Johnson Controls 13 SEER - GCGD User Manual

0 (0)
R-22 OUTDOOR SPLIT-SYSTEM
INSTALLATION MANUAL
AIR CONDITIONING SHIPPED WITH NITROGEN CHARGE ONLY
MODELS: 13 SEER - GCGD
1.5 TO 5 TONS
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
ORIFICE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
TXV INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LIST OF FIGURES
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation of Vapor Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Orifice Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Outdoor Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
LIST OF TABLES
Application Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 R-22 Saturated Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Typical Field Wiring (Air Handler / Electrical Heat) . . . . . . . . . . . . . . . 7
Thermostat Chart - Single Stage AC with PSC Air Handler . . . . . . . . 8
Thermostat Chart - Single Stage AC with PSC Air Handler . . . . . . . . 9
Thermostat Chart - Single Stage AC with PSC Furnace . . . . . . . . . 10
Thermostat Chart - Single Stage AC with PSC Furnace . . . . . . . . . 11
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Sweat connect units have been shipped from the factory with a nitrogen holding charge.
The refrigerant charge may need to be changed for some indoor-out­door unit combinations, elevation differences or total line lengths. Refer to Application Data covering “General Piping Recommendations and Refrigerant Line Length” (Part Number 247077). This unit has a com­pressor containing POE oil.
This unit does not contain any refrigerant. It contains a nitrogen hold­ing charge. Operating this unit with the nitrogen holding charge will damage the compressor.
Before operating this unit, vent the nitrogen and evacuate the entire system below 500 microns. Weigh in the refrigerant using the Tabular Data Sheet and Installation Manual.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury
.
WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or mo derate injury alert against unsafe practices and hazards involving only property dam­age.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assis­tance or for additional information, consult a qualified contractor, installer or service agency.
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
INSPECTION
As soon as a unit is received, it should be inspected for possib le dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s delivery receipt. A separate request for inspection by the carrier’s agent should be made in writing. See Local Distributor for more information.
.
. It is also used to
Johnson Controls Unitary Products 1031452-UIM-B-0513
1031452-UIM-B-0513
NOTICE
THERMOSTAT
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
TO INDOOR COIL
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NEC CLASS 2 WIRING
NEC CLASS 1 WIRING
ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
CONTROL ACCESS PANEL
WEATHERPROOF DISCONNECT SWITCH
MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE
60” OVERHEAD CLEARANCE
10” CLEARANCE AROUND PERIMETER
NOTE:
LIMITATIONS
The unit should be installed in accordance with all National, State and Local Safety Codes and the limitations listed below:
1. Limitations for the indoor unit, coil, and appropriate accessories must also be observed.
2. The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is the propeller type and is not designed to operate against any additional external static pressure.
3. The maximum and minimum conditions for operation must be observed to ensure a system that will give maximum performance with minimum service.
TABLE 1:
Application Limitations
Ambient Air Temperature
on Outdoor Coil
Air Temperature on
Indoor Coil
Min. DB Max. DB Min. WB Max. WB
50 °F 115 °F 57 °F 72 °F
4. The unit should not be operated at outdoor temperatures below 50° F without an approved low ambient operation accessory kit installed.
5. The maximum allowable line length for this product is 75 feet.
SECTION III: UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements.
The outdoor unit must have sufficient clearance for air entrance to the condenser coil, air discharge, and service access. See Figure 1.
For multiple unit installations, units must be spaced a minimum of 24 inches apart (coil face to coil face).
If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit.
Provide an adequate structural support.
ADD-ON REPLACEMENT/RETROFIT
The following steps should be performed in order to insure proper sys­tem operation and performance.
1. Change-out the indoor coil, if required, to an approved R-22 coil/ condensing unit combination with the appropriate metering device.
2. If the outdoor unit is being replaced due to a compressor burnout, then installation of a 100% activated alumina suction-line filter drier in the suction-line is required, in addition to the factory installed liquid-line drier. Operate the system for 10 hours. Monitor the suction drier pressure drop. If the pressure drop exceeds 3 psig, replace both the suction-line and liquid-line driers. After a total of 10 hours run time where the suction-line pressure drop has not exceeded 3 psig, replace the liquid line drier, and remove the suction-line drier. Never leave a suction-line drier in the system longer than 50 hours of run time.
FIGURE 1: Typical Installation
GROUND INSTALLATION
The unit should be installed on a solid base that is 2” above grade and will not shift or settle, causing strain on the refrigerant lines and possible leaks. Maintain the clearances shown in Figure 1 and install the unit in a level position. The base pad should not come in contact with the foun­dation or side of the structure because sound may be transmitted to the residence.
The length of the refrigerant tubing between the outdoor unit and indoor coil should be as short as possible to avoid capacity and efficiency losses. Excessive spacing of the outdoor unit from the home can result in the refrigerant lines being restricted by trampling or being punctured by lawn mowers. Locate the outdoor unit away from bedroom windows or other rooms where sound might be objectionable.
2 Johnson Controls Unitary Products
Adverse effects of snow or sleet accumulating on the outdoor coil can be eliminated by placing the outdoor unit where the prevailing wind does not blow across the unit. Trees, shrubs, corners of buildings, and fences standing off from the coil can reduce capacity loss due to wind chill effect.
Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into the coil.
ROOF INSTALLATION
When installing units on a roof, the structure must be capable of sup­porting the total weight of the unit, including a pad, lintels, rails, etc., which should be used to minimize the transmission of sound or vibra­tion into the conditioned space.
LIQUID LINE FILTER-DRIER
NOTICE
NOTICE
Liquid Line
Incorrect
Correct
Tape
Sheet Metal Hanger
Insulated Vapor Line
TO INDOOR COIL
Liquid Line
PVC Conduit
Insulated Vapor Line
TO OUTDOOR UNIT
Cap
The air conditioning unit’s copper spun filter/dryer is located on the liq­uid line.
Replacements for the liquid line drier must be exactly the same as marked on the original factory drier. See Source 1 for O.E.M. replace­ment driers.
Failure to do so or using a substitute drier or a granular type may result in damage to the equipment.
1031452-UIM-B-0513
FIGURE 2: Installation of Vapor Line
Filter-Drier
Source 1 Part No.
S1-02922156000 1.5 to 3 Tons S1-02922157000 3.5 to 5 Tons
Apply with Models
13 SEER
PIPING CONNECTIONS
The outdoor condensing unit must be connected to the indoor evapora­tor coil using field supplied refrigerant grade (ACR) copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for approved system combinations as specified in tabular data sheet. The charge given is applicable for total tubing lengths up to 15 feet. See Application Data Part Number 247077 for installing tubing of longer lengths and elevation differences.
Using a larger than specified line size could result in oil return prob­lems. Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant flow. Slope horizontal vapor lines at least 1" every 20 feet toward the outdoor unit to facili­tate proper oil return.
PRECAUTIONS DURING LINE INSTALLATION
1. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary. If soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction.
2. The lines should be installed so that they will not obstruct service access to the coil, air handling system, or filter.
3. Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.
4. The vapor line must be insulated with a minimum of 1/2" foam rub­ber insulation (Armaflex or equivalent). Liquid lines that will be exposed to direct sunlight, high temperatures, or excessive humid­ity must also be insulated.
5. Tape and suspend the refrigerant lines as shown. DO NOT allow tube metal-to-metal contact. See Figure 2.
6. Use PVC piping as a conduit for all underground installations as shown in Figure 3. Buried lines should be kept as short as possible to minimize the build up of liquid refrigerant in the vapor line during long periods of shutdown
7. Pack fiberglass insulation and a sealing material such as perma­gum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility.
8. For systems with total line length exceeding 50 feet, see APPLI­CATION DATA and worksheet "General Piping Recommendations and Refrigerant Line Length" for vapor and liquid line sizing, cali­bration of liquid line pressure loss or gain, determination of vapor line velocity, elevation limitations, orifice connections, system charging, traps, etc.
FIGURE 3: Underground Installation
PRECAUTIONS DURING BRAZING OF LINES
All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. Units are shipped from factory with a nitrogen holding charge. Refer to Tabular Data Sheet for refrigerant charge quantities. Reusable service valves are provided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precau­tions to assure an internally clean and dry system.
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
PRECAUTIONS DURING BRAZING SERVICE VALVE
Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4. Also, protect all painted surfaces, insulation, and plastic base during brazing. After braz­ing, cool joint with wet rag.
This is not a backseating valve. The service access port has a valve core. Opening or closing valve does not close service access port.
If the valve stem is backed out past the chamfered retaining wall, the O-ring can be damaged causing leakage or system pressure could force the valve stem out of the valve body possibly causing personal injury.
Valve can be opened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter-clockwise until valve stem just touches the chamfered retaining wall.
Johnson Controls Unitary Products 3
1031452-UIM-B-0513
NOTICE
Connect the refrigerant lines using the following procedure:
1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres­sure nitrogen to the liquid line service port.
2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to con­tinue flowing.
3. Carefully remove the plugs from the evaporator liquid and vapor connections at the indoor coil.
Line set and indoor coil can be pressurized to 250 psig with dry nitro­gen and leak tested with a bubble type leak detector. Then release the nitrogen charge.
11. Evacuate the vapor line, evaporator, and liquid line to 500 microns or less.
12. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system.
Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of refrigerant will be lost each time a stan­dard manifold gauge is connected.
13. Release the refrigerant charge into the system since these units have been shipped from the factory with a nitrogen holding charge.
14. Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/2 hex flat). Cap must be replaced to prevent leaks.
FIGURE 4: Heat Protection
Do not install any coil in a furnace which is to be operated during the heating season without attaching the refrigerant lines to the coil. The coil is under 30 to 35 psig inert gas pressure which must be released to prevent excessive pressure build-up and possible coil damage.
4. Braze the liquid line to the evaporator liquid connection. Nitrogen should be flowing through the evaporator coil.
5. Slide the grommet away from the vapor connection at the indoor coil. Braze the vapor line to the evaporator vapor connection. After the connection has cooled, slide the grommet back into original position.
6. Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit. The nitrogen flow should be exiting the system from the vapor service port connection. After this con­nection has cooled, remove the nitrogen source from the liquid fit­ting service port.
7. Vent the nitrogen holding charge in the outdoor unit by opening both service valves slowly and waiting for the pressure to dissi­pate. Open both the liquid and vapor valves by removing the plunger cap and with an allen wrench back out counter-clockwise until valve stem just touches the chamfered retaining wall. If the service valve is a ball valve, use a crescent wrench to turn valve stem one-quarter turn counterclockwise to open. Do not overturn or the valve stem may break or become damaged. See “PRECAU­TIONS DURING BRAZING SERVICE VALVE”.
8. Replace the Schrader core in the liquid and vapor valves.
9. Go to “SECTION V” or “SECTION IV” for orifice or TXV installation depending on application.
10. Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight. DO NOT OVER­TIGHTEN (between 40 and 60 inch - lbs. maximum).
Never attempt to repair any brazed connections while the system is under pressure. Personal injury could result.
See "System Charge” section for checking and recording system charge.
Supplied with the outdoor unit is a Schrader Valve Core and Orifice for highest sales volume indoor coil. The valve core must be installed in equalizer fitting of the indoor coil.
SECTION IV: ORIFICE INSTALLATION
Failure to install Schrader Valve Core on orifice applications could result in total refrigerant loss of the system!
Install Schrader Valve Core as follows:
1. Slide indoor coil out of cabinet far enough to gain access to equal­izer fitting on the suction line.
2. After holding charge is completely discharged remove black plas­tic cap on equalizer fitting.
3. Install Schrader Valve Core supplied with the outdoor unit into equalizer fitting using a valve core tool.
4. Loosen and remove the liquid line fitting from the orifice distributor assembly. Note that the fitting has right hand threads
5. Install proper size orifice supplied with outdoor unit. Refer to sup­plied Tabular Data Sheet for specific orifice size and indoor coil match up.
6. After orifice is installed reinstall the liquid line to the top of the ori­fice distributor assembly. Hand tighten and turn an additional 1/8 turn to seal. Do not over tighten fittings.
7. Leak test system.
8. Replace black plastic cap on equalizer fitting.
9. Slide indoor coil back into cabinet.
.
4 Johnson Controls Unitary Products
FIGURE 5: Orifice Installation
LIQUID LINE SWIVEL COUPLING (This fitting is a right-hand thread, turn counter-clockwise to remove)
ORIFICE
DISTRIBUTOR
1031452-UIM-B-0513
SECTION VI: EVACUATION
It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. Repair the leak and test again.
To verify that the system has no leaks, simply close the valve to the vac­uum pump suction to isolate the pump and hold the system under vac­uum. Watch the micron gauge for a few minutes. If the micron gauge indicates a steady and continuous rise, it’s an indication of a leak. If the gauge shows a rise, then levels off after a few minutes and remains fairly constant, it’s an indication that the system is leak free but still con­tains moisture and may require further evacuation if the reading is above 500 microns.
SECTION VII: SYSTEM CHARGE
See tabular data sheet provided in unit literature packet for charge requirements. Each unit has been shipped from the factory with a nitro­gen holding charge and POE oil in the compressor.
SECTION V: TXV INSTALLATIONS
When using a TXV, models 18-48 require a hard start kit.
The following are the basic steps for installation. For detailed instruc­tions, refer to the Installation Instructions accompanying the TXV kit. Install TXV kit as follows:
1. Relieve the holding charge by pulling off the rubber cap plug on the suction manifold line of the coil.
2. After holding charge is completely discharged, loosen and remove the schraeder cap seal.
3. Loosen and remove distributor cap seal.
4. Install the thermal expansion valve to the orifice distributor assem­bly with supplied fittings. Hand tighten and turn an additional 1/4 turn to seal. Do not overtighten fittings.
5. Install the liquid line to the top of the thermal expansion valve with fitting supplied with the liquid line. Hand modify the liquid line to align with casing opening. Hand tighten the liquid line and an addi­tional 1/4 turn to seal.
6. Install the TXV equalizer line into the vapor line as follows: a. Hand tighten the 1/4” SAE nut to the schraeder fitting and an
additional 1/3 turn to seal.
7. Install the TXV bulb to the vapor line near the equalizer line, using the bulb clamp(s) furnished with the TXV assembly. Ensure the bulb is making maximum contact.
a. Bulb should be installed on a horizontal run of the vapor line if
possible. The bulb should be installed on top of the line.
b. If bulb installation is made on a vertical run, the bulb should
be located at least 16 inches from any bend, and on the tub­ing sides opposite the plane of the bend. The bulb should be positioned with the bulb tail at the top, so that the bulb acts as a reservoir.
c. Bulb should be insulated using thermal insulation provided to
protect it from the effect of the surrounding ambient tempera­ture. Cover completely to insulate from air-stream.
In all cases, mount the TXV bulb after vapor line is brazed and has had sufficient time to cool.
This unit does not contain any refrigerant. It contains a nitrogen hold­ing charge. Operating this unit with the nitrogen holding charge will damage the compressor.
Do not leave the system open to the atmosphere.
The “TOTAL SYSTEM CHARGE” must be permanently stamped on the unit data plate.
Total system charge is determined as follows:
1. Determine initial unit charge from tabular data sheet.
2. Calculate the line charge using the tabular data sheet if line length is greater than 15 feet.
3. Total system charge = item 1 + item 2.
4. Permanently stamp the unit data plate with the total amount of refrigerant in the system.
Use the following charging method whenever additional refrigerant is required for the system charge.
DO NOT attempt to pump “Total System Charge” into outdoor unit for maintenance, service, etc. This may cause damage to the compres­sor and/or other components. the outdoor unit only has enough vol­ume for the factory charge, not the “Total System Charge”.
Refrigerant charging should only be carried out by a qualified air con­ditioning contractor.
Compressor damage will occur if system is improperly charged. On new system installations, charge system per tabular data sheet for the matched coil and follow guidelines in this instruction.
If a calibrated charging cylinder or accurate weighing device is avail­able, add refrigerant accordingly. Otherwise, model-specific charging charts are provided on the access panel of the unit.
Schrader valve core MUST NOT be installed with TXV installation. Poor system performance or system failure could result.
Johnson Controls Unitary Products 5
Loading...
+ 11 hidden pages