YORK® Affinity Model DNQ units are cooling/heating air
conditioners designed for outdoor installation. Only gas piping,
electric power and duct connections are required at the point of
installation.
The single or two stage gas-fired heaters have spark to pilot
ignition. The tubular heat exchangers are aluminized steel.
The refrigerant system is fully charged with R-410A Refrigerant,
and is tested and factory sealed.
10 Typical Field Power Wiring Diag r am . . . . . . . . . . . . . . . 12
This is a safety alert symbol . When you see this symbol on
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION.
DANGER indicates an imminently hazardous situation, which,
if not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation, which, if
not avoided may result in minor or moderate injury
used to alert against unsafe practices and hazards involving
only property damage.
ISO9001
CertifiedQuality
ManagementSystem
.
.
. It is also
437758-YIM-A-0409
437758-YIM-A-0409
Improper installation may create a condition where the
operation of the product could cause personal injury or
property damage. Improper installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Refer to this manual for assistance or
for additional information, consult a qualified contractor,
installer or service agency.
This product must be installed in strict compliance with
the installation instructions and any applicable local,
state and national codes including, but not limited to
building, electrical, and mechanical codes.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury. Improper installation,
adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to this manual.
For assistance or additional information consult a
qualified installer, service agency or the gas supplier.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system. Gage sets, hoses, refrigerant
containers and recovery systems must be designed to
handle R-410A. If you are unsure, consult the equipment
manufacturer. Failure to use R-410A compatible servicing
equipment may result in property damage or injury.
Due to system pressure, moving parts, and electrical
components, installation and servicing of air conditioning
equipment can be hazardous. Only qualified, trained service
personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions
of cleaning coils and filters and replacing filters.
Observe all precautions in the literature, labels, and tags
accompanying the equipment whenever working on air
conditioning equipment. Be sure to follow all other applicable
safety precautions and codes including ANSI Z223.1 or CSAB149.1- latest edition.
Wear safety glasses and work gloves. Use quenching cloth and
have a fire extinguisher available during brazing operations.
Inspection
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier’s freight bill. A separate
request for inspection by the carrier’s agent should be made in
writing.
This product must be installed in strict compliance with
the enclosed installation instructions and any applicable
local, state and national codes including, but not limited
to, building, electrical, and mechanical codes.
The furnace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing at pressures in excess of 1/2 PSIG.
Pressures greater than 1/2 PSIG will cause gas valve
damage resulting in a hazardous condition. If it is
subjected to a pressure greater than 1/2 PSIG, the gas
valve must be replaced.
The furnace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
If the information in this manual is not followed exactly, a
fire or explosion may result causing property damage,
personal injury or loss of life.
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
a. Do not try to light any appliance.
b. Do not touch any electrical switch; do not use any
phone in your building.
c. Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
d. If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
2Johnson Controls Unitary Products
Reference
Additional information is available in the following reference
forms:
• Technical Guide - DNQ024-060, 333491
• General Installation - DNQ024-060, 437758
Renewal Parts
®
Contact your local York
parts distribution center for authorized
replacement parts.
Approvals
Design certified by CSA as follows:
1.For use as a cooling only unit, cooling unit wi th
supplemental electric heat or a forced air furnace.
2.For outdoor installation only.
3.For installation on combustible material and may be
installed directly on combustible flooring or, in the U.S., on
wood flooring or Class A, Class B or Class C roof covering
materials.
4.For use with natural gas (convertible to LP with kit).
This product must be installed in strict compliance with
the enclosed installation instructions and any applicable
local, state, and national codes including, but not limited
to, building, electrical, and mechanical codes.
Nomenclature
437758-YIM-A-0409
Improper installation may create a condition where the
operation of the product could cause personal injury or
property damage.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system.
Read these instructions before continuing this appliance
installation. This is an outdoor combination heating and cooling
unit. The installer must assure that these instructions are made
available to the consumer and with instructions to retain them
for future reference.
1.Refer to the unit rating plate for the approved type of gas
for this product.
2.Install this unit only in a location and position as specified
on Page 5 of these instructions.
3.Never test for gas leaks with an open flame. Use
commercially available soap solution made specifically for
the detection of leaks when checking all connections, as
specified on Pages 3 and 16 of these instructions.
4.Always install furnace to operate within the furnace's
intended temperature-rise range with the duct system and
within the allowable external static pressure range, as
specified on the unit name/rating plate, specified on
Page 17 of these instructions.
5.This equipment is not to be used for temporary heating of
buildings or structures under construction.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result
in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically
for the detection of leaks to check all connections. A fire
or explosion may result causing property damage,
personal injury or loss of life.
Limitations
These units must be installed in accordance with the following:
In U.S.A.:
2.National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3.Gas-Fired Central Furnace Standard, ANSI Z21.47a. Latest Edition
4.Local building codes, and
5.Local gas utility requirements
110 = 110,000 BTUH (70,200 BTUH)
Johnson Controls Unitary Products3
437758-YIM-A-0409
In Canada:
1.Canadian Electrical Code, CSA C22.1
2.Installation Codes, CSA - B149.1.
3.Local plumbing and waste water codes, and
4.Other applicable local codes.
Refer to unit application data found in this document.
After installation, gas fired units must be adjusted to obtain a
temperature rise within the range specified on the unit rating plate.
Blow-Through Design With
Reliable Aluminized Steel
Tubular Heat Exchangers
Long Lasting Powder
Paint Finish
Rear and Bottom Return Air
and Supply Airduct Openings
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer’s and/or customer’s
expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculation made according to the methods of Air
Conditioning Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings
or structures under construction.
Direct Drive
Condenser Fan Motor
Highly Efficient Enhanced Copper
Tube/Aluminum Fin Evaporator Coil
Highly Efficient Enhanced Copper Tube/Enhanced Aluminum Fin
OR Micro-Channel Aluminum Tube/Aluminum Fin Condenser
Decorative Louvered Coil Guard
(Except 5 Ton which ships with a
“Wire Form” Coil Guard)
High Efficiency
Compressor Rigidly
Mounted
Heavy Gauge
Removable Base Rails
Direct Drive Blower Motor With
Slide-Out Blower Assembly
Figure 1: Component Location
Table 1: Unit Limitations
Use the following guidelines to select a suitable location for
these units:
1.Unit is designed for outdoor installation only.
2.Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
3.Suitable for mounting on roof curb.
4.For ground level installation, a level pad or slab should be
used. The thickness and size of the pad or slab used
should meet local codes and unit weight. Do not tie the
slab to the building foundation.
5.Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed on a
solid, level roof curb or appropriate angle iron frame.
6.Maintain level tolerance to 1/8” across the entire width and
length of unit.
Excessive exposure of this furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include:
permanent wave solution, chlorinated waxes and
cleaners, chlorine based swimming pool chemicals,
water softening chemicals, carbon tetrachloride,
Halogen type refrigerants, cleaning solvents (e.g.
perchloroethylene), printing inks, paint removers,
varnishes, hydrochloric acid, cements and glues,
antistatic fabric softeners for clothes dryers, masonry
acid washing materials.
codes. Refer to Table 5 for clearances required for combustible
construction, servicing, and proper unit operation.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion air
inlet or vent outlets.
Rigging And Handling
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit, MUST be used
across the top of the unit.
If a unit is to be installed on a roof curb other than a
York® roof curb, gasketing must be applied to all
surfaces that come in contact with the unit underside.
Before lifting, make sure the unit weight is distributed
equally on the rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift. Slotted openings in
the base rails are provided for this purpose.
Clearances
All units require particular clearances for proper operation and
service. Installer must make provisions for adequate
combustion and ventilation air in accordance with section 5.3 of
Air for Combustion and Ventilation of the National Fuel Gas
Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2,
7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) -
Latest Edition, and/or applicable provisions of the local building
Johnson Controls Unitary Products5
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
437758-YIM-A-0409
"D"
FRONT
OF
UNIT
"A"
49-1/8
Figure 2: Unit 4 Point Load Weight
Table 2: Weights and Dimensions
Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
060
(5.0)
Weight (lbs.)Center of Gravity4 Point Load Location (lbs.)
ShippingOperatingX YABCD
3953902024.51138182114
4304252024.251228890125
4354302024.251238991127
490485202413899104144
4954902024139100105146
5355302024150108114158
CENTER OF
GRAVITY
"C"
X
"B"
Y
47-1/4
Table 3: Unit Accessory Weights
Unit AccessoryModel
Add EconomizerAll4540
ShippingOperating
Weight (lbs.)
6Johnson Controls Unitary Products
GAS SUPPLY
1-1/4" DIAMETER HOLE
(1/2" NPTF CONNECTION)
UNIT CONDENSATE
CONNECTION 3/4" NPTF
(TRAP RECOMMENDED)
HIGH VOLTAGE
CONN. 1-3/8" DIA.
KNOCKOUT
GAS SUPPLY
1-1/4" DIA. KNOCKOUT
1/2" NPTF CONNECTION)
LOW VOLTAGE
CONN.1-3/8" DIA.
KNOCKOUT x 7/8" HOLE
VENT AIR OUTLET HOOD
BLOWER SERVICE ACCESS
COMPARTMENT PANEL
B
3-3/4
2-1/2
47-1/4
(OVERALL)
1-1/2
3-1/3
5-3/8
2-5/8
11
CONDENSER COIL
12-3/4
49-1/8
(OVERALL)
437758-YIM-A-0409
A
2-3/8
REFRIGERANT
CONNECTIONS
COMBUSTION AIR
INLET LOUVERS
FRONT
GAS/ELECTRIC CONTROL
SERVICE ACCESS
COMPARTMENT PANEL
Figure 3: Unit Dimensions
Table 4: Unit Dimensions Front
1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air
discharge outlet.
4. Units may be installed on combustable floors made from wood or class A, B or C roof covering
materials.
“A”“B”
2
Distance
(in.)
36Right12
Dimensions
Direction
Distance
(in.)
4
0
Johnson Controls Unitary Products7
437758-YIM-A-0409
HIGH VOLTAGE
CONN. 1-3/32"
DIA. KNOCKOUT
8-7/8
11-7/8
19-1/4
FRONT
GAS SUPPLY 1-5/8"
DIA. KNOCKOUT (1/2"
NPTF CONNECTION)
LOW VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT
CONDENSATE
DRAIN 3/4" NPTF
26-3/4
Figure 4: Dimensions Front and Bottom
CONDENSER
BOTTOM SUPPLY
AIR OPENING
COIL
SIDE SUPPLY
AIR OPENING
6
14-1/2
28-3/8
14-1/2
4-5/8
BACK
3-3/8
SIDE RETURN
AIR OPENING
1-3/4
15
Figure 5: Dimensions Back and Bottom
8Johnson Controls Unitary Products
28-9/16
15
3-1/2
1-3/4
BOTTOM RETURN
1-3/4
AIR OPENING
15
4
14-1/2
4-1/4
42-2/3
40-3/4
17-5/8
RECOMMENDED
DUCT SIZE
17-1/2" x 16-3/4"
17-1/4
437758-YIM-A-0409
45-1/8
43-1/4
OPENING FOR
RETURN AIR DUCT
14
Figure 6: Roof Curb
3-1/2
1
Ductwork
These units are adaptable to downflow use as well as rear
supply and return air duct openings. To convert to downflow,
use the following steps:
1.Remove the duct covers found in the bottom return and
supply air duct openings. There are four (4) screws
securing each duct cover (save these screws to use in
Step 2).
2.Install the duct covers (removed in step one) to the rear
supply and return air duct openings. Secure with the four
(4) screws used in step one.
3.Seal duct covers with silicone caulk.
Duct work should be designed and sized according to the
methods of the Air Conditioning Contractors of America
(ACCA), as set forth in their Manual D.
A closed return duct system shall be used. This shall not
preclude use of economizers or ventilation air intake. Flexible
joints may be used in the supply and return duct work to
minimize the transmission of noise.
NOTE: Be sure to note supply and return openings.
22
OPENING FOR
SUPPLY AIR DUCT
RECOMMENDED
DUCT SIZE
17-1/8" x 21-1/2"
1
Refer to Figures 4 and 5 for information concerning rear and
bottom supply and return air duct openings.
Roof Curb
On applications when a roof curb is used, the unit must be
positioned on the curb so the front of the unit is tight against the
curb.
Filters
Single phase units are shipped without a filter or filter racks. It is
the responsibility of the installer to secure a filter in the return air
ductwork or install a Filter/Frame Kit (1FF0110, 1FF0112 or
1FF0114).
A filter rack and high velocity filters are standard on three phase
units.
Filters must always be used and must be kept clean. When
filters become dirt laden, insufficient air will be delivered by the
blower, decreasing your units efficiency and increasing
operating costs and wear-and-tear on the unit and controls.
Filters should be checked monthly; this is especially important
since this unit is used for both heating and cooling.
1. 8” Roof Curb also available.
Johnson Controls Unitary Products9
437758-YIM-A-0409
Condensate Drain
A condensate trap is recommended to be installed in the
condensate drain. The plumbing must conform to local codes.
Use a sealing compound on male pipe threads. Install the
condensate drain line (3/4” NPTF) to spill into an open drain.
Hand tighten only.
Service Access
Access to all serviceable components is provided at the
following locations:
• Blower compartment access panel
• Gas control/electrical access panel
• Refrigerant connections
Refer to Figure 3 for location of these access locations and
minimum clearances in Table 5.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system. Gage sets, hoses, refrigerant
containers and recovery systems must be designed to
handle R-410A. If you are unsure, consult the
equipment manufacturer. Failure to use R-410A
compatible servicing equipment may result in property
damage or injury.
Wear safety glasses and gloves when handling
refrigerants. Failure to follow this warning can cause
serious personal injury.
Refer to Figure 19 for the R-410A Quick Reference Guide.
Thermostat
The room thermostat should be located on an inside wal l
approximately 56" above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or
appliances. Follow manufacturer's instructions enclosed with
the thermostat for general installation procedure. Color coded
insulated wires (minimum #18 AWG) should be used to connect
thermostat to unit. See Figures 7 thru 10.
Power And Control Wiring
Field wiring to the unit must conform to provisions of the current
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.
The unit must be electrically grounded in accordance with local
codes or, in their absence, with the N.E.C./C.E.C. Voltage
tolerances which must be maintained at the compressor
terminals during starting and running conditions are indicated
on the unit Rating Plate and Table 6.
The wiring entering the cabinet must be provided with
mechanical strain relief.
A fused disconnect switch should be field provided for the unit.
If any of the wire supplied with the unit must be replaced,
replacement wire must be of the type shown on the wiring
diagram.
Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.
Refer to Figures 7 thru 10 for typical field wiring and to the
appropriate unit wiring diagram for control circuit and power
wiring information.
10Johnson Controls Unitary Products
** = Minimum wire size of 18 AWG
wire should be used for all field
installed 24 volt wire.
THERMOSTAT
R
G
UNIT CONTROL BOARD
TERMINAL STRIP
**
R
G
437758-YIM-A-0409
NOTE: HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
YY
W
C
W
C
PROGRAMMABLE
THERMOSTAT ONLY
Figure 7: Typical Field Control Wiring Diagram Single Stage Thermostat-Single Stage Gas Heat
NOTE: HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
** = Minimum wire size of 18 AWG
wire should be used for all field
installed 24 volt wire.
THERMOSTAT
R
G
W
UNIT CONTROL BOARD
TERMINAL STRIP
* *
R
G
Y Y
W
1
24 VOLT
TRANSFORMER
24 VOLT
TRANSFORMER
W
2
C
C
PROGRAMMABLE
THERMOSTAT ONLY
Figure 8: Typical Field Control Wiring Diagram Single Stage Thermo stat-Two Stage Gas Heat
Johnson Controls Unitary Products11
437758-YIM-A-0409
** = Minimum wire size of 18 AWG
wire should be used for all field
installed 24 volt wire.
THERMOSTAT
R
G
UNIT CONTROL BOARD
TERMINAL STRIP
* *
R
G
NOTE: HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
1
Y
2
W
1
W
2
C
Y Y
W
1
W
2
C
PROGRAMMABLE
THERMOSTAT ONLY
Figure 9: Typical Field Control Wiring Diagram Two Stage Thermo stat-Two Stage Gas Heat
24 VOLT
TRANSFORMER
Figure 10: Typical Field Power Wiring Diagram
Table 6: Electrical Data
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Supply
Blower
Motor
MCA
(Amps)
1
Max
Fuse
Breaker
Size
(Amps)
2
/
3
12Johnson Controls Unitary Products
437758-YIM-A-0409
Table 7: Single Stage Physical Data
Component
Nominal Tonnage2.02.53.03.54.05.0
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu)24.029.835.743.549.656.8*
ARI net capacity (Btu)23.529.034.542.048.055.0*
EER12.012.012.012.012.012.0*
SEER14.014.014.014.014.014.0*
Nominal CFM8009001100140015001550
System power (KW)2.02.42.93.54.04.6
Refrigerant typeR-410AR-410AR-410AR-410AR-410AR-410A
Refrigerant charge (lb-oz)3-83-154-45-45-06-5
ARI HEATING PERFORMANCE
Heating modelN036N056N036N056N036N056N072N065N090N065N090N110N065N090N110
Heat input (K Btu)45704570457090801088010813580108135
Heat output (K Btu)36563656365672648764871086487108
AFUE %80.080.080.080.080.080.080.080.080.080.080.080.080.080.080.0
Steady state efficiency (%)808080808080808080808080808080
No. burners232323434345345
No. stages111111111111111
Temperature Rise Range (ºF)25-55 30-60 25-5530-60 25-55 25-55 30-60 25-55 45-75 25-55 35-65 45-75 25-55 35-6545-75
Gas Limit Setting (ºF)140160140160140160160140160150175160150175160
Gas piping connection (in.)1/21/21/21/21/21/2
Face area (Sq. Ft.)7.911.911.9151515
Rows111111
Fins per inch232323232323
Tube diameter (in.)0.71 / 180.71 / 180.71 / 180.71 / 180.71 / 180.98 / 25
Circuitry Type2-pass2-pass2-pass2-pass2-pass2-pass
EVAPORATOR COIL DATA
Face area (Sq. Ft.)3.43.43.44.44.44.4
Rows233334
Fins per inch151313161613
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry TypeInterlacedInterlacedInterlacedInterlacedInterlacedInterlaced
Refrigerant controlTXVTXVTXVTXVTX VTXV
CONDENSER FAN DATA
Quantity111111
Fan diameter (Inch)222222222222
TypePropPropPropPropPropProp
Drive typeDirectDirectDirectDirectDirectDirect
No. speeds111111
Number of motors111111
Motor HP each 1/4 1/4 1/4 1/3 1/31/3
RPM110011001100110011001100
Nominal total CFM240024002400320032003200
DIRECT DRIVE EVAP FAN DATA
Quantity111111
Fan Size (Inch)10 x 810 x 811 x 1012 x 1112 x 1112 x 11
TypeCentrifugalCentrifugalCentrifugalCentrifugalCentrifugalCentrifugal
Motor HP each1/2 3/4 3/4111
RPMVariableVariableVariableVariableVariableVariable
Frame size484848484848
FILTERS
Quantity - Size1 - 20 x 20 x 11 - 20 x 20 x 11 - 20 x 20 x 12 - 20 x 12 x 12 - 20 x 12 x 12 - 20 x 12 x 1
DNQ024DNQ030DNQ036DNQ042DNQ048DNQ060
Models
* Rating established with a “Wire Form” coil guard which ships as standard.
Johnson Controls Unitary Products13
437758-YIM-A-0409
Table 8: Two Stage Physical Data
Component
Nominal Tonnage2.02.53.03.54.05.0
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu)24.029.835.743.549.656.8*
ARI net capacity (Btu)23.529.034.542.048.055.0*
EER12.012.012.012.012.012.0*
SEER14.014.014.014.014.014.0*
Nominal CFM8009001100140015001550
System power (KW)2.02.42.93.54.04.6
Refrigerant typeR-410AR-410AR-410AR-410AR-410AR-410A
Refrigerant charge (lb-oz)3-83-154-45-45-06-5
ARI HEATING PERFORMANCE
Heating modelD056D056D056D072D090D090D110D090D110
Heat input (K Btu)70/45.570/45.570/45.5 90/58.5108/70.2108/70.2 135/87.8108/70.2 135/87.8
Heat output (K Btu)56/36.456/36.456/36.4 72/46.887/56.287/56.2108/70.287/56.2108/70.2
AFUE %80.080.080.080.080.080.080.080.080.0
Steady state efficiency (%)808080808080808080
No. burners333444545
No. stages222222222
Temperature Rise Range (ºF)30-6030-6025-5530-6045-7535-6545-7535-6545-75
Gas Limit Setting (ºF)160160160160175175170175170
Gas piping connection (in.)1/21/21/21/21/21/2
Face area (Sq. Ft.)7.911.911.9151515
Rows111111
Fins per inch232323232323
Tube diameter (in.)0.71 / 180.71 / 180.71 / 180.71 / 180.71 / 180.98 / 25
Circuitry Type2-pass2-pass2-pass2-pass2-pass2-pass
EVAPORATOR COIL DATA
Face area (Sq. Ft.)3.43.43.44.44.44.4
Rows233334
Fins per inch151313161613
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry TypeInterlacedInterlacedInterlacedInterlacedInterlacedInterlaced
Refrigerant controlTXVTXVTXVTXVTXVTXV
CONDENSER FAN DATA
Quantity111111
Fan diameter (Inch)222222222222
TypePropPropPropPropPropProp
Drive typeDirectDirectDirectDirectDirectDirect
No. speeds111111
Number of motors111111
Motor HP each 1/4 1/4 1/4 1/3 1/31/3
RPM110011001100110011001100
Nominal total CFM240024002400320032003200
DIRECT DRIVE EVAP FAN DATA
Quantity111111
Fan Size (Inch)10 x 810 x 811 x 1012 x 1112 x 1112 x 11
TypeCentrifugalCentrifugalCentrifugalCentrifugalCentrifugalCentrifugal
Motor HP each1/2 3/4 3/4111
RPMVariableVariableVariableVariableVariableVariable
Frame size484848484848
FILTERS
Quantity - Size1 - 20 x 20 x 11 - 20 x 20 x 11 - 20 x 20 x 12 - 20 x 12 x 12 - 20 x 12 x 12 - 20 x 12 x 1
DNQ024DNQ030DNQ036DNQ042DNQ048DNQ060
Models
* Rating established with a “Wire Form” coil guard which ships as standard.
14Johnson Controls Unitary Products
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.