Johnson Controls A11 Series Data Sheet

A11 Series Low Temperature
Cutout Control
A11 Series Low Temperature Cutout Controls Dimensions, in. (mm)
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
Code No. LIT-1927005 Issued November 13, 2015
A11 Series Low Temperature Cutout Controls
Description
A11 Series Low Temperature Cutout Controls are available with single-pole, single-throw (SPST) or single-pole, double-throw (SPDT) contact action. Typical applications include the sensing of low temperature conditions to avoid over cooling or icing of hydronic coils, cooling coils, and liquid-handing pipes. The controls are compact and sturdy, and have an adjustable temperature setpoint range with a fixed differential. The range adjustment screw is accessible at the bottom of the control, and at the top of the control when the cover is removed.
The A11 Controls are compact and sturdy and feature an adjustable range with a fixed differential. The range adjustment screw is accessible at the bottom of the control or at the top, when the cover is removed. A factory-set low temperature stop is available when specified.
Refer to the A11 Series Low Temperature
Cutout Controls Product Bulletin (LIT-125010)
Features
• precision repeat accuracy remains unaffected by ambient temperature at the control diaphragm cup and 4 ft (1.2 m) capillary (20 ft [6.1 m] sensing bulb must be in the controlled area)
• trip-free manual reset allows the lever to reset. You must press and release the lever before operation resumes.
• precision snap-acting contacts in a dust protected enclosure enables the A11 Control to operate to the fullest potential
• direct reading scale provides easy-to-adjust setpoint. Adjustments can be made from the top or bottom of the control.
Repair Information
If the A11 Series Low Temperature Cutout Control fails to operate within its specifications, replace the unit. For a replacement control, contact the nearest Johnson representative.
Controls®
for important product application information.
Electrical Rating
Motor Rating Motor Description
AC Full Load Amperes 16.0 9.2 8.0 AC Locked Rotor Amperes 96.0 55.2 48.0 Non-Inductive Amperes 16.0 9.2 8.0 Pilot Duty 125 VA, 24 to 277 VAC
120 V 208 V 240 V
Selection Chart
Model Description
A11A SPST, open low, manual reset A11B SPST, open low, automatic recycle A11D SPDT, manual reset A11E SPDT, automatic recycle
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
www.johnsoncontrols.com
1
A11 Series Low Temperature Cutout Controls (Continued)
Technical Specifications
A11 Low Temperature Cutout Controls
Product Codes A11A: SPST, open low, manual reset
Range Cutout 35 to 45°F (2 to 7°C) Differential A11A and A11D: Temperature must be 12°F (6.7°C) above cutout point before control can be reset.
Ambient Temperature Minimum: 0°F (-18°C)
Maximum Temperature at Bulb 250°F (121°C) Sensing Element 1/8 in. x 20 ft (3 mm x 6.1 m) or 1/8 in. x 40 ft (3 mm x 12.2 m) Capillary Length 4 ft (1.2 m) Switch Snap-acting contacts in dust-protected enclosure Material Case: 0.6 (2 mm) cold rolled steel
Finish Galvanized steel Conduit Opening 22 mm (9/10 in.) hole for 13 mm (1/2 in.) conduit Mounting Bracket Standard on all controls Shipping Weight Individual pack: 1.8 lb (0.8 kg)
Electrical Rating Pilot Duty: 125 VA, 24 to 277 VAC Motor Ratings AC Full Load Ampere: 120 V = 16.0 A, 208 V = 9.2 A, 240 V = 8.0 A
Compliance United States UL Listed, File SA516, SDFY
A11B: SPST, open low, automatic recycle A11D: SPDT, manual reset A11E: SP DT, automatic recycle
A11B and A11E: 12°F (6.7°C)
Maximum: 140°F (60°C)
Cover: 0.3 in. (1 mm) cold rolled steel
Overpack of 20 units: 38 lb (17 kg)
AC Locked Rotor Ampere: 120 V = 96.0 A, 208 V = 55.2 A, 240 V = 48.0 A Non-Inductive Ampere: 120 V = 16.0 A, 208 V = 9.2 A, 240 V = 8.0 A
FCC Compliant to CFR 47, Part 15 Subpart B, Class A
Canada UL Listed, CSA Class No. 1222 01, File LR948
Industry Canada, ICES-003
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
www.johnsoncontrols.com