The Current Switch Devices Self-Calibrating (CSDSC)
Series of Current Switch Devices provide reliable
verification of electrical equipment operation in a
variety of applications, including fans and pumps.
CSDSC current switch devices use a single-turn dial to
select motor full load amps, eliminating the need for
live calibration and significantly reducing installation
time compared to traditional current switches.
CSDSC switches use full load amps instead of
horsepower, eliminating the need for separate part
numbers as a function of line voltage. CSDSC current
switches are installed when the panel is de-energized.
The ability to preset the sensor eliminates the need for
Personal Protective Equipment (PPE) that is required
by OSHA when working with a live panel.
Code No. LIT-12012403
Issued September 2017
The fixed setpoint Current Switch Device for
Electronically Commutated Motors (CSDECM) Series
of Current Switch Devices feature a range of minimum
turn-on options including 250 mA, 350 mA, and
500 mA. These options eliminate the possibility of a
false reading. Even when idle, ECMs draw a small
amount of current. Some fixed point sensors feature a
minimum turn-on value within the vicinity of the ECM’s
idle current, making them ineffective in distinguishing
between on and off status.
CSDECM Current Switch Devices can also be used
with other electrical loads when a simple sensor is
needed.
Features and Benefits
•Split and Solid Core Models with Mini-Sized Variants—Fit in tight enclosures.
•Monitored Load—Supplies power without a power supply.
•Optional N.O. Relay—Adds 10 A at 125 VAC switching power with a choice of 24 or 12 V coil.
•Low Turn on Current—Extends use to sub-fractional HP motors.
•LED Indication of Switch Status—Allows you to easily check the switch’s on/off status (CSDSC switch only).
CSDSC and CSDECM Current Switch Devices Product Bulletin
1
Operation
The CSDSC and CSDECM Current Switch Devices
have an N.O. output (1.0 at 30 VAC/VDC). The output
on the CSDSC switch closes when the monitored
current exceeds 70% full load amps and opens when
the current falls below 60% full load amps, making the
loss of load detection permissible without calibration.
The output on the CSDECM switch closes when the
monitored current exceeds the indicated minimum
turn-on amps; it remains open when falling below the
same threshold.
Ordering
Table 1: CSDSC Current Switch Devices Ordering Information
Code NumberCore TypeMinimum Turn-On
Amps
CSDSC-C45050LxClamp0.45 A50 AHigh, Low,
CSDSC-C50100Lx0.50 A100 A
CSDSC-C50150Lx150 A
CSDSCM-C010501.00 A50 ATripNo
CSDSCM-S75050LSolid0.75 A50 A
CSDSCM-S75005L
CSDSCMM-S75050L
Maximum
Amps
LEDsRelay Option
Power
Yes
1
1.See Table 3 for relay order code information.
Ta bl e 2: CSDECM Current Switch Devices Ordering In fo rmat ion
Code NumberCore TypeMinimum Turn-On
Amps
CSDECM-C35200LxClamp0.35 A200 ANoYes
CSDECMM-C500500.50 A50 ANo
CSDECM-S25050LSolid0.25 A
CSDECMM-S25050L
1.See Table 3 for relay order code information.
Maximum
Amps
LEDsRelay Option
1
Table 3: CSDSC and CSDECM Relay Options
Relay Order CodeContact RatingCoilRelay Code
Number (Field
Relay Dimensions, in.
(mm) (L x H x W)
Accessory)
1N.O. 10 A at 125 VAC24 VAC/VDC 15 mACRCSDP-NO-240.84 x 0.72 x 2.06
2N.C. 10 A at 125 VACCRCSDP-NC-24
3N.O. 10 A at 125 VAC12 VDC 30 mACRCSDP-NO-12
4N.C. 10 A at 125 VACCRCSDP-NC-12
0No RelayN/AN/AN/A
(21.3 x 18.3 x 52.3)
CSDSC and CSDECM Current Switch Devices Product Bulletin
2
Repair Information
If the CSDSC and CSDECM Current Switch Devices
fail to operate within their specifications, replace the
units. For a replacement switch device, contact the
nearest Johnson Controls® representative.
Technical Specifications
CSDSC Current Switch Devices
CSDSC-C45050Lx
CSDSC-C50100Lx
CSDSC-C50150Lx
Status OutputSwitch normally open
Switch Load
Capacity
Switch SetpointAdjustable
Maximum Current50 A
Minimum Trip
Setpoint Value
Aperture (Sensing
Hole) Size;
Dimensions, in.
(mm)
Switch LED
Indication
Current Switching
Mode
Sensor Supply
Voltage
Status Output
Wire Size
Screw Torque3.5 to 4.4 in·lb (0.4 to 0.5 N·m)
Isolation Voltage600 VAC rms (UL), 300 VAC rms (CE)
Frequency Range50/60 Hz
Temperature
Range
Humidity Range0 to 95% noncondensing
Dimensions, in.
(mm)
Command Relay
Device Actuation
Coil
Relay Contact
Rating
Relay LED
Indication
1.0 at 30 VAC/VDC
100 A
150 A
0.45 A
0.50 A
0.50 A
0.75 x 0.75
(19.1 x 19.1)
Yes
Over/Under
Induced from power conductor cable
14 to 24 AWG (1.6 to 0.5 mm)
5 to 140°F (-15 to 60°C)
2.5 x 0.57 x 2.23
(63.5 x 14.5 x 56.6)
20 to 30 VAC/VDC,
12 to 20 mA or
10 to 14 VAC/VDC,
25 to 35 mA
(models except -0L0)
N.O. 10A at 125 VAC or
N.C. 10A at 125 VAC
YesN/AN/AN/A
CSDSCM-C01050CSDSC-S75050LCSDSCM-S75005L
50 A50 A5 A
1.00 A0.75 A0.75 A
0.4 x 0.32
(10.2 x 8.1 mm)
2.0 x 0.75 x 1.75
(50.8 x 19.1 x 44.5)
N/AN/AN/A
N/AN/AN/A
CSDSCM-S75050L
50 A
0.75 A
0.51 (13.0)0.30 (7.6)
2.26 x 0.97 x 1.6
(57.4 x 24.6 x 40.6)
1.91 x 0.88 x 1.31
(48.5 x 22.4 x 33.3)
CSDSC and CSDECM Current Switch Devices Product Bulletin
3
CSDSC Current Switch Devices
ComplianceUnited StatesUL Listed, File E493157, CCN NMTR, Under UL 508, Industrial Control
Equipment
CanadaUL Listed, File E493157, CCN NMTR7, Under CAN/CSA C22.2 No. 14-M91
EuropeCE Mark - Johnson Controls declares that this product is in compliance with
Shipping Weight0.15 lb (0.07 kg)
the essential requirements and other relevant provisions of the EMC
Directive and the Low Voltage Directive.
ComplianceUnited StatesUL Listed, File E493157, CCN NMTR, Under UL 508, Industrial Control
CanadaUL Listed, File E493157, CCN NMTR7, Under CAN/CSA C22.2 No. 14-M91
EuropeCE Mark - Johnson Controls declares that this product is in compliance with
Shipping Weight0.15 lb (0.07 kg)
Equipment
the essential requirements and other relevant provisions of the EMC
Directive and the Low Voltage Directive.
The performance specifications are nominal and conform to acceptable industry standards.
misuse of its products.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
Published in U.S.A.
CSDSC and CSDECM Current Switch Devices Product Bulletin