Johnson Controls DHR24CSB21S, DHR36CSB21S, DHR30CSB21S, DHR18CSB21S, DHR42CSB21S Installation And Maintenance Manual

...
Installation
and
Maintenance
Manual
"R" SERIES
INVERTER-DRIVEN
AIR CONDITIONING UNITS
Type
OUTDOOR UNITS
Type
INDOOR UNITS
DUCT
Type
INDOOR UNITS
CASSETTE
Model
DHR18CSB21S DHR24CSB21S DHR30CSB21S DHR36CSB21S DHR42CSB21S DHR48CSB21S
Model
DHR18NDB21S
DHR24NDB21S
DHR30NDB21S DHR36NDB21S
DHR42NDB21S DHR48NDB21S
Model
DHR18NKB21S
DHR24NKB21S
DHR30NKB21S DHR36NKB21S
DHR42NKB21S DHR48NKB21S
Type
INDOOR UNITS
CEILING
Model
DHR18NCB21S
DHR24NCB21S
DHR30NCB21S DHR36NCB21S
DHR42NCB21S DHR48NCB21S
,03257$17
PLEASE READ AND
. KEEP
Important Notice
Johnson Controls, Inc. pursues a policy of continuing improvement in design and performance in its
products. As such, Johnson Controls, Inc. reserves the right to make changes at any time without prior notice.
Johnson Controls, Inc. cannot anticipate every possible circumstance that might involve a potential hazard.
This inverter air conditioning unit is designed for standard air conditioning applications only. Do not use
this unit for anything other than the purposes for which it was intended for.
The installer and system specialist shall safeguard against leakage in accordance with local pipetter
and electrical codes. The following standards may be applicable, if local regulations are not available. International Organization for Standardization: (ISO 5149 or European Standard, EN 378). No part of this manual may be reproduced in any way without the expressed written consent of Johnson Controls, Inc.
This inverter-driven (cooling or heat pump) air conditioning unit will be operated and serviced in the
United States of America and comes with all required Safety, Danger, and Caution, warnings.
If you have questions, please contact your distributor or dealer.
This manual provides common descriptions, basic and advanced information to maintain and service
this inverter-driven (cooling or heat pump) air conditioning unit which you operate, as well for other models.
This inverter-driven (cooling or heat pump) air conditioning unit has been designed for a specic
temperature range. For optimum performance and long life, operate this unit within range limits.
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
Product Inspection upon Arrival
1. Upon receiving this product, inspect it for any damages incurred in transit. Claims for damage, either
apparent or concealed, should be led immediately with the shipping company.
2. Check the model number, electrical characteristics (power supply, voltage, and frequency rating), and any accessories to determine if they agree with the purchase order.
3. The standard utilization for this unit is explained in these instructions. Use of this equipment for purposes other than what it designed for is not recommended.
4. Please contact your local agent or contractor as any issues involving installation, performance, or
maintenance arise. Liability does not cover defects originating from unauthorized modications
performed by a customer without the written consent of Johnson Controls, Inc. Performing any mechanical alterations on this product without the consent of the manufacturer will render your warranty null and void.
2
P5415467
Table of Contents
1. INTRODUCTION AND SAFETY SUMMARY ......................................................................................... i
2. INDOOR UNIT INSTALLATION ................................................................................................................1
2.1 Installation of Duct Type ................................................................................................................. 1
2.2 Installation of Floor Ceiling Type ................................................................................................10
2.3 Installation of Cassette Type ........................................................................................................16
3. OUTDOOR UNIT INSTALLATION............................................................................................................26
3.1 Before Installation .......................................................................................................................... 26
3.2 Installation Site ................................................................................................................................26
3.3 Caution for Installation ................................................................................................................. 27
3.4 Dimension Data ................................................................................................................................27
4. REFRIGERATION PIPING WORK ........................................................................................................... 28
4.1 Refrigeration Piping Work Procedures and Caution in Connecting ...................................28
4.2 Specification of Connection Pipe .................................................................................................33
5. ELECTRIC WIRING WORK ........................................................................................................................33
5.1 Wiring Precautions ...........................................................................................................................33
5.2 Electrical Wiring................................................................................................................................ 34
6. MAINTENANCE TROUBLESHOOTING.................................................................................................. 41
6.1 Main Control Malfunction ............................................................................................................... 41
6.2 Description of Drive Malfunction ..................................................................................................43
7. FLOW CHART OF TROUBLESHOOTING ............................................................................................. 45
7.1 Troubleshooting Flow Chart of Main Control Malfunction ....................................................45
7.2 Troubleshooting Flow Chart of Drive Malfunction...................................................................52
7.3 Interface ..............................................................................................................................................57
7.4 IPM, PFC Testing Method ...............................................................................................................63
8. WIRING DIAGRAM ....................................................................................................................................64
8.1 Outdoor unit ...................................................................................................................................... 64
8.2 Indoor unit ......................................................................................................................................... 67
CUSTOMER SERVICE, TECHNICAL SUPPORT........................................................................................ 71
1. Introduction
This manual concentrates on inverter-driven cooling or heat pump air conditioning units. Read this manual carefully before installation.
This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air conditioning equipment.
2. Important Safety Instructions
Safety Messages
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions thoroughly and follow all warnings or cautions included in all manuals that accompanied the product and are attached to the unit. Refer back to these
safety instructions as needed.
This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be qualied according to local, state and national building and safety codes and regulations. Incorrect installation could cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance requirements are specied, the appropriate measures should be taken during installation to guard against
possible damage or injury that might occur in an earthquake if the unit is not installed correctly, injuries may occur due to a falling unit.
Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and, where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited
for electrical operation purposes. Keep a quenching cloth and a re extinguisher nearby during brazing.
Use care in handling, rigging, and setting of bulky equipment.
When transporting, be careful when picking up, moving and mounting these units. Although the unit may be packed using plastic straps, do not use them for transporting the unit from one location to another. Do not stand on or put any material on the unit. Get a partner to help, and bend with your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum ns on the air conditioner can cut ngers,
so wear protective gloves.
Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features, disengagement, and interlocks must be in place and functioning correctly before the equipment is put into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident can occur. Never bypass or jump-out any safety device or switch.
Johnson Controls, Inc. will not assume any liability for injuries or damage caused by not following steps outlined or described in this manual. Unauthorized modications to Johnson Controls products are
prohibited as they…
May create hazards which could result in death, serious injury or equipment damage. Will void product warranties. May invalidate product regulatory certications. ◦ May violate OSHA standards.
31
i
P5415467
Take the following precautions to reduce the risk of property damage.
Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during
installation work. Foreign matter could damage internal components or cause blockages.
If air lters are required on this unit, do not operate the unit without the air lter set in place. If the air lter is not installed, dust may accumulate and breakdown may result.
Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules attach themselves to the surface of the heat exchanger, the nned surfaces will repel water. As a result, any amount of condensate can overow from the condensate pan and could run inside of the
electrical box, possibly causing electrical failures.
When installing the unit in a hospital or other facility where electromagnetic waves are generated from nearby medical and/or electronic devices, be prepared for noise and electronic interference Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment, and radio communications equipment may cause the unit to malfunction. The operation of the unit may also adversely affect these same devices. Install the unit at least 10 ft. (approximately 3m) away from such devices.
When a wireless zone controller is used, locate at a distance of at least 3.3 ft. (approximately 1 meter) between the indoor unit and electric lighting. If not, the receiver part of the unit may have difculty
receiving operation commands.
Do not install the unit in any location where animals and plants can come into direct contact with the outlet air stream. Exposure could adversely affect the animals and plants.
Do not install the unit with any downward slope to the side of the drain boss. If you do, you may have water owing back which may cause leaks.
Be sure the condensate hose discharges water properly. If connected incorrectly, it may cause leaks.
Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in
restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These specialized oil-resistant units can be ordered for such applications. However, in places where large quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used. These products should not be installed in such locations.
Installation Precautions
To reduce the risk of serious injury or death, the following installation
precautions must be followed.
When installing the unit into… A wall: Make sure the wall is strong enough to hold the unit’s weight. It may be necessary to
construct a strong wood or metal frame to provide added support.
A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
cause dripping and water damage to wall and oors.
Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air bafe.
A snowy area (only for heat pump model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
Do not install the unit in the following places. Doing so can result in an explosion, re, deformation,
corrosion, or product failure.
Explosive or ammable atmosphere ▫ Where re, oil, steam, or powder can directly enter the unit, such as in close proximity or directly
above a kitchen stove.
Where oil (including machinery oil) may be present. Where corrosive gases such as chlorine, bromine, or sulde can accumulate, such as near a hot
tub or hot spring.
Where dense, salt-laden airow is heavy, such as in coastal regions. ▫ Where the air quality is of high acidity. Where harmful gases can be generated from decomposition.
ii
4
P5415467
Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive gases may be present. If you do, toxic gases can seep into breathable air spaces and can cause respiratory injuries. If the condensate pipe is installed incorrectly, water leakage and damage to the
ceiling, oor, furniture, or other possessions may result. If condensate piping becomes clogged,
moisture can back up and can drip from the indoor unit. Do not install the indoor unit where such dripping can cause moisture damage or uneven locations: Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the unit to prevent water damage and abnormal vibration.
Before performing any brazing work, be sure that there are no ammable materials or open ames nearby.
Perform a run test to ensure normal operation. Safety guards, shields, barriers, covers, and protective devices must be in place while the compressor/unit is operating. During the test run, keep ngers and
clothing away from any moving parts.
Clean up the site when nished, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being installed.
During transportation, do not allow the backrest of the forklift to make contact with the unit, otherwise, it may cause damage to the heat exchanger and also may cause injury when stopped or started suddenly.
Remove gas inside the closing pipe when the brazing work is performed. If the brazing ller metal is
melted with remaining gas inside, the pipes will be blown off and it may cause injury.
Be sure to use nitrogen gas for an airtight test. If other gases such as oxygen gas, acetylene gas or uorocarbon gas are accidentally used, it may cause explosion or gas intoxication.
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use and maintenance of the unit to the customer according to the information in all manuals that came with the system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
Controls uses only refrigerants that have been approved for use in the unit’s intended home country
or market. Johnson Controls distributors similarly are only authorized to provide refrigerants that have been approved for use in the countries or markets they serve. The refrigerant used in this unit
is identied on the unit’s faceplate and/or in the associated manuals. Any additions of refrigerant into this unit must comply with the country’s requirements with regard to refrigerant use and should be
obtained from Johnson Controls distributors. Use of any non-approved refrigerant substitutes will void the warranty and will increase the potential risk of injury or death.
If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum
allowable concentration in the event that refrigerant gases should escape. Refrigerant gases can cause asphyxiation (0.42 kg/m3 based on ISO 5149 for R410A). Consult with your distributor for countermeasures (ventilation system and so on). If refrigerant gas has leaked during the installation work, ventilate the room immediately.
The design pressure for this product is 601 psi (4.15MPa). The pressure of R410A refrigerant is 1.4
times higher than that of the refrigerant R22. Therefore, the refrigerant piping for R410A shall be
thicker than that for R22. Make sure to use the specified refrigerant piping. If not, the refrigerant piping may rupture due to an excessive refrigerant pressure. Besides, pay attention to the piping
thickness when using copper refrigerant piping. The thickness of copper refrigerant piping differs depending on its material.
The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
as moisture, oxide lm, (or fat). Perform the installation work with care to prevent moisture, dust, or
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the cycle from such parts as expansion valve and the operation may be unavailable.
To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the
sizes of the charging connections have been changed from R407C type and R22 type. It is necessary to prepare the appropriate tools before performing the installation work.
Use refrigerant pipes and joints which are approved for use with R410A.
A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is
5
P5415467
iii
under pressure and never open pressurized system parts.
Before installation is complete, make sure that the refrigerant leak test has been performed. If
refrigerant gases escape into the air, turn OFF the main switch, extinguish any open ames and
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
should leak and come into contact with open ames, toxic gas could be generated. Also, because the uorocarbons are heavier than air, they settle to the oor, which could cause asphyxiation.
When installing the unit, and connecting refrigerant piping, keep all piping runs as short as
possible, and make sure to securely connect the refrigerant piping before the compressor starts operating. If the refrigerant piping is not connected and the compressor activates with the stop valve opened, the refrigerant cycle will become subjected to extremely high pressure, which can
cause an explosion or re.
Tighten the are nut with a torque wrench in the specied manner. Do not apply excessive force to the
are nut when tightening. If you do, the are nut can crack and refrigerant leakage may occur.
When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the
compressor stops.
When pipes are removed out from under the piping cover, after the insulation work is completed,
cover the gap between the piping cover and pipes by a packing (eld-supplied). If the gap is not
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
valve ies out due to refrigerant pressure. At the run test, fully open the gas and liquid valves,
otherwise, these devices will be damaged. (It is closed before shipment.)
If the arrangement for outdoor units is incorrect, it may cause owback of the refrigerant and result in
failure of the outdoor unit.
The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15o.
Electrical Precautions
Take the following precautions to reduce the risk of electric shock, re or
explosion resulting in serious injury or death.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram
and these instructions when wiring. Improper connections and inadequate grounding can cause serious injury or death.
Perform all electrical work in strict accordance with this installation and maintenance manual and all
the relevant regulatory standards.
Before servicing, open and tag all disconnect switches. Never assume electrical power is
disconnected. Check with meter and equipment.
Only use electrical protection equipment and tools suited for this installation.
Use specied cables between units.
The new air conditioner may not function normally in the following instances:
If electrical power for the new air conditioner is supplied from the same transformer as the device*
referred to below.
If the power source cables for this device* and the new air conditioner unit are located in close
proximity to each other.
Device*: (Example): A lift, container crane, rectier for electric railway, inverter power
device, arc furnace, electric furnace, large-sized induction motor and large-sized switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply cables for the packaged air conditioner due to a rapid change in power consumption of the device and an activation of a switch.
Check eld regulations and standards before performing electrical work in order to protect the
power supply for the new air conditioner unit.
iv
6
P5415467
Communication cabling shall be a minimum of 18-Gauge, 2-Conductor, Stranded Copper. Shielded
cable must be considered for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors. When shielded cabling is applied, proper bonding and termination of the cable shield is required as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be considered per application and local code requirments.
Use an exclusive power supply for the air conditioner at the unit’s rated voltage.
Be sure to install circuit breakers (ground fault interrupter, isolating switch, molded case circuit
breaker and so on), with the specied capacity. Ensure that the wiring terminals are tightened securely to recommended torque specications.
Clamp electrical wires securely with a cable clamp after all wiring is connected to the terminal block.
In addition, run wires securely through the wiring access channel.
When installing the power lines, do not apply tension to the cables. Secure the suspended cables at
regular intervals, but not too tightly.
Make sure that the terminals do not come into contact with the surface of the electrical box. If the
terminals are too close to the surface, it may lead to failures at the terminal connection.
Turn OFF and disconnect the unit from the power source when handling the service connector. Do not
open the service cover or access panel to the indoor or outdoor units without turning OFF the main power supply.
After ceasing operation, be sure to wait at least ve minutes before turning off the main power
switch. Otherwise, water leakage or electrical breakdown may result. Disconnect the power source completely before attempting any maintenance for electrical parts. Check to ensure that no residual voltage is present after disconnecting the power source.
Do not clean with, or pour water into, the controller as it could cause electric shock and/or damage the
unit. Do not use strong detergent such as a solvent. Clean with a soft cloth.
Check that the ground wire is securely connected. Do not connect ground wiring to gas piping, water
piping, lighting conductor, or telephone ground wiring.
If a circuit breaker or fuse is frequently activated, shut down the system and contact your
service contractor.
Perform all electrical work in accordance with this manual and in compliance with all regulations and
safety standards.
Do not open a service access cover or panel of an indoor or outdoor unit without rst turning OFF the
power at the main power supply.
Residual voltage can cause electric shock. At all times, check for residual voltage after disconnecting
from the power source before starting work on the unit.
This equipment can be installed with a Ground Fault Circuit Breaker (GFCI), which is a recognized
measure for added protection to a properly grounded unit. Install appropriate sized breakers/fuses/ overcurrent protection switches, and wiring in accordance with local, state and NEC codes and requirements. The equipment installer is responsible for understanding and abiding by applicable codes and requirements.
v
7
P5415467
2. INDOOR UNIT INSTALLATION
2.1 Installation of Duct Type
2.1.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or internal
damage, please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the specification
and quantity of accessory parts are correct.
Determine the correct handling route and methods to avoid damaging the unit or causing possible
hazard. For the sake of protection and safety, it is suggested to move the unit with the packaging box.
Even though it is not the best to do this under some special situations,
thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the
building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
do not remove the packaging box,
2.1.2 Installation Site
Ensure the top mounting bracket is strong enough to withstand the weight of the unit.
Ensure condensate pipe has convenient flow of water.
Ensure there is no obstacle blocking the return air inlet and exhaust outlet, so as to ensure
sound air circulation.
The installation spaces required by the drawing must be ensured, so as to provide enough space
for service and maintenance.
The installation site must be far away from
The indoor unit is of ceiling mount (indoor unit is hidden inside the ceiling).
The indoor and outdoor units, the power cable and the connecting electrical lines must be at least
40 inches from any TV set or radio. This is to avoid image interference or noise of the TV set or radio.
n if the distance is 40 inches, noise can also exist if there is a strong electric wave.)
(Eve
heat source, leakage of inflammable gas or smoke.
2.1.3 Caution for Installation
Generally, the unit is installed indoors on a ceiling. For ceiling mounting, ensure that the
hangers on
To meet the noise and vibration requirements, the unit should be installed by using a rubber pad
(thickness 20mm (13/16inch)) and rubber connector.
Insert a M10 expansion bolt into the hole. Drive a nail into the bolt. Refer to the profile dimensions
ceiling have adequate strength to support the weight of the unit.
1
drawing of the indoor unit for the distance between the holes. Refer to Figure 3-1-1 for the installation of the
expansion bolt.
Air-conditioning Unit
Ceiling-mount Screw
Hanger
Figure 3-1-1 Figure 3-1-2
Hook
Screw
Nut
Nut
Figure 3-1-3
Install the hanger onto the indoor unit as Figure 3-1-2 and Figure 3-1-3 shows.
Install the indoor unit at the ceiling as Figure 3-1-4 shows.
I
Air Intake
Precautions for unfavorable installation:
Figure 3-1-4
Screw
Hanger
Nut
Air Supply
48mm(1-7/8inch)
"I" Detail
The preparation of all pipes (connecting pipes and condensate pipes) and cables (connecting lines of
wire zone controller, indoor unit and outdoor unit) must be ready before the installation, so as to achieve
smooth installation.
Drill an opening on the ceiling depending on the ceiling type. Providing additional support may be required to prevent vibration and ensure the evenness of the ceiling. Consult with the user or a construction company
for advice.
In case the strength of ceiling is not enough, use angle iro
n sections to set up a beam support.
Place the unit at the beam and secure it.
Level inspection of the indoor unit
After the indoor unit is installed, it is required to check the level of the whole unit. The unit must be
placed horizontally, but the condensate pipe shall be installed obliquely, so as to facilitate the drainage of
condensate.
2
Level Instrument
Condensate
Pipes
B
2.1.4 Dimension Data
For the units: 18k
Air Intake
Enlarged View
Condensate Pipe
A
Figure 3-1-5
Air Supply
As the inside of the unit is in the negative pressure status, it is required to set up a backwater elbow. The requirement is:
A=B≥(0.145P/10000+20)/25.4(inch)
P is the absolute pressure inside the unit. The unit of the pressure is psig.
B
For the units: 24k~42k
3
For the units: 48k
Item
Model
B C D E F G H I J
945
(37-1/4)
618
(24-3/8)
738 (29)
892
(35-1/8)
1037
(40-7/8)
721
(28-3/8)
738 (29)
125
(4-7/8)
203
(8)
266
(10-1/2)
1101
(43-3/8)
517
(20-3/8)
820
(32-1/4)
1159
(45-5/8)
1279
(50-3/8)
558 (22)
1002
(39-1/2)
160
(6-1/4)
235
(9-1/4)
268
(10-1/2)
1011
(39-3/4)
748
(29-1/2)
820
(32-1/4)
1115
(43-7/8)
1226
(48-1/4)
775
(30-1/2)
979
(38-1/2)
160
(6-1/4)
231
(9-1/8)
290
(11-3/8)
1177
(46-3/8)
646
(25-3/8)
852
(33-1/2)
1150
(45-1/4)
1340
(52-3/4)
750
(29-1/2)
953
(37-1/2)
190
(7-1/2)
316
(12-1/2)
350
(13-3/4)
Name & Shape
QTY
Notes
Installation and Operating
Instructions
Insulation materials for gas pipe
1
Used for gas pipe connector on indoor unit.
Insulation materials for liquid
pipe
Used for liquid pipe connector on indoor unit.
Insulation materials for drainage
pipe
Used for wrapping the condensate pipe and
rubber plug.
Nut
1
To connect liquid pipe.
Nut
1
To connect gas pipe.
Nut M6 with gasket
8
Use for fixing the hanger hook.
Nut M10 with gasket
4
Use for fixing the hanger hook.
Nut M10
4
4 sets, used for ceiling mounting of the indoor
spring gasket
4
Hook
4
Used for ceiling mounting of the indoor unit.
1
DHR18NDB21S
H
J
C
A
B
D E
G
I
F
Figure 3-1-6
Table 3-1-1
Unit
: mm (inch)
A
DHR24NDB21S
DHR30NDB21S
DHR36NDB21S
DHR42NDB21S
DHR48NDB21S
Table 3-1-2 Installation Accessor
1
1
2
ies List for Duct-type Indoor Unit
unit.
Wired zone controller
Screw M4 2
To fix the base plate of wired zone c
and installation hole of the wall together.
4
ontroller
2.1.5 Installation Clearance Data
Nut with Washer
G
250mm
(9-7/8inch)
Nut Spring Washer
2500mm
(98-3/8inch)
G
250mm
(9-7/8inch)
Figure 3-1-7
Warning! The height of installation for the indoor unit should be 2.5m (8-1/5ft) above.
2.1.6 Condensate Piping Work
Installation of Condensate Pipeline:
Install the condensate hose in accordance with the instructions in this
enough to prevent condensation. Problems with the piping may lead to water leaks.
installation manual and keep the a rea warm
(1) (Install the condensate hose with downward gradient (1/50 to 1/100) and no risers or traps are
used for the hose (Figure 3-1-8).
(2) Be sure there i
s no crack or leak on the condensate hose to avoid the formation of air pockets
(Figure 3-1-8).
(3) When the hose is long, install supporters (Figure 3-1-9).
(4) Always use the condensate
Arrange the condensate
hose lower than this drain port
hose which has been insulated properly.
Condensate hose
Rise
Trap
Air bleeding
Figure 3-1-8
5
Supporter
Always check that the drain cap is installed to the unused drain port and is fastened with the nylon fastener. If the drain
cap is not installed, or is not sufficiently fastened by the nylon fastener, water may drip during the cooling operation.
Condensate Pipe
1~1.5m(3-2/7~5feet)
Condensate hose
Figure 3-1-9 Figure 3-1-10
A
Enlarged View
Condensate Pipe
A
B
As the inside of the unit is in the negative pressure status, it is required to set up a backwater elbow. The requirement is:
A=B≥(0.145P/10000+20)/25.4(inch)
P is the absolute pressure inside the unit. The unit of the pressure is psig.
B
Figure 3-1-11
(5) Use a suitable condensate hose, and see Table 3-3-3 for its size.
(6)
There is a drain port on both the left and right sides. Select the drain port
to match the local
conditions (Figure 3-1-10).
(7) When the unit is shipped from the factory, the drain port is defaulted to be the one on the left side
(electric box side). T
he port on right side has been plugged.
(8) When using the drain port on the right side of the unit, reinstall the drain cap to the left side drain
port (Figure 3-1-12).
Drain port
Drain cap
Fastener
Figure 3-1-12
(9) Be sure to insulate where
the drain port and the condensate hose is connected (Figure
3-1-13).(10) The unused drain port also should be insulated properly (Figure 3-1-14).
6
Condensate hose insulation
Insulated condensate hose
Unit
Condensate hose insulation
Drain port
Unit
Drain cap
Drain port
Insulated Condensate hose
0mm(0inch)
Drain cap
0mm(0inch)
Figure 3-1-13 Figure 3-1-14
(11) There is adhesive on one side of the insulation so that after removing the protective paper over it
the insulation can be directly attached to the condensate
hose.
(12) Considerations for the unit with the condensate pump:
For the unit with the condensate pump, only one drain port at the side close to the electric box
1)
is prep
2)
See table 3 for the size of the drain port of the unit with the condensate pump, which is different
ared and only through it can the condensate hose can be connected.
from that of the unit without the condensate pump.
For the unit with the condensate pump, two drain ports at the bottom are defaulted to be
3)
factory
plugged with drain caps. After the installation of the condensate hose, these two drain
ports also need to be insulated properly with the same way as aforementioned.
The condensate hose for the unit with
4)
the condensate pump should be arranged as shown
in the figure below.
Ceiling
300mm(11-3/4inch)
1000~1500mm(39-3/8~59inch)
Condensate hose(attachment)
Hoisting stand
Drain raising hose
Clamp(attachment)
100mm
(39-3/8inch)
Figure 3-1-15
ķ The vertical height of the condensate hose should be 75mm (3inch) or less so that it is
unnecessary for the drain port
Condensate hose(attachment)
to withstand additional force.
75mm(3inch)
1000mm
(39-3/8inch)
Figure 3-1-16
8 When multiple condensate hoses are used, their installation should be performed as
shown in the figure below.
7
T-joint converging condensate pipes
Item
Model
Supply Air Outlet
Return Air Inlet
A B C
D
123(4-7/8)
736(29)
710(28)
166(6-1/2)
158(6-1/4)
818(32-1/4)
994(39-1/8)
195(7-5/8)
158(6-1/4)
818(32-1/4)
994(39-1/8)
195(7-5/8)
158(6-1/4)
818(32-1/4)
1000(39-3/8)
206(8-1/8)
158(6-1/4)
818(32-1/4)
1000(39-3/8)
206(8-1/8)
190(7-1/2)
850(33-1/2)
940(37)
286(11-1/4)
0~1000mm(0~39-3/8inch) 100mm(3-7/8inch)
2.1.7 Installation of air duct
Dimensions of the Supply Air Outlet/Return Air Inlet
21mm(7/8inch)
A
Figure 3-1-18 Su
D
T-joint converging condensate pipes
Figure 3-1-17
B
pply Air Outlet
DHR18NDB21S
DHR24NDB21S
DHR30NDB21S
DHR36NDB21S
DHR42NDB21S
DHR48NDB21S
C
Figure 3-1-19 Return Air Inlet
Table 3-1-3
Unit: mm (inch)
8
2.1.8 Installation of the Supply Air Duct
The maximum length of the duct means the maximum length of the supply air duct plus the maximum length of the
return air duct.
Among all supply air outlets, at
least one should be kept open.
ectangular duct
No.
Name
No.
Name
1
Hanger
5
Filter
2
Pipe
6
Main Air
Supply Pipe
3
Canvas Air Pipe
7
Air Supply
Outlet
4
Air Intake
(1) Installation of the Rectangular Duct.
Figure 3-1-20
ķ.
Table 3-1-4 Installation of the r
Air Intake
ĸ. The duct is rectangular and connected with the air inlet/outlet of the indoor unit.
Bottom Return Air Installation only for Units 18k
(2) The default installation location of the rectangular flange is at the back and the return air cover
plate is at the bottom, as shown in Figure 3-1-21
Bottom Return Air
.
Rectangular Flange
Rear Return Air
Return Air Cover Plate
Figure 3-1-21
(3) If a bottom return air is desired,
just change the place of the rectangular flange and the return air
cover plate.
(4) Connect one end of the return air duct to the return air outlet of the unit by rivets and the other to
the return air louver. For the sake of convenience to freely adjust the height, a cutting of
canvas duct will be helpful, which can be reinforced and folded by 8# iron wire.
(5)
More noise is likely to be produced in the bottom return air mode than the backward return air
mode, so it is suggested to install a silencer and a static pressure box to minimize the noise.
(6) The installation method can be chosen with considering the conditions of the building and
9
maintenance etc., as shown in Figure 3-1-22.
No.
Name
No.
Name
1
Return Air Inlet (with filter)
4
Indoor unit
2
Canvas Duct
5
Supply Air Duct
3
Return Air Duct
6
Grille
4
6
5
4
2
Supply air
1
Return air
Install the return air duct(a) Install the return air duct(b)
5
Supply air
3
1
Return air
Figure 3-1-22
Table 3-1-5 Installation of the return air duct
2.2 Installation of Floor Ceiling Type
2.2.1 Before Installation
After receiving the unit, please check for any transport damage
damage, please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the specification
and quantity of accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing
possible hazard. For the sake of protection and safety, it is suggested to move the unit with the packaging
box. Even though it is not permitted to do like this under special occasions, do not remove the packaging
box, thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the
building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
. If finding any surface or internal
2.2.2 Installation Site
(1) Install the unit at a place strong enough to withstand the weight of the unit.
(2) The air inlet and outlet of the unit s
(3) Leave service space around the unit as required in Figure 3-1-23.
hould never be clogged so that the airflow can reach every
corner of the room.
10
Floor type
Ceiling type
Figure 3-1-23
(4) Install the unit where the condensate pipe can be easily installed.
(5) The space from the unit to the ceiling should be kept
convenient service.
as much as possible so as for more
2.2.3 Indoor Unit Installation
(1) Determine the location of the hanger through the paper template, and then remove the paper
template.
Figure 3-1-24
(2) Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts
with a hammer.
11
(3) First, unfix two buckles on the grille as s
hown on the picture. Remove the screws under the
buckles by a screwdriver and then open the inlet grille.
Remove the screw
Figure 3-1-25
(4) Remove the screws shown in the picture. Push the side plate as per the arrow direction and
take it down.
Remove the screw
Figure 3-1-26
(5) Put the hanger bolt into the clasp of the indoor unit and tighten screws on the hanger to prevent
the indoor unit from moving.
(6) Reinstall and tighten the right and left side panels.
Floor type
Wall
Paper template
Left side panel
Right side panel
Figure 3
12
-1-27
Ceiling type
Ceiling
Suspension
40(1-5/8inch)
bolt
Nut
Spring washer
Left side panel
Nut
Hanger
Right side panel
Figure 3-1-28
(7) Adjust the height of the unit to make the condensate pipe slant slightly downward so that the
drainage
will become much smoother.
2.2.4 Leveling
The water level test must be done after installing the indoor unit to make sure the unit is
horizontal, as shown below.
Horizontal tester
Figure 3-1-29
13
2.2.5 Dimension Data
7/8)
280(11)
5/8)
280(11)
1700(66-7/8)
245(9-5/8)
1634(64-3/8)
280(11)
700(27-1/2)
Figure 3-1-30
Table 3-1-6
Model A B C D H
DHR18NCB21S
DHR24NCB21S
DHR30NCB21S
DHR36NCB21S
DHR42NCB21S
DHR48NCB21S
1220(48) 225(8-
1420(55-7/8)
245(9-
1158(45-5/8)
1354(53-1/4)
Unit: mm (inch)
700(27-1/2)
700(27-1/2)
2.2.6 Condensate Piping Work
2.2.6.1 Precautions When Doing the Piping Work
(1) Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that air
may not remain trapped inside the pipe.
(2) Keep pipe siz
(3) Install the condensate piping as shown and take measures against condensation. Improperly
rigged
piping could lead to leaks and eventually property damage.
Extension condensate piping (commercially available)
e equal to or greater than that of the connecting pipe.
Insulating tube
(commercially available)
Insulating tape (accessory)
Figure 3-1-31
Indoor unit
condensate hose
14
(4) Connect the condensate hose (Figure 3-1-32).
Condensate hose must
slope downward.
Allow no trap to form in the piping
Do not allow end
of hose to touch water
Figure 3-1-32
2.2.6.2 Installing the Condensate Pipes
(1) For determining the position of the condensate hose, perform the following procedures.
(2) Insert the condensate pipe to the drain outlet of
with tape (Figure 3-1-33).
(3) Connect the extension condensate
clamp with tape.
pipe to the condensate pipe and then tighten the
Drain pan
Seal
Drain hose
the unit and then tighten the clamp securely
2
1
3
4mm(1/8inch)
1
2
Figure 3-1-33 Figure 3-1-34 Figure 3-1-35
Tighten the clamp until the screw head is less than 4mm
(1/8inch) from the hose (Figure 3-1-34).
ķ- Metal clamp ĸ- Drain hose Ĺ- Grey tape
Insulate the pipe clamp and the condensate hose using heat insulation sponge ( Figure 3-1-35).
ķ- Metal clamp ĸ- Insulation sponge
Note:
Step 1 to Step 3 have been finished by the manufacturer.
(4) When condensate hose requires extension, obtain an extension hose available commercially.
(5) After connecting the local condensate hose, tape the slits of the heat insulation tube.
(6) Connect the condensate hose to the local condensate pipe. Position the interconnecting wire
in the same
direction as the piping
.
2.2.6.3 Connecting the Condensate Hose
(1) Connect the extension auxiliary pipe to the local piping.
(2) Prepare the local piping at the connec
installation
Note:
Be sure to place the condensate hose as shown in the figure below, in a downward
drawin
gs.
tion point for the condensate pipe, as shown in the
sloping direction.
15
ĸ
Bottom-right piping
2.2.6.4 Testing of Condensate Piping
Condensate pan
Condensate hose
ķRight side piping
Figure 3-1-36
(1) After
(2) As shown in the figure, pour water into the condensate pan from the right side to check that
water flows
pipi
ng work
freely from the condensate hose.
is finishe
Ceiling type Floor type
d, c
heck if
drainage flows freely.
Figure 3-1-37
2.3 Installation of Cassette Type
2.3.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or internal
damage, please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the specification
and quantity of accessory parts are correct.
Determine the correct handling route and methods to avoid damaging the unit or causing possible
hazard. For the sake of protection and safety, it is suggested to move the unit with the packaging box.
Even though some circumstances may limit this, do not remove the packaging box to avoid loosening or
falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the
building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far
substances are stored in order to avoid possible explosion or fire due to leakage.
from the area where the flammable or explosive
16
2.3.2 Installation Site
H
mm (inch)
255(10)
260(10-1/4)
340(13-3/8)
340(13-3/8)
340(13-3/8)
320(12-5/8)
Select an installation site where the following conditions are fulfilled and that meets your customer's
approval.
(1) Obstructions should be moved
away from the intake or outlet vent of the indoor unit so that the airflow can
be blown throughout the room.
(2)
Make sure that the installation meets the requirement of the schematic diagram of installation
spaces.
(3) Select the place where it can withstand four tim
es the weight of the indoor unit and would not
increase operating noise and vibration.
(4) Ensure horiz
ontal position of
the installation place.
(5) Select the place where it is easy to drain condensate water, and connect with the outdoor unit.
(6) Make sure that there is enough space for care and maintenance, and the height between the
indoor unit and ground is above 1800mm
(7)
When installing the suspension bolt, check if the installation place can withstand four times the
weight
Note:
of the unit. If not, reinforce it before installation.
There could be a large amount of greasy dirt accumulated on the fan, heat exchanger and water
(6ft).
pump located in a dining room and kitchen, which would reduce the capacity of the heater exchanger,
and lead to leakage and abnormal operation of the water pump.
1500mm
(59inch)
DHR18NKB21S
DHR24NKB21S
DHR30NKB21S
DHR36NKB21S
DHR42NKB21S
DHR48NKB21S
H
>20mm(3/4inch)
1500mm
(59inch)
2500mm(98-3/8inch)
Figure 2-3-2
Table 2-3-2
Models
17
2.3.3 Installing the Main Body Unit
Nut(field supplied)
Gas(attachment)
Hoisting stand
Tighten(double nuts)
[Fix the hoisting stand firmly]
Insert
Gasket anchor board(attachment)
[Fix the gasket firmly]
One bolt located at one corner of the outlet pipe should be fixed on one corner of the drainage slot.
paper template
Bolt(attachment)
Water level
Polyethylene pipe
Center of the ceiling opening
Bolt(attachment) [Fix the paper template]
Figure 3-1-39
(1) Install the hoisting stand on the hoisting screw by using nuts and gaskets at both the upper and
lower sides of the hoisting stand. To prevent the gasket from breaking off, a gasket anchor board
can be helpful.
(2) Install the paper template on the unit, and secure the condensate pipe at the outlet vent.
(3) Adjust the unit to the best position.
(4) Check if the unit is installed horizontally at four directions. If not, the water pump and the float
switch would function improperly and even lead to water leakage.
(5) Remove the gasket anchor board and tighten the remaining nut.
(6) Remove the paper template.
2.3.4 Installing the Suspension Bolts
(1) Using the installation template, drill holes for bolts (four holes) (Figure 3-1-40).
(2) Install the bolts to the ceiling at a place strong enough to hang the unit. Mark the bolt positions
from the installation template. With a concrete drill, drill for 12.7mm (1/2inch) diameter holes
(Figure 3-1-41).
Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts
(3)
with a hammer (Figure 3-
Figure 3-1-40 Figure 3-1-41 Figure
1-42).
3-1-42
18
2.3.5 Leveling
The water level test must be done after installing the indoor unit to make the unit is horizontal, as
shown below.
Horizontal tester
Figure 3-1-43
2.3.6 The Panel Installation
(1) See the figure below for the positions of the front panel
Figure 3-1-44
(2) Place the panel at the unit, and latch the hooks beside and opposite the swing flap motor.
(3) Latch other two hooks.
(4) Tighten four hexagonal screws under the latches about 15mm (5/8inch).
(5) Adjust the panel along the direction indicated by the arrow as shown in Figure 3-1-45.
(6) Tighten the screws until the thickness of the sealing material between the panel and the indoor
unit reduces to 5~8mm (1/4~3/8inch).
and the connecting pipe.
19
ĸ
Swing flap motor
Ĺ
Indoor unit
ĺ
Ceiling
Air outlet
Piping position
Latch
Ļ
ķ
ĸ
Indoor unit
5~8mm(1/4~3/8inch)
Panel
Hook
Figure 3-1-45
(7) Improper screwing of the screws may cause the troubles shown in Figure 3-1-46.
Air leak
Condensate
Figure 3-1-46
(8) If gap still exists between ceiling and decorative
height of the indoor unit (Figure 3-1-47).
Adjustment of the indoor unit body from the holes
in the corner of the panel is possible if the indoor unit can always be kept horizontal and the condensate pipe will be unaffected.
No gap is allowed
Figure 3-1-47
panel after tightening the screws, readjust the
20
(9) Wire the swing flap motor as shown in Figure 3-1-48.
Item
Model
B C D E F G H I J
670
(26
3/8)
596
(23
1/2)
592
(23
1/4)
575
(22
5/8)
145
(5
3/4)
240
(9
1/2)
665
(26
1/8)
236
(9
1/4)
575
(22
5/8)
505
(19
7/8)
Figure 3-1-48
2.3.7 Dimension Data
For the units: 18k
Connect them to the main body according to the size of terminals
DHR18NKB21S
For the units: 24k~42k
Table 3-1-8 Unit: mm (inch)
A
-
-
-
-
-
-
-
-
-
-
Table 3-1-9
21
Unit: mm (inch)
Item
Model
B C D E F G H
950
(37-3/8)
840
(33-1/8)
780
(30-3/4)
680
(26-3/4)
160
(6-1/4)
240
(9-1/2)
917
(36-1/8)
215
(8-1/2)
993
(39-1/8)
950
(37-3/8)
840
(33-1/8)
780
(30-3/4)
680
(26-3/4)
160
(6-1/4)
320
(12-5/8)
917
(36-1/8)
215
(8-1/2)
993
(39-1/8)
950
(37-3/8)
840
(33-1/8)
780
(30-3/4)
680
(26-3/4)
160
(6-1/4)
320
(12-5/8)
917
(36-1/8)
215
(8-1/2)
993
(39-1/8)
950
(37-3/8)
840
(33-1/8)
780
(30-3/4)
680
(26-3/4)
160
(6-1/4)
320
(12-5/8))
917
(36-1/8))
215
(8-1/2)
993
(39-1/8)
Model
1040(41)
7/8)
1/8)
3/4)
3/8)
DHR24NKB21S
DHR30NKB21S
DHR36NKB21S
DHR42NKB21S
For the units: 48k
A
C
D A
Bottom face of ceiling
B
F
E
I
Figure 3-1-49
Table 3-1-10
Unit: mm (inch)
Item
DHR48NKB21S
A B C D E F
910(35-
842(33-
788(31)
170(6-
290(11-
2.3.8 Installation of Condensate Piping
(1) Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that air
may not remain trapped inside the pipe.
(2) Keep pipe size equal to or greater
(3) Install the condensate piping as shown and take measures against condensation. Improperly
rigged
piping could lead to leaks and eventually
Extension condensate
piping (commercially
available)
Insulating tube
(commercially available)
than that of the connecting pipe.
property damage.
Indoor unit
condensate hose
Insulating tape (accessory)
Figure 3-1-50
22
2.3.9 Installing the Condensate Pipes
Tighten the clamp until the screw head is less then 4mm
(1/8inch) from the hose.
(1) Insert the condensate pipe to the drain outlet of the unit and then tighten the clamp securely with
tape.
(2) Connect the extension condensate pipe to the condensate
tape.
Insulate the pipe clamp and the condensate hose
ķ Metal clamp (accessory)
ĸ Insulation sponge (accessory)
using heat insulation sponge.
ķ Metal clamp
ĸ Condensate hose (accessory)
Ĺ
G
rey tape (accessory)
(3) When unifying multiple condensate pipes, install the pipes as in Figure 3-1-51. Select converging
condensate pipes whose gauge is suitable for the operating capacity of the unit (take the cassette
type unit for example).
pipe and then tighten the clamp with
(4) When the condensate hos
pipe (field supplied) to it.
(5) If the air flow of indoor unit is
of outdoor air. Therefore, U-type water trap should
unit (Figure 3-1-52).
(6) Install one water trap for each unit.
(7) Installation of wa
Figure 3-1-52 Figure 3-1-53 Figure 3-1-54
ter trap should consider easy cleaning in
Figure 3-1-51
e can
not
keep a sufficient gr
adie
nt, it is necessary to fit
a riser
high, this might cause negative pressure and result in return suction
be designed on the drainage side of each indoor
the future.
23
(8) Connection of drainage branch pipe to the standpipe or horizontal pipe of drainage main pipe.
(9) The horizontal pipe cannot be connected to the vertical pipe at a same height. It can be connected
in a manner as shown below:
NO.1: Attach the 3-way connection of the condensate pipe joint as shown in Figure 3-1-55.
NO.2: Attach the drain elbow as shown in Figure 3-1-56.
NO.3: Attach the horizontal pipe as shown in Figure 3-1-57.
3-way connection of condensate pipe joint
Connection of drain elbow
Connection of horizontal pipe
Figure 3-1-55 Figure 3-1-56 Figure 3-1-57
2.3.10 Precautions When Doing Riser Piping Work
(1) Make sure that heat insulation work is executed on the following two spots to prev
water leakage due to condensation.
Connect the condensate hose to the drain lift pipe, and insulate them.
1)
2)
Connect the condensate hose to the drain outlet on the indoor unit, and tighten it with the clamp.
ent any possible
Figure 3-1-58
(2) Make sure the lift pipe is at most 280mm (11inch).
(3) Stand the lift pipe vertically, and make sure it is not further than 300mm (11-3/4inch) from the
base of the drain outlet.
(4) Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this, mount
supporting brackets at an interval of 1~1.5m (3-2/7~5feet).
24
1~1.5m(3-2/7~5feet)
(Correct) 1/100 or more gradient
× (wrong
)
Figure 3-1-59
(5) The incline of attached condensate hose should be 75mm (3inch) or less so that the drain
outlet does
not have to withstand additional force.
Condensate hose(attachment)
75mm(3inch)
1000mm(39-3/8inch)
Figure 3-1-60
2.3.11 Testing of Condensate Piping
After piping work is finished, check if drainage flows freely
. Shown in
approximately 1liter of water slowly into the condensate pan and check drainage flow during COOL
running.
Condensate hose
Drain vent for repair use (plastic stopper is included) (drain the water in waterspout by this outlet vent)
the Fi
gure 3-
Test hole cover
1-61, a
dd
Above 100mm(3-7/8inch)
Test hole
<Limiting water from the rest of hole>
Plastic water pot [The length of
the pipe should be about
100mm(3-7/8inch)].
<Limiting water from the outlet vent terminal>
Figure 3-1-61
25
3. OUTDOOR UNIT INSTALLATION
3.1 Before Installation
After receiving the unit, please check for any transport damage. If finding any
damage, please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and
and quantity of accessory parts are correct.
Determine the correct handling route and methods to avoid damaging the unit or causing possible
hazard. For the sake of protection
not permitted to do this even under special circumstances, do not remove the packaging box to avoid
loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the
building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or
ive substances are stored to avoid possible explosion or fire due to leakage.
explos
the unit is in good condition. Please also check if the specification
and safety, it is suggested to move the unit with the packaging box. It is
surface or internal
3.2 Installation Site
ķ. Install the unit where it will not be tilted by more than 5°.
ĸ. During installation, if the outdoor unit has to be exposed to strong wind, it must be fixed securely.
If possible, do not install the unit where it will be exposed to direct sunlight. (If necessary, install a blind
that does not interfere with the air flow.)
(1) Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as
much as possible.
(2) Install the outdoor unit where it is convenient to connect with the indoor unit.
(3) Install the outdoor unit where the condensate water can be drained out freely during heating
operation.
(4) Do not place animals and plants in the path of the warm air.
(5) Take the air conditioner weight into account and select a place where noise and vibration are
less.
(6) Install the outdoor unit where it is capable of withstanding the weight of the un
as little noise and vibration as possible.
(7) Provide the space shown in Figure 3-2-1, so that the air flow is not blocked. Also for
efficient
operation, make sure to leave three planes clear of any obstructions.
it and generates
26
500mm
G
500mm
G
(1-2/3feet)
(1-2/3feet)
2000mm
(6-5/9feet)
3.3 Caution for Installation
500mm
G
(1-2/3feet)
Figure 3-2-1
2000mm
(6-5/9feet)
1000mm
(3-2/7feet)
G
500mm
(1-2/3feet)
The outdoor unit should be s
o install
ed
that th
e ai
r discharged out of the outdoor unit will not flow
back and that enough space shall be maintained around the machine for repair.
The installing position should allow good ventilation so that the machine can breathe and exhaust
enough air. Ensure that there is no obstruction at the inlet and outlet of the machine. If any, please
remove the obstructions blocking the air inlet and outlet.
If the outdoor unit is installed on concrete or solid ground, it should be secured by using M10 bolts
and nuts. And ensure that the machine is kept vertically and horizontally correct.
The outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect
the air conditioner and avoid
knocking the metal parts to prevent rusting in the future.
To meet the noise and vibration requirements, the outdoor unit should be installed by using
rubber damping pad or spring damper.
To install the condensate pipe, please insert the drainage joint to the drainage hole on the outdoor
chassis and connect a condensate pipe on the drainage joint. (The installing height of outdoor unit should
be at least 5cm (2inches) if drainage joint is to be used).
To insert the pipe through the wall, the wall cross tube must be installed.
The installing dimensions should comply with the installation requirements in these instructions.
The outdoor unit must be secured at the installing position.
The installation should be done by certified technicians.
3.4 Dimension Data
Figure 3-2-2
27
Item
Model
955
(37-5/8)
396
(15-5/8)
700
(27-1/2)
560 (22)
360
(14-1/8)
DHR18CSB21S
1107
(43-5/8)
440
(17-3/8)
1100
(43-1/4)
631
(24-7/8)
400
(15-3/4)
DHR24CSB21S
DHR30CSB21S
DHR36CSB21S
Table 3-2-1
A B C D E
980
(38-5/8)
427
(16-3/4)
790
(31-1/8)
610
(24)
Unit: mm (inch)
395
(15-1/2)
DHR42CSB21S
DHR48CSB21S
958
(37-3/4)
412
(16-1/4)
1349
(53-1/8)
572
(22-1/2)
376
(14-3/4)
4. REFRIGERATION PIPING WORK
4.1 Refrigeration Piping Work Procedures and Caution in Connecting
4.1.1 Flare Processing
(1) Cut the connection pipe with the pipe cutter and remove the burrs.
(2) Hold the pipe downward to prevent cuttings from entering the pipe.
(3) Remove the flare nuts at the stop valve of the outdoor unit and inside the accessory bag of the
indoor unit, then insert them to the connection pipe, after that, flare the connection pipe with a
flaring tool.
(4) Check to ensure the flare part is spread evenly and t
d1
d2
here are no cracks (see Figure 3-3-1).
d1
90°±1°
d2
Figure 3-3-1
4.1.2 Bending Pipes
(1) The pipes are shaped by your hands. Be careful not to collapse them.
Extend the pipe by unwinding it
Figure 3-3-2
(2) Do not bend the pipes in an angle more than 90°.
(3) When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or
28
×
stretch them any more. Do not bend or stretch the pipes more than three times.
7/8inch)
or over.
. If the pipe is bent repeatedly at the same place, it will break.
If the centering is improper, the flare nut
Do not remove the flare nut until the connection pipe is to be connected so as to prevent dust and impurities from
coming into the pipe system.
(4) When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the heat
insulating pipe with a sharp cutter as shown in Figure 3-3-3, and bend it after exposing the pipe.
After bending the pipe as you want, be sure to put the heat insulating pipe back on the pipe, and
secure it with tape.
Pipe
Heat insulating
pipe
Cutter
Cutt line
Figure 3-3-3
ķ. To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curvature of 150mm (5-
ĸ
4.1.3 Connecting the Pipe at the Indoor Unit Side
Detach the caps and plugs from the pipes.
ķ. Be sure to apply the pipe against the port on the indoor unit correctly.
cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
ĸ.
When connecting the pipe to the unit or removing it from the unit, please do use both the wrench and
the torque wrench (Figure 3-3-4).
When c
onnecting, smear both inside and outsi
the flare nut with refrigeration oil, screw it tight
de of
by hand and then tighten it with the wrench.
Refer to Table 3-3-1 to check if the wrench has been tightened properly (too tight would mangle the nut
and lead to leakage).
Examine the connection pipe to see if it leaks, then take the treatment of heat insulation, as shown in
the Figure 3-3-4.
Use the medium-sized sponge to insulate the coupler of the gas pipe.
29
Threaded fastener(×4)
Pipe Diameter
Tightening Torque
6mm (1/4inch)
15~30N·m (11~22ft.-1b.)
9.5mm (3/8inch)
35~40N·m (26~29ft.-1b.)
12.7mm (1/2inch)
45~50N·m (33~37ft.-1b.)
16mm (5/8inch)
60~65N·m (44~48ft.-1b.)
Be sure to connect the gas pipe after connecting the liquid pipe completely.
Gas inlet pipe
Liquid pipe
Sponge
Heat insulation sheath (for the liquid tube)
Heat insulation sheath (for the gas tube)
Figure 3-3-4
Table 3-3-1 Flare nut tightening torque
4.1.4 Connecting the Pipe at the Outdoor Side Unit
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method
is the same as that as at the indoor side.
Gas pipe
coupling
Liquid pipe
Pipe
or
3-way valve 2-way valve
Figure
30
3-3-5
or
4.1.5 Checking the Pipe Connections for Gas Leaking
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra refrigerant in the
outdoor unit for air purging!
For both indoor and outdoor unit side, check the joints for gas leaking by the use of a gas leakage
detector without fail when the pipes are connected.
4.1.6 Heat Insulation on the Pipe Joints (Indoor Side Only)
Stick coupler heat insulation (large and small) to the place where connecting pipes.
Reference A
Front outlet
Coupler heat insulation (small) on the pipe
Coupler heat insulation (large) on the pipe
Liquid pipe
Gas pipe
Figure 3-3-6
4.1.7 Vacuum and Gas Leakage Inspection
4.1.7.1 Vacuum
Reference A: Cover this portion with heat insulating material also without fail
No gap
Heat insulation pipe
(1) Remove the caps of the liquid valve, gas valve and also the service port.
(2) Connect the hose at the low pressure side of the manifold valve assembly to the service port of
the unit’s gas valve, and make sure the gas and liquid valves should be kept closed in case of
refrigerant leak.
(3) Connect the hose used for evacuation to the vacuum pump.
(4) Open the switch at the lower pressure side of the manifold valve assembly and start the vacuum
pump. Meanwhile, the switch at the high pressure side of the manifold valve assembly should be
kept closed, otherwise evacuation would fail.
(5) The evacuation duration depends on the unit’s capacity, generally, 20 minutes for the 18kunits,
30 minutes for the 24k/30k/36k units, 45 minutes for the 42k/48k units. And verify if the pressure
gauge at the low pressure side of the manifold valve assembly reads -1.0MPa (145psig), if not, it
indicates there is leak somewhere. Then, close the switch fully and then stop the vacuum pump.
(6) Wait for some time to see if the system pressure can remain unchanged, 3 minutes for the
18k/24k units, 10 minutes for the 30k/36k/42k/48k units. During this time, the reading of the
pressure gauge at the low pressure side can not be larger than 0.005MPa (0.72psig).
31
(7) Slightly open the liquid valve and let some refrigerant go to the connection pipe to balance the
Model
Additional Refrigerant Amount for
18k
45g per 1.5 m (1.6 ounce per 5 feet )
24k~48k
90g per 1.5 m (3.2 ounce per 5 feet )
pressure inside and outside of the connection pipe, so that air will not come into the connection
pipe when removing the hose. Note that the gas and liquid valve can be opened fully only after the
manifold valve assembly is removed.
(8) Place back the caps of the liquid valve, gas valve and also the service port.
Pressure gauge (Low-pressure)
Switch (Low-pressure)
Connection pipe (to indoor unit)
Liquid valve
Gas valve
Service port
Cap
Vacuum pump
gauge manifold
Hose
Pressure gauge (Hi-pressure)
Switch (Hi-pressure)
Connection pipe
Cap
Service pipe
Cap
Hose with the valve pin
Note:
For the large-sized unit, it has the service port for both the gas valve and the liquid valve.
During evacuation, it is available to connect two hoses of the manifold valve assembly to two service ports
to quicken the evacuating speed.
4.1.7.2 Additional Charge
Refrigerant suitable for a piping length of 7.6m (25feet) is charged in the outdoor unit at the factory.
When the piping is longer than 7.6m (25feet), additional charging is necessary.
For the additional amount, see Table 3-3-2.
When the height difference between the indoor unit and outdoor unit is larger than 10m (32-4/5feet),
Item
Figure 3-3-7
Table 3-3-2
Extra Pipe
32
an oil bend should be employed for every 6m (19-2/3 feet).
Item
Size of Fitting Pipe
mm (inch)
Max. Pipe
Max. Height Difference
en Indoor Unit and
m (feet)
Drainage pipe(Outer
mm (inch)
Liquid
Gas
6(1/4)
12.7(1/2)
3/5)
Φ17
100)
9.5(3/8)
16(5/8)
2/5)
Φ17×1.75(Φ5/8 × 7/100)
2/5)
Φ17×1.75(Φ5/8 × 7/100)
2/5)
Φ17×1.75(Φ5/8 × 7/100)
Φ17×
7/100)
Φ17×1.75(Φ5/8 × 7/100)
. Before obtaining access to terminals, all supply circuits must be disconnected.
. The rated voltage of the unit is as shown as Table 1-4-1 and Table 1-4-2
. Before turning on, verify that the voltage is within the 187~252V range (for single phrase units).
. Always use a special branch circuit and install a special receptacle to supply po wer to the air conditioner.
. Use a special branch circuit breaker and receptacle matched to the capacity of the air conditioner.
Always use a circuit that can trip all the poles
of the wiring and has an isolation distance of at least 3mm (1/8inch) between the contacts of each pole.
. Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
cuit breaker in accordance with the related laws and regulations and electric
company standards.
Oil bend
Outdoor
Indoor
Oil bend
6m(19-2/3feet)
Figure 3-3-8
4.2 Specification of Connection Pipe
Table 3-3-3
betwe
Outdoor Unit
15(49-1/5)
15(49-1/5)
15(49-1/5)
15(49-1/5)
30(98-2/5)
30(98-2/5)
Model
DHR18CSB21S
DHR24CSB21S
DHR30CSB21S
DHR36CSB21S
DHR42CSB21S
DHR48CSB21S
Length
m (feet)
20(65-
30(98-
30(98-
30(98-
50(164)
50(164)
The connection pipe should be insulated with proper water-proof insulating material.
The pipe wall thickness shall be 0.5~1.0mm (1/50~1/25inch) and the pipe wall shall be able to
withstand the pressure of 6.0MPa (870psig). The longer the connecting pipe, the lower the cooling and
heating effect performs.
Diameter × wall
thickness)
×1.75(Φ5/8 × 7/
1.75(Φ5/8 ×
5. ELECTRIC WIRING WORK
5.1 Wiring Precautions
ķ
ĸ
Ĺ
ĺ
Ļ
ļ. The special branch circuit breaker is installed in the permanent wiring.
Ľ
ľ. Install a leakage special branch cir
33
ķ.
The power source capacity must be the sum of the air conditioner current and the current of other electrical
appliances. When the current contracted capacity is insufficient, change the contracted capacity.
. When the voltage is low and the air conditioner is difficult to start, contact the power company to raise the voltage.
8
5.2 Electrical Wiring
(1) For solid core wiring (Figure 3-4-1)
1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation about 25mm (1
inch).
2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
4) Shape the loop wire properly, place it on the terminal board and tighten securely with the
terminal screw using a screwdriver.
For strand wiring (Figure 3-4-1).
(2)
Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation about 10mm
1)
(3/8inch).
Using a screwdriver, remove the terminal screw (s) on the terminal board.
2)
3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire
end.
4) Position the round terminal wire, and replace and tighten the terminal screw with a screwdriver
(Figure 3-4-2).
A Solid wire B Strand wire
Solderless terminal
25mm(1inch)
Insulation layer
10mm(3/8inch)
Figure 3-4-1
Screw with special washer
Round
terminal
Terminal board
Wire
Screw with special washer
Round terminal
Wire
Insulation tube
Insulation tube
Cord clamp
Figure 3-4-2 Figure 3-4-3
(3) How to fix connection cord and power cord by cord clamp
After passing the connection cord and power cord through the insulation tube, fasten it with the cord
34
clamp (Figure 3-4-3).
. Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
Erroneous wiring
may cause burning of the electric parts.
. Erroneous wiring may cause burning of the electric parts.
. Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
(If the insulator is not clamped, electric
leakage may occur.)
. Always connect the ground wire.
ķ
ĸ. Match the terminal block numbers and connection cord colors with those of the indoor unit side.
Ĺ
ĺ
Ļ. Always fasten the outside covering of the connection cord with cord clamps.
ļ
(4) Electric wiring between the indoor and outdoor units
Duct Type Unit:
Single-phase units (18k~30k)
Single-phase unit
s (36k~48k)
35
Cassette Type Unit:
Single-phase units: 18k
Single-phase units: 24
k~30k
Single-phase units: 36k~42k
36
Single-phase units: 48k
Floor ceiling Type Unit:
Single-phase units (18k~30k)
Single-phase units (36k~4
8k)
Figure 3-4-4
37
(5) Electric wiring of indoor unit side
Remove the electric box cover from the electric box sub-assy and then connect the wire.
Duct Type Unit:
L1 L2
F C O
1 2
H1 H2
Electric box sub-assy
Electric box
cover
Figure 3-4-5
The F, C, O connect to the COMMOM, CLOSE and OPEN terminal of the fresh air valve respectively.
Cassette Type Unit:
For the units: 18k~42k
38
For the units: 48k
L1
L2
H1
2
1
H2
Figure 3-4-6
Floor Ceiling Type Unit:
Electric box cover
Left side panel
L2
L1
1
H2
H1
2
Figure 3-4-7
ķ. The power cord and the wire of the fresh air valve are high-voltage, while the communication cord and connection
wire of the wired zone controller are low-voltage. They should run separately against electromagnetic interference.
8. The high-voltage and low-voltage lines should pass through the rubber rings at different electric box covers.
Do not bundle the connection wire of the wired
9.
them in parallel, otherwise improper operation would occur.
zone controller and the communication cord together, or arrange
39
ĺ. The high-voltage and low-
voltage lines should be fixed separately and securely, with internal big clamps for the
former and small clamps for the latter.
Tighten the indoor/outdoor connection cord and power cord respectively on the terminal boards with screws. Faul ty
connection may cause a fire.
If the indoor unit connection cord (to the outdoor unit) and power supply are wired incorrectly, the air conditioner
may be damaged.
. Ground both the indoor and outdoor units by attaching a ground wire.
. Unit shall be grounded in compliance with the applicable local and national codes.
Ļ.
ļ.
Ľ. Connect the indoor unit connection cord properly based on the corresponding marks as show n in Figure 3-4-4.
ľ
Ŀ
(6) Electric wiring of outdoor unit side
TICE!
NO
When connecting the power supply cord, make sure that the phase of the power supply
matches with the exact terminal board. If not, the compressor will rotate reversely and run improperly.
Remove the big handle (18k~30k) /front board (36k~48k) of the outdoor unit and insert the end of the
communication cord and the power cable into the terminal board.
Single phase:
2
L1 L2
1
L1 L2
2
1
18k~30k 36k~48k
Figure 3-4-8
40
6.
No.
Error code
Malfunction
name
Origin of
malfunction signal
1
High pressure
Hi
pressure
When outdoor unit detects the high pressure switch is cut off for 3s successively, high pressure protection will occur. All the loads (except the 4
way valve in heating mode) will be switched off. In
this case, all the buttons and remote
control signals except ON/OFF button will be disabled and cannot be recovered automatically. Switch off the unit or re
energize the unit after
cutting off power to eliminate this protection.
2
Freeze protection
Indoor evaporator
temperature
If detecting that the evaporator temperature is lower than protective temp. value after the unit has been running for a period of time under cooling or dry mode, the unit will report this fault, in which case the compressor and outdoor fan motor will be stopped. The unit will not run until evaporator temperature is higher than the protective temp. value and the compressor is stopped for 3min.
3
Low pressure
Low pressure
If it is detected within 30s successively that the low-pressure switch is cut off under ON or standby state, the unit will report low pressure protection. If the fault occurs successively 3 times within 30min, the unit cannot be recovered automatically.
Refrigerant
lacking protection
If the unit reports system refrigerant lacking within 10min after turning on the unit, the unit will stop operation. If the fault occurs successively 3 times, the unit cannot be recovered automatically.
Refrigerant
recycling mode
If enter refrigerant recycling mode through special operation, E3 will be displayed. After exiting refrigerant recycling mode, the code will disappear.
4
Compressor high
ischarge
temperature
Compressor
discharge
temperature is
If outdoor unit detects that the discharge temperature is higher than protective temp. value, the unit will report high discharge temperature protection. If the protection occurs over 6 times, the unit cannot be recovered automatically. Switch off the unit or re-energize the unit after cutting off power to eliminate this protection.
5
Communication
malfunction
Communication
between indoor
and outdoor main
If the outdoor unit does not receive data from indoor unit, communication malfunction will be reported. If there is communication abnormity between display board and indoor unit, communication malfunction will be reported too.
6
Malfunction of
indoor fan motor
Indoor fan motor
If the indoor unit does not receive signal from indoor fan motor for 30s successively when the fan motor is operating, indoor fan motor malfunction will be reported. In this case, the unit can automatically resume operation after stopping. If the malfunction occurs 6 times within one hour, the unit cannot be recovered automatically. Switch off the unit or re
energize the unit after
cutting off power to eliminate this malfunction.
MAINTENANCE TROUBLESHOOTING
ERROR CODES TABLE
6.1 Main Control Malfunction
Table 4-1-1 Fault Display on Indoor Wired Zone Controller
Control description
E1
E2
E3
protection
protection
gh
switch
sensor
switch
-
-
E4
E6
E8
d
protection
high
board
-
41
No.
Error code
Malfunction
name
Origin of
malfunction signal
7
E9
Full water protection
Water level switch
If cut-off of water level switch is detected for 8s successively once energized, the system will enter full water protection. In this case, switch off the unit and then switch it on to eliminate this malfunction.
8
Malfunction of
indoor ambient
temperature
sensor at air
return port
Indoor ambient
temperature
If the indoor ambient temperature sensor is detected of open circuit or short circuit for 5s successively, indoor ambient temperature sensor malfunction will be reported. The unit can automatically resume operation after the malfunction disappears. If indoor ambient temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
9
Malfunction of
evaporator
temperature
Evaporator
temperature
If the indoor evaporator temperature sensor is detected of open circuit or short circuit for 5s successively, evaporator temperature sensor malfunction will be reported. The unit can automatically resume operation after the malfunction disappears. If evaporator temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
0
Malfunction of
condenser
temperature
Condenser
temperature
If the outdoor condenser temperature sensor is detected of open circuit or short circuit for 5s successively, condenser temperature sensor malfunction will be reported. The unit
can automatically resume operation after the malfunction disappears. If condenser temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
1
Malfunction of
outdoor ambient
temperature
Outdoor ambient
temperature
If the outdoor ambient temperature sensor is detected of open circuit or short circuit for 5s successively, outdoor ambient temperature sensor malfunction will be reported. The unit can automatically resume operation after the malfunction disappears. If outdoor ambient temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
2
Malfunction of
discharge
temperature
Discharge
temperature
If the outdoor discharge temperature sensor is detected of open circuit or short circuit for 5s successively after the compressor has been operating for 3min, outdoor discharge temperature sensor malfunction will be reported. The unit can automatica lly resume operation after the malfunction disappears.
3
Malfunction wired
controller
temperature
sensor
Wired controller
If the wired controller detects open circuit or short circuit of its temperature sensor for 5s successively, wired controller temperature sensor malfunction will be reported.
4
Malfunction of
outdoor drive
memory chip
Outdoor drive
If the memory chip of outdoor drive board is broken, the unit cannot be started. The unit cannot be recovered automatically. If the malfunction cannot be eliminated after switching off the unit and then energizing the unit for several times, please replace the outdoor drive board.
15
Compressor
overload
protection
Compressor
overload switch
If it is detected within 3s successively that the overload switch is cut off under ON or standby state, the unit will report overload protection. If the fault occurs successively 3 times, the unit cannot be recovered automatically. Switch off the unit or re
energize the
unit after cutting off power to eliminate this protection.
F0
F1
sensor
Control description
sensor
sensor
1
1
1
1
F2
F3
F4
F5
sensor
sensor
sensor
sensor
sensor
sensor
1
ee
board
H3
-
42
No.
Error code
Malfunction
name
Origin of
malfunction signal
Control description
16
Overload
protection
Evaporator
perature,
condenser
temperature
If outdoor unit detects that the tube temperature is higher than protective temp. value, the unit will report overload protection. The unit will not restart operation until tube temperature is lower than the protective temp. value and the compressor is stopped for 3min. If the protection occurs over 6 times, the unit cannot be recovered automatically. Switch off the unit or re
energize the unit
after cutting off power to eliminate this protection.
17
Malfunction of
outdoor fan motor
Outdoor fan motor
If the outdoor unit does not receive signal from outdoor fan motor for 30s successively when the fan motor is operating, outdoor fan motor malfunction will be
reported. In this case, the unit can automatically resume operation after stopping. If the malfunction occurs 6 times within one hour, the unit cannot be recovered automatically. Switch off the unit or re
energize the unit after
cutting off power to eliminate this malfunction.
18
Direction changing
malfunction of
way valve
way valve
After the compressor starts operation in heating mode, if the outdoor unit detects the difference between evaporator temperature and indoor ambient temperature is lower than the protective value for 10min successively, direction changing malfunction of 4
way valve will be reported and the outdoor unit will stop operation. The unit can automatically resume operation in the first two malfunctions. If the malfunction occurs 3 times, the unit cannot be recovered automatically. Switch off the unit or re-energize the unit after cutting off power to eliminate this malfunction.
19
Communication
malfunction
between main
control and drive
Communication
between main
control board and
drive board
If the outdoor main control board does not receive data from drive board, communication malfunction between main control and drive will be reported. This malfunction can be eliminated automatically.
20
Malfunction of
outdoor main
control memory
Outdoor main
control board
If the memory chip of outdoor main control board is broken, the unit cannot be started. The unit cannot be recovered automatically. If the malfunction cannot be eliminated after switching off the unit and then
energizing the unit for several
times, please replace the outdoor main control board.
H4
H6
U7
P6
tem
-
-
4-
-
4-
EE
chip
43
6.2 Description of Drive Malfunction
Indoor Unit Display
Outdoor unit display of dual 8 numeral
tube
IPM or PFC over-temperature protection
IPM or PFC temperature sensor error
ection
Drive
control communication error
)
Main board dual 8 numeral tube Display Codes for Outdoor Unit of 18k~48k
Malfunction Item
DC busbar over-voltage protection
Current sense circuit error Pc Pc
Compressor current protection P5 P5
DC busbar under-voltage prot
Compressor startup failure Lc Lc
Drive module reset P0 P0
Compressor motor desynchronizing
Phase loss Ld Ld
-to-main-
IPM protection H5 H5
Compressor overload protection H3 H3
AC current protection (input side)
Charging circuit error PU PU
PFC protection HC (48k only
DC fan error H6 H6
PH PH
P8 P8
P7 P7
PL PL
H7 H7
P6 P6
PA PA
HC (48k only)
Input AC voltage abnormality PP PP
Driving board memory chip error ee ee
44
7. FLOW CHART OF TROUBLESHOOTING
7.1 Troubleshooting Flow Chart of Main Control Malfunction
E1 High Pressure Protection
45
E2 Freeze Protection
Freeze protection is normal protecti
on but not abnormal malfunction. If freeze protection
occurs frequently during operation, please check if the indoor filter is dirty or if the indoor air outlet is
abnormal. The user is required to clean the filter, check the air outlet and air return pipe periodically to
ensure smooth air return and air outlet.
E3 stands for three statuses:
(1) Low pressure protection
(2) Refrigerant lacking protection
(3) Refrigerant recycling mode
1) If enter refrigerant recycling mode through special operation, the displayed E3 is not an error
code. It will be eliminated when exiting refrigerant recycling mode.
If you do not want to have refrigerant lacking protection, you
2)
can enter the debugging mode
through wired zone controller and then cancel the refrigerant lacking protection mode.
46
E4 Discharge Protection
E6 Communication Malfunction
Communication
communication wire between
indoor unit and outdoor unit is
connected well
Check if there is
open circuit in the communication
wire between indoor unit and
outdoor unit is energized
malfunction
Check if the
Yes
outdoor unit
No
Check if the
No
Yes
No
Reconnect the
communication
wire
Replace the
communication
wire
Energize the
outdoor unit
Yes
Replace the mainboard
47
E9 Full Water Protection
E9 protection
F0 Malfunction of
If the unit is
installed with
water pump
Yes
Check if the water pump
works normally
Yes
Replace the full water switch
or make sure the float of full
water switch works normally
No
mainboard according to the circuit
No
Indoor Ambient Temperature Sensor
Malfunction of
indoor ambient
temperature
sensor
Short circuit the full water
protection interface on indoor
diagram
Replace the water pump
Check if the
indoor ambient temperature
sensor on mainboard is inserted
on the needle
stand correctly
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the indoor
mainboard
48
No
No
Correctly insert the temperature sensor on the needle stand
Replace the
temperature sensor
F1 Malfunction of Evaporator Temperature Sensor
Malfunction of
evaporator
temperature
sensor
Check if the evaporator
temperature sensor on
mainboard is inserted on the
needle stand correctly
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the
indoor
mainboard
F2 Malfunction of Condenser Temperature Sensor
Malfunction of
condenser
temperature
sensor
No
No
Correctly insert the
temperature
sensor on the
needle stand
Replace the temperature
sensor
Check if the condenser
temperature sensor on
mainboard is inserted on the
needle stand correctly
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the
outdoor
mainboard
49
No
No
Correctly insert the temperature sensor on the needle stand
Replace the
temperature sensor
F3 Malfunction of Outdoor Ambient Temperature Sensor
Malfunction of
outdoor ambient
temperature
sensor
Check
if the outdoor ambient
temperature sensor on mainboard
is inserted on the needle stand
correctly
Yes
No
Correctly insert the
temperature sensor on
the needle stand
Disconnect
the temperature sensor and
measure if its resistance is
F4 Malfunction of Discharge Temperature Sensor
normal
Yes
Replace the
outdoor
mainboard
Malfunction of
discharge
temperature
sensor
Check if the
discharge temperature sensor on
mainboard is inserted on the
needle stand correctly
No
No
Replace the
temperature sensor
Correctly insert the temperature sensor on the needle stand
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the
outdoor
mainboard
50
No
Replace the
temperature sensor
F5 Malfunction of Wired Controller Temperature Sensor
Malfunction of
wired controller
temperature
sensor
Replace the
wired controller
H6 Malfunction of Outdoor Fan Motor
51
E8 Malfunction of Indoor Fan Motor
Malfunction of
indoor fan motor
Check if the
control wire of indoor fan motor is
connected on the outdoor
mainboard correctly
Yes
Replace
the indoor fan motor and then
restart the unit to see if there still
is malfunction of indoor
fan motor
Yes
Replace the
indoor
mainboard
No
No
Correctly connect the
control wire of fan motor
on the mainboard
Operate the unit with
the new motor
7.2 Troubleshooting Flow Chart of Drive Malfunction
Note: For Outdoor Unit
P0 Drive module reset
Drive (Inverter) by Single-phase Motor
P7 IPM or PFC temperature sensor error
PA AC current protection (input side)
PC Current sensor circuit error
HC PFC protection (48k only)
P0ǃP7 ˆPA ˆHC or
PC is displayed on
wired zone controller
P0 ˆP7 ˆPA ˆHc or
PC is displayedin the
mainboard 88
Indicating Light
Replace the
mainboard
Works Normally
52
P8 IPM or PFC over-temperature protection
P8 is displayed on
P8 is displayed in the
wired zone
controller
mainboard 88
Indicating light
Yes
Replace the
mainboard
PH DC busbar over-v
oltage protection
PL DC busbar under-voltage protection
Is the
IPM or PFC module
of mainboard
tightened˛
Works normally
No
Tighten the IPM
or PFC module
53
P6 Drive-to-main-control communication error
Lc Compressor Startup Failure
Lc is displayed on
the wired controller
Lc is displayed in
the mainboard 88
indicating light
Yes
P5 Compressor
current protection
H7 Compressor motor desynchronizing
H5 IPM protection
Ld Phase loss
P5, H7, H5 or Ld is displayed
on wired zone controller
P5, H7, H5 or Ld is displayed
in the mainboard 88
indicating light
Replace the
mainboard. Does it
work normally?
No
Replace the
compressor
Works normally
Is the compressor
phase sequence right?
Yes
Is the compressor wire
terminals tightened˛
No
Replace the mainboard.
Does it work normally˛
No
Replace the compressor Work normally
No
Yes
adjust the
compressor
phase sequence
Tighten the
compressor wire
terminals
Yes
54
PU Charging circuit error
Yes
PU is displayed on
wired zone
controller
PU is displayed in
the mainboard 88
indicating light
Is the PFC wire
tightened or is the
sequence right?
No
Replace the
mainboard
ee driving board chip err
ee is displayed
or
on the wired
controller
Yes
Is the
jumper
loose˛
No
Replace the
mainboard
Works normally
Yes
Tighten the
Tighten the PFC
wire or adjust the
sequence
jumper
Works Normally
55
H6 DC fan error
56
7.3 Interface
NO.
SILK-SCREEN
1
2
3
Power supply interface to the drive
4
DC_MOTOR2
5
DC_MOTOR1
6
Power supply interface to the drive
DHR18CSB21S / DHR24CSB21S / DHR30CSB21S / DHR36CSB21S / DHR42CSB21S /
DHR48CSB21S Main Control Board
INTERFACE INTERFACE INSTRUCTION
AC-L Live wire input Live wire input
AC-N Neutral wire input Neutral wire input
PWR 1
Control power output[1- DC bus voltage, 3- GND]
DC fan motor2 1-pin: Power supply of fan motor 3-pin: Fan GND 4-pin: +15V 5-pin: Signal control 6-pin: NC
DC fan motor1 1-pin: Power supply of fan motor 3-pin: Fan GND 4-pin: +15V 5-pin: Signal control 6-pin: Signal Feedback
1-pin: DC bus voltage 3-pin: DC bus GND
Interface of DC fan motor 1-pin: DC bus voltage 2-pin: Suspended 3-pin: DC bus GND 4-pin: +15V 5-pin: Control signal input 6-pin: Not connected
Interface of DC fan motor 1-pin: DC bus voltage 2-pin: Suspended 3-pin: DC bus GND 4-pin: +15V 5-pin: Control signal input 6-pin: DC fan motor feedback
CN3
Control power output[1-GND 2-18Vˆ3-15V]
57
ǃ
1-pin: GND
2-pin: +18V
3-pin: +15V
7
COMM1
TX
Communication needle stand of
8
Communication needle stand with
9
pin plus
Communication interface
10 H-PRESS
High pressure switch for fan speed
Pressure protection switch for fan
11
Interface of high pressure
12
Interface of low pressure
13
COMP
Interface of compressor overload
14
T-SENSOR2
1&2 pin: Case temperature sensor 3&4 pin: Ambient temperature
5&6 pin: Discharge temperature
15
nterface of electronic expansion
16
17
18
Communication line [1-3.3Vǃ2­3-RXǃ4-GND]
main control drive
1-pin: +3.3V
ǃ
2-pin: TXD
3-pin: RXD
4-pin: GND
OVC-
CN2
CN1
HPP
LPP
Communication line with1-pin GND, 2-pin B and 3-pinA˅
Communication line with 1­12V, 2-pin B, 3-pin A and 4-pin GND
adjustment
High pressure switch for system protection (obligate˅
Low pressure switch for system protection (obligate˅
Compressor overload protection
1&2 pin: Tube sensor 3&4 pin: Ambient temperature 5&6 pin: Air discharge
indoor unit
1-pin: GND
2-pin: B
3-pin: A
(reserved):
1-pin: +12V
2-pin: B
3-pin: A
4-pin: GND
speed adjustment
protection
protection
protection
sensor
sensor
I
valve:
1 to 4-pin: Drive impulse output;
5-pin: +12V;
FA
Electronic expansion valve line 1 to 4-pin: Drive impulse output;5-pin: +12V;
HEAT Compressor electrical heater Compressor electric heating belt
VA-1 Chassis electrical heater Chassis electric heating belt
4V 4-way valve 4-way valve
58
DHR18CSB21S / DHR24CSB21S / DHR30CSB21S / DHR36CSB21S / DHR42CSB21S
No.
No.
Printing
1
PFC induction wire (blue)
2
3
)
4
5
COMM/COMM1
Communication interface
6
JTAG1
7
8
DC-BUS1
Bus electric discharging interface (for
testing)
9
PFC induction wire (yellow)
10
11
12 G-OUT
13
14
15
(1) Driving Board
8910131415 1112
7
6
2 3 41 5
Printing
Interface
L2_2
N Neutral wire input (white
PWR Control power input
L2-1
P-OUT (Reserved)
W Compressor Phase W
U Compressor Phase U
Interface
L1_1
AC-L
PFC induction wire (brown)
Live wire input (red)
(Reserved)
L1-2
PFC induction wire (white)
(Reserved)
V Compressor Phase V
59
(2)
No.
Printing
No.
Printing
1 N-OUT1
Neutral wire output 1 (white) (only for
18k)
2 N-OUT
Neutral wire output
(white)
3 L-OUT
4 E1
5
6
Live wire input (red)
7
Filtering Board
1
2
3
Interface
Live wire output (red)
E2 (Reserved)
AC-N
Neutral wire input (white)
AC-L
Interface
Grounding wire
7
6
5
4
60
DHR48CSB21S
No.
Printing
No.
Printing
1
L
2 L1-1
3 N
4 L2-2
5
1
PFC induction wire (yellow)
6 L1-2
7
PWR
8
JTAG1
9
COMM
10
DC-BUS1
DC bus electric discharging needle
stand (for testing)
11
DC-BUS
DC bus interface (connect to
filtering board)
12 U
13 V
14 W
(1) Drive Board:
1
2
3
4
5
6
7
121314
11
10
AC-
L2-
Interface
Live wire input (red)
Neutral wire input (white)
Control power input
Communication interface
Compressor Phase V
8
9
Interface
PFC induction wire (brown)
PFC induction wire (blue)
PFC induction wire (white)
(Reserved)
Compressor Phase U
Compressor Phase W
61
(2) Filtering Board:
No.
Printing
No.
Printing
1 N-OUT
2
L-OUT
3
BUS
DC bus interface (connect to drive board)
4 AC-L
5
6
E1
7
1
67
5
2
Interface
Neutral wire output (white)
DC-
N Neutral wire input (white)
E Grounding wire (screw hole)
4
3
Interface
Live wire output (red)
Live wire input (red)
(Reserved)
62
7.4 IPM, PFC Testing Method
7.4.1 Method of Testing IPM Module
(1) Preparation before test: Prepare a universal meter and
the wires U, V, W of the compressor after it is powered off for one minute.
(2) Testing Steps
Step 1: Put the black probe on the place of P and the red one on the wiring terminal U, V, W
respectively as shown in the followi
Step 2: Put the red probe on the place of N and the black one on the wiring terminal U, V, W respectiv
as shown in the following figure to measure the voltage between NU, NV and NW.
(3) If the measured voltages between UP, VP, WP, NU, NV, NV are all among 0.3V-0.7V, then it
indicates the IPM module is normal; If any measured valve is 0, it indicates the IPM is damaged.
7.4.2
Method of Testing PFC Module Short Circuit (only for DHR48CSB21S):
(1) Preparation before test: prepare a universal meter and turn to its diode option, and then remove
the wires L1-2, L2-1 after it is powered off for one minute.
Testing Steps
(2)
Step 1: put the black probe on the place P and the red one on the wiring terminal L1-2,
L2-1respectively as shown in the following figure to measure the voltage between L1-2P and.L2-1 P.
Step 2: put the red probe on the place N and the black one on the wiring terminal L1-2,
L2-1respectively as shown in the following figure to measure the voltage between N L1-2 and NL2-1.
ng figure to measure the voltage between UP, VP and WP.
turn to its diode option, and then remove
ely
(3) If the measured voltages between L1-2P ,L2-1 P, N L1-2 , NL2-1 are all among 0.3V-0.7V, then it
indicates the PFC module is normal; If any measured valve is 0, it indicates the PFC is damaged.
DHR18CSB21S /
DHR24CSB21S / DHR30CSB21S / DHR36CSB21S / DHR42CSB21S
63
DHR48CSB21S
8. WIRING DIAGRAM
8.1 Outdoor unit
The actual wiring should always refer to the wiring diagram of the unit.
Model: DHR18CSB21S
64
Model: DHR24CSB21S
Model: DHR30CSB21S
65
Model: DHR36CSB21S
Model: DHR42CSB21S
66
Model: DHR48CSB21S
8.2 Indoor unit
The actual wiring should always refer to the wiring diagram of the unit.
8.2.1 Duct Type
Model: DHR18NDB21S / DHR24NDB21S / DHR30NDB21S / DHR36NDB21S / DHR42NDB21S
67
Model: DHR48NDB21S
8.2.2 Floor Ceiling Type
Model: DHR18NCB21S /DHR24NCB21S /DHR30NCB21S / DHR36NCB21S / DHR42NCB21S /
DHR48NCB21S
68
8.2.3 Cassette Type
Model: DHR18NKB21S
Model: DHR24NKB21S / DHR30NKB21S / DHR36NKB21S / DHR42NKB21S
69
Model: DHR48NKB21S
70
71
Product improvement, specifications and appearance in this manual are subject to change without prior notice.
© Johnson Controls, Inc. USA
LIT - 12012157
Loading...