Johnson Controls 13 SEER User Manual

INSTALLATION MANUAL
R-22 OUTDOOR SPLIT-SYSTEM AIR CONDITIONING
MODELS: 13 SEER AY018-030 SERIES
1.5 TO 2.5 TONS
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
ORIFICE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LIST OF FIGURES
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Oil Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation of Vapor Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Orifice Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LIST OF TABLES
Application Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 R-22 Saturated Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATIONS REQUIRING AN ADD-ON TXV KIT . . . . . . . . . . . .5
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Outdoor Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Typical Field Wiring (Air Handler / Electrical Heat) . . . . . . . . . . . . . . . .6
Thermostat Chart - Single Stage AC with PSC Air Handler . . . . . . . . .7
Thermostat Chart - Single Stage AC with PSC Air Handler . . . . . . . . .8
Thermostat Chart - Single Stage AC with PSC Furnace . . . . . . . . . . .9
Thermostat Chart - Single Stage AC with PSC Furnace . . . . . . . . . .10
ISO 9001
Certified Quality
Management System
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Sweat connect units are factory charged with refrigerant for a matching indoor coil plus 15 feet of field supplied lines.
The refrigerant charge may need to be changed for some indoor-out­door unit combinations, elevation differences or total line lengths. Refer to Application Data covering “General Piping Recommendations and Refrigerant Line Length” (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING , or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury CAUTION indicates a potentially hazardous situation, which, if not
avoided may resul t in minor or moderate injury alert against unsafe practices and hazards involving only property dam­age.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified con­tractor, installer or service agency.
.
.
. It is also used to
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
INSPECTION
As soon as a unit is received, it should be inspected for possib le dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s delivery receipt. A separate request for inspection by the carrier’s agent should be made in writing. See Local Distributor for more information.
LIMITATIONS
The unit should be installed in accordance with all National, State and Local Safety Codes and the limitations listed below:
1. Limitations for the indoor unit, coil, and appropriate accessories must also be observed.
2. The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is the propeller type and is not designed to operate against any additional external static pressure.
3. The maximum and minimum conditions for operation must be observed to ensure a system that will give maximum performance with minimum service.
TABLE 1:
4. The unit should not be operated at outdoor temperatures below
Application Limitations
Ambient Air Temperature
on Outdoor Coil
Min. DB Max. DB Min. WB Max. WB
50 °F 115 °F 57 °F 72 °F
50° F without an approved low ambient operation accessory kit installed.
Air Temperature on
Indoor Coil
347337-UIM-A-0408
347337-UIM-A-0408
SECTION III: UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements.
The outdoor unit must have sufficient clearance for air entrance to the condenser coil, air discharge, and service access. See Figure 1.
NOTE: For multiple unit installations, units must be spaced a minimum
of 18 inches apart (coil face to coil face).
If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit.
Provide an adequate structural support.
MINIMUM 24” SERVICE ACCESS CLEARANCE ON ONE SIDE
48” OVERHEAD
12” CLEARANCE AROUND PERIMETER
CLEARANCE
WEATHERPROOF DISCONNECT SWITCH
ADD-ON REPLACEMENT/RETROFIT
The following steps should be performed in order to insure proper sys­tem operation and performance.
1. Change-out the indoor coil, if required, to an approved R-22 coil/ condensing unit combination with the appropriate metering device.
2. If the outdoor unit is being replaced due to a compressor burnout, then installation of a 100% activated alumina suction-line filter drier in the suction-line is required, in addition to the factory installed liquid-line drier. Operate the system for 10 hours. Monitor the suction drier pressure drop. If the pressure drop exceeds 3 psig, replace both the suction-line and liquid-line driers. After a total of 10 hours run time where the suction-line pressure drop has not exceeded 3 psig, replace the liquid line drier, and remove the suction-line drier. Never leave a suction-line drier in the system longer than 50 hours of run time.
THERMOSTAT
NEC CLASS 1 WIRING
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NOTE:ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
CONTROL ACCESS PANEL
FIGURE 1: Typical Installation
GROUND INSTALLA TION
The unit should be installed on a solid base that is 2” above grade and will not shift or settle, causing strain on the refrigerant lines and possible leaks. Maintain the clearances shown in Figure 1 and install the unit in a level position. The base pad should not come in contact with the foun­dation or side of the structure because sound may be transmitted to the residence.
The length of the refrigerant tubing between the outdoor unit and indoor coil should be as short as possible to avoid capacity and efficiency losses. Excessive spacing of the outdoor unit from the home can result in the refrigerant lines being restricted by trampling or being punctured by lawn mowers. Locate the outdoor unit away from bedroom windows or other rooms where sound might be objectionable.
Adverse effects of snow or sleet accumulating on the outdoor coil can be eliminated by placing the outdoor unit where the prevailing wind does not blow across the unit. Trees, shrubs, corners of buildings, and fences standing off from the coil can reduce capacity loss due to wind chill effect.
Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into the coil.
NEC CLASS 2 WIRING
TO INDOOR COIL
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
ROOF INSTALLATION
When installing units on a roof, the structure must be capable of sup­porting the total weight of the unit, including a pad, lintels, rails, etc., which should be used to minimize the transmission of sound or vibra­tion into the conditioned space.
LIQUID LINE FILTER-DRIER
The air conditioning unit’s copper spun filter/dryer is located on the liq­uid line.
NOTE: Replacements for the liquid line drier must be exactly the same
as marked on the original factory drier. See Source 1 for O.E.M.
replacement driers.
Failure to do so or using a substitute drier or a granular type may result in damage to the equipment.
R-22
Filter-Drier
Source 1 Part No.
029-22156-000 All Models
Apply with Models
AY
2 Johnson Controls Unitary Products
347337-UIM-A-0408
PIPING CONNECTIONS
The outdoor condensing unit must be connected to the indoor evapora­tor coil using field supplied refrigerant grade (ACR) copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for approved system combinations as specified in tabular data sheet. The charge given is applicable for total tubing lengths up to 15 feet. See Application Data Part Number 036-61920-000 for installing tubing of longer lengths and elevation differences.
NOTE: Using a larger than specified line size could result in oil return
problems. Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant flow. Slope horizontal vapor lines at least 1" every 20 feet toward the out­door unit to facilitate proper oil return.
OIL TRAPPING
When the outdoor unit is above the indoor coil, oil trapping is necessary . An oil trap should be provided for every 20 ft. of rise. See Figure 2.
OUTDOOR COIL
10 In.
20 Ft.
INDOOR
COIL
20 Ft.
6 In.
FIGURE 2: Oil Trap
PRECAUTIONS DURING LINE INSTALLATION
1. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary. If soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction.
2. The lines should be installed so that they will not obstruct service access to the coil, air handling system, or filter.
3. Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.
4. The vapor line must be insulated with a minimum of 1/2" foam rub­ber insulation (Armaflex or equivalent). Liquid lines that will be exposed to direct sunlight, high temperatures, or excessive humid­ity must also be insulated.
5. Tape and suspend the refrigerant lines as shown. DO NOT allow tube metal-to-metal contact. See Figure 3.
6. Use PVC piping as a conduit for all underground installations as shown in Figure 4. Buried lines should be kept as short as possible to minimize the build up of liquid refrigerant in the vapor line during long periods of shutdown
7. Pack fiberglass insulation and a sealing material such as perma­gum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility.
8. For systems with total line length exceeding 50 ft., see APPLICA­TION DATA and worksheet "General Piping Recommendations and Refrigerant Line Length" for vapor and liquid line sizing, cali­bration of liquid line pressure loss or gain, determination of vapor line velocity, elevation limitations, orifice connections, system charging, traps, etc.
Sheet Metal Hanger
Liquid Line
Incorrect
Correct
Insulated Vapor Line
Tape
FIGURE 3: Installation of Vapor Line
TO OUTDOOR UNIT
Cap
Liquid Line
PVC Conduit
TO INDOOR COIL
Insulated Vapor Line
FIGURE 4: Underground Installation
PRECAUTIONS DURING BRAZING OF LINES
All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. The total system refrigerant charge is retained within the outdoor unit during shipping and installation. The reusable service valves are pro­vided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precau­tions to assure an internally clean and dry system.
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is pro­vided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
PRECAUTIONS DURING BRAZING SERVICE VALVE
Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 5. Also, protect all painted surfaces, insulation, and plastic base during brazing. After braz­ing, cool joint with wet rag.
This is not a backseating valve. The service access port has a valve core. Opening or closing valve does not close service access port.
If the valve stem is backed out past the chamfered retaining wall, the O-ring can be damaged causing leakage or system pressure could force the valve stem out of the valve body possibly causing personal injury.
Valve can be opened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter-clockwise until valve stem just touches the chamfered retaining wall.
Johnson Controls Unitary Products 3
347337-UIM-A-0408
Connect the refrigerant lines using the following procedure:
1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres­sure nitrogen to the liquid line service port.
2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to con­tinue flowing.
3. Carefully remove the plugs from the evaporator liquid and vapor connections at the indoor coil.
FIGURE 5: Heat Protection
Do not install any coil in a furnace which is to be operated during the heating season without attaching the refrigerant lines to the coil. The coil is under 30 to 35 psig inert gas pressure which must be released to prevent excessive pressure build-up and possible coil damage.
4. Braze the liquid line to the evaporator liquid connection. Nitrogen should be flowing through the evaporator coil.
5. Slide the grommet away from the vapor connection at the indoor coil. Braze the vapor line to the evaporator vapor connection. After the connection has cooled, slide the grommet back into original position.
6. Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit. The nitrogen flow should be exiting the system from the vapor service port connection. After this con­nection has cooled, remove the nitrogen source from the liquid fit­ting service port.
7. Replace the Schrader core in the liquid and vapor valves.
8. Go to “SECTION V” or “SECTION IV” for orifice or TXV installation depending on application.
9. Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight. DO NOT OVER­TIGHTEN (between 40 and 60 inch - lbs. maximum).
NOTE: Line set and indoor coil can be pressurized to 250 psig with dry
nitrogen and leak tested with a bubble type leak detector. Then release the nitrogen charge.
NOTE: Do not use the system refrigerant in the outdoor unit to purge or
leak test.
10. Evacuate the vapor line, evaporator, and liquid line to 500 microns or less.
11. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system.
12. Release the refrigerant charge into the system. Open both the liq­uid and vapor valves by removing the plunger cap and with an allen wrench back out counter-clockwise until valve stem just touches the chamfered retaining wall. See Page 3 "PRECAU­TIONS DURING BRAZING SERVICE VALVE".
13. Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/2 hex flat). Cap must be replaced to prevent leaks.
Never attempt to repair any brazed connections while the system is under pressure. Personal injury could result.
See "System Charge” section for checking and recording system charge.
Supplied with the outdoor unit is a Schrader Valve Core and Orifice for highest sales volume indoor coil. The valve core must be installed in equalizer fitting of the indoor coil.
SECTION IV: ORIFICE INSTALLATION
Failure to install Schrader Valve Core on orifice applications could result in total refrigerant loss of the system!
Install Schrader Valve Core as follows:
1. Slide indoor coil out of cabinet far enough to gain access to equal­izer fitting on the suction line.
2. After holding charge is completely discharged remove black plas­tic cap on equalizer fitting.
3. Install Schrader Valve Core supplied with the outdoor unit into equalizer fitting using a valve core tool.
4. Loosen and remove the liquid line fitting from the orifice distributor assembly. Note that the fitting has right hand threads
5. Install proper size orifice supplied with outdoor unit. Refer to sup­plied Tabular Data Sheet for specific orifice size and indoor coil match up.
6. After orifice is installed reinstall the liquid line to the top of the ori­fice distributor assembly. Hand tighten and turn an additional 1/8 turn to seal. Do not over tighten fittings.
7. Leak test system.
8. Replace black plastic cap on equalizer fitting.
9. Slide indoor coil back into cabinet.
LIQUID LINE SWIVEL COUPLING (This fitting is a right-hand thread, turn counter-clockwise to remove)
ORIFICE
DISTRIBUTOR
.
FIGURE 6: Orifice Installation
Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of refrigerant will be lost each time a stan­dard manifold gauge is connected.
4 Johnson Controls Unitary Products
SECTION V: INSTALLATIONS REQUIRING AN ADD-ON TXV KIT
For installations requiring a TXV kit, refer to the Installation Instructions accompanying the TXV kit.
Schrader valve core MUST NOT be installed with TXV installation. Poor system performance or system failure could result.
SECTION VI: EVACUATION
It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. Repair the leak and test again.
To verify that the system has no leaks, simply close the valve to the vac­uum pump suction to isolate the pump and hold the system under vac­uum. Watch the micron gauge for a few minutes. If the micron gauge indicates a steady and continuous rise, it’s an indication of a leak. If the gauge shows a rise, then levels off after a few minutes and remains fairly constant, it’s an indication that the system is leak free but still con­tains moisture and may require further evacuation if the reading is above 500 microns.
SECTION VII: SYSTEM CHARGE
The factory charge in the outdoor unit includes enough charge for the unit, a 15 ft. line set, and the smallest indoor coil match-up. Some indoor coil matches may require additional charge. See tabular data sheet provided in unit literature packet for charge requirements.
Do not leave the system open to the atmosphere.
The “TOTAL SYSTEM CHARGE” must be permanently stamped on the unit data plate.
Total system charge is determined as follows:
1. Determine outdoor unit charge from tabular data sheet.
2. Determine indoor coil adjustment from tabular data sheet.
3. Calculate the line charge using the tabular data sheet if line length is greater than 15 feet.
4. Total system charge = item 1 + item 2 + item 3.
5. Permanently stamp the unit data plate with the total amount of refrigerant in the system.
Use the following charging method whenever additional refrigerant is required for the system charge.
347337-UIM-A-0408
Refrigerant charging should only be carried out by a qualified air conditioning contractor.
Compressor damage will occur if system is improperly charged. On new system installations, charge system per tabular data sheet for the matched coil and follow guidelines in this instruction.
If a calibrated charging cylinder or accurate weighing device is avail­able, add refrigerant accordingly. Otherwise, model-specific charging charts are provided on the access panel of the unit. If mix matched TXV indoor coils are used with these models, the following subcooling charg­ing method must be used. Superheat charging charts are not valid with TXV equipped systems.
SUBCOOLING CHARGING METHOD - MIXED MA T CH COILS
The recommended subcooling is 10°F
1. Set the system running in the cooling mode by setting the thermo­stat at least 6°F below the room temperature.
2. Operate the system for a minimum of 15-20 minutes.
3. Refer to the tabular data sheet for the recommended airflow and verify this indoor airflow (it should be about 400 SCFM per ton).
4. Measure the liquid refrigerant pressure P and temperature T at the service valve.
5. Calculate the saturated liquid temperature ST from Table 2.
6. Subcooling temperature TC = Saturated T emperature (ST) - Liquid Temp (T).
Example: The pressure P and temperature T measured at the liq­uid service port is 196 psig and 90°F, respectlvely. From Table 2, the saturated temperature for 196 psig is 100°F. The subcooling temperature TC = 100°-90°=10°F
Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level. Remove and recover the refrigerant if the subcooling TC is higher than the recommended level. See Table
2.
Check flare caps on service ports to be sure they are leak tight. DO NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
TABLE 2:
Pressure
R-22 Saturated Properties
PSIG
80 48 110 64 140 78 170 91 200 101 230 111 82 49 112 65 142 79 172 91 202 102 232 112 84 50 114 66 144 80 174 92 204 103 234 112 86 51 116 67 146 81 176 93 206 103 236 113 88 52 118 68 148 82 178 94 208 104 238 114 90 54 120 69 150 83 180 94 210 105 240 114 92 55 122 70 152 84 182 95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 126 72 156 85 186 97 216 107 246 116
98 58 128 73 158 86 188 97 218 107 248 117 100 59 130 74 160 87 190 98 220 108 250 117 102 60 132 75 162 88 192 99 222 109 252 118 104 61 134 76 164 88 194 99 224 109 254 118 106 62 136 77 166 89 196 100 226 110 256 119 108 63 138 78 168 90 198 101 228 111 258 119
Temp °F
Pressure
PSIG
Temp °F
Pressure
PSIG
Temp °F
Pressure
PSIG
Temp °F
Pressure
PSIG
Temp °F
Pressure
PSIG
Temp °F
Johnson Controls Unitary Products 5
347337-UIM-A-0408
CONTACTOR
IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS­CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE OWNER’S APPROVAL.
SECTION VIII: ELECTRICAL CONNECTIONS
GENERAL INFORMATION & GROUNDING
Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label.
Power wiring, control (low voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per NEC requirements.
All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National, Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accor­dance with the above codes.
The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel.
FIELD CONNECTIONS POWER WIRING
1. Install the proper size weatherproof disconnect switch outdoors and within sight of the unit.
2. Remove the screws at the top and sides of the corner cover. Slide corner cover down and remove from unit.
3. Run power wiring from the disconnect switch to the unit.
4. Route wires from disconnect through power wiring opening pro­vided and into the unit control box as shown in Figure 6.
5. Install the proper size time-delay fuses or circuit breaker, and make the power supply connections.
GROUND LUG
LOW VOLTAGE BOX
REVERSIBLE HIGH VOLTAGE CONDUIT PLATE
DUAL RUN/FAN CAPACITOR
“FINGERED” BUSHING
FIGURE 7: Outdoor Unit Control Box
FIELD CONNECTIONS CONTROL WIRING
1. Route low voltage wiring into bottom of control box as shown in Figure 6. Make low voltage wiring connections inside the low volt­age box per Figures 7-9.
2. The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel.
3. Replace the corner cover removed in Step 2.
4. All field wiring to be in accordance with national electrical codes (NEC) and/or local-city codes.
NOTE: A Start Assist Kit is available and recommended for long line set
applications or in areas of known low voltage problems.
5. Mount the thermostat about 5 ft. above the floor, where it will be exposed to normal room air circulation. Do not place it on an out­side wall or where it is exposed to the radiant effect from exposed glass or appliances, drafts from outside doors or supply air grilles.
6. Route the 24-volt control wiring (NEC Class 2) from the outdoor unit to the indoor unit and thermostat.
NOTE: To eliminate e rratic operation, seal the hole in the wall at the
thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat.
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING CONTROL WIRING FACTORY WIRING
*
GND.
LUG
POWER WIRING
208/230-1-60
CONTACTOR TERMINALS
COIL
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2)
*
TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
YRGW
ROOM THERMOSTAT
FIGURE 8: Typical Field Wiring (Air Handler / Electrical Heat)
6 Johnson Controls Unitary Products
347337-UIM-A-0408
For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section.
AC 1A Single Stage Air Conditioner – PSC Air Handler
ID MODELS
AHP SHP
THERMOSTAT
*PP11C70224
MA
PSC
AIR HANDLER
SINGLE STAGE SINGLE STAGE
AIR
AIR CONDITIONER
CONDITIONER
Y
Full Stage Compressor
RH 24 – Volt Hot (Heat XFMR)
G
Fan
RC 24 – Volt Hot (Cool XFMR)
W
Full Stage Heat
HM1
Humidistat
Clipping Jumper W914 for electric heat on thermostat
is not necessary
24VAC Humidifier
(Optional)
24VAC
Electronic Air Cleaner
(Optional)
PSC
AIR HANDLER CONTROL
COM
24 – Volt Common
Y/Y2
Second or Full
Stage Compressor
R
24 – Volt Hot
G
Fan
W2
Second Stage Heat
Single Stage Compressor
if humidistat is to be used.
Refer to AH documentation
Y1
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
W1
First Stage Heat
HUM
Humidity Switch
Open on Humidity Rise
HUM OUT
(24 VAC out)
Humidifier
EAC(24 VAC out)
Electronic Air Cleaner
Move HUM STAT
jumper to “YES”
for W1 and W2 electric
heat staging options.
SINGLE STAGE
1
SINGLE STAGE
AIR CONDITIONER
AIR CONDITIONER
C
24 – Volt Common
Y
Y
Compressor
Compressor Contactor
Other Part Numbers:
Part Numbers:
SAP = Legacy
SAP = Legacy
265902 = 031-09167
159480 = 031-09156
2
1
FIGURE 9: Thermostat Chart - Single Stage AC with PSC Air Handler
Johnson Controls Unitary Products 7
347337-UIM-A-0408
AC 1B Single Stage Air Conditioner – PSC Air Handler
THERMOSTAT
THERMOSTAT
ID MODELS
AHP SHP
MA
*BN11C00124
C
24 – Volt Common
Y
Full Stage Compressor
RH
24 – Volt Hot
(Heat XFMR)
G
Fan
RC
24 – Volt Hot
(Cool XFMR)
W
Full Stage Heat
2
Thermostat Installer Setup
1-System Type-must be
set to 0 Thermostat Installer Setup 15-Compressor Protection
must be set to 5
*BP11C50124 *BN11C01124 *DP11C40124
*DN11C00124
C
24 – Volt Common
Y
Full Stage Compressor
RH
24 – Volt Hot
(Heat XFMR)
G
Fan
RC 24 – Volt Hot (Cool XFMR)
W
Full Stage Heat
External Humidistat
(Optional)
Open on Humidity Rise
Selection of GAS/ELEC
switch on thermostat
is not necessary
24VAC Humidifier
(Optional)
24VAC
Electronic Air Cleaner
(Optional)
PSC
AIR HANDLER
PSC
AIR HANDLER CONTROL
COM
24 – Volt Common
Y/Y2
Second or Full
Stage Compressor
R
24 – Volt Hot
G
Fan
W2
Second Stage Heat
Single Stage Compressor
if humidistat is to be used.
Refer to AH documentation
Y1
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
W1
First Stage Heat
HUM
Humidity Switch
Open on Humidity Rise
HUM OUT
(24 VAC out)
Humidifier
EAC(24 VAC out)
Electronic Air Cleaner
Move HUM STAT
jumper to “YES”
for W1 and W2 electric
heat staging options.
SINGLE STAGE
AIR
CONDITIONER
1
SINGLE STAGE
AIR CONDITIONER
C
24 – Volt Common
Y
Compressor Contactor
Other Part Numbers:
2
Part Number:
S1-2HU16700124
Part Numbers:
SAP = Legacy
SAP = Legacy
265902 = 031-09167
159480 = 031-09156
2
1
FIGURE 10: Thermostat Chart - Single Stage AC with PSC Air Handler
8 Johnson Controls Unitary Products
AC 5D Single Stage Air Conditioner – Single Stage PSC Furnace
ID MODELS
THERMOSTAT
G*(8/9)S
G*9F
L(Y/M)8S
G8C
GF(8/9)
LF8 TG(8/9)S (G/T)GLS
347337-UIM-A-0408
*PP11C70224
Y
Full Stage Compressor
RH
24 – Volt Hot
(Heat XFMR)
G
Fan
RC 24 – Volt Hot (Cool XFMR)
W
Full Stage Heat
HM1
Humidistat
24VAC Humidifier
(Optional)
SINGLE STAGE
PSC
FURNACE
SINGLE STAGE PSC
FURNACE
C
24 – Volt Common
Y/Y2
Full Stage Compressor
R
24 – Volt Hot
G
Fan
W
Full Stage Heat
SINGLE STAGE
AIR
CONDITIONER
1
SINGLE STAGE
SINGLE STAGE
AIR CONDITIONER
AIR CONDITIONER
C
24 – Volt Common
Y
Y
Compressor
Compressor Contactor
Clipping Jumper W914 for electric heat on thermostat
is not necessary
Other Part Numbers:
SAP = Legacy
265901 = 031-09166
1
FIGURE 11: Thermostat Chart - Single Stage AC with PSC Furnace
Johnson Controls Unitary Products 9
347337-UIM-A-0408
AC 5E Single Stage Air Conditioner – Single Stage PSC Furnace
G*(8/9)S
G*9F
THERMOSTAT
*BN11C00124
THERMOSTAT
*BP11C50124 *BN11C01124 *DP11C40124 *DN11C00124
L(Y/M)8S
G8C
SINGLE STAGE
ID MODELS
PSC
FURNACE
GF(8/9)
LF8 TG(8/9)S (G/T)GLS
SINGLE STAGE
AIR
CONDITIONER
C
24 – Volt Common
Y
Full Stage Compressor
RH
24 – Volt Hot
(Heat XFMR)
G
Fan
RC 24 – Volt Hot (Cool XFMR)
W
Full Stage Heat
24 – Volt Common
Full Stage Compressor
24 – Volt Hot (Heat XFMR)
Fan
24 – Volt Hot (Cool XFMR)
Full Stage Heat
External Humidistat
2
(Optional)
Open on Humidity Rise
RH
RC
SINGLE STAGE PSC
FURNACE
C
Y
G
W
24VAC Humidifier
(Optional)
C
24 – Volt Common
Y/Y2
Full Stage Compressor
R
24 – Volt Hot
G
Fan
W
Full Stage Heat
1
SINGLE STAGE
AIR CONDITIONER
C
24 – Volt Common
Y
Compressor Contactor
Thermostat Installer Setup
1-System Type-must be
set to 0 Thermostat Installer Setup 15-Compressor Protection
must be set to 5
Selection of GAS/ELEC
switch on thermostat
is not necessary
Part Number:
2
S1-2HU16700124
Other Part Numbers:
SAP = Legacy
265901 = 031-09166
1
FIGURE 12: Thermostat Chart - Single Stage AC with PSC Furnace
10 Johnson Controls Unitary Products
347337-UIM-A-0408
INDICATIONS OF PROPER OPERATION
Cooling
1. The outdoor fan should be running, with warm air being dis­charged from the top of the unit.
2. The indoor blower (furnace or air handler) will be operating, dis­charging cool air from the ducts. Coils or other parts in the air cir­cuit should be cleaned as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment, or other suitable means.
3. The vapor line at the outdoor unit will feel cool to the touch.
4. The liquid line at the outdoor unit will feel warm to the touch.
Instructing the Owner
Assist owner with processing warranty cards. Review Owners Guide and provide a copy to the owner and guidance on proper operation and maintenance. Instruct the owner or the operator how to start, stop and adjust temperature setting.
When applicable, instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the “OFF” cycle. The heater is energized only when the unit is not running. If the main switch is disconnected for long peri­ods, do not attempt to start the unit until 8 hours after the switch has been connected. This will allow sufficient time for all liquid refrigerant to be driven out of the compressor.
The installer should also instruct the owner on proper operation and maintenance of all other system components.
Maintenance
1. Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit. Clean as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment, or other suitable means.
2. The outdoor fan motor is permanently lubricated and does not require periodic oiling.
3. If the coil needs to be cleaned, it should be washed with Calgon Coilclean (mix one part Coilclean to seven parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted surfaces.
4. Refer to the furnace or air handler instructions for filter and blower motor maintenance.
5. The indoor coil drain pan should be inspected and cleaned regu­larly to prevent odors and assure proper drainage.
Johnson Controls Unitary Products 11
NOTES
Subject to change without notice. Printed in U.S.A. 347337-UIM-A-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 259715-UIM-A-0606
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 7306
Loading...