Johnson Controls 260 Series Installation Guide

Installation Guide
“Multi-Sense” Model 260 Series
Multi-Range Differential Pressure Transducer
MECHANICAL INSTALLATION
Mounting Position
Mount and calibrate in vertical position for quick and easy installation on ducts, w alls or c eilings and in c ontrol r ooms .
GENERAL INFORMATION
Every Model 260 has been calibrated and tested before shipment to guarantee performance for all pressure ranges.
The Model 260 is available in four versions, which have field selectable range capability via a slide switch. See four versions below:
Ranges
Version Unidirectional Bidirectional
Model MS1 0.1”, 0.25”, 0.5” and 1.0” W.C. FS +/- 0.1”, 0.25”, 0.5” and 1.0” W.C. FS Model MS2 1.0”, 2.5”, 5.0” and 10” W.C. FS +/- 1.0”, 2.5”, 5.0” and 10” W.C. FS Model MS3 25, 50, 100 and 250 Pa FS +/- 25, 50, 100 and 250 Pa FS Model MS4 .25, .50, 1.00 and 2.5 kPa +/- .25, .50, 1.00 and 2.5 kPa
Media Compatibility
Model 260 transducers are designed to be used with air or nonconducting gases.
Use with liquids or corrosive gases will damage the unit.
Environment
The operating temperature limits of the 260 are as follows: Operating Temperature 32°F to 122°F (0°C to 50°C)
Compensated Temperature Range 32°F to 122°F (0°C to 50°C)
SIMPLE 5-STEP SETUP INSTRUCTIONS ­STEP 1 ELECTRICAL CONNECTIONS
Removable Terminal Block for Easy Wiring
STEP 1: Wire and Power Up Unit - Follow diagrams
below for 2-wire and 3-wire configurations. After completing wiring requirements - Apply power to the Model 260.
Multi-Sense Voltage
3-Wire, 1-5, 0-5, 0-10 VDC Configuration
24V AC/DC
Nominal
Excitation
Power
Supply
13 - 30V
Model 260
EXC COM OUT
+ +
+
-
­ +
-
Voltage Monitor
Multi-Sense Current
2-Wire, 4-20 mA Configuration
The Model 260 is available in four field selectable output configurations. See four versions below:
2-Wire 4-20 mA (Current) 3-Wire 1-5, 0-5, or 0-10 VDC (Voltage)
SIMPLE 5-STEP SETUP INSTRUCTIONS - STEPS 2 - 5
Power On - LCD Display
Display momentarily toggles thru all existing setup parameters on initial power up. Pressure is normally indicated on display. Units are either in inches of water column (WC) MS1 & MS2, or Pascal (Pa) MS3 & MS4.
*STEP 2: Select Pressure Range: Set
appropriate full scale range using the Slide Switch Multiplier. LCD will momentarily indicate selected range.
STEP 3: Select Unidirectional
or Bi-directional mode.
STEP 4: Select Current (mA)
or Voltage 1-5, 0-5, or 0-10 VDC output range.
*Step 2 will follow same instructions for other inches of water column and pascal ranges.
RANGE:
1 0.5 0.25 0.1
UNI/BI ZERO
mA/1-5V/5V /10V
+
+-
EXC COM OUT
STEP 5: Push Button
Zero - While at
zero pressure Press and hold the Zero Push Button for 1 second to automatically reset output to zero.
24V (DC Only)
Nominal
Excitation
Power
Supply
13 - 30V
+
-
Model C260
EXC COM OUT
-
+
2601MS1
S/N:
X
+
Current Monitor
-
Typical 250 Ohm
Sense Resistor for 1-5V Output
Measurement
Date Code
PERFORMANCE SPECIFICATIONS
Accuracy RSS* (at constant temperature.) ±1% FS *RSS of Non-Linearity, Non-Repeatability and Hysteresis.
Thermal Effects Compensated Range °F(°C) +32 to +122°F (0 to 50) Zero/Span Shift %FS/°F(°C) 0.02 (0.036) Maximum Line Pressure 10 PSI Warm-up Shift ±0.2% FS total Position Effects (Unit is factory calibrated at 0g effect in the vertical position) Zero Offset (%FS/G) 0.2%
WARRANTY AND LIMITATION OF LIABILITY
SETRA warrants its Model 260 Transducer products to the original consumer purchaser against defects for a period of one year from the date of sale by SETRA, as shown in its shipping documents. Without charge, SETRA will repair or replace products found to have manufacturing defects within the warranty period. The serial number or date code must not have been removed, defaced or otherwise changed. SETRA must be notified in advance of any returns; any products returned to SETRA must be transporta­tion prepaid. The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not limited to, any implied warranty of merchantability for a particular purpose. SETRA’s liability for breach of warranty is limited to repair or replacement, or if the goods cannot be repaired or replaced, to a refund of the purchase price. SETRA’s liability for all other breaches is limited to a refund of the purchase price. In no instance shall SETRA be liable for incidental or consequential damages arising from a breach of warranty, or from the use or installation of its products. No representative or person is authorized to give any warranty other than as set out above or to assume for SETRA any other liability in connection with the sale of its products.
SS2125 Rev.A 1/17/05