow light)
"DEF" (green light)
"DEF" flashes three times (0.5 second ON/ 0.5 second OFF)
"FILTER" flashes five times (0.5 second ON/ 0.5 second OFF
● ”RUN” (red light) ashing (1 second ON/1 second OFF) indicates an abnormal transmission (connector
loose, connector disconnection, broken wire, or incorrect wiring, or something similar) between the
indoor unit and the IR receiver kit.
● When the IR receiver kit is connected to multiple indoor units, the alarm code is indicated for each
indoor unit in order.
Alarm Code Table
Further details for alarm codes can be found in the “Installation and Maintenance Manual” for the indoor unit.
3-12
TC-16005-rev.2
OPTIONAL PARTS
2-φ4.5
1-15/16 (50)
9/16 (15)
Base
Connector
(“XARP-03V” of NIPPON
A
)]
with soldering.
3.4 3P Connector Cable: PCC-1A
This accessory connector is utilized to provide remote start/stop capability (binary input) to an indoor unit and
provide operating status (binary output) of an indoor unit's functions. (System Parts: One set contains ve
3P cords.)
CCHAKU TANSHI = JST)
Lead Wire AWG22 (0.3mm2)
Name3P Connector Cable
ModelPCC-1A
One set contains ve 3P connector
cables.
Approximately
11-13/16inch (300mm)
If long cord is needed,
connect field supplied
wires [AWG22 (0.3 to 0.5mm
Remarks
2
3P Connector Cable
3.5 Remote Sensor: THM-R2A
When a remote temperature sensor is installed with an indoor unit, the indoor unit is congurable to use the
temperature at the location of the remote sensor OR the average of the unit's return air temperature and
the temperature at the location of the remote sensor to control that unit. (reference the specic controller
Installation Manual for function conguration details)
Sensor
1-1/4 (32)3/8 (9)
1-1/4 (32)3/8 (9)
1-15/16 (50)
Unit: inch (mm)
Cord
Case
Specications
ItemSpecication
ModelTHM-R2A
Case
Base
Sensor
MaterialABS Resin
ColorSilky White
MaterialABS Resin
ColorSilky White
Part NameThermistor
Cord Lengthapprox. 26 ft (8m)
TC-16005-rev.2
3-13
OPTIONAL PARTS
r
3.6 Relay and 3 Pin Connector Kit: PSC-5RA
This relay kit provides for basic input/output integration functionality (indoor unit ON/OFF, operating mode,
alarm status) to third party controllers and Building Management Systems (BMS).
5/16
(7.5)
5/16
(7.5)
4-5/16 (110)
4-15/16 (125)
5/16
(7.5)
1-1/4 (31.5)
Fixing Hole:
ɸ1/4 (6)
Max. 4-1/2 (115)
4 (101)
3-3/8 (86)
1-1/2 (38)
Connecting Cable
for Indoor Unit
5/16
(7.5)
9/16
PCB
72-13/16 (1850)
9/16
5-7/8 (150)
Unit: inch (mm)
(15)
3-3/4 (95)
(15)
NameRelay and 3 Pin Connector Kit
ModelPSC-5RA
1-9/16 (40)
Opening for
Controller or BMS (3rd Party) Cable
Third Party
Controller
or BMS
Connection Cable
(6 conductors)
Max. 229.7ft (70m)
(field-supplied)
TB1
TB2
Adapter
(PSC-5RA)
0.3mm2 (AWG22)
- 6 conductors
6.6ft (2m)
(Accessory)
PCB
CN3*
CN7
Indoor
Unit
*: Refer to Service Manual for connector numbers.
ItemSignalDescriptionSpecications
Third Party
Controller
or BMS
Third Party
Controller
or BMS
Input 1
Input 2
Output 1
Output 2
Input level signal or pulse signal for voltage
from the third party controller or BMS
Output signal from the wired controller
Voltage: 12VDC, 10mA
Voltage: 24VDC, 10mA
Pulse Range: 500ms or more
24VDC
From 10mA to 1A
Wired
Controlle
Refer to the Indoor Unit Manual for Input/Output mode setting by the wired controller.
Depend on the installation environment and the purpose of use, the DOAS control function can be
chosen from two options.
< Indoor Temperature Control >
Control system that bring the room atmosphere temperature closer to the set point temperature in the
wired controller, using a temperature sensor (remote sensor or thermistor in wired controller) mounted
in the room.
[Advantage]
Because of using a indoor temperature sensor, the system enables to create the atmosphere
temperature in collaboration with other indoor units.
1. Do not set “Indoor Temperature Control” and “Outlet Air Temperature Control” control modes
2. If multiple DOAS units are connected to the same refrigerant system, set the Outlet Air Temperature
TC-16005-rev.2
DOAS
Connected Indoor UnitDOAS only
Other Standard Indoor Unit
Indoor Temperature Control
Outlet Air Temperature Control
+
enabled in the same refrigerant system.
Control with the temperature on the wired controller same for all of the units.
4-1
SELECTION DATA
(3) Combination of Outdoor Unit and DOAS Unit
Indoor units can be connected to the outdoor unit (VRF system).
Refer to the table below for connection capacity ratio of each outdoor unit.
< Connection Capacity Ratio >
Outdoor Unit Model Name
VRF
(Standard
Type)
VRF
(Less Module
Type)
Low
Ambient
VRF
DOAS Only
Minimum Maximum Minimum Maximum
(H,Y)VAH(P,R)072B(3,4)1S100%145%70%150%
(H,Y)VAH(P,R)096B(3,4)1S100%145%65%135%
(H,Y)VAH(P,R)120B(3,4)1S100%145%60%130%
(H,Y)VAH(P,R)144B(3,4)1S100%145%75%150%
(H,Y)VAH(P,R)168B(3,4)1S100%145%65%140%
(H,Y)VAH(P,R)192B(3,4)1S100%145%65%135%
(H,Y)VAH(P,R)216B(3,4)1S100%145%70%150%
(H,Y)VAH(P,R)240B(3,4)1S100%145%70%150%
(H,Y)VAH(P,R)264B(3,4)1S100%145%65%140%
(H,Y)VAH(P,R)288B(3,4)1S100%145%65%135%
(H,Y)VAH(P,R)312B(3,4)1S100%145%65%130%
(H,Y)VAH(P,R)336B(3,4)1S100%145%65%140%
(H,Y)VAH(P,R)360B(3,4)1S100%145%65%135%
(H,Y)VAH(P,R)240B(3.4)1LM100%120%60%120%
(H,Y)VAH(P,R)336B(3.4)1LM100%120%60%120%
(H,Y)VAH(P,R)360B(3.4)1LM100%120%60%120%
(H,Y)VAHP072B(3,4)1CW100%145%60%130%
(H,Y)VAHP096B(3,4)1CW100%145%60%110%
(H,Y)VAHP144B(3,4)1CW100%145%60%130%
(H,Y)VAHP168B(3,4)1CW100%145%60%110%
(H,Y)VAHP192B(3,4)1CW100%145%60%110%
(H,Y)VAHP288B(3,4)1CW100%145%60%110%
DOAS with other Indoor Units
[ Capacity of DOAS shall be
calculated by multiplying with 1.5.]
NOTES:
1. DOAS cannot be connected to a Heat Recovery system.
2. DOAS cannot be connected with Mini VRF.
3. When connecting multiple DOAS and/or other standard indoor unit to the outdoor unit, be sure to operate all
indoor units simultaneously.
In addition, it is recommended that only connect one DOAS to each outdoor unit.
(4) Indication of Selection
For selection of required outside airow (and required number of DOAS units), refer to applicable local
codes or latest issue of :
ANSI/ASHRAE Standard 62.1-2016, Ventilation for Acceptable Indoor Air Quality and/or,
ANSI/ASHRAE Standard 62.2-2016, Ventilation and Acceptable Indoor Air Quality in Low-Rise
Residential Buildings.
The standard species minimum ventilation rates, and other measures, for new and existing buildings
that provide indoor air quality that is acceptable to human occupants and that minimizes adverse
health effects.
The standards list minimum required outside air (in CFM/person) depending on type of activity in the
building/room.
4-2
TC-16005-rev.2
---------
--------
-------
-----
----
4.2 Capacity Table
------
------
-----
----
4.2.1 Cooling Capacity
SELECTION DATA
Outdoor Air Temp.
Outdoor Air
o
F DB)
Temp. (
6832.334.7
7132.334.6
7532.334.436.4
7932.334.237.149.6
83-34.137.849.672.4---
87-33.938.649.671.797.2--
91--39.349.671.0
95---49.670.395.1122.0151.0
99---51.770.394.3120.4149.7
103----70.393.5119.5148.5
107-----93.1118.3147.3
109-----91.0117.9146.8
o
F WB)
(
6266707478828690
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC: Total Capacity
NOTES:
1. The above capacities are based on the following conditions:
Air Discharge Temperature Setting: 64
o
F DB (18.0oC DB) for Cooling Operation
Equivalent Piping Length: 24.6ft. (7.5m)
Level Difference: 0ft. (0m)
2. A value enclosed in
means rated capacity.
TC
(MBH)
TC
(MBH)
96.0
TC
(MBH)
122.0-
(MBH)
TC
4.2.2 Heating Capacity
Outdoor Air Temp.
Outdoor Air
Temp. (
o
F WB)
(
o
F DB)
2080.0
2276.476.4
27--67.3
32---
37----51.850.9
42----43.643.543.6---
47-----36.436.536.4--
52------29.129.0--
57-------21.521.120.7
TC: Total Capacity
NOTES:
1. The above capacities are based on the following conditions:
Air Discharge Temperature Setting: 72
Equivalent Piping Length: 24.6ft. (7.5m)
Level Difference: 0ft. (0m)