Johnson Controls DHR18CSB21S, DHR36CSB21S, DHR24CSB21S, DHR30CSB21S, DHR42CSB21S Service Manual

...
Page 1
Service
Manual
"R" SERIES
INVERTER-DRIVEN
AIR CONDITIONING UNITS
Type
OUTDOOR UNITS
Type
INDOOR UNITS
DUCT
Type
INDOOR UNITS
CASSETTE
Model
DHR18CSB21S DHR24CSB21S DHR30CSB21S DHR36CSB21S DHR42CSB21S DHR48CSB21S
Model
DHR18NDB21S
DHR24NDB21S
DHR30NDB21S DHR36NDB21S
DHR42NDB21S DHR48NDB21S
Model
DHR18NKB21S
DHR24NKB21S
DHR30NKB21S DHR36NKB21S
DHR42NKB21S DHR48NKB21S
Type
INDOOR UNITS
CEILING
Model
DHR18NCB21S
DHR24NCB21S
DHR30NCB21S DHR36NCB21S
DHR42NCB21S DHR48NCB21S
,03257$17
PLEASE READ AND
UNDERSTAND THIS MANUAL BEFORE USING THIS INVERTER-DRIVEN AIR CONDITIONING UNIT. THIS MANUAL FOR FUTURE REFERENCE.
KEEP
Page 2
Important Notice
Johnson Controls, Inc. pursues a policy of continuing improvement in design and performance in its
products. As such, Johnson Controls, Inc. reserves the right to make changes at any time without prior notice.
Johnson Controls, Inc. cannot anticipate every possible circumstance that might involve a potential hazard.
This inverter air conditioning unit is designed for standard air conditioning applications only. Do not use
this unit for anything other than the purposes for which it was intended for.
The installer and system specialist shall safeguard against leakage in accordance with local pipetter
and electrical codes. The following standards may be applicable, if local regulations are not available. International Organization for Standardization: (ISO 5149 or European Standard, EN 378). No part of this manual may be reproduced in any way without the expressed written consent of Johnson Controls, Inc.
This inverter-driven (cooling or heat pump) air conditioning unit will be operated and serviced in the
United States of America and comes with all required Safety, Danger, and Caution, warnings.
If you have questions, please contact your distributor or dealer.
This manual provides common descriptions, basic and advanced information to maintain and service
this inverter-driven (cooling or heat pump) air conditioning unit which you operate, as well for other models.
This inverter-driven (cooling or heat pump) air conditioning unit has been designed for a specic
temperature range. For optimum performance and long life, operate this unit within range limits.
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
Product Inspection upon Arrival
1. Upon receiving this product, inspect it for any damages incurred in transit. Claims for damage, either
apparent or concealed, should be led immediately with the shipping company.
2. Check the model number, electrical characteristics (power supply, voltage, and frequency rating), and any accessories to determine if they agree with the purchase order.
3. The standard utilization for this unit is explained in these instructions. Use of this equipment for purposes other than what it designed for is not recommended.
4. Please contact your local agent or contractor as any issues involving installation, performance, or
maintenance arise. Liability does not cover defects originating from unauthorized modications
performed by a customer without the written consent of Johnson Controls, Inc. Performing any mechanical alterations on this product without the consent of the manufacturer will render your warranty null and void.
2
P5415467
Page 3
TABLE OF CONTENTS
SAFETY SUMMARY................................................................................................................................................... i
1 MODELS LIST ................................................................................................................................................. 1
1.1 Outdoor Unit ........................................................................................................................................ 1
1.2 Indoor Unit ........................................................................................................................................... 2
2 NOMENCLATURE .......................................................................................................................................... 3
3 PRODUCT DATA ............................................................................................................................................. 4
3.1 Product Data of Indoor Unit ............................................................................................................. 4
3.2 Operation Range ............................................................................................................................... 10
3.3 Electrical Data ................................................................................................................................... 10
4 PIPING DIAGRAM ........................................................................................................................................ 11
CONTROL.................................................................................................................................................................. 12
5 OPERATION FLOWCHART ........................................................................................................................ 12
5.1 Cooling/Dry Operation .................................................................................................................... 12
5.2 Heating Operation ............................................................................................................................ 13
6 WIRELESS REMOTE CONTROLLER ...................................................................................................... 14
6.1 Operation and Display View .......................................................................................................... 14
7 WIRED CONTROLLER ................................................................................................................................ 16
7.1 Display View ...................................................................................................................................... 16
7.2 Operation View .................................................................................................................................. 18
8 SPECIAL FUNCTIONS SETTINGS ........................................................................................................... 21
8.1 Setting of Filter Clean Reminder Function ................................................................................ 21
8.2 Low Temperature Drying Function .............................................................................................. 23
8.3 Lock Function ................................................................................................................................... 23
8.4 Memory Function.............................................................................................................................. 24
8.5 Door Control Function/Occupancy Function ........................................................................... 24
8.6 Switch between Fahrenheit and Celsius ................................................................................... 24
8.7 Ambient Temperature .................................................................................................................... 24
8.8 Error Code Recall ............................................................................................................................ 25
8.9 Programming Function ...................................................................................................................25
9 CENTRAL CONTROLLER ......................................................................................................................... 29
9.1 Smart Zone Controller .................................................................................................................... 29
9.2 Additional Special Functions ....................................................................................................... 33
MAINTENANCE ..................................................................................................................................................... 41
10 ERROR CODES........................................................................................................................................... 41
10.1 Main Control Malfunction ............................................................................................................. 41
10.2 Description of Drive Malfunction ............................................................................................... 44
Page 4
TABLE OF CONTENTS (cont'd)
11 FLOW CHART FOR TROUBLESHOOTING ........................................................................................... 45
11.1 Troubleshooting Flow Chart of Main Control Malfunction .................................................. 45
11.2 Troubleshooting Flow Chart of Drive Malfunction................................................................. 52
11.3 Interface ............................................................................................................................................ 57
11.4 IPM, PFC Testing Method ............................................................................................................ 63
12 DISASSEMBLY AND ASSEMBLY PROCEDURES FOR MAIN PARTS...........................................65
12.1 Outdoor Unit .................................................................................................................................... 65
12.2 Indoor Unit....................................................................................................................................... 69
CUSTOMER SUPPORT................................................................................................................................... 83
Page 5
1. Introduction
This manual concentrates on inverter-driven cooling or heat pump air conditioning units. Read this manual carefully before installation.
This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air conditioning equipment.
2. Important Safety Instructions
Safety Messages
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions thoroughly and follow all warnings or cautions included in all manuals that accompanied the product and are attached to the unit. Refer back to these
safety instructions as needed.
This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be qualied according to local, state and national building and safety codes and regulations. Incorrect installation could cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance requirements are specied, the appropriate measures should be taken during installation to guard against
possible damage or injury that might occur in an earthquake if the unit is not installed correctly, injuries may occur due to a falling unit.
Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and, where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited
for electrical operation purposes. Keep a quenching cloth and a re extinguisher nearby during brazing.
Use care in handling, rigging, and setting of bulky equipment.
When transporting, be careful when picking up, moving and mounting these units. Although the unit may be packed using plastic straps, do not use them for transporting the unit from one location to another. Do not stand on or put any material on the unit. Get a partner to help, and bend with your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum ns on the air conditioner can cut ngers,
so wear protective gloves.
Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features, disengagement, and interlocks must be in place and functioning correctly before the equipment is put into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident can occur. Never bypass or jump-out any safety device or switch.
Johnson Controls, Inc. will not assume any liability for injuries or damage caused by not following steps outlined or described in this manual. Unauthorized modications to Johnson Controls products are
prohibited as they…
May create hazards which could result in death, serious injury or equipment damage. Will void product warranties. May invalidate product regulatory certications. ◦ May violate OSHA standards.
31
i
P5415467
Page 6
Take the following precautions to reduce the risk of property damage.
Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during
installation work. Foreign matter could damage internal components or cause blockages.
If air lters are required on this unit, do not operate the unit without the air lter set in place. If the air lter is not installed, dust may accumulate and breakdown may result.
Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules attach themselves to the surface of the heat exchanger, the nned surfaces will repel water. As a result, any amount of condensate can overow from the condensate pan and could run inside of the
electrical box, possibly causing electrical failures.
When installing the unit in a hospital or other facility where electromagnetic waves are generated from nearby medical and/or electronic devices, be prepared for noise and electronic interference Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment, and radio communications equipment may cause the unit to malfunction. The operation of the unit may also adversely affect these same devices. Install the unit at least 10 ft. (approximately 3m) away from such devices.
When a wireless zone controller is used, locate at a distance of at least 3.3 ft. (approximately 1 meter) between the indoor unit and electric lighting. If not, the receiver part of the unit may have difculty
receiving operation commands.
Do not install the unit in any location where animals and plants can come into direct contact with the outlet air stream. Exposure could adversely affect the animals and plants.
Do not install the unit with any downward slope to the side of the drain boss. If you do, you may have water owing back which may cause leaks.
Be sure the condensate hose discharges water properly. If connected incorrectly, it may cause leaks.
Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in
restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These specialized oil-resistant units can be ordered for such applications. However, in places where large quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used. These products should not be installed in such locations.
Installation Precautions
To reduce the risk of serious injury or death, the following installation
precautions must be followed.
When installing the unit into… A wall: Make sure the wall is strong enough to hold the unit’s weight. It may be necessary to
construct a strong wood or metal frame to provide added support.
A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
cause dripping and water damage to wall and oors.
Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air bafe.
A snowy area (only for heat pump model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
Do not install the unit in the following places. Doing so can result in an explosion, re, deformation,
corrosion, or product failure.
Explosive or ammable atmosphere ▫ Where re, oil, steam, or powder can directly enter the unit, such as in close proximity or directly
above a kitchen stove.
Where oil (including machinery oil) may be present. Where corrosive gases such as chlorine, bromine, or sulde can accumulate, such as near a hot
tub or hot spring.
Where dense, salt-laden airow is heavy, such as in coastal regions. ▫ Where the air quality is of high acidity. Where harmful gases can be generated from decomposition.
ii
4
P5415467
Page 7
Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive gases may be present. If you do, toxic gases can seep into breathable air spaces and can cause respiratory injuries. If the condensate pipe is installed incorrectly, water leakage and damage to the
ceiling, oor, furniture, or other possessions may result. If condensate piping becomes clogged,
moisture can back up and can drip from the indoor unit. Do not install the indoor unit where such dripping can cause moisture damage or uneven locations: Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the unit to prevent water damage and abnormal vibration.
Before performing any brazing work, be sure that there are no ammable materials or open ames nearby.
Perform a run test to ensure normal operation. Safety guards, shields, barriers, covers, and protective devices must be in place while the compressor/unit is operating. During the test run, keep ngers and
clothing away from any moving parts.
Clean up the site when nished, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being installed.
During transportation, do not allow the backrest of the forklift to make contact with the unit, otherwise, it may cause damage to the heat exchanger and also may cause injury when stopped or started suddenly.
Remove gas inside the closing pipe when the brazing work is performed. If the brazing ller metal is
melted with remaining gas inside, the pipes will be blown off and it may cause injury.
Be sure to use nitrogen gas for an airtight test. If other gases such as oxygen gas, acetylene gas or uorocarbon gas are accidentally used, it may cause explosion or gas intoxication.
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use and maintenance of the unit to the customer according to the information in all manuals that came with the system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
Controls uses only refrigerants that have been approved for use in the unit’s intended home country
or market. Johnson Controls distributors similarly are only authorized to provide refrigerants that have been approved for use in the countries or markets they serve. The refrigerant used in this unit
is identied on the unit’s faceplate and/or in the associated manuals. Any additions of refrigerant into this unit must comply with the country’s requirements with regard to refrigerant use and should be
obtained from Johnson Controls distributors. Use of any non-approved refrigerant substitutes will void the warranty and will increase the potential risk of injury or death.
If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum
allowable concentration in the event that refrigerant gases should escape. Refrigerant gases can cause asphyxiation (0.42 kg/m3 based on ISO 5149 for R410A). Consult with your distributor for countermeasures (ventilation system and so on). If refrigerant gas has leaked during the installation work, ventilate the room immediately.
The design pressure for this product is 601 psi (4.15MPa). The pressure of R410A refrigerant is 1.4
times higher than that of the refrigerant R22. Therefore, the refrigerant piping for R410A shall be
thicker than that for R22. Make sure to use the specified refrigerant piping. If not, the refrigerant piping may rupture due to an excessive refrigerant pressure. Besides, pay attention to the piping
thickness when using copper refrigerant piping. The thickness of copper refrigerant piping differs depending on its material.
The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
as moisture, oxide lm, (or fat). Perform the installation work with care to prevent moisture, dust, or
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the cycle from such parts as expansion valve and the operation may be unavailable.
To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the
sizes of the charging connections have been changed from R407C type and R22 type. It is necessary to prepare the appropriate tools before performing the installation work.
Use refrigerant pipes and joints which are approved for use with R410A.
A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is
5
P5415467
iii
Page 8
under pressure and never open pressurized system parts.
Before installation is complete, make sure that the refrigerant leak test has been performed. If
refrigerant gases escape into the air, turn OFF the main switch, extinguish any open ames and
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
should leak and come into contact with open ames, toxic gas could be generated. Also, because the uorocarbons are heavier than air, they settle to the oor, which could cause asphyxiation.
When installing the unit, and connecting refrigerant piping, keep all piping runs as short as
possible, and make sure to securely connect the refrigerant piping before the compressor starts operating. If the refrigerant piping is not connected and the compressor activates with the stop valve opened, the refrigerant cycle will become subjected to extremely high pressure, which can
cause an explosion or re.
Tighten the are nut with a torque wrench in the specied manner. Do not apply excessive force to the
are nut when tightening. If you do, the are nut can crack and refrigerant leakage may occur.
When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the
compressor stops.
When pipes are removed out from under the piping cover, after the insulation work is completed,
cover the gap between the piping cover and pipes by a packing (eld-supplied). If the gap is not
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
valve ies out due to refrigerant pressure. At the run test, fully open the gas and liquid valves,
otherwise, these devices will be damaged. (It is closed before shipment.)
If the arrangement for outdoor units is incorrect, it may cause owback of the refrigerant and result in
failure of the outdoor unit.
The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15o.
Electrical Precautions
Take the following precautions to reduce the risk of electric shock, re or
explosion resulting in serious injury or death.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram
and these instructions when wiring. Improper connections and inadequate grounding can cause serious injury or death.
Perform all electrical work in strict accordance with this installation and maintenance manual and all
the relevant regulatory standards.
Before servicing, open and tag all disconnect switches. Never assume electrical power is
disconnected. Check with meter and equipment.
Only use electrical protection equipment and tools suited for this installation.
Use specied cables between units.
The new air conditioner may not function normally in the following instances:
If electrical power for the new air conditioner is supplied from the same transformer as the device*
referred to below.
If the power source cables for this device* and the new air conditioner unit are located in close
proximity to each other.
Device*: (Example): A lift, container crane, rectier for electric railway, inverter power
device, arc furnace, electric furnace, large-sized induction motor and large-sized switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply cables for the packaged air conditioner due to a rapid change in power consumption of the device and an activation of a switch.
Check eld regulations and standards before performing electrical work in order to protect the
power supply for the new air conditioner unit.
iv
6
P5415467
Page 9
Communication cabling shall be a minimum of 18-Gauge, 2-Conductor, Stranded Copper. Shielded
cable must be considered for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors. When shielded cabling is applied, proper bonding and termination of the cable shield is required as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be considered per application and local code requirments.
Use an exclusive power supply for the air conditioner at the unit’s rated voltage.
Be sure to install circuit breakers (ground fault interrupter, isolating switch, molded case circuit
breaker and so on), with the specied capacity. Ensure that the wiring terminals are tightened securely to recommended torque specications.
Clamp electrical wires securely with a cable clamp after all wiring is connected to the terminal block.
In addition, run wires securely through the wiring access channel.
When installing the power lines, do not apply tension to the cables. Secure the suspended cables at
regular intervals, but not too tightly.
Make sure that the terminals do not come into contact with the surface of the electrical box. If the
terminals are too close to the surface, it may lead to failures at the terminal connection.
Turn OFF and disconnect the unit from the power source when handling the service connector. Do not
open the service cover or access panel to the indoor or outdoor units without turning OFF the main power supply.
After ceasing operation, be sure to wait at least ve minutes before turning off the main power
switch. Otherwise, water leakage or electrical breakdown may result. Disconnect the power source completely before attempting any maintenance for electrical parts. Check to ensure that no residual voltage is present after disconnecting the power source.
Do not clean with, or pour water into, the controller as it could cause electric shock and/or damage the
unit. Do not use strong detergent such as a solvent. Clean with a soft cloth.
Check that the ground wire is securely connected. Do not connect ground wiring to gas piping, water
piping, lighting conductor, or telephone ground wiring.
If a circuit breaker or fuse is frequently activated, shut down the system and contact your
service contractor.
Perform all electrical work in accordance with this manual and in compliance with all regulations and
safety standards.
Do not open a service access cover or panel of an indoor or outdoor unit without rst turning OFF the
power at the main power supply.
Residual voltage can cause electric shock. At all times, check for residual voltage after disconnecting
from the power source before starting work on the unit.
This equipment can be installed with a Ground Fault Circuit Breaker (GFCI), which is a recognized
measure for added protection to a properly grounded unit. Install appropriate sized breakers/fuses/ overcurrent protection switches, and wiring in accordance with local, state and NEC codes and requirements. The equipment installer is responsible for understanding and abiding by applicable codes and requirements.
v
7
P5415467
Page 10
PRODUCT
1 MODELS LIST
1.1 Outdoor Unit
Service Manual
Model Name
DHR18CSB21S 208/230V~60Hz
DHR24CSB21S 208/230V~60Hz
DHR30CSB21S 208/230V~60Hz
DHR36CSB21S 208/230V~60Hz
Power Supply
(V, Ph, Hz)
Appearance
DHR42CSB21S 208/230V~60Hz
DHR48CSB21S 208/230V~60Hz
1
Page 11
Service Manual
Type
Model Name
Duct
Type
Cassette
Type
Ceiling
Type
1.2 Indoor Unit
Nominal Capacity
Cooling/Heating
(Btu/h)
DHR18NDB21S 17100/18800 208/230V~60Hz
DHR24NDB21S 23800/27200 208/230V~60Hz
DHR30NDB21S 28200/31200 208/230V~60Hz
DHR36NDB21S 34000/41000 208/230V~60Hz
DHR42NDB21S 39500/44000 208/230V~60Hz
DHR48NDB21S
48000/54500 208/230V~60Hz
Power Supply
(V, Ph, Hz)
Appearance
DHR18NKB21S 17100/18400 208/230V~60Hz
DHR24NKB21S 23800/27200 208/230V~60Hz
DHR30NKB21S 28200/31200 208/230V~60Hz
DHR36NKB21S 34000/41000 208/230V~60Hz DHR42NKB21S 39500/44000 208/230V~60Hz
DHR48NKB21S 48000/54500 208/230V~60Hz
DHR18NCB21S 17100/19100 208/230V~60Hz
DHR24NCB21S 23800/27200 208/230V~60Hz DHR30NCB21S 28200/31200 208/230V~60Hz
DHR36NCB21S 34000/41000 208/230V~60Hz DHR42NCB21S 39500/44000 208/230V~60Hz
Note: This series allows the customer to choose any of the three types of indoor units to match up with the outdoor equipment.
DHR48NCB21S 48000/54500 208/230V~60Hz
Note: 1 Ton =12000Btu/h = 3.517kW
2
Page 12
2 Nomenclature
Service Manual
3
Page 13
Service Manual
Model
Indoor unit
Outdoor unit
Capacity
Cooling Capacity
Btu/h
17100(5400~19800)
23800(7400~29000)
28200(8200~29600)
Heating Capacity
Btu/h
18800(4700~23200)
27200(8200~32400)
31200(8200~33600)
Power Input
Cooling
kW
1.55(0.55~1.75)
2.23(0.85~2.50)
3.30(0.85~3.70)
Heating
kW
1.65(0.50~1.90)
2.36(0.80~2.75)
3.10(0.80~3.50)
SEER / HSPF
(Btu/h)/W
16.00/9.50
16.00/9.00
16.00/9.00
Indoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Fan
Drive
-
Direct
Direct
Direct
Motor Output
kW
0.06×1
0.15×1
0.15×1
Air Flow
m3/h(CFM)
1000(585)
1400(820)
1400(820)
Rated Ext. Static
Pressure
Pa(InWg)
25(0.1)
25(0.1)
37(0.15)
Ext. Static Pressure
Range
Pa(InWg)
0~30(0~0.12)
0~75(0~0.3)
0~75(0~0.3)
Sound Pressure Level(SS/H/M/L)
dB(A)
40/39/36/28
47/46/44/40
47/46/44/40
Air Filter
-
PP
PPKZ
PPKZ
mm(inch)
Φ30×1.5
(φ1.18×0.06)
Φ20×1.2
(φ0.79×0.05)
Φ20×1.2
(φ0.79×0.05)
Outline Dimensions (W×H×D)
mm
(inch)
1037×266×721
(40.8×10.5×28.4)
1279×268×558
(50.4×10.6×22.0)
1279×268×558
(50.4×10.6×22.0)
Net Weight
kg(lb)
33.0(72.8)
34.0(75.0)
35.0(77.2)
Outdoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Compressor
Type
-
Rotary
Rotary
Rotary
Power Input
W
1440
2550
2550
Control
-
Electronic Expansion
Valve
Electronic Expansion
Valve
Electronic Expansion
Valve
Charge
kg(oz)
1.4(49.4)
2.2(77.6)
2.4(84.7)
Outline Dimensions (W×H×D)
mm(inch)
955×700×396
(37.6×27.6×15.6)
980×790×427
(38.6×31.1×16.8)
980×790×427
(38.6×31.1×16.8)
Net Weight
kg(lb)
48.0(105.8)
69.0(152.1)
72.0(158.8)
Piping
Connections
Liquid
Inch
Φ1/4
Φ3/8
Φ3/8
Gas
Inch
Φ1/2
Φ5/8
Φ5/8
Max. Length
m(ft)
20(65.6)
30(98.4)
30(98.4)
Max. Height
m(ft)
15(49.2)
15(49.2)
15(49.2)
3 PRODUCT DATA
3.1 Product Data of Indoor Unit
3.1.1 Duct Type
DHR18NDB21S DHR24NDB21S DHR30NDB21S
DHR18CSB21S DHR24CSB21S DHR30CSB21S
Heat Exchanger
Condensate Piping
Heat Exchanger
DHR18NDB21S DHR24NDB21S DHR30NDB21SI
208/230V1Ph~60Hz 208/230V1Ph~60Hz 208/230V1Ph~60Hz
DHR18CSB21S DHR24CSB21S DHR30B21S
208/230V1Ph~60Hz 208/230V1Ph~60Hz 208/230V1Ph~60Hz
Refrigerant
R410A
4
Page 14
Service Manual
Model
Indoor unit
Outdoor unit
Capacity
Cooling Capacity
Btu/h
34000(10800~39000)
39500(12000~42500)
48000(20400~49500)
Heating Capacity
Btu/h
41000(9800~49500)
44000(13000~52500)
54500(17500~58000)
Power Input
Cooling
kW
3.28(0.70~4.50)
4.15(0.65~4.70)
5.15(1.40~5.60)
Heating
kW
3.75(0.70~4.60)
3.90(0.76~4.75)
5.15(1.30~5.50)
SEER / HSPF
(Btu/h)/W
16.00/9.00
16.00/9.00
16.00/9.00
Indoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Fan
Drive
-
Direct
Direct
Direct
Motor Output
kW
0.25×1
0.25×1
0.56×1
Air Flow
m3/h(CFM)
2000(1175)
2000(1175)
2500(1470)
Rated Ext. Static
Pressure
Pa(InWg)
37(0.15)
37(0.15)
50(0.2)
Ext. Static Pressure
Range
Pa(InWg)
0~100(0~0.4)
0~100(0~0.4)
0~125(0~0.5)
Sound Pressure Level(SS/H/M/L)
dB(A)
53/52/48/44
53/52/48/44
55/53/49/45
Air Filter
-
PPKZ
PPKZ
PPKZ
mm(inch)
Φ20×1.2
(φ0.79×0.05)
Φ20×1.2
(φ0.79×0.05)
Φ20×1.2
(φ0.79×0.05)
Outline Dimensions (W×H×D)
mm
(inch)
1226×290×775
(48.3×11.4×30.5)
1226×290×775
(48.3×11.4×30.5)
1340×350×750
(52.8×13.8×29.5)
Net Weight
kg(lb)
46.0(101.4)
46.0(101.4)
56.0(123.5)
Outdoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Compressor
Type
-
Rotary
Rotary
Rotary
Power Input
W
4150
4150
4580
Control
-
Electronic Expansion
Valve
Electronic Expansion
Valve
Electronic Expansion
Valve
Charge
kg(oz)
3.5(123.5)
3.7(130.5)
4.0(141.1)
Outline Dimensions (W×H×D)
mm(inch)
1107×1100×440
(43.6×43.3×17.3)
958×1349×412
(37.7×53.1×16.2)
958×1349×412
(37.7×53.1×16.2)
Net Weight
kg(lb)
93.0(205.1)
95.0(209.5)
105.0(231.5)
Piping
Connections
Liquid
Inch
Φ3/8
Φ3/8
Φ3/8
Gas
Inch
Φ5/8
Φ5/8
Φ5/8
Max. Length
m(ft)
30(98.4)
50(164.0)
50(164.0)
Max. Height
m(ft)
15(49.2)
30(98.4)
30(98.4)
Heat Exchanger
DHR36NDB21S DHR42NDB21S
DHR36CSB21S DHR42CSB21S DHR48CSB21S
DHR36NDB21S DHR42NDB21S DHR48NDB21S
208/230V1Ph~60Hz 208/230V1Ph~60Hz 208/230V1Ph~60Hz
DHR48NDB21SI
Refrigerant
R410A
Condensate Piping
DHR36CSB21S DHR42CSB21S DHR48CSB21S
208/230V1Ph~60Hz 208/230V1Ph~60Hz 208/230V1Ph~60Hz
Heat Exchanger
5
Page 15
Service Manual
Model
Indoor unit
Outdoor unit
Capacity
Cooling Capacity
Btu/h
17100(5400~18700)
23800(8200~29000)
28200(8800~31400)
Heating Capacity
Btu/h
18400(4700~22200)
27200(8200~32400)
31200(8200~33600)
Power Input
Cooling
kW
1.70(0.55~1.75)
2.23(0.85~2.50)
2.70(0.85~3.70)
Heating
kW
1.80(0.50~1.90)
2.36(0.80~2.75)
2.50(0.80~3.50)
SEER / HSPF
(Btu/h)/W
16.00/9.50
16.00/9.00
17.00/9.00
Indoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Fan
Drive
-
Direct
Direct
Direct
Motor Output
kW
0.045×1
0.045×1
0.075×1
Air Flow
m3/h(CFM)
760(445)
1300(765)
1500(880)
Sound Pressure Level(SS/H/M/L)
dB(A)
47/46/44/37
47/46/42/38
49/48/45/40
Air Filter
-
PP
ABS+PP
ABS+PP
mm(inch)
Φ25×1.5
(φ0.98×0.06)
Φ25×1.5
(φ0.98×0.06)
Φ25×1.5
(φ0.98×0.06)
Outline Dimensions (W×H×D)
mm(inch)
665×240×596
(26.2×9.4×23.5)
917×240×840
(36.1×9.4×33.1)
917×320×840
(36.1×12.6×33.1)
Net Weight
kg(lb)
20.0(44.1)
27.0(59.5)
32.0(70.6)
Outdoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Compressor
Type
-
Rotary
Rotary
Rotary
Power Input
W
1440
2550
2550
Control
-
Electronic
Expansion Valve
Electronic
Expansion Valve
Electronic
Expansion Valve
Charge
kg(oz)
1.4(49.4)
2.2(77.6)
2.4(84.7)
Outline Dimensions (W×H×D)
mm(inch)
955×700×396
(37.6×27.6×15.6)
980×790×427
(38.6×31.1×16.8)
980×790×427
(38.6×31.1×16.8)
Net Weight
kg(lb)
48.0(105.8)
69.0(152.1)
72.0(158.8)
Piping
Connections
Liquid
Inch
Φ1/4
Φ3/8
Φ3/8
Gas
Inch
Φ1/2
Φ5/8
Φ5/8
Max. Length
m(ft)
20(65.6)
30(98.4)
30(98.4)
Max. Height
m(ft)
15(49.2)
15(49.2)
15(49.2)
3.1.2 Cassette Type
Heat Exchanger
Condensate Piping
DHR18NKB21S DHR24NKB21S
DHR18CSB21S DHR24CSB21S DHR30CSB21S
DHR18NKB21S DHR24NKB21S DHR30NKB21S
208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
DHR30NKB21S
Heat Exchanger
Refrigerant
R410A
DHR18CSB21S DHR24CSB21S DHR30CSB21S
208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
6
Page 16
Service Manual
Model
Indoor unit
Outdoor unit
Capacity
Cooling Capacity
Btu/h
34000(10800~39000)
39500(11000~41000)
48000(20400~50500)
Heating Capacity
Btu/h
41000(9800~49500)
44000(12000~51000)
54500(17500~61500)
Power Input
Cooling
kW
3.28(0.75~4.50)
4.40(0.53~4.65)
5.50(1.30~5.70)
Heating
kW
3.75(0.60~4.80)
4.45(0.64~4.80)
4.80(1.20~5.40)
SEER / HSPF
(Btu/h)/W
16.00/9.00
16.00/9.00
16.00/9.00
Indoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Fan
Drive
-
Direct
Direct
Direct
Motor Output
kW
0.075×1
0.075×1
0.1×1
Air Flow
m3/h(CFM)
1860(1095)
1860(1095)
2300(1350)
Sound Pressure Level(SS/H/M/L)
dB(A)
51/49/46/43
51/49/46/43
53/52/47/41
Air Filter
-
ABS+PP
ABS+PP
ABS+PP
mm(inch)
Φ25×1.5
(φ0.98×0.06)
Φ25×1.5
(φ0.98×0.06)
Φ25×1.5
(φ0.98×0.06)
Outline Dimensions (W×H×D)
mm(inch)
917×320×840
(36.1×12.6×33.1)
917×320×840
(36.1×12.6×33.1)
910×290×910
(35.8×11.4×35.8)
Net Weight
kg(lb)
32.0(70.6)
32.0(70.6)
43.0(94.8)
Outdoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Compressor
Type
-
Rotary
Rotary
Rotary
Power Input
W
4150
4150
4580
Control
-
Electronic
Expansion Valve
Electronic
Expansion Valve
Electronic
Expansion Valve
Charge
kg(oz)
3.5(123.5)
3.7(130.5)
4.0(141.1)
Outline Dimensions (W×H×D)
mm(inch)
1107×1100×440
(43.6×43.3×17.3)
958×1349×412
(37.7×53.1×16.2)
958×1349×412
(37.7×53.1×16.2)
Net Weight
kg(lb)
93.0(205.1)
95.0(209.5)
105.0(231.5)
Piping
Connections
Liquid
Inch
Φ3/8
Φ3/8
Φ3/8
Gas
Inch
Φ5/8
Φ5/8
Φ5/8
Max. Length
m(ft)
30(98.4)
50(164.0)
50(164.0)
Max. Height
m(ft)
15(49.2)
30(98.4)
30(98.4)
Heat Exchanger
Condensate Piping
DHR36NKB21S DHR42NKB21S
DHR36CSB21S DHR42CSB21S DHR48CSB21S
DHR36NKB21S DHR42NKB21S DHR48NKB21S
208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
DHR48NKB21S
Heat Exchanger
Refrigerant
R410A
DHR36CSB21S DHR42CSB21S DHR48CSB21S
208/230V1PH~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
7
Page 17
Service Manual
Model
Indoor unit
Outdoor unit
Capacity
Cooling Capacity
Btu/h
17100(5400~19800)
23800(8200~27800)
28200(8800~31400)
Heating Capacity
Btu/h
19100(4700~23200)
27200(8200~30600)
31200(8200~33600)
Power Input
Cooling
kW
1.55(0.55~1.75)
2.23(0.85~2.50)
2.40(0.85~3.70)
Heating
kW
1.55(0.50~1.90)
2.36(0.80~2.75)
2.60(0.80~3.50)
SEER / HSPF
(Btu/h)/W
17.00/9.50
16.00/9.00
17.00/9.00
Indoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Fan
Drive
-
Direct
Direct
Direct
Motor Output
kW
0.06×1
0.06×1
0.15×1
Air Flow
m3/h(CFM)
1000(585)
1200(705)
1500(880)
Sound Pressure Level(SS/H/M/L)
dB(A)
44/42/38/32
49/48/46/40
49/46/44/38
Air Filter
-
PP
PP
PP
mm(inch)
Φ17×1.75
(φ0.67×0.07)
Φ17×1.75
(φ0.67×0.07)
Φ17×1.75
(φ0.67×0.07)
Outline Dimensions (W×H×D)
mm(inch)
1220×225×700
(48.0×8.9×27.6)
1220×225×700
(48.0×8.9×27.6)
1420×245×700
(55.9×9.6×27.6)
Net Weight
kg(lb)
39.0(86.0)
40.0(88.2)
48.0(105.8)
Outdoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Compressor
Type
-
Rotary
Rotary
Rotary
Power Input
W
1440
2550
2550
Control
-
Electronic Expansion
Valve
Electronic Expansion
Valve
Electronic Expansion
Valve
Charge
kg(oz)
1.4(49.4)
2.2(77.6)
2.4(84.7)
Outline Dimensions (W×H×D)
mm(inch)
955×700×396
(37.6×27.6×15.6)
980×790×427
(38.6×31.1×16.8)
980×790×427
(38.6×31.1×16.8)
Net Weight
kg(lb)
48.0(105.8)
69.0(152.1)
72.0(158.8)
Piping
Connections
Liquid
Inch
Φ1/4
Φ3/8
Φ3/8
Gas
Inch
Φ1/2
Φ5/8
Φ5/8
Max. Length
m(ft)
20(65.6)
30(98.4)
30(98.4)
Max. Height
m(ft)
15(49.2)
15(49.2)
15(49.2)
3.1.3 Floor-ceiling Type
Heat Exchanger
DHR18NCB21S DHR24NCB21S DHR30NCB21S
DHR18CSB21S DHR24CSB21S DHR30CSB21S
DHR18NCB21S DHR24NCB21S DHR30NCB21S
208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
Condensate Piping
Heat Exchanger
Refrigerant
R410A
DHR18CSB21S DHR24CSB21S DHR30CSB21S
208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
8
Page 18
Model
Indoor unit
Outdoor unit
Capacity
Cooling Capacity
Btu/h
34000(10800~39000)
39500(12000~42500)
48000(20400~50500)
Heating Capacity
Btu/h
41000(9800~49500)
44000(13000~52500)
54500(17500~61500)
Power Input
Cooling
kW
3.28(0.80~4.60)
4.05(0.60~4.70)
4.95(1.30~5.50)
Heating
kW
3.75(0.65~4.80)
4.05(0.69~4.80)
4.60(1.20~5.40)
SEER / HSPF
(Btu/h)/W
16.00/9.00
16.00/9.00
16.00/9.00
Indoor Unit
Power Supply
V/Ph/Hz
Heat Exchanger
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Fan
Drive
-
Direct
Direct
Direct
Motor Output
kW
0.15×1
0.15×1
0.25×1
Air Flow
m3/h(CFM)
1900(1115)
1900(1115)
2300(1350)
Sound Pressure Level(SS/H/M/L)
dB(A)
54/53/51/46
55/54/52/47
56/55/50/46
Air Filter
-
PP
PP
PP
mm(inch)
Φ17×1.75
(φ0.67×0.07)
Φ17×1.75
(φ0.67×0.07)
Φ17×1.75
(φ0.67×0.07)
Outline Dimensions (W×H×D)
mm(inch)
1420×245×700
(55.9×9.6×27.6)
1420×245×700
(55.9×9.6×27.6)
1700×245×700
(66.9×9.6×27.6)
Net Weight
kg(lb)
48.0(105.8)
50.0(110.3)
59.0(130.1)
Outdoor Unit
Power Supply
V/Ph/Hz
-
Cross Fin Coil
Cross Fin Coil
Cross Fin Coil
Compressor
Type
-
Rotary
Rotary
Rotary
Power Input
W
4150
4150
4580
Control
-
Electronic Expansion
Valve
Electronic Expansion
Valve
Electronic Expansion
Valve
Charge
kg(oz)
3.5(123.5)
3.7(130.5)
4.0(141.1)
Outline Dimensions (W×H×D)
mm(inch)
1107×1100×440
(43.6×43.3×17.3)
958×1349×412
(37.7×53.1×16.2)
958×1349×412
(37.7×53.1×16.2)
Net Weight
kg(lb)
93.0(205.1)
95.0(209.5)
105.0(231.5)
Piping
Connections
Liquid
Inch
Φ3/8
Φ3/8
Φ3/8
Gas
Inch
Φ5/8
Φ5/8
Φ5/8
Max. Length
m(ft)
30(98.4)
50(164.0)
50(164.0)
Max. Height
m(ft)
15(49.2)
30(98.4)
30(98.4)
Indoor
Outdoor
Cooling
Heating
Piping Length
18k~48k units
Service Manual
DHR36NCB21S DHR42NCB21S DHR48NCB21S
DHR36CSB21S DHR42CSB21S DHR48CSB21S
DHR36NCB21S DHR42NCB21S DHR48NCB21S
208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
Condensate Piping
DHR36CSB21S DHR42CSB21S DHR48CSB21S
208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz 208/230V1Ph~ 60Hz
Heat Exchanger
Refrigerant
R410A
Nominal capacities are based on the following conditions.
Note:
The air volume is measured at the relevant standard external static pressure. Noise is tested in a semi-anechoic room, so it should be slightly higher in the actual operation due to
environmental change.
DB: 80.0℉ (26.7)
WB: 67.0℉ (19.4℃)
DB: 70.0℉ (21.1)
WB: 60.0℉ (15.6)
9
DB: 95.0℉ (35.0)
WB: 75.0℉ (23.9)
DB: 47.0℉ (8.33)
WB: 43.0℉ (6.11)
25.0ft (7.6m)
Page 19
Service Manual
Mode
Range of Outdoor Temperature
Cooling
Heating
Model
Compressor
Fan Motor
Fuse/Breaker
Capacity
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Power Supply
Qty.
RLA
FLA
V/Ph/Hz
A A A A
A
12.0
1.5
5/25
17
25
18.0
1.5
5/40
24
40
18.0
1.5
5/40
24
40
21.2
2.0
5/45
29
45
21.2
2*2.0
5/50
31
50
32.5
2*2.0
5/70
45
70
Model
Power Supply
Fan Motor FLA
Fuse/Breaker
Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
V/Ph/Hz
A A A
A
0.6
5/15
1
15
1.3
5/15
2
15
1.3
5/15
2
15
2.1
5/15
3
15
2.1
5/15
3
15
4.0
5/15
5
15
0.5
5/15
1
15
0.5
5/15
1
15
0.9
5/15
1.5
15
0.9
5/15
1.5
15
0.9
5/15
1.5
15
1.5
5/15
2
15
0.6
5/15
1
15
0.6
5/15
1
15
1.4
5/15
2
15
1.4
5/15
2
15
1.4
5/15
2
15
2.1
5/15
3
15
3.2 Operation Range
3.3 Electrical Data
3.3.1 Outdoor unit
DHR18CSB2 208/230V1Ph ~ 60Hz 1 DHR24CSB21S 208/230V1Ph ~ 60Hz 1 DHR30CSB21S 208/230V1Ph ~ 60Hz 1
0℉ (-18.0)~118.4℉ (48.0)
0℉ (-18.0)~75.2℉ (24.0)
Table 1-3-1 Electrical Data of Outdoor Unit
DHR36CSB21S 208/230V1Ph ~ 60Hz 1 DHR42CSB21S 208/230V1Ph ~ 60Hz 1 DHR48CSB21S 208/230V1Ph ~ 60Hz 1
3.3.2 Indoor unit
DHR18NDB21S 208V/230V1Ph ~ 60Hz DHR24NDB21S 208V/230V1Ph ~ 60Hz DHR30NDB21S 208V/230V1Ph ~ 60Hz DHR36NDB21S 208V/230V1Ph ~ 60Hz DHR42NDB21S 208V/230V1Ph ~ 60Hz
DHR48NDB21S 208V/230V1Ph ~ 60Hz DHR18NKB21S 208V/230V1Ph ~ 60Hz DHR24NKB21S 208V/230V1Ph ~ 60Hz
Table 1-3-2 Electrical Data of Indoor Unit
DHR30NKB21S 208V/230V1Ph ~ 60Hz DHR36NKB21S 208V/230V1Ph ~ 60Hz DHR42NKB21S 208V/230V1Ph ~ 60Hz DHR48NKB21S 208V/230V1Ph ~ 60Hz DHR18NCB21S 208V/230V1Ph ~ 60Hz
DHR24NCB21S 208V/230V1Ph ~ 60Hz
DHR30NCB21S 208V/230V1Ph ~ 60Hz
DHR36NCB21S 208V/230V1Ph ~ 60Hz
DHR42NCB21S 208V/230V1Ph ~ 60Hz
DHR48NCB21S 208V/230V1Ph ~ 60Hz
10
Page 20
Service Manual
Indoor Unit
Outdoor Unit
TH-OE
TH-D
Condenser
Strainer
with Service Port
4-Way Valve
Muffler
TH-C
Low Pressure Switch
Accumulator
High Pressure Switch
Compressor
Suction Service Valve
with Service Port
TH-IE
Evaporator
TH-E
Cooling Heating
TH-OE: Outdoor Environment Thermal Bulb TH-C: Outdoor Condenser Thermal Bulb TH-D: Compressor Discharge Thermal Bulb
TH-IE: Indoor Environment Thermal Bulb TH-E: Indoor Evaporator Thermal Bulb
Strainer
Strainer
Note:
RLA: Rated load amperes (marked in the nameplate of the outdoor unit) FLA: Full load amperes
The fuse is located on the main board.Install the disconnect device with a contact gap of at least 3mm (1/8inch) in all poles near the
outdoor unit.The outdoor unit must be positioned so that the disconnect is reachable from the unit..
Interconnecting cable from outdoor unit to indoor unit should be a minimum 14AWG stranded
3-conductor with ground. Maximum cable length is 164 feet.
When connecting a wired zone controller to an indoor unit use 18AWG stranded cabling not
exceeding 98 feet.
4 PIPING DIAGRAM
Electronic Expansion Valve Liquid Service Valve
Note:
Not all items depicted in the diagram will necessarily apply to all units.
11
Page 21
5 CONTROLLERS
Comp. starts after
3min delay
Temp of indoor
≤Set temp
Comp. stop
for 3 min
NY
N
Y
Y
N
Indoor fan run
Comp. and outdoor
fan run
Comp. and
outdoor fan stop
Power
On
OPERATION FLOWCHART
5.1 Cooling/Dry Operation
Set controller to cool or dry mode
Service Manual
12
Page 22
Service Manual
Comp. starts after
3min delay
N
Y
N
Y
Y
N
Power
On
Comp. and
outdoor
fan run
Temp of indoor
≥Set temp
Comp. and
outdoor fan stop
Comp. stop
for 3 min
5.2 Heating Operation
Indoor unit running
in heat mode
Indoor fan starts only
with hot coil
13
Page 23
6 WIRELESS REMOTE CONTROLLER
No.
Name
Function Description
Signal
transmitter
Signal transmitter
ON/OFF
button
MODE
button
AUTO; COOL; DRY; FAN;
6.1 Operation and Display View
Service Manual
Table 2-2-1 Instructions for wireless remote controller
Press this button and the unit will be turned on; press it once more and the unit will be turned off. When turning off the unit, the Sleep function will be canceled, but the current time is still displayed. By pressing this button, Auto, Cool, Dry, Fan, Heat mode can be selected. Auto mode is default after power on. Under the Auto mode, the setpoint temperature will not be displayed; Under the Heat mode, the initial value is 28°C (82°F); under other modes, the initial value is 25°C (77°F).
HEAT (heat pump only)
14
Page 24
- button
+ button
FAN button
Low speed Middle speed High speed
Note: Under the DRY mode, the fan will be kept running at the low speed and the fan speed isn't adjustable.
SWING
UP/DOWN
button
When the guide louver starts to swing up and down, if SWING functions are canceled, the
air guide louver will stop and remains at the current position.
CLOCK
button
By pressing this button, the clock is allowed to be set, with blinking, and then press
TIMER ON
button
Service Manual
Preset temperature can be decreased by pressing this button. Pressing and holding this button for more than 2 seconds will quickly adjust the temperature until released. The temperature adjustment is unavailable under the Auto mode. Celsius setting range: 16° C~30°C; Fahrenheit scale setting range 61°F~86°F.
Preset temperature can be increased by pressing this button. Pressing and holding this button for more than 2 seconds can make the temperature changed quickly until release the button and then transmit this order. The temperature adjustment is unavailable under the Auto mode, but the order can be sent by pressing this button. Celsius setting range: 16~30; Fahrenheit scale setting range 61~86. By pressing this button, Auto, Low, Middle, High speeds can be selected. After power on, Auto fan speed is default.
Press this button to set up the swing angle, which changes as below:
Indicates the guide louver swings up and down among those five directions (Simplified SWING function applicable for some Fan Coil Units: When the wireless remote controller is energized initially with the unit under the OFF status, it should be set by pressing the + button and the SWING button simultaneously, with the symbol blinking twice. Then, after the unit is turned on, this function can be activated by pressing the SWING button, with the displayed symbol indicating swing function is on. If the swing symbol is not showing, then the function is turned off..
the +/- button to adjust the clock. If the +/-button is held down for more than 2 seconds, the clock setting will be increased or decreased 10 minutes every 0.5 seconds. After that, another press on the CLOCK button accepts the setting. 12:00 is displayed, when the wireless remote controller is powered up for the first time. When TIMER O N is activated, ON will blink while the symbol will disappear. Within 5 seconds it is allowed to set the ON time by pressing the +/- button. Each press will make the time increase or decrease one minute. If the +/- button is held down, the time will
change quickly in single minute increments to begin with, then in 10 minute increments.
After the desired time value is set, press TIMER ON again to confirm the setting within five seconds. After that, another press on TIMER ON will cancel the setting. Prior to the timer
set up, the current time must be set for the timer to work correctly.
15
Page 25
Service Manual
X-FAN
button
TEMP button
By pressing the TEMP button, when the temperature symbol is displayed, the indoor
is displayed, it will show the
indoor ambient temperature; when
TIMER
OFF button
By pressing this button it is available to go to the TIMER OFF setting state with the same
setting method as that of the TIMER ON, in which case the OFF symbol blinks.
TURBO
button
In the Cool or Heat mode, pressing this button can activate or deactivate the TURBO
function. When the TURBO function is activated, its symbol will be displayed; when the running mode or the fan speed is changed, this function will be canceled automatically (This function is applicable to partial of models).
SLEEP
button
LIGHT
button
Pressing this button can activate or deactivate the X-FAN function. In Cool or Dry mode, by pressing this button, if " " is displayed, it indicates the X-FAN function is activated. By repressing this button, if " " disappears, it indicates the X-FAN function is deactivated. When powering on the remote, the X-FAN function will be off. If the unit is turned off, X-FAN can be deactivated but can't be activated. By pressing this button you can choose to select the indoor setpoint temperature or the indoor ambient temperature.
The indoor setpoint temperature is displayed when the remote is first powered on.
unit display will show the indoor setpoint temperature; when
is displayed, this is indicating that the outdoor temperature, if received the other remote control signal, it will display presetting temperature is being read. (This is not applicable to all models.)
By pressing this button, Sleep On and Sleep Off can be selected. After powered on, default mode is Sleep Off. Once the unit is turned off, the Sleep function is canceled. When Sleep is set to On, the symbol of SLEEP will display. Under the Fan and Auto modes, this function is not available.
Press this button to select LIGHT on or off at the indoor display. When the LIGHT is set to on, the icon will be displayed at the hand-held remote. When the LIGHT is set to off, the icon
be turned off.
will no longer be shown at the hand-held remote and the display of the indoor unit will
7 WIRED ZONE CONTROLLER
7.1 Display View
Figure 2-3-1 Appearance of wired zone controller
16
Page 26
Service Manual
No.
Icons
Introduction
1
Left and right swing function
2
Up and down swing function
3
Air exchange function
4
Sleep function
5
Auto mode
6
COOL mode
7
DRY mode
8
FAN mode
9
HEAT mode
10
Health function
11
I-Demand function
12
Vacation function
13
14
3
Figure 2-3-2 LCD display of wired controller
Table 2-3-1 Instruction to LCD Display
Status display of main and secondary wired zone controller
Shield function
This button disables temperature adjustment, On/Off function, mode change
and the Energy Save function.
17
Page 27
15
Fan speed
16
Memory function
17
Turbo function
18
Energy-saving function
19
Ambient/setting temperature
20
Electric heater
21
22
23
24
Timer Setting
25
26
Quiet function
27
Lock function
The unit will resume the original setting state after power is restored
Blow function (Coil drying function)
Defrosting function (Heat Pump only)
Filter cleaning reminder
Service Manual
Keycard control / Motion Sensor Activation
7.2 Operation View
7.2.1 Wired Zone Controller Buttons
Figure 2-3-3 Wired zone controller buttons
18
Page 28
Service Manual
No.
Description
Functions
1
Enter/Cancel
. Function selection and canceling;. Press it for 5s to view the ambient temperature; press Mode button
to select viewing outdoor ambient temperature or indoor ambient temperature.
2
. Running temperature setting range of indoor unit:
. Timer setting range: 0.5~24hr;. Setting of air function level;. Setting of energy-saving temperature;. Setting of cleaning class.
6
3
Fan
Setting of high/medium high/medium/medium low/low/auto fan speed.
4
Mode
Setting of auto/cooling/heating/fan/dry mode of indoor unit.
5
Function
7
Timer
Timer setting.
8
On/Off
Turn on/off indoor unit.
4 Mode
and
2 ▲
Memory function
2 ▲
and
6 ▼
Lock
4 Mode
and
5 Function
5 Function
and
7 Timer
4 Mode
and
6 ▼
5 Function
and
6 ▼
Viewing historical
malfunction
1 Enter/Cancel
and
4 Mode
7.3.2 Button Functions
Table 2-3-2 Wired Zone Controller Button Functions
61°F~86℉ (16°C~30);
Switch over among these functions of swing/air/sleep/health/ I-Demand/turbo/save and cancel/e-heater/X-fan/clean/quiet.
Press Mode and ▲ buttons at the same time for 5s under off state of the
unit to enter/cancel memory function (If memory function is set, indoor unit will resume original setting state after power failure and then power recovery. If not, indoor unit is defaulted to be off after power recovery.
(Factory default for this function is "on").
Upon startup of the unit without malfunction or under off state of the unit,
press ▲ and ▼ buttons at the same time for 5s to enter lock state. All
wired zone controller buttons are locked out when lock is turned on.
Repress ▲ and ▼ buttons for 5s to quit lock state.
Programming
function (Unit/
controller
address)
Programming
Function
(General
Parameters)
Switch between
Fahrenheit and
Celsius
Setting of main and secondary wired zone controller
Pressing Mode and Function buttons at the same time with the unit turned
off puts the controller into Program Mode to allow confirmation/setting of
the unit/controller address. (See below for Programming information)
Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the programming menu. Press Mode button to scroll
through parameters and press ▲ or ▼ buttons to set the actual value.
Under off state of the unit, press Mode and ▼ buttons at the same time for
5s to switch between Fahrenheit and Celsius.
Continuously press Function and ▼ buttons for 5s to view historical
malfunction. Then press ▲ and ▼ buttons to scroll through listed error
codes if any. The timer displaying position displays the sequence of malfunction and the detailed error code. Up to five error codes may be
displayed.
Under off state of the unit, press Enter/Cancel and Mode buttons at the same
time for 5s to set main and secondary wired zone controller. Press ▲ or ▼
button to adjust. (Additional details available in the programming section.)
19
Page 29
Service Manual
Note:
The following functions can be set through Function and Timer buttons: setting of ambient temperature sensor, selecting three speeds in high speed and three speeds in low speed of indoor fan motor, display setting of freeze protection error code, setting of cold air prevention and hot air hot prevention function, setting of refrigerant-lacking protection function, selecting of blowing residual heat of indoor unit, selecting of compressor electric heater mode, selecting of low-power consumption mode, selecting door control function, selecting human sensitive function, long­distance monitoring, temperature compensation value at the air return port.
7.2.3 Setting of Wired Zone Controller/Indoor Unit Address
7.2.3.1 Setting and Confirmation of Address
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting
interface of wired controller‟s address. In this case, LCD displays address number. Then press▲ or ▼
button to adjust address and then press Enter/Cancel button to confirm. The address setting is related to the setting of Programming Function 4.9.10. When the selection in 4.9.10 is 00, this indicates the use of a
central controller and must have an address from 01 - 16. When the selection in 4.9.10 is 01, this
indicates the use of a BAS (building automation system) or BMS (building management system). In this
case, the unit/controller address would range from 01-255.
Confirming or setting of the indoor unit/controller address as shown in Figure 2-3-4 below:
Figure 2-3-
4 Setting and confirming of address
20
Page 30
Service Manual
7.2.3.2 Setting of Main/Secondary for Wired Zone Controllers
With the indoor unit turned off, press Enter/Cancel and Mode buttons at the same time for 5s to go to
the programming of main/secondary wired zone controller. Once in the program area, the LCD displays
the wired zone controller‟s address (01 for main wired zone controller and 02 for secondary wired zone
controller). Press ▲ or ▼ button to adjust address of main/secondary wired zone controller and then press
Enter/Cancel button to confirm. If wired zone controller is set as a secondary, the icon will be displayed.
Note: If there is only one wired zone controller, it can only be set as the main; if there are two
wired zone controllers, one should be the main and the other should be the secondary.
Setting
of main/secondary wired zone controller‟s address is shown as Figure 2-3-5 below:
Figure 2-3-5 Enquiry and setting of main/secondary wired zone controller‟s address
8 SPECIAL FUNCTIONS SETTINGS
8.1 Setting of Filter Clean Reminder Function
When unit is on, press Function button to switch to filter clean reminder function. The icon will blink and then enter setting of filter clean reminder function. Timer zone displays the set pollution level and you can press ▲ or ▼ button to adjust the level. Then press Enter/Cancel button to turn on this function.
When filter clean reminder function is turned on, press Function button to switch to filter clean reminder function. The icon will blink and press ▲ or ▼ button to adjust timer zone to display “00”. Then press Enter/Cancel button to cancel this function.
21
Page 31
Setting of filter clean reminder function is shown as Figure 2-4-1 below:
Service Manual
Figure 2-4-1 Setting of filter clean reminder function
When setting the filter clean reminder function, timer zone will display 2 digits, of which the former indicates the pollution degree of operating place and the latter indicates the accumulated operating time of indoor unit. There are 4 types of situations:
(1) Clean Reminder is off (Timer zone shows “00 .);
(2) Low particulate: the former digit in timer zone shows 1 while the latter one shows 0, which indicates the accumulated operating time is 5500hr. Each time the latter digit increases 1, the accumulated operating time increases 500hr. When it reaches 9, it means the accumulated operating time is 10000hr.
(3) Medium particulate: the former digit in timer zone shows 2 while the latter one shows 0,
which indicates the accumulated operating time is 1400hr. Each time the latter digit increases 1,
22
Page 32
Service Manual
level
Accumulated
operating time
(hour)
Pollution
level
Accumulated
operating time
(hour)
Pollution
level
Accumulated
operating time
(hour)
10
5500
20
1400
30
100
11
6000
21
1800
31
200
12
6500
22
2200
32
300
13
7000
23
2600
33
400
14
7500
24
3000
34
500
15
8000
25
3400
35
600
16
8500
26
3800
36
700
17
9000
27
4200
37
800
18
9500
28
4600
38
900
19
10000
29
5000
39
1000
accumulated operating time increases 400hr. When it reaches 9, it means the accumulated operating time is 5000hr;
(4) High particulate: the former digit in timer zone shows 3 while the latter one shows 0, which
indicates the accumulated operating time is 100hr. Each time the latter digit increases 1, the accumulated operating time increases 100hr. When it reaches 9, it means the accumulated operating time is 1000hr; The detailed pollution level and the corresponding time is as shown in Table 2-4-1 below:
Table 2-4-1 Pollution level and corresponding time
Pollution
If filter clean reminder function is turned on, the icon will be on.
(1) If cleaning time is not reached, no mater the setting is changed or not, the accumulated operating
time won‟t be recalculated when pressing Enter/Cancel button;
(2) If cleaning time is reached, in unit on or off state, will blink every 0.5s for reminder. Press
Function button to switch to icon and press ▲ and ▼ button to adjust the level. Then press
Enter/Cancel button, so the accumulated operating time won‟t be cleared (If the adjusted level is
higher than the present accumulated operating time, the icon won‟t blink any more; if the adjusted level is lower than the present accumulated operating time, the icon will go on blinking).
(3) The only way to cancel filter clean reminder function is to press Function button to switch to filter
clean reminder function. The icon will blink and press ▲ or ▼ button to adjust timer zone to
display “00”. In this case, the accumulated operating time will be cleared.
8.2 Low Temperature Drying Function
Under dry mode and when set temperature is 16(61), continuously press ▼ button until the
temperature is set to 12 (54). At this point, the unit will enter the low temperature drying function.
To exit low temperature drying function, press the temperature up button or mode button.
8.3 Lock Function
retained in the unit memory in the event of a power failure.
When unit is turned on normally or turned off, pressing ▲ and ▼ buttons at the same time for 5s will turn on Lock function. LCD will display . Pressing ▲ and ▼ buttons at the same time for 5s will turn off this function.
When Lock function is turned on, no other buttons will respond when pressed. This function will be
23
Page 33
Service Manual
8.4 Memory Function
Press Mode and ▲ buttons at the same time for 5s under off state of the unit to turn on or cancel
memory function. If memory function is set, is displayed. If not, indoor unit is defaulted to be off after power recovery.
If memory function is set, indoor unit will resume original setting state after power failure and then
power recovery.
Do not turn off power to the system immediately after activating/deactivating the memory function
Note:
as this may result in improper operation.
8.5 Door Control Function/Occupancy Function
When door control function is selected, the wired zone controller will work when the room card is inserted and stop working when the room card is removed; when occupancy function is selected, the wired controller will work when it senses there is somebody in the room and stop working when it senses there is nobody in the room. When the door control function senses the room card is not inserted or
occupancy function senses there is nobody in the room, the wired zone controller will display icon.
These two functions cannot be used at the same time.
Note:
In long-distance monitoring or centralized control, no matter the room card is inserted or not,
the ON/OFF of unit can be controlled. If long-distance monitoring or centralized control information is received when the room card is not inserted, icon is cleared. When the card is reinserted, door control function is judged to be turned on. If long-distance monitoring or centralized control information is received when the room card is inserted, the indoor unit will maintain its original status.
The unit can not be controlled by the wired zone controller when the card is not inserted.When door control function and occupancy function have been set at the same time, only the
door control function will be operational.
8.6 Changing from Fahrenheit to Celsius
Under off state of the unit, press Mode and ▼ buttons at the same time for 5s to switch between
Fahrenheit and Celsius.
8.7 Ambient Temperature
Under off or on state of the unit, press it for 5s to view the ambient temperature. In this case, timer zone displays ambient temperature type 01 or 02. Ambient temperature zone displays the corresponding temperature of that type. 01 stands for outdoor ambient temperature and 02 stands for the indoor ambient temperature after compensation. Press Mode button to switch between 01 and 02. Pressing other buttons except Mode button or receiving remote control signal will exit enquiry state. If there is no operation within 20s will also exit enquiry state.
24
Page 34
Service Manual
Note:
If the unit is not connected to outdoor ambient temperature sensor, display of outdoor
ambient temperature will be shielding after energizing for 12hr.
If there is malfunction of outdoor ambient temperature sensor, display of outdoor ambient
temperature will be shielding after energizing for 12hr.
8.8 Error Code Recall
Under off or on state of the unit, continuously press Function and ▼ buttons for 5s to view recent
error codes.
When recalling error codes, you will see "00" in the set temperature area of the controller. Press ▲
and ▼ buttons to view the five most recent error codes, if any. The error code(s) will be displayed in the timer section of the controller. The fifth displayed code is the most recent.
8.9 Programming Function
Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the
programming menu. Press Mode button to adjust the setting items and press ▲ or ▼ button to set the actual value.
8.9.1 Setting ambient temperature sensor (dual ambient temperature sensors function)
In the programming area, press Mode button to adjust to “00” in temperature displaying area of
controller. Press ▲ or ▼ button to adjust. There are three selections:
(1) If the room temperature is to be read at the return air of the unit then the setting value would be "01". (2) If the room temperature is to be read at the wired zone controller, then the setting value would
be "02".
(3) To read the the room temperature at the indoor unit return in cooling, dry and fan mode, and/or
to read the room temperature at the wired zone controller in heating and auto modes, select "03".
25
Page 35
Service Manual
8.9.2 Freeze protection error code
In the programming area, press Mode button until “02” is displayed on the controller. Press ▲ or ▼
button to adjust. There are two selections:
(1) When activated controller displays "01"
(2) When deactivated controller displays "02"
This function may not apply to all models.
8.9.3 Low refrigerant lock out protection
In the programming area, press Mode button until "04" is displayed at the controller. Press ▲ or ▼
button to adjust. There are two selections:
(1) When protection is on, "01" will be displayed. (2) When protection is off, "02" will be displayed.
8.9.4 Selecting blowing residual heating of indoor unit
In the programming area, press Mode button until "05" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) Mode 1 will be displayed as "00" on the controller (2) Mode 2 will be displayed as "01"
Mode 1: Outdoor unit stops when indoor unit reaches temperature setpoint. The indoor unit fan continues to run if in cooling mode; after outdoor unit stops when reaching temperature setpoint in heating mode, duct type unit and floor ceiling unit will blow residual heat for 60s and then stop indoor unit fan. Cassette units always operate in low fan speed and will blow residual heat for 60s.
Mode 2: After outdoor unit stops when reaching temperature setpoint. The indoor fan motor stops
operation with a 10s delay regardless if in heating or cooling mode.
8.9.5 Mode selecting of compressor crankcase heater
In programming area, press Mode button until "06" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) Mode 1 (LCD displays 00) (2) Mode 2 (LCD displays 01)
Notes:
Mode 1: Compressor crankcase heater starts when outdoor ambient temperature is below
35℃(95℉) and stops when outdoor ambient temperature is above 37℃ (99℉). When outdoor ambient temperature is within 35℃ (95℉)~ 37℃ (99℉), the heater will maintain its previous operation state. Mode 2: Compressor crankcase heater starts when outdoor ambient temperature is below -2°C
(28℉) and stops when outdoor ambient temperature is above 0℃ (32℉). When outdoor ambient temperature is within -2℃ (28℉)~0℃ (32℉), the heater will maintain its previous
26
Page 36
Service Manual
operation state.
8.9.6 Selecting low-power consumption mode
In the programming area, press Mode button until "07" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) With low-power consumption mode (LCD displays 00) (2) Without low-power consumption mode (LCD displays 01)
8.9.7 Selecting door control function
In the programming area, press Mode button until "08" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) Without door control function (LCD displays 00) (2) With door control function (LCD displays 01)
8.9.8 Selecting occupancy function
In the programming area, press Mode button until "09" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) Without occupancy function (LCD displays 00) (2) With occupancy function (LCD displays 00)
8.9.9 Selecting building management system or central controller
In the programming area, press Mode button until "10" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) Central controller (LCD displays 00) (2) Building management sys tem (LCD displays 01)
8.9.10 Selecting fan mode of indoor fan motor
In the programming area, press Mode button until "11" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) P3 (LCD displays 03) (2) P4 (LCD displays 04) (3) P5 (LCD displays 05) (4) P6 (LCD displays 06) (5) P7 (LCD displays 07)
Note:
different fan mode combinations are corresponding to different static pressure. Ex-factory defaulted mode is P05. You can set the mode through wired controller. S01 (lowest), S02, S03……S12, S13 (highest).
You can select P03, P04, P05, P06, P07 in fan mode of indoor fan motor, which means
27
Page 37
Service Manual
Static pressure selection
Super
high
speed
High
speed
Medium
high speed
speed
Medium
low speed
Low
speed
Quiet
R1
speed
Quiet
R2
speed
Quiet
R3
speed
P03
S09
S08
S07
S06
S05
S04
S03
S02
S01
P04
S10
S09
S08
S07
S06
S05
S04
S03
S02
P05
S11
S10
S09
S08
S07
S06
S05
S04
S03
P06
S12
S11
S10
S09
S08
S07
S06
S05
S04
P07
S13
S12
S11
S10
S09
S08
S07
S06
S05
Table 2-4-2 Combination relationship of P03, P04, P05, P06, P07
Medium
8.9.11 Selecting compensation of temperature sensor at air return
In the programming area, press Mode button until "12" is displayed at the controller. Press ▲ or ▼
button to scroll through selections:
(1) Compensate 0℃ (32℉) (LCD displays 00) (2) Compensate 1℃ (34℉) (LCD displays 01) (3) Compensate 2℃ (36℉) (LCD displays 02) (4) Compensate 3℃ (37℉) (LCD displays 03) (5) Compensate 4℃ (39℉) (LCD displays 04) (6) Compensate 5℃ (41℉) (LCD displays 05) (7) Compensate 6℃ (43℉) (LCD displays 06) (8) Compensate 7℃ (45℉) (LCD displays 07)
(9) Compensate 8℃ (46℉) (LCD displays 08) (10) Compensate 9℃ (48℉) (LCD displays 09) (11) Compensate 10℃ (50℉) (LCD displays 10) (12) Compensate 11℃ (52℉) (LCD displays 11) (13) Compensate 12℃ (54℉) (LCD displays 12) (14) Compensate 13℃ (55℉) (LCD displays 13) (15) Compensate 14℃ (57℉) (LCD displays 14) (16) Compensate 15℃ (59℉) (LCD displays 15)
Note:
Indoor ambient temperature compensation can be set through wired zone controller (e.g. If
02 is selected, it indicates the compensation temperature is 36 (2℃). If the indoor ambient
temperature detected by the temperature sensor at air return is 84℉ (29), the ambient temperature after compensation is 29 (84)-2 (36)=27 (81)).
After finishing setting, press
Enter/Cancel button to save and exit setting. If there is no input for
20s while in this programming area, it will automatically exit to normal controller function. Any changes made will not be saved.
28
Page 38
Service Manual
PE
Temperature excursion protection
PL
Low voltage protection of bus bar
PH
High voltage protection of bus bar
PU
Charging circuit malfunction
PP
Abnormity of input voltage
ee
Malfunction of outdoor drive memory chip
When there is a malfunction during operation, error will be displayed at the controller. When several
malfunctions occur at the same time, these error codes will be displayed as a sequence that can be
scrolled through.
When there is a malfunction, please turn off the unit and call the installing contractor or local service professional. See below for an example of a displayed error (E1-high pressure protection).
Figure 2-6-1
9 CENTRAL CONTROLLER
9.1 Smart Zone Controller
9.1.1 Function
The smart zone controller can directly control up to 16 sets of indoor units in a control network and is available to check the running status of any unit through the LCD, including running mode, timer, fan speed, centralized control, etc.
29
Page 39
Service Manual
No.
Name
Function Description
1
Mode
It is used for the switchover among different modes.
2
Fan
It is used to set the fan speed, high, medium, low or auto.
3
On/Off
It is used to set the on/off status of the indoor unit.
4
. Under the single/centralized control status: It is used to set the running
5
6
Mon
1/9
7
Tue 2/10
8
Wed
3/11
9.1.2 Buttons and Display of Central Controller
Figure 2-7-1
9.1.3 Function Buttons
Table 2-7-1 Functions of Buttons
temperature of the indoor unit with max. 86 (30°C ) and min. 61 (16°C );
. Under the timer setting status: It is used to set the timer period with max. 24
hours;
. Under the clock setting status: It is used to set the hour and minute.
It is used for the switchover between unit 1 and unit 9; Under the timer or clock setting status, it indicates Monday. It is used for the switchover between unit 2 and unit 10; Under the timer or clock setting status, it indicates Tuesday. It is used for the switchover between unit 3 and unit 11; Under the timer or clock setting status, it indicates Wednesday.
30
Page 40
9
Thu 4/12
It is used for the switchover between unit 4and unit 12;
10
Fri
5/13
11
Sat
6/14
12
Sun 7/15
13
8/16
It is used for the switchover between unit 8 and unit 16.
14
Timer/Time
15
Central
It is used for the switchover between single and centralized control modes.
16
Shield
17
All on/off
It is used to start/stop all indoor units.
Under the timer or clock setting status, it indicates Thursday. It is used for the switchover between unit 5and unit 13; Under the timer or clock setting status, it indicates Friday. It is used for the switchover between unit 6 and unit 14; Under the timer or clock setting status, it indicates Saturday. It is used for the switchover between unit 7 and unit 15; Under the timer or clock setting status, it indicates Sunday.
It is used to set the timer or on/off time of the selected indoor unit as well as to set the clock of the system.
It is used to deactivate some or all functions of a single or a group of indoor unit(s).
9.1.4 LCD of the Controller
Service Manual
9.1.4.1 Outline Drawing of the LCD
Figure 2-7-2
9.1.4.2 Introduction to Symbols on the LCD
Figure 2-7-3
31
Page 41
Service Manual
No.
Name
Description
1
Fan speed
It displays the fan speed of the indoor unit, high, medium, low and auto.
2
Running mode
It displays the running mode of the indoor unit, auto, cool, dry, fan and heat.
3
System clock
It displays the current time (hour and minute) in 24-hour time system and also the week day.
4
5
Weekly timer
6
Set temperature Indoor unit code
It displays the set temperature, indoor unit code (01-16), and symbols of Celsius and Fahrenheit scale.
7
Control mode
It displays “CENTER” under the centralized control mode and no
display under the single control mode.
8
Ambient
temperature
Serial port
It displays the ambient temperature, serial port as well as symbols of Celsius and Fahrenheit scale.
9
Indoor unit code
On/off status
Numbers indicate the indoor unit codes which will be displayed when
the corresponding indoor unit is online; “” indicates the on/off status of
the indoor unit, its flashing for “on” or else for “off”
10
Error
Child lock
It displays the error codes when some error(s) arises and also “CHILD LOCK” when this function is activated.
Table 2-7-2 Introduction to the Symbols on the LCD
Shield/Lock It displays the shield/lock status, “ALL‟, “TEMP”, “MODE” and „On/Off”.
It displays the timer period (unit: 0.5 hour) which will repeat every week.
9.1.4.3 Network Topology
Network Connection of the Smart Zone Controller
Figure 2-7-4
32
Page 42
9.1.4.4 Dimensions
9.2 Additional Special Functions
9.2.1 Door control function
Door control function is available for this series. In order to carry out this function, please consult
Service Manual
Figure 2-7-5
the Call Center for information on door control accessories. (Call Center Support information is on last
page of this manual.)
(1) Interface instructions
1) The interface printing is DOOR-C and the type is B2B-XH-B. The wires of door control accessories must be connected to this interface;
2) Electrical characteristic: none;
3)
Working principle: When a room card or similar object is inserted, the interface allows the
indoor unit to be operated normally. When the card is removed, the indoor unit returns to the
off state and cannot be turned on.
Connect the door control detection port of indoor main board with the interface of door control board (CN1 in the following Figure); connect the door control signal to the door control signal input port (X1 and X2 in the following Figure). X1 is AC 220V signal input and X2 is DC +5V to 24V. You can only choose X1 or X2. Definition of interface is as shown in Figure below:
Figure 2-7-6 Illustration of door control port
33
Page 43
Service Manual
No.
Terminal name
Terminal instruction
1
CN1
CN1 wiring terminal and door control interface of indoor main board
2
X1(AC-L, AC-N)
X1(AC-L, AC-N) wiring terminal, connected to door control input
signal, rated voltage 220V.
3
X2
Table 2-7-3 Door control wiring port
X2 wiring terminal, connected to door control input signal (low voltage)
(2) Function instructions:
In order to achieve this function, set it through wired controller and refer to the following operation method. Factory default is that this function is not activated; if this function is set and door control accessories are connected, the unit will control the ON/OFF of unit according to the card state detected by door control detection board. When the card is not inserted, the unit will go to standby state. If the unit has a wired zone controller, icon will be displayed on the wired zone controller.
If the unit has no wired zone controller, there will be no display. The unit will control the ON/OFF of
unit according to the detected information.
(3) Setting method:
Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the
programming menu. Press Mode button until "08" is displayed at the controller. Press ▲ or ▼ button to
scroll through selections:
1) Without door control function (LCD displays 00)
2) With door control function (LCD displays 01)
Choose the second selection and then press Enter/Cancel button to save and exit setting. Now, door control function is activated. The unit will memorize this setting status. The setting value will be maintained in the event of a power failure. The detailed setting is as shown in the Figure below:
Figure 2-7-7
34
Page 44
Service Manual
9.2.2 Occupancy function
You must purchase the occupancy module for this function to be activated. An interface for this module is reserved on the mainboard of indoor unit.
(1) Interface instruction:
1) The printing is CN23 and the interface type is JST B3B-PH-K-S;
2) Electrical characteristic: 1-pin: +12V; 2-pin: detection port; 3-pin: GND; current: 150mA;
3) Working principle: When the module detects there is nobody in the room, 2-pin and 3-pin are short-circuited and they are low electrical level; when there is somebody in the room, 2-pin output is high electrical level.
(2) Function instructions:
In order to achieve this function, set it through wired controller and refer to the following operation method. It is defaulted that this function is not activated; if this function is set and occupancy module is connected, the unit will control the ON/OFF of unit according to the signal detected by occupancy module. When there is nobody in the room and the unit has a wired zone controller, icon will be displayed on the wired zone controller; if the unit has no wired zone controller, there will be no display. The unit will control the ON/OFF of unit according to detected information.
(3) Setting method:
With the indoor unit turned off, press Function and Timer buttons simultaneously for 5s to go to the
programming menu. Press Mode button until "09" is displayed at the controller. Press ▲ or ▼ button to
adjust. There are 2 selections:
1) Without occupancy function (LCD displays 00)
2) With occupancy function (LCD displays 01)
Choose the second selection and then press Enter/Cancel button to save and exit setting. Now, occupancy function is activated. The unit will maintain this setting status. The setting value will be maintained after a power failure. The detailed setting is as shown in the Figure on the next
page.
35
Page 45
Service Manual
Note:
When the door control function and occupancy function have been set at the same time, it is
defaulted that door control function is valid and occupancy function is invalid.
The user can purchase the occupancy module as an accessory. Please pay attention to the
following notes:
There is a dedicated connection on the mainboard. The interface module inserted into this
connection must be PH-3P-K.
The current consumption of module can not exceed the current capacity provided by this
interface.
Figure 2-7-8 ("human sensitive" = "occupancy"
9.2.3 Connect to interface of central controller:
The indoor unit is interfaced with the central controller. When a central controller is connected, centralized control of a unit can be realized if the wired zone controller is not connected; (1) Interface instruction:
1) The connection is COM-BMS2, COM-BMS3 and the interface type is B2B-XH-K3;
2) Working principle: Centralized control and communication of indoor mainboard and unit control;
(2) Function instructions:
In order to achieve this function, set the address mode and address through the wired zone controller. Please refer to Point 3 (below) for the setting method. The address mode is defaulted to be connecting to a central controller mode and the defaulted address is 1. When the central controller is connected, centralized control of the unit can be realized to control unit ON/OFF, operation mode, set fan speed/temperature and weekly timer.
36
Page 46
Service Manual
(3) Setting method: First, set the address mode of the wired zone controller into central controller address mode. The setting method is:
1) Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the programming menu. Press Mode button until "10" is displayed at the controller. Press ▲ or ▼ button to scroll through selections:
Centralized controller address mode (LCD displays 00)
Building management control address mode (LCD displays 01)
Choose the first selection and then press Enter/Cancel button to save and exit setting. Now, the address of wired zone controller is set to match the address of centralized controller. The unit will memorize this setting status. The setting value will be maintained after a power failure. The detailed setting is as shown in the Figure below:
Figure 2-7-12
2) Address setting of each unit: When the address mode is set to be central controller address mode. The address setting value range is 01~16. The setting method is:
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting interface of wired zone controller address. LCD displays address sequence. Press ▲ or ▼ button to adjust the address sequence and then press Enter/Cancel button to confirm. The setting value will be maintained after a power failure. The detailed setting is as shown in the Figure below:
37
Page 47
Service Manual
Figure 2-7-13
38
Page 48
Service Manual (2) Function instructions:
In order to achieve this function, set the address mode and address through wired zone controller. Please refer to Point 3 below for the setting method. The address mode is defaulted to be connecting to central controller mode and the defaulted address is 1;
When the central controller is connected, central control of the unit can be realized to control unit ON/OFF, operation mode, set fan speed/temperature and weekly timer.
(3) Setting method:
First, set the address mode of wired zone controller into central controller address mode. The setting method is:
1) Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to
the programming menu. Press Mode button until "10" is displayed at the controller. Press ▲ or
▼ button scroll through selections:
Central controller address mode (LCD displays 00)Building management control address mode (LCD displays 01)
Choose the first selection and then press Enter/Cancel button to save and exit setting. Now, the address of wired controller is set to match the address of centralized controller. The unit will memorize this setting status. The setting value will be maintained after a power failure. The detailed setting is as shown in the Figure below:
Figure 2-7-12
2) Address setting of each unit: When the address mode is set to be central controller address mode. The address setting value range is 01~16. The setting method is:
39
Page 49
Service Manual
Under off state of the unit, press Function and Mode buttons simultaneously for 5s to enter setting
interface of wired zone controller address. LCD displays address sequence. Press ▲ or ▼ button to
adjust the address sequence and then press Enter/Cancel button to confirm. The setting value will be
maintained after a power failure. The detailed setting is as shown in the Figure below:
Figure 2-7-13
When the address is set, the wired zone controller can be removed and connect the central controller
to the indoor mainboard. Then connect the required units to realize central control of these units.
Notes:
When central controller is to be connected, set the address mode into central controller
address mode through wired zone controller. Building management system control address mode can not be set;
The unit addresses in the same network must be different, otherwise, communication
malfunction will occur and the unit will not work correctly.
When central controller is to be connected, the unit address range is 1-16. Only 16 indoor
units can be connected to each central controller.
The code and model of central controller is as below:
Name Remark
Central Controller
DCCRMW
Only 16 indoor units can be connected to this
controller
40
Page 50
No.
Error code
Malfunction
name
Origin of
malfunction signal
1
High pressure
Hi
pressure
When outdoor unit detects the high pressure switch is cut off for 3s successively, high pressure protection will occur. All the loads (except the 4
way valve in heating mode) will be switched off. In
this case, all the buttons and remote
control signals except ON/OFF button will be disabled and cannot be recovered automatically. Switch off the unit or re
energize the unit after
cutting off power to eliminate this protection.
2
Freeze protection
Indoor evaporator
temperature
If detecting that the evaporator temperature is lower than protective temp. value after the unit has been running for a period of time under cooling or dry mode, the unit will report this fault, in which case the compressor and outdoor fan motor will be stopped. The unit will not run until evaporator temperature is higher than the protective temp. value and the compressor is stopped for 3min.
3
Low pressure
Low pressure
If it is detected within 30s successively that the low-pressure switch is cut off under ON or standby state, the unit will report low pressure protection. If the fault occurs successively 3 times within 30min, the unit cannot be recovered automatically.
Refrigerant
lacking protection
If the unit reports system refrigerant lacking within 10min after turning on the unit, the unit will stop operation. If the fault occurs successively 3 times, the unit cannot be recovered automatically.
Refrigerant
recycling mode
If enter refrigerant recycling mode through special operation, E3 will be displayed. After exiting refrigerant recycling mode, the code will disappear.
4
Compressor high
ischarge
temperature
Compressor
discharge
temperature is
If outdoor unit detects that the discharge temperature is higher than protective temp. value, the unit will report high discharge temperature protection. If the protection occurs over 6 times, the unit cannot be recovered automatically. Switch off the unit or re-energize the unit after cutting off power to eliminate this protection.
5
Communication
malfunction
Communication
between indoor
and outdoor main
If the outdoor unit does not receive data from indoor unit, communication malfunction will be reported. If there is communication abnormity between display board and indoor unit, communication malfunction will be reported too.
6
Malfunction of
indoor fan motor
Indoor fan motor
If the indoor unit does not receive signal from indoor fan motor for 30s successively when the fan motor is operating, indoor fan motor malfunction will be reported. In this case, the unit can automatically resume operation after stopping. If the malfunction occurs 6 times within one hour, the unit cannot be recovered automatically. Switch off the unit or re
energize the unit after
cutting off power to eliminate this malfunction.
Service Manual
10
MAINTENANCE AND TROUBLESHOOTING
ERROR CODES TABLE
10.1 Main Control Malfunction
Table 4-1-1 Fault Display on Indoor Wired Zone Controller
E1
E2
protection
gh
switch
sensor
Control description
-
-
E3
E4
E6
E8
protection
d
protection
switch
high
board
-
41
Page 51
No.
Error code
Malfunction
name
Origin of
malfunction signal
7
E9
Full water
protection
Water level switch
If cut-off of water level switch is detected for 8s successively once energized, the system will enter full water protection. In this case, switch off the unit and then switch it on to eliminate this malfunction.
8
Malfunction of
indoor ambient
temperature
sensor at air
return port
Indoor ambient
temperature
If the indoor ambient temperature sensor is detected of open circuit or short circuit for 5s successively, indoor ambient temperature sensor malfunction will be reported. The unit can automatically resume operation after the malfunction disappears. If indoor ambient temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
9
Malfunction of
evaporator
temperature
Evaporator
temperature
If the indoor evaporator temperature sensor is detected of open circuit or short circuit for 5s successively, evaporator temperature sensor malfunction will be reported. The unit can automatically resume operation after the malfunction disappears. If evaporator temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
0
Malfunction of
condenser
temperature
Condenser
temperature
If the outdoor condenser temperature sensor is detected of open circuit or short circuit for 5s successively, condenser temperature sensor malfunction will be reported. The unit
can automatically resume operation after the malfunction disappears. If condenser temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
1
Malfunction of
outdoor ambient
temperature
Outdoor ambient
temperature
If the outdoor ambient temperature sensor is detected of open circuit or short circuit for 5s successively, outdoor ambient temperature sensor malfunction will be reported. The unit can automatically resume operation after the malfunction disappears. If outdoor ambient temperature sensor malfunction occurs in fan mode, only the error code is displayed and the indoor unit can work normally.
2
Malfunction of
discharge
temperature
Discharge
temperature
If the outdoor discharge temperature sensor is detected of open circuit or short circuit for 5s successively after the compressor has been operating for 3min, outdoor discharge temperature sensor malfunction will be reported. The unit can automatica lly resume operation after the malfunction disappears.
3
Malfunction wired
controller
temperature
sensor
Wired controller
If the wired controller detects open circuit or short circuit of its temperature sensor for 5s successively, wired controller temperature sensor malfunction will be reported.
4
Malfunction of
outdoor drive
memory chip
Outdoor drive
If the memory chip of outdoor drive board is broken, the unit cannot be started. The unit cannot be recovered automatically. If the malfunction cannot be eliminated after switching off the unit and then energizing the unit for several times, please replace the outdoor drive board.
15
Compressor
overload
protection
Compressor
overload switch
If it is detected within 3s successively that the overload switch is cut off under ON or standby state, the unit will report overload protection. If the fault occurs successively 3 times, the unit cannot be recovered automatically. Switch off the unit or re
energize the
unit after cutting off power to eliminate this protection.
F0
F1
sensor
Service Manual
Control description
sensor
sensor
1
1
1
1
1
F2
F3
F4
F5
ee
sensor
sensor
sensor
sensor
sensor
sensor
board
H3
-
42
Page 52
No.
Error code
Malfunction
name
Origin of
malfunction signal
16
Overload
protection
Evaporator
perature,
condenser
temperature
If outdoor unit detects that the tube temperature is higher than protective temp. value, the unit will report overload protection. The unit will not restart operation until tube temperature is lower than the protective temp. value and the compressor is stopped for 3min. If the protection occurs over 6 times, the unit cannot be recovered automatically. Switch off the unit or re
energize the unit
after cutting off power to eliminate this protection.
17
Malfunction of
outdoor fan motor
Outdoor fan motor
If the outdoor unit does not receive signal from outdoor fan motor for 30s successively when the fan motor is operating, outdoor fan motor malfunction will be
reported. In this case, the unit can automatically resume operation after stopping. If the malfunction occurs 6 times within one hour, the unit cannot be recovered automatically. Switch off the unit or re
energize the unit after
cutting off power to eliminate this malfunction.
18
Direction
changing
malfunction of
way valve
way valve
After the compressor starts operation in heating mode, if the outdoor unit detects the difference between evaporator temperature and indoor ambient temperature is lower than the protective value for 10min successively, direction changing malfunction of 4
way valve will be reported and the outdoor unit will stop operation. The unit can automatically resume operation in the first two malfunctions. If the malfunction occurs 3 times, the unit cannot be recovered automatically. Switch off the unit or re-energize the unit after cutting off power to eliminate this malfunction.
19
Communication
malfunction
between main
control and drive
Communication
between main
control board and
drive board
If the outdoor main control board does not receive data from drive board, communication malfunction between main control and drive will be reported. This malfunction can be eliminated automatically.
20
Malfunction of
outdoor main
control memory
Outdoor main
control board
If the memory chip of outdoor main control board is broken, the unit cannot be started. The unit cannot be recovered automatically. If the malfunction cannot be eliminated after switching off the unit and then
energizing the unit for several
times, please replace the outdoor main control board.
Service Manual
Control description
H4
H6
U7
P6
tem
-
-
4-
4-
-
EE
chip
43
Page 53
10.2 Description of Drive Malfunction
Indoor Unit Display
Outdoor unit display of dual 8 numeral
tube
IPM or PFC over-temperature protection
IPM or PFC temperature sensor error
ection
Drive
control communication error
)
Main board dual 8 numeral tube Display Codes for Outdoor Unit of 18k~48k
Malfunction Item
Service Manual
DC busbar over-voltage protection
Current sense circuit error Pc Pc
Compressor current protection P5 P5
DC busbar under-voltage prot
Compressor startup failure Lc Lc
Drive module reset P0 P0
Compressor motor desynchronizing
Phase loss Ld Ld
-to-main-
IPM protection H5 H5
Compressor overload protection H3 H3
AC current protection (input side)
Charging circuit error PU PU
PFC protection HC (48k only
DC fan error H6 H6
PH PH
P8 P8
P7 P7
PL PL
H7 H7
P6 P6
PA PA
HC (48k only)
Input AC voltage abnormality PP PP
Driving board memory chip error ee ee
44
Page 54
Service Manual
11 FLOW CHART FOR TROUBLESHOOTING
11.1 Troubleshooting Flow Chart of Main Control Malfunction
E1 High Pressure Protection
45
Page 55
Service Manual
E2 Freeze Protection
Freeze protection is normal protection b
ut not abnormal malfunction. If freeze protection
occurs frequently during operation, please check if the indoor filter is dirty or if the indoor air outlet is
abnormal. The user is required to clean the filter, check the air outlet and air return pipe periodically to
ensure smooth air return and air outlet.
E3 stands for three statuses:
(1) Low pressure protection
(2) Refrigerant lacking protection
(3) Refrigerant recycling mode
1) If enter refrigerant recycling mode through special operation, the displayed E3 is not an error
code. It will be eliminated when exiting refrigerant recycling mode.
If you do not want to have refrigerant lacking protection, you can
2)
enter the debugging mode
through wired zone controller and then cancel the refrigerant lacking protection mode.
46
Page 56
Service Manual
E4 Discharge Protection
E6 Communication Malfunction
Communication
communication wire between
indoor unit and outdoor unit is
connected well
Check if there is
open circuit in the communication
wire between indoor unit and
outdoor unit is energized
malfunction
Check if the
Yes
outdoor unit
No
Check if the
No
Yes
No
Reconnect the
communication
wire
Replace the
communication
wire
Energize the
outdoor unit
Yes
Replace the mainboard
47
Page 57
E9 Full Water Protection
Service Manual
E9 protection
F0 Malfunction of
If the unit is
installed with
water pump
Yes
Check if the water pump
works normally
Yes
Replace the full water switch
or make sure the float of full
water switch works normally
No
mainboard according to the circuit
No
Indoor Ambient Temperature Sensor
Malfunction of
indoor ambient
temperature
sensor
Short circuit the full water
protection interface on indoor
diagram
Replace the water pump
Check if the
indoor ambient temperature
sensor on mainboard is inserted
on the needle
stand correctly
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the indoor
mainboard
48
No
No
Correctly insert the
temperature sensor
on the needle stand
Replace the
temperature sensor
Page 58
Service Manual
F1 Malfunction of Evaporator Temperature Sensor
Malfunction of
evaporator
temperature
sensor
Check if the evaporator
temperature sensor on
mainboard is inserted on the
needle stand correctly
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the
indoor
mainboard
F2 Malfunction of Condenser Temperature Sensor
Malfunction of
condenser
temperature
sensor
No
No
Correctly insert the
temperature
sensor on the
needle stand
Replace the temperature
sensor
Check if the condenser
temperature sensor on
mainboard is inserted on the
needle stand correctly
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the
outdoor
mainboard
49
No
No
Correctly insert the
temperature sensor
on the needle stand
Replace the
temperature sensor
Page 59
F3 Malfunction of Outdoor Ambient Temperature Sensor
Malfunction of
outdoor ambient
temperature
sensor
Check
if the outdoor ambient
temperature sensor on mainboard
is inserted on the needle stand
correctly
Yes
No
Service Manual
Correctly insert the
temperature sensor on
the needle stand
Disconnect
the temperature sensor and
measure if its resistance is
F4 Malfunction of Discharge Temperature Sensor
normal
Yes
Replace the
outdoor
mainboard
Malfunction of
discharge
temperature
sensor
Check if the
discharge temperature sensor on
mainboard is inserted on the
needle stand correctly
No
No
Replace the
temperature sensor
Correctly insert the temperature sensor on the needle stand
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the
outdoor
mainboard
50
No
Replace the
temperature sensor
Page 60
Service Manual
F5 Malfunction of Wired Controller Temperature Sensor
H6 Malfunction of Outdoor Fan Motor
Malfunction of
wired controller
temperature
sensor
Replace the
wired controller
51
Page 61
E8 Malfunction of Indoor Fan Motor
Malfunction of
indoor fan motor
Service Manual
Check if the
control wire of indoor fan motor is
connected on the outdoor
mainboard correctly
Yes
Replace
the indoor fan motor and then
restart the unit to see if there still
is malfunction of indoor
fan motor
Yes
Replace the
indoor
mainboard
No
No
Correctly connect the
control wire of fan motor
on the mainboard
Operate the unit with
the new motor
11.2 Troubleshooting Flow Chart of Drive Malfunction
Note: For Outdoor Unit Drive
P0 Drive module reset
(Inverter) by Single-phase Motor
P7 IPM or PFC temperature sensor error
PA AC current protection (input side)
PC Current sensor circuit error
HC PFC protection (48k only)
P0ǃP7 ˆPA ˆHC or
PC is displayed on
wired zone controller
P0 ˆP7 ˆPA ˆHc or
PC is displayedin the
mainboard 88
Indicating Light
Replace the
mainboard
Works Normally
52
Page 62
Service Manual
P8 IPM or PFC over-temperature protection
P8 is displayed on
wired zone
controller
P8 is displayed in the
mainboard 88
Indicating light
Yes
Replace the
mainboard
PH DC busbar over-volt
age protection
PL DC busbar under-voltage protection
Is the
IPM or PFC module
of mainboard
tightened˛
Works normally
No
Tighten the IPM
or PFC module
53
Page 63
P6 Drive-to-main-control communication error
Lc Compressor Startup Failure
Service Manual
Lc is displayed on
the wired controller
Lc is displayed in
the mainboard 88
indicating light
Yes
P5 Compressor curr
ent protection
H7 Compressor motor desynchronizing
H5 IPM protection
Ld Phase loss
P5, H7, H5 or Ld is displayed
on wired zone controller
P5, H7, H5 or Ld is displayed
in the mainboard 88
indicating light
Replace the
mainboard. Does it
work normally?
No
Replace the compressor
Works normally
Is the compressor
phase sequence right?
Yes
Is the compressor wire
terminals tightened˛
No
Replace the mainboard.
Does it work normally˛
No
Replace the compressor Work normally
No
Yes
adjust the
compressor
phase sequence
Tighten the
compressor wire
terminals
Yes
54
Page 64
Service Manual
PU Charging circuit error
Yes
PU is displayed on
wired zone
controller
PU is displayed in
the mainboard 88
indicating light
Is the PFC wire
tightened or is the
sequence right?
No
Replace the
mainboard
ee driving board chip error
ee is displayed
on the wired
controller
Replace the
mainboard
Yes
Is the
jumper
loose˛
No
Works normally
Yes
Tighten the
Tighten the PFC
wire or adjust the
sequence
jumper
Works Normally
55
Page 65
H6 DC fan error
Service Manual
56
Page 66
NO.
SILK-SCREEN
1
2
3
Power supply interface to the drive
4
DC_MOTOR2
5
DC_MOTOR1
6
Power supply interface to the drive
Service Manual
11.3 Interface
DHR18CSB21S / DHR24CSB21S / DHR30CSB21S / DHR36CSB21S / DHR42CSB21S /
DHR48CSB21S Main Control Board
INTERFACE
AC-L Live wire input Live wire input
AC-N Neutral wire input Neutral wire input
PWR 1
Control power output[1- DC bus voltage, 3- GND]
DC fan motor2 1-pin: Power supply of fan motor 3-pin: Fan GND 4-pin: +15V 5-pin: Signal control 6-pin: NC
DC fan motor1 1-pin: Power supply of fan motor 3-pin: Fan GND 4-pin: +15V 5-pin: Signal control 6-pin: Signal Feedback
INTERFACE INSTRUCTIONS
1-pin: DC bus voltage 3-pin: DC bus GND
Interface of DC fan motor 1-pin: DC bus voltage 2-pin: Suspended 3-pin: DC bus GND 4-pin: +15V 5-pin: Control signal input 6-pin: Not connected
Interface of DC fan motor 1-pin: DC bus voltage 2-pin: Suspended 3-pin: DC bus GND 4-pin: +15V 5-pin: Control signal input 6-pin: DC fan motor feedback
CN3
Control power output[1-GND 2-18Vˆ3-15V]
57
ǃ
1-pin: GND
2-pin: +18V
3-pin: +15V
Page 67
7
COMM1
TX
Communication needle stand of
8
Communication needle stand with
9
pin plus
Communication interface
10 H-PRESS
High pressure switch for fan speed
Pressure protection switch for fan
11
Interface of high pressure
12
Interface of low pressure
13
COMP
Interface of compressor overload
14
T-SENSOR2
1&2 pin: Case temperature sensor 3&4 pin: Ambient temperature
5&6 pin: Discharge temperature
15
nterface of electronic expansion
16
17
18
Communication line [1-3.3Vǃ2­3-RXǃ4-GND]
main control drive
1-pin: +3.3V
ǃ
2-pin: TXD
3-pin: RXD
4-pin: GND
Service Manual
OVC-
CN2
CN1
HPP
LPP
Communication line with1-pin GND, 2-pin B and 3-pinA˅
Communication line with 1­12V, 2-pin B, 3-pin A and 4-pin GND
adjustment
High pressure switch for system protection (obligate˅
Low pressure switch for system protection (obligate˅
Compressor overload protection
1&2 pin: Tube sensor 3&4 pin: Ambient temperature 5&6 pin: Air discharge
indoor unit
1-pin: GND
2-pin: B
3-pin: A
(reserved):
1-pin: +12V
2-pin: B
3-pin: A
4-pin: GND
speed adjustment
protection
protection
protection
sensor
sensor
Electronic expansion valve line
FA
HEAT Compressor electrical heater Compressor electric heating belt
VA-1 Chassis electrical heater Chassis electric heating belt
4V 4-way valve 4-way valve
1 to 4-pin: Drive impulse output;5-pin: +12V;
58
I
valve:
1 to 4-pin: Drive impulse output;
5-pin: +12V;
Page 68
No.
No.
Printing
1
PFC induction wire (blue)
2
3
)
4
5
COMM/COMM1
Communication interface
6
JTAG1
7
8
DC-BUS1
Bus electric discharging interface (for
testing)
9
PFC induction wire (yellow)
10
11
12 G-OUT
13
14
15
Service Manual
DHR18CSB21S / DHR24CSB21S / DHR30CSB21S / DHR36CSB21S / DHR42CSB21S
(1) Drive Board
8910131415 1112
7
6
2 3 41 5
Printing
Interface
L2_2
N Neutral wire input (white
PWR Control power input
L2-1
P-OUT (Reserved)
W Compressor Phase W
U Compressor Phase U
Interface
L1_1
AC-L
PFC induction wire (brown)
Live wire input (red)
(Reserved)
L1-2
PFC induction wire (white)
(Reserved)
V Compressor Phase V
59
Page 69
(2)
No.
Printing
No.
Printing
1 N-OUT1
Neutral wire output 1 (white) (only for
18k)
2 N-OUT
Neutral wire output
(white)
3 L-OUT
4 E1
5
6
Live wire input (red)
7
Filtering Board
Service Manual
1
2
3
Interface
Live wire output (red)
E2 (Reserved)
AC-N
Neutral wire input (white)
AC-L
Interface
Grounding wire
7
6
5
4
60
Page 70
No.
Printing
No.
Printing
1
L
2 L1-1
3 N
4 L2-2
5
1
PFC induction wire (yellow)
6 L1-2
7
PWR
8
JTAG1
9
COMM
10
DC-BUS1
DC bus electric discharging needle
stand (for testing)
11
DC-BUS
DC bus interface (connect to
filtering board)
12 U
13 V
14 W
Service Manual
DHR48CSB21S
(1) Drive Board:
1
2
3
4
5
6
7
121314
11
AC-
L2-
Interface
Live wire input (red)
Neutral wire input (white)
Control power input
Communication interface
Compressor Phase V
10
8
9
Interface
PFC induction wire (brown)
PFC induction wire (blue)
PFC induction wire (white)
(Reserved)
Compressor Phase U
Compressor Phase W
61
Page 71
(2) Filtering Board:
No.
Printing
No.
Printing
1 N-OUT
2
L-OUT
3
BUS
DC bus interface (connect to drive board)
4 AC-L
5
6
E1
7
1
Service Manual
67
5
2
Interface
Neutral wire output (white)
DC-
N Neutral wire input (white)
E Grounding wire (screw hole)
4
3
Interface
Live wire output (red)
Live wire input (red)
(Reserved)
62
Page 72
Service Manual
11.4 IPM, PFC Testing Method
11.4.1 Method of Testing IPM Module
(1) Preparation before test: Prepare a universal meter and turn to its diode option
the wires U, V, W of the compressor after it is powered off for one minute.
(2) Testing Steps
Step 1: Put the black probe on the place of P and the red one on the wiring terminal U, V, W
respectively as shown in the following figure to measure the volta
Step 2: Put the red probe on the place of N and the black one on the wiring terminal U, V, W respectiv
as shown in the following figure to measure the voltage between NU, NV and NW.
(3) If the measured voltages between UP, VP, WP, NU, NV, NV are all among 0.3V-0.7V, then it
indicates the IPM module is normal; If any measured valve is 0, it indicates the IPM is damaged.
11.4.2
L2-1respectively as shown in the following figure to measure the voltage between L1-2P and.L2-1 P.
L2-1 respectively as shown in the following figure to measure the voltage betw
Method of Testing PFC Module Short Circuit (only for DHR48CSB21S):
(1) Preparation before test: prepare a universal meter and turn to its diode option, and then remove
the wires L1-2, L2-1 after it is powered off for one minute.
Testing Steps
(2)
Step 1: Put the black probe on the place P and the red one on the wiring terminal L1-2,
Step 2: Put the red probe on the place N and the black on
ge between UP, VP and WP.
e on the wiring terminal L1-2,
een N L1-2 and NL2-1.
, and then remove
ely
(3) If the measured voltages between L1-2P ,L2-1 P, N L1-2 , NL2-1 are all among 0.3V-0.7V, then it
indicates the PFC module is normal; If any measured valve is 0, it indicates the PFC is damaged.
DHR18CSB21S / DHR24CSB21S /
DHR30CSB21S / DHR36CSB21S / DHR42CSB21S
63
Page 73
DHR48CSB21S
Service Manual
Service Manual
64
Page 74
Service Manual
Step
Illustration
Handling Instruction
1. Remove external casing
1. Remove the top cover and handle;
2. Remove the grille, outer case and right side plate.
2. Remove motor
1. Remove the blade nut and then remove the blade;
2. Remove the motor from motor support.
3. Remove compressor
1.
2. compressor;
3.
4.
12 DISASSEMBLY AND ASSEMBLY PROCEDURES FOR MAIN PARTS
12.1 Outdoor Unit
18k:
Important: Before disassembly and assembly, make sure that the power to the system has been disconnected and verified as voltage free.
Reclaim the refrigerant from the entire system Unsolder the 4-way valve piping assy from
Remove the compressor mounting bolts; Carefully remove the compressor from chassis.
65
Page 75
Service Manual
4. Assemble unit
Step
Illustration
Handling Instruction
1. Remove external casing
1. Remove the top cover and handle;
2. Remove the grille, outer case, front side plate and right side plate.
2. Remove motor
1. Remove the blade nut and then remove the blade;
2. Remove the motor from motor support.
3. Remove compressor
Assemble the unit in the reverse order of disassembly.
24k/30k:
Important: Before disassembly and assembly, make sure that the power to the system has been disconnected and verified as voltage free.
66
1. Reclaim the refrigerant from the entire system.
2.Unsolder the 4-way valve piping assy from compressor;
3. Remove the compressor mounting bolts;
4. Carefully remove
the compressor from
chassis.
Page 76
Service Manual
4. Assemble unit
Step
Illustration
Handling Instruction
1. Remove external casing
1. Remove the top cover and handle;
2. Remove the grille, outer case and right side plate.
2. Remove motor
1. Remove the blade nut and then remove the blade;
2. Remove the motor from motor support.
3. Remove gas liquid separator
2.
3. Remove the gas liquid separator.
Assemble the unit in the reverse order of disassembly.
36k:
Important: Before disassembly and assembly, make sure that the power to the system has been disconnected and verified as voltage free.
1. Reclaimthe refrigerant from the entire system. Unsolder the 4-way valve piping assy from gas
liquid separator;
67
Page 77
Service Manual
4. Remove compressor compressor;
5. Assemble unit
Step
Illustration
Handling Instruction
1. Remove external casing
1. Remove the top cover and handle;
2. Remove the grille, outer case and right side plate.
2. Remove motor
1.
2.
1. Unsolder the 4-way valve piping assy from
2. Remove the compressor mounting bolts;
3. Carefully remove the compressor from chassis.
Assemble the unit in the reverse order of disassembly.
42k/48k:
Important: Before disassembly and assembly, make sure that the power to the system has been disconnected and verified as voltage free.
Remove the blade nuts and then remove the
blades;
Remove the motors from motor supports.
68
Page 78
Service Manual
3. Remove gas liquid separator.
2.
3. Remove the gas liquid separator.
4. Remove compressor
1.
5. Assemble unit
Removal and Assembly of Fan Motor
Step
Illustration
Handling Instruction
1. Unplug the motor cables
2. Remove the filter sub-assembly and air inlet cover board
Remove the filter sub-assembly from the air inlet frame and use screwdriver to remove the air inlet cover board.
1. Reclaim the refrigerant from the entire system. Unsolder the 4-way valve piping assy from gas
liquid separator;
Unsolder the 4-way valve piping assy from
compressor;
Remove the compressor mounting bolts;
2.
Carefully remove the compressor from chassis.
3.
Assemble the unit in the reverse order of disassembly.
12.2 Indoor Unit
12.2.1 Duct type
Important: Before removing the fan, make sure power to the system is disconnected..
Use screwdriver to remove the electric box cover and unplug the motor cables in electric box.
69
Page 79
Service Manual
3. Remove the screws on fan sub-assembly.
Remove the screws on fan sub-assembly.
4.
5. Loosen the fan and motor.
6. Replace the motor
7.
Disassembly of filter screen for return air
Step
Illustration
Handling Instruction
Disassembly of filter screen for return air
Removing the fan cage enclosure
Rotate the fan cage housing toward
supply opening and remove.
Use a hex wrench to loosen the screws
holding the fan cage to the motor shaft.
Remove outer housing holding motor in
place.
Remove the motor from the support
bracket. Then remove the fan cages from
the motor shafts. Remove the motor from the air inlet and replace with new motor. If
the new motor comes with a mounting
bracket, attach the bracket to the housing
after sliding on the fan cages. Be sure to
tighten the cages onto the motor shafts.
Reassembly of the unit
Important: Make sure that the power supply to the system is turned off before disassembling and protect all the
parts during disassembly. Do not put filter screen near a high temperature heat source.
Reassemble the unit in the reverse order
of disassembly and test operation.
Gently push down on the filters in the slots
and pull/slide out slowly to prevent damage.
70
Page 80
Service Manual
Disassembly of electrical parts box cover panel and electrical parts box
Step
Illustration
Handling Instruction
1. Disassembly of electric box cover
2. Disassembly of electric parts box
Step
Illustration
Handling Instruction
1.Disassembly of cover plate
2.
Important: Make sure that power supply is turned off before disassembling and protect all parts during disassembly,
especially electrical components. Keep all moisture away from the electrical box area and protect the board and components.
The cover can be removed once the screw(s)
are removed.
By removing the screws inside the box, the
electrical box can be completely removed. This
should not be necessary unless the box is
damaged.
Removal of condensate pan
Important: Make sure that the power supply is turned off before disassembling and protect all the parts during disassembly.
To access the condensate drain pan the bottom
plate will need to be removed first. This is done
by removing the cover plate screws.
The condensate pan will drop down once the
Removal of condensate pan
screws holding the pan to the chassis are
removed.
71
Page 81
Service Manual
Step
Illustration
Handling Instruction
Disassemble the fixing screws on the fan components. (As is shown in graph, circle represents 6 screws.) Disassemble the fastening screws on the fan and motor. Remove the fan. (As is shown in the graph, box represents screws.)
Step
Illustration
Handling Instruction
1.
2.
3. Removal of evaporator
Removal of fan and motor
Important: Make sure that the power supply is turned off before disassembling and protect all the parts during disassembly.
Removal of fan motor
Removal of evaporator Important: Make sure that the power supply is off and protect the copper tube and aluminum fin. Use caution when
removing coil to prevent damage.
Removal of evaporator
screws
Seal plate removal
Remove the cover plate and the screws on
each end of the coil.
Remove the screws holding the seal plate for
the tubing assemblies. At this point the flare
connections may be disconnected provided
that system refrigerant has been reclaimed or
charge has been pumped down into outdoor
unit.
Be aware that if coil is being replaced due to a
leak then refrigerant should be reclaimed as
charge in the system is unknown at this point.
72
Page 82
12.2.2 Cassette-type Unit
Step
Illustration
Handling Instruction
1. Loosen the screws
2.
3.
4.
Replacement of Fan Motor
holding condensate pan
Service Manual
Use screwdriver to loosen the screws holding the drain pan in place.
Remove the condensate
pan
Loosen the bolts holding
the fan blades in place
Remove the fan blade The fan blade can now be removed.
Carefully remove the condensate pan.
Use a wrench or socket to carefully
remove the fan blade bolts
73
Page 83
Service Manual
5. Loosen the screws
6. Remove the motor and replace it
Remove the motor and replace it.
7. Tighten the screws
8.
9.
holding the motor in place
Use screwdriver to loosen the screws holding the motor.
holding the motor
Mount the fan blade and
tighten the bolts
Use screwdriver to carefully tighten the screws holding the motor.
Mount the fan blade and use a wrench or
socket to carefully tighten the bolts
holding the fan blade in place. Do not
overtighten as damage may occur.
Reinstall the condensate
pan and tighten the screws
Use a screwdriver to carefully tighten the screws holding the condensate pan
in place. Take care to not overtighten as
damage to pan will occur.
74
Page 84
Removal and Installation of Condensate Pump
Step
Illustration
Handling Instruction
1. Loosen the screws
2.
3. Pull out the water outlet
4. Take out the pump and replace it
Take out the pump and replace it
holding the condensate pan
Service Manual
Use a screwdriver to loosen the screws holding the condensate pan in
place.
Remove the condensate
pan
pipe and loosen the screws holding the condensate pump.
Remove the condensate pump and replace it.
Pull out the water outlet pipe and use screwdriver to loosen the screws holding the condensate pump.
75
Page 85
Service Manual
5.
6.
Step
Illustration
Handling Instruction
1. and the 2 screws of the clasps.
2.
Connect the condensate pipe and tighten the screws holding the condensate pump.
Mount the condensate pan and tighten the screws
Connect the condensate pipe and use a screwdriver to tighten the screws holding
the condensate pump in place.
Use a screwdriver to carefully tighten
the screws holding the condensate pan in
place. Damage may occur if over
tightened.
12.2.3 Floor Ceiling Type
Model: DHR30NCB21S / DHR36NCB21S / DHR42NCB21S
Removal of main outer cover
Important: Make sure that the power supply is turned off before disassembling. Use care when disassembling and
do not put the cover or filters near a high temperature heat source.
Unscrew the 2 clasps of the upper grille Disassembly of sub-assy of front grille
Disassembly of right and left panels
Important: Make sure the power supply is off before disassembling and protect all the parts during disassembly.
Do not scratch the outer parts.
Open the grille, disassemble the two
bottom clasps to remove the grille.
76
Page 86
Service Manual
Disassembly of right and left finishing plates
Disassembly of panel parts
Step
Illustration
Handling Instruction
Disassembly of panel parts
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
Step Illustration Handling Instruction
Disassemble the screws as shown with a screwdriver and then push upward to remove the right and left panels. Screw
locations are shown in the drawing.
Important: Make sure the power supply to the system is cut off before disassembling and protect all the parts during disassembly. Do not scratch the outer parts.
Remove the three screws on the cover to remove the cover.
Disassembly of electrical box
Important: Make sure that the power supply is turned off before disassembling and protect all the parts during disassembly, especially the components inside the box as these are prone to moisture and impact damage.
Removal of electrical box cover
Disassembly of air deflecting louvers
Important: Make sure the power supply is cut off before disassembling and protect all the parts during disassembly, especially the linkages of the air deflecting louvers.
Disassembly of air deflecting louvers
Remove the three screws as shown in the
picture, then remove the cover.
Remove the air deflecting louvers from the air deflecting louver support assembly, and then remove both ends from the
stepper motor linkage.
Removal of condensate pan
Important: Make sure the power supply is turned off before disassembling and protect all the parts during disassembly.
Removal of the
condensate pan
Once the outer cover has been removed, then the condensate pan can be accessed and removed.
77
Page 87
Service Manual
Disassembly of evaporator components
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
1. Disassembly of front
2.
Important: Make sure that the power supply is turned off. Work deliberately to avoid damaging the copper tube
assemblies and the fins of the coil.
Remove the six screws of the coil, three
Removal of evaporator
coil
Removal of discharge air guide
Important: Make sure that the power supply is off before disassembling and protect all the parts during disassembly.
screws of the water channel and the two screws of the condensate deflector to remove the evaporator.
Removal of the
discharge air guide
Disassembly of fan and motor components
Important: Make sure that the power supply is turned off before disassembling and protect all the parts
during disassembly, especially the fastening screws for the fans.
and back fan cage housings
Remove the display board, mounting support and mounting plate of the motor in this order.
Press the buckle at the joints of front and back housings with hands and pull upward to remove the front housing. Then remove the screws on the back housing. Lift the buckle of the back housing with hands and remove it.
Removal of fan assemblies
Unscrew the two screws of the center coupling, take out the main shaft and blower wheels, then loosen the set screws of the blower wheels to remove them from
the main shaft.
78
Page 88
Service Manual
3.
Unscrew the 3 screws and 2 nuts of support to remove the mounting support.
4.
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
1.
2.
Step
Illustration
Handling Instruction
Removal of the bearing mounting plates
Loosen the two screws of the motor
Removal of motor
Removal of right and left fixing plates
,PSRUWDQW0DNHVXUHWKDWWKHSRZHUVXSSO\LVWXUQHGRIIEHIRUHGLVDVVHPEOLQJDQGSURWHFWDOOWKHSDUWVGXULQJ GLVDVVHPEO\
mounting bracket andremove. The motor
can then be removed.
Removal of right and left mounting plates
Disassemble the bolts on right and left mounting plates with tools. (As is shown by the arrows in the drawing.)
Model: DHR18NCB21S / DHR24NCB21S / DHR48NCB21S
Removal of the main grille cover
,PSRUWDQW0DNHVXUHWKDWWKHSRZHUVXSSO\LVWXUQHG RIIEHIRUHGLVDVVHPEOLQJDQGSURWHFWDOOWKHSDUWVGXULQJ GLVDVVHPEO\'RQRWSXWILOWHUDVVHPEOLHVQHDUDKLJKWHPSHUDWXUHKHDWVRXUFH
Unscrew the 2 clasps of the upper grille and
Removal of grille sections
Removal of the left and right panels
Important: Make sure the power supply is turned off before disassembling and protect all the parts during
disassembly. Do not scratch the outer panels.
the two screws of the clasps.
Open the grille, disassemble the two
bottom clasps to remove the grille.
Removal of right and left finishing panels
Remove the screws as shown in the drawing
and then push upward to remove the right and left panels.
79
Page 89
Service Manual
Disassembly of panel parts
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
1.
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
Important: Make sure the power supply is turned off before disassembling and protect all the parts during
disassembly. Do not scratch the panels.
Panel removal Remove the three screws on the cover to
remove the cover.
Removal of the electrical box
Important: Make sure that the power supply is turned off before disassembling and protect all the parts
during disassembly, especially the components inside the box to prevent moisture and impact damage.
Removal of electrical box cover
Removal of the discharge air louvers
Important: Make sure the power supply is turned off before disassembling and protect all the parts during
disassembly, especially linkages and connections of the louvers.
Removal of the
discharge air louvers
Removal of the condensate pan
Important: Make sure the power supply is turned off before disassembling and protect all the parts during disassembly.
Remove three screws as shown by the arrows in the drawing on the left and remove the electrical box cover.
Remove the discharge air louvers from the support assembly, and then remove both ends from the stepper motor linkages.
Condensate pan
removal
Once the outer cover has been removed, then the condensate pan can be accessed and removed.
80
Page 90
Service Manual
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
Step
Illustration
Handling Instruction
1.
Evaporator coil removal
Important: Make sure that the power supply is cut off and protect the copper tube and aluminum fin if coil is to be re-used.
Remove the six screws of the evaporator
Removing the coil
Removal of the discharge air guide
Important: Make sure that the power supply is turned off before disassembling and protect all the parts during disassembly.
coil, three screws of the water channel and the two screws of the condensate reflector to remove the evaporator coil.
Removal of the
discharge air guide
Removal of fan and motor components
Important: Make sure that the power supply is turned off before disassembling and protect all the parts during disassembly, especially the fastening screws for fans.
Disassembly of front and back fan cage
housings
Removal of fan and motor components
Remove the display board, mounting support and mounting plate of the motor in this order.
Press the buckle at the joints of front and back of the fan cage housings by hand and pull upward to remove the front housing. Then remove the screws on the back housing. Lift the buckle of back housing with hands and remove it.
Important: Make sure that the power supply is turned off before disassembling and protect all the parts during disassembly, especially the fastening screws for fans.
Unscrew the two screws of the center coupling,
Removal of fans
81
take out the main shaft and blower wheels, then
loosen the screws of the blower wheels to
remove them from the main shaft.
Page 91
Service Manual
2.
3.
Step
Illustration
Handling Instruction
Removing the bearing mounting plates
Removal of motor
Removal of right and left mounting plates
Important: Make sure that the power supply is turned off before disassembling and protect all the parts during disassembly.
Removal of right and left mounting plates
Remove the three screws and two nuts to
remove the mounting plate.
Loosen the two screws of the motor attaching clamp, remove the motor attaching clamp and motor attaching clamp subassembly to remove the motor.
Disassemble the bolts on right and left mounting plates with tools. (As is shown by the arrows in the drawing.)
82
Page 92
83
Page 93
Product improvement, specifications and appearance in this manual are subject to change without prior notice.
© Johnson Controls, Inc. USA
LIT - 12012189
Loading...