Johnson Controls CTD Series Installation Guide

CTD Series Current Transducer Devices
34- 10345-69, Rev. D
Installation Instructions
CTD-C1G00-1, CTD-C2G00-1, CTD-C3H00-1
Refer to the QuickLIT website for the most up-to-date version of this document.
Part No. 24-10345-69, Rev. D
Issued March 2016

Applications

The Current Transducer Device (CTD) Series of anal og output current transducers are nonintrusive devices designed to detect current flowing through a cable or wire. These units are a cost-effective solution for monitoring load or proof of operation. The current transducers are ideal for monitoring current loads on pumps, driving fans and blowers, and sensing the status of heating coils and lighting. CTD devices used for load trending over time are effective sensors for predictive maintenance programs.
Optional command relays provide externally controlled auxiliary contacts. The relays offer a solution for switching loads that require higher power levels than the rating of the current switch contacts.
These units are available with standard 4 to 20 mA current loop, 0 to 5 VDC, and 0 to 10 VDC analog output. Completely self-powered, the CTD-C2G00-1 and CTD-3H00-1 units draw their power from the current induced from the monitored cable or line. The CTD-C1G00-1 device requires a 24 VDC power supply.
IMPORTANT: The CTD Series Current Transducer Device is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the transducer could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the transducer.
IMPORTANT : Le CTD Series Current Transducer Device est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du transducer risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du transducer.
IMPORTANT: Be sure to install the CTD Series Current Transducer Device only on the input side of a variable speed drive.
CTD Series Current Transducer Devices Installation Instructions 1

Installation

!
!
Figure 1: CTD Dimensions, in. (mm)
1-1/16 (27)
Fig:sc_sde
2-9/16 (65)
2-23/32 (69)
Fig:splt_cre_frnt
Figure 2: Model CTD-C1G00-1
Contactor
Motor
Fan or Pump
WARNING: Risk of Electric Shock.
Disconnect the power supply before making electrical connections. Cont act with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
AVERTISSEMENT : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout branchement électrique. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.
WARNING: Risk of Personal Injury.
Do not touch the relay while power is applied to it. The relay surface is hot during use, and may cause a serious burn upon contact.
AVERTISSEMENT : Risque de blessure.
Ne pas toucher le relais lorsque le relais est sous tension. La surface du relais devient extrêmement chaude durant son utilisation et risque de provoquer des brûlures graves en cas de contact.

Wiring

1. Disconnect the conductor cable from the power source.
2. Snap the split core around the power conductor cable, and close the core until the core snaps shut.
3. Wire the CTD output terminals to the control box Analog Input (AI) terminal. See Technical Specifications for wire size and screw torque.
4. Select the input current range at the front panel slide switch. See Figure 5 and Setting the Current Range section.
5. Reconnect the power conductor cable. For a wiring example, see Figure 2.

Dimensions

Mounting

1. Use the two screws (included) to attach the
2. Snap the CTD device into place on the mounting
mounting bracket to the back of the electrical enclosure.
bracket.
If the measured current is too low to be detected or it is higher than the maximum current rating of the CTD device, use the following methods to increase or decrease the current.
CTD Series Current Transducer Devices Installation Instructions2

If Measured Current Is Too Low to Be Dete cted

Figure 3: CSD Device Shown with Four Turns
F
i
g
:
s
c
_
t
r
n
s
Figure 4: CTD Device with CT Transformer
Current > 135 A
Fig:spc_w ct
Figure 5: Current Setting Switch
Amperage Range
120 60 30
Fig:CTD
4-20 mA
+ -
Wrap the conductor (wire) through the sensing hole and around the CTD body to produce multiple turns to increase the measured current. The measured current is equal to the actual current multiplied by the number of turns (Figure 3).
You must scale the controller to account for the extra turns. If four turns pass through the transducer as shown, the normal controller reading must be divided by 4.
IMPORTANT: Failure to derate the current cap acity could result in damage to the CTD device when using multiple turns to increase the measured current. Use the following formula to determine the new maximum current: The new maximum current is equal to the CDT current rating divided by the number of turns. Example: If the new maximum current is equal to the CDT current rating of 120 A, then Maximum Current = 120 A / 4 = 30 A.
2. Run the CT secondary wire through the sensing hole.
3. Terminate the two secondary wires of the 5 A CT to each other, and then install the 5 A CT on the monitored conductor.
4. Set the CTD device for the lowest current range (20 or 30 A).

Setup and Adjustments

Setting the Current Range

Position the current range slide switch to a level consistent with the load.
Table 1: Current Settings
Model Current Settings (A)
CTD-C1G00-1 30, 60, or 120 CTD-C2G00-1 30, 60, or 120 CTD-C3H00-1 20, 100, or 150

To Monitor Currents Exceeding the Maximum Current Rating of the CTD Device

For currents greater than 120 A (CTD-C1G00-1 and CTD-C200-1), or greater than 150 A (CTD-C3H00-1), proceed as follows.
1. Use a 5 A Current Transformer (CT) to reduce the current passing through the CTD device, as shown in Figure 4.
CTD Series Current Transducer Devices Installation Instructions 3

Wiring and Output

Figure 6: CTD-C1G00-1
Amperage Range
120 60 30
Fig:CTD1
4-20 mA
+ -
-
+
+
-
AI
DDC Controller
24 VDC Power Supply
Figure 7: CTD-2G00-1
Amperage Range
120 60 30
Fig:CTD2
0-5 VDC
+ -
­+
AI
DDC Controller
Figure 8: CTD-C3H00-1
Amperage Range
120 60 30
Fig:CTD3
0-10 VDC
+ -
­+
AI
DDC Controller
Figure 9: Transducer Linear Outputs
Analog Output
Input Current
CTD-C2G00-1
5 VDC
0 VDC
0 A 30/60/
120 A
Analog Output
Input Current
CTD-C3H00-1
10 VDC
0 VDC
0 A
20/100/ 150 A
A
nalog O
utp
u
t
Input Current
CTD-C1G00-1
20 mA
4 mA
0 A 30/60/
120 A

Linear Outputs

Accessories

See Table 2 for acce sso ries .
Table 2: Accessories
Code Number Description CR-01200-0 12 VAC/VDC Single-Pole,
Single-Throw (SPST), Normally Open (N.O.) Relay
CR-02400-0 24 VAC/VDC SPST, N.O. Relay

Repair Information

If the CTD Device fails to operate within its specifications, replace the unit. For a replacement CTD device, contact the nearest Johnson Controls® representative.
CTD Series Current Transducer Devices Installation Instructions4

Troubleshooting

Table 3: Troubleshooting
Symptom Action
The CTD device output does not function.
There is no CTD output at controller.
CTD-C1G00-1 1. Verify that the loop power between the CTD terminals and the control panel analog
CTD-C2G00-1, CTD-C3H00-1
Verify you did not exceed the maximum current range. Voltages or currents above the rated levels may damage the CTD device.
input is 18–30 VDC.
2. Verify that the current is 4 mA without a load. a. Turn off the monitored load.
b. Disconnect the inputs to the controller. c. Measure the current in the power supply and CTD output loop with a multimeter.
3. Check the current loop polarity.
4. Check the clamp surface is free of dirt or debris.
5. Check the clamp is fully close d .
1. Check the current rating in monitored conductor.
2. Check the polarity of th e sensor output and controller output.
3. Check the clamp surface is free of dirt or debris.
4. Check the clamp is fully close d .
5. Measure the voltage across the CTD output terminals.

Technical Specifications

CTD-C1G00-1, CTD-C2G00-1, and CTD-C3H00-1 Current Transducer Models

Product Code CTD-C1G00-1 CTD-C2G00-1 CTD-C3H00-1 Current Range (Selectable) 30/60/120 A 30/60/120 A 20/100/150 A Continuous Operating Current 30/60/120 A 30/60/120 A 20/100/150 A Output 4 to 20 mA 0 to 5 VDC 0 to 10 VDC Accuracy ±2.0% Full Scale from 10% to 100% of Selected Range Response Time 2 Seconds to 100% of Selected Range Sensor Supply Voltage 24 VDC (18 to 30 VDC) Self-Powered Self-Powered Wire Size 12 to 22 AWG (2.1 to 0.6 mm) Diameter Recommended Isolation Voltage 600 VAC rms Temperature Range 5 to 140°F (-15 to 60°C) Frequency Range 50/60 Hz Humidity Range 0 to 95% RH, Noncondensing Screw Torque 4 lb·in (0.5 N·m) Dimensions 2-23/32 x 2-9/16 x 1-1/16 in. (69 x 65 x 27 mm) Aperture (Sensing Hole) Size 23/32 in. x 13/16 in. (18 x 20 mm Diameter) Compliance United States UL Listed, File E310692, CCN NRNT, Under UL 508, Industrial Control Equipment
Canada UL Listed, File E310692, CCN NRNT7, Under CAN/CSA C22.2 No. 14-05
Industrial Control Equipment
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive and the Low Voltage Directive.
Shipping Weight 0.35 lb (0.16 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application of conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
CTD Series Current Transducer Devices Installation Instructions 5
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MIL WAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
CTD Series Current Transducer Devices Installation Instructions6
Published in U.S.A. www.johnsoncontrols.com
Loading...