T500 Series Thermostats provide an economical
control solution for single-stage, multi-stage, or heat
pump systems. Two temperature settings can be
selected, as well as heat, cool, automatic
changeover, and off modes.
Thermostats are available in the following types:
T500HCN-1 (1 heat/1 cool), T500HPN-1 (heat pump,
3 heat, 2 cool), T500MSN-1 (2 heat/2 cool). Each
thermostat is packaged with the necessary mounting
hardware, and installation is simple and fast for
reduced cost.
Part No. 24-8341-19, Rev. Cwww.johnsoncontrols.com
Code No. LIT-216178
1
Page 2
ntroduction
I
ocation Considerations
L
The T500 thermostats use an adaptive control
routine, based on fuzzy logic, to determine the
heating or cooling load of the controlled space.
The routine calculates load by evaluating recent
room conditions, and room reactions to heating and
cooling. This load is used to determine the cycle rate
of the equipment, giving optimal control of the space.
114. 3
(4-1/2)
101.6
(4)
22.2
(7/8)
Locate T500 thermostats as follows:
•
on a partitioning interior wall, and approximately
1.5 m (5 ft) above the floor in a location of
average temperature
•
away from direct sunlight or radiant heat, outside
walls or behind doors, air discharge grills,
stairwells, or outside doors
•
away from steam or water pipes, warm air
stacks, unheated/uncooled areas, or sources of
electrical interference
!
CAUTION:
nstallation and Wiring
I
Note:When replacing an existing thermostat,
remove and use wire tags to identify terminal
designations.
To install and wire the thermostat:
Shock Hazard.
Disconnect power supply
before wiring connections are
made to prevent electrical
shock or possible damage to
the equipment.
1. Lift the thermostat cover and insert a small coin
Dmnsn
Figure 2: T500 Dimensions, mm (in.)
upplies Needed
S
•
drill
•
4.7 mm (3/16 in.) drill bit
•
3 mm (1/8 in.) flat-blade screwdriver
•
hammer
•
marking pencil
•
wire stripper
2
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
into the slot located in the bottom center of the
thermostat case and twist 1/4 turn. Grasp the
base from the bottom two corners and separate
from the thermostat. (See Figure 3.)
2. Swing the thermostat out from the bottom, and
lift up and out of the base. Place the rectangular
opening in the base over the equipment control
wires protruding from the wall and, using the
base as a template, mark the location of the two
mounting holes. No leveling is required.
3. Use the supplied anchors and screws for
mounting on drywall or plaster. Drill two 4.7 mm
(3/16 in.) holes at the marked locations, and tap
nylon anchors flush to wall surface and fasten.
(See Figure 4.)
4. Connect the wires from the existing system to
the thermostat terminals according to the wiring
designations in Table 4, Table 5, or Table 6.
Push extra wire back into the wall. Wires must
be flush to the plastic base. Plug hole with a
fireproof material to prevent drafts from affecting
the ambient temperature readings.
Page 3
!
CAUTION:
Equipment Damage Hazard.
Before applying power, make
all wiring connections and
check the connections.
Short-circuited or improperly
connected wires may result in
permanent damage to the
unit.
Mount
Figure 4: Mounting the Base
Figure 3: Separating the T500 from the Base
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
3
Page 4
nstalling the Thermostat Cover Lock
I
If desired, insert the plastic lock piece into the
bottom of the mounted base. The ends of the lock
piece should fit snugly under the lock pins extending
from the bottom of the mounted base. The tab in the
middle of the lock piece should extend downward
from the mounted base. (See Figure 5.)
To release the lock, press the lock piece up and into
the base while gently prying open the thermostat’s
cover at the same time. Use caution to avoid
cracking the thermostat base or cover.
eattaching the Thermostat and Cover
R
to the Installed Base
1. Position the thermostat inside the cover and
attach on the hinged tabs located at the top of
the base.
2. Swing the thermostat and cover down, and press
on the bottom center edge until they snap in
place. (See Figure 6.)
Hinged
Ta b s
Plastic Lock Pin
Snap
plastic lock
into place.
Figure 5: Installing the Thermostat Lock
Thermostat
Base
Figure 6: Installing the T500 Thermostat
4
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Page 5
IP Switch Selections
D
!
CAUTION:
Equipment Damage Hazard.
Before selecting a minimum
on/off time, ensure the
equipment can tolerate the
following maximum hourly cycle
rates: 7.5 cycles per hour when
using 4-minute on/off, or
15 cycles per hour when using
2-minute on/off.
Table 1: T500HCN-1 DIP Switch Selections
DIP SwitchSwitch
Selection
1
2
3
OnAllows 2-minute minimum on/off time for heating or cooling equipment.
OffAllows 4-minute minimum on/off time for heating or cooling equipment.
OnLocks the keyboard, disabling buttons to prevent tampering.
OffUnlocks the keyboard.
OnIn heating mode, allows the fan to delay with the plenum switch with a call
OffIn heating or cooling mode, allows the fan to operate immediately with a
Description
(Only the
Thermostat, Changing Settings While the Keyboard is Locked
Temporary Override While the Keyboard is Locked
for heat. However, in cooling mode, allows the fan to operate immediately
with a call for cooling.
call for heat or cooling.
Outdoor
and ∨∨∨∨ and ∧∧∧∧ buttons will function. See
in this bulletin.)
Setting the
and
5
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Page 6
Table 2: T500HPN-1 DIP Switch Selections
DIP SwitchSwitch
Selection
Description
1
2
3
4
5
6
7
8
OnCompressor/Auxiliary Interlocked: Turns off the compressor when the auxiliary
heat is on. The compressor will remain off for two minutes after the auxiliary
heat is turned off to ensure that the heat pump coil has cooled.
OffCompressor/Auxiliary Normal: Allows the compressor and auxiliary heat to be
on simultaneously.
Not usedNot used. Switch should remain in the off position.
OnAllows 2-minute minimum on/off time for heating or cooling equipment.
OffAllows 4-minute minimum on/off time for heating or cooling equipment.
OnLocks the keyboard, disabling buttons to prevent tampering.
(Only the
Thermostat, Changing Settings While the Keyboard is Locked,
Override While the Keyboard is Locked
OffUnlocks the keyboard.
OnMinimizes the use of auxiliary heat by disabling the auxiliary heat when the
room temperature is within 0.5° of the setpoint and not allowing a forced “On”
of the equipment.
OffAllows a forced “On” of the equipment by allowing the user to raise the setpoint
over 2° above the room temperature.
OnAllows multi-stage heating or cooling.
OffAllows single-stage heating or cooling.
LED 1 icon
off/on
(See Table 7.)
LED 2 icon
off/on
(See Table 7.)
Optional selection: LCD icon comes on with LED 1.
Optional selection: LCD icon comes on with LED 2.
Outdoor
and ∨∨∨∨ and ∧∧∧∧ buttons will function. See
in this bulletin.)
Setting the
and
Temporary
6
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Page 7
Table 3: T500MSN-1 DIP Switch Selections
DIP SwitchSwitch
Selection
Description
1
2
3
4
5
6
OnAllows 2-minute minimum on/off time for heating or cooling equipment.
OffAllows 4-minute minimum on/off time for heating or cooling equipment.
OnLocks the keyboard, disabling buttons to prevent tampering.
(Only the
Thermostat, Changing Settings While the Keyboard is Locked,
Temporary Override While the Keyboard is Locked
OffUnlocks the keyboard.
OnIn heating mode, allows the fan to delay with the plenum switch with a call for
heat. However, in cooling mode, allows the fan to operate immediately with a
call for cooling.
OffIn heating mode or cooling mode, allows the fan to operate immediately with
a call for heat or cooling.
OnAllows multi-stage heating or cooling.
OffAllows single-stage heating or cooling.
LED 1 icon off/on
(See Table 7.)
LED 2 icon off/on
(See Table 7.)
Optional selection: LCD icon comes on with LED 1.
Optional selection: LCD icon comes on with LED 2.
Outdoor
and ∨∨∨∨ and ∧∧∧∧ buttons will function. See
Setting the
and
in this bulletin.)
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
7
Page 8
ON
Heat/Cool: 4 Minute
Minimum On/Off
Fan Immediate
with Call for Heat
1
2
3
Heat/Cool: 2 Minute
Minimum On/Off
Keyboard LockedKeyboard Unlocked
Fan On with Plenum
Temperature Switch
Figure 7: T500HCN-1 Factory-Set DIP Switch
Settings (All Off)
CLK1
CLK2
RS2
RS1
RS+V
Heating
Cooling
Fan
24VAC
Common
W1
Y1
G
R
24V
24V(c)
Table 4: T500HCN-1 Output Terminal
Designations
TerminalFunction
W1
Y1
G
R
24V
24V(c)
CLK1
CLK2
RS2
RS1
RS+V
Energizes on call for heating
Energizes on call for cooling
Energizes fan on call for heating or
cooling or by pressing the
Fan
button
Independent switching voltage
24 VAC from equipment transformer
24 VAC (common) from equipment
transformer
Connections for remote clock/timer for
alternate setpoints
Connections for outdoor air temperature
or indoor remote sensors; refer to
instructions included with sensors
Hcn-1wire
Figure 8: T500HCN-1 Wiring Configuration
8
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Page 9
Compressor/Auxiliary
Normal
Not Used
Heat/Cool: 4 Minute
(Minimum On)
Keyboard Unlocked
Economy
Single Stage
LED 1 Icon Off
LED 2 Icon Off
1
2
3
4
5
6
7
8
ON
Compressor/Auxiliary
Interlocked
Not Used
Heat/Cool: 2 Minute
(Minimum On)
Keyboard Locked
Comfort
Multi-stage
LED 1 Icon
(Filter)
LED 2 Icon
(Wrench/Fault)
Figure 9: T500HPN-1 Factory-Set DIP Switch
Settings
LED1
2nd Stage Heat Pump
LED2
CLK1
CLK2
RS2
RS1
RS+V
1st Stage Heating
1st Stage Cooli ng
Cool Reversing Valve
Heat Reversing Valve
Fan
24VAC
Common
Y2
W1
Y1
Table 5: T500HPN-1 Output Terminal
Designations
TerminalFunction
Y2
W1
Y1
G
R
24V
24V(c)
LED 1
LED 2
CLK1
CLK2
RS2
RS1
RS+V
O
B
Energizes compressor No. 2 on a call
for second-stage heating or cooling
Energizes auxiliary stage heat as
third-stage heating or emergency heat
Energizes compressor No. 1 on a call
for second-stage heating or cooling
Energizes fan on a call for heating or
cooling or by pressing
Fan
button
Independent switching voltage
24 VAC from equipment transformer
24 VAC (common) from equipment
transformer
Input connection that energizes LED 1
or LED 2 from remote status device
(See Figure 10 and Table 7.)
Connections for remote clock/timer for
alternate setpoints
Connections for outdoor air
temperature or indoor remote sensors;
refer to instructions included with
sensors
Energizes reversing valve in the
cooling mode
Energizes reversing valve in the
heating mode
Figure 10: T500HPN-1 Wiring Configuration
Hpn-1wire
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
9
Page 10
Heat/Cool: 4 Minute
(Minimum On/Off)
Keyboard Unlocked
Fan immediate with
a call for heat
Single Stage
LED 1 Icon Off
LED 2 Icon Off
1
2
3
4
5
6
ON
Heat/Cool: 2 Minute
(Minimum On/Off)
Keyboard Locked
Fan on with plenum
switch
Multi-stage
LED 1 Icon
(Filter)
LED 2 Icon
(Wrench/Fault)
Figure 11: T500MSN-1 Factory-Set DIP Switch
Settings
2nd Stage Cooling
LED1
1st Stage Heating
LED2
1st Stage Cooli ng
CLK1
CLK2
RS2
RS1
RS+V
Fan
24VAC
Common
Y2
R
24V
Table 6: T500MSN-1 Output Terminal
Designations
TerminalFunction
W2
Y2
W1
Y1
G
R
24V
24V(c)
LED 1
LED 2
CLK1
CLK2
RS2
RS1
RS+V
Energizes on a call for second-stage
heat
Energizes on a call for second-stage
cooling
Energizes on a call for first-stage
heat
Energizes on a call for first-stage
cooling
Energizes fan on call for heating or
cooling or by pressing the
Fan
button
Independent switching voltage
24 VAC from equipment transformer
24 VAC (common) from equipment
transformer
Input connection that energizes
LED 1 or LED 2 from remote status
device (See Figure 12 and Table 7.)
Connections for remote clock/timer
for alternate setpoints
Connection for outdoor temperature
sensor and/or indoor remote sensor
option; refer to instructions included
with sensors
MSN-1Wire
Figure 12: T500MSN-1 Wiring Configuration
10
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Page 11
iring Diagrams
W
If the transformer (T2) is to power all of the loads R and
24V must be connected by insert ing jumper J 1 located
above the relays. If a separate 24V transformer (T1) is to be
used, remove the jumper J 1 to disconnect R and 24V(c).
P
P
JP1
Electronics
W1
1st Stage
Heat
Y1G
1st Stage
Compressor
24V
Fan
Optional
R
T1
24V(c)
T2
RS+V
RS1
Remote
Sensor
(if used)
RS2
Figure 13: T500HCN-1 Wiring Schematic
CLK2
CLK1
Remote
Clock/Timer
(if used)
Thermostat
Equipment
Hcn-1
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
11
Page 12
If the transformer (T2) is to power all of the loads
R and 24V must be connected by inserting jumper J 1
located above the relays. If a separate 24V transformer
(T1) is to be used remove the jumper J 1 to disconnect R and 24V(c).
P
P
J1P
Compressor
1st Stage
Auxiliary
Y1Y2GOBR
1st Stage
2nd Stage
Compressor
Fan
Reverse
Val ve
Heating
Reverse
Val ve
Cooling
Optional
24V
T1
Figure 14: T500HPN-1 Wiring Schematic
If the transformer (T2) is to power all of the loads R and 24V
must be connected by inserting jumper J 1 located above
the relays. If a separate 24V transformer (T1) is to
be used, remove the jumper J 1 to disconnect R and 24V(c).
P
P
JP1
24V(c)
T2
Electronics
LED1W1
LED2
Field Contact Switches
RS+V RS1 RS2
Remote
Sensor
(if used)
Electronics
CLK2
CLK1
Remote
Clock/Timer
(if used)
Thermostat
Equipment
HPN-1
W1
1st Stage
Heat
Y1
2nd Stage
1st Stage
Cool
W2
Heat
Y2
2nd Stage
Cool
Optional
G
Fan
24V
R
T1T2
24V(c)
LED2
LED1
Field Contact Switches
Figure 15: T500MSN-1 Wiring Schematic
RS+V
Remote
Sensor
(if used)
RS1
RS2
CLK1
Clock/Timer
CLK2
Remote
(if used)
Thermostat
Equipment
12
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Page 13
ommissioning
C
The thermostat normally displays room temperature
and mode of operation (whether cooling
heating
T
is currently on).
hermostat Operation Overview
or
Table 7: LED Indicators (T500MSN-1,
T500HPN-1 only)
LED PositionFunction
Left
Center
Right
LEDs (T500HPN, T500MSN only) indicate
system activity or problems (See Table 1).
Indicates filter needs
changing. Controlled by
external switch on LED 1.
Display of the filter symbol can
be enabled; see Table 2 and
Table 3.
(T500HPN-1 only) Indicates
when highest stage heat is
activated. Internally controlled.
Indicates a fault. Controlled by
external switch on LED 2.
Display of the wrench symbol
can be enabled; see Table 2
and Table 3.
Used to select heating or
cooling mode of operation
Used to run fan
continuously.
Mode
Fan
Outdoor
Day/Night
Face
Used to display outdoor
temperature (optional).
Used to alternate between day
and night setpoints.
Used to increase/decrease values
or change between Degree C or F.
Figure 16: T500 Non-Programmable Pushbuttons
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
13
Page 14
Mode
Repeated pressing of the
Mode
button allows
selection from four modes of operation (five for the
T500HPN-1/Heat Pump model):
•
When the
COOL
Snowflake
symbol
and the word
are displayed, the thermostat is in the
cooling mode. When the thermostat is calling for
cooling, the snowflake will flash.
•
When the
Flame
symbol
and the word
HEAT
are displayed, the thermostat is in the heating
mode. When the thermostat is calling for
heating, the flame will flash.
•
When the
Flame
symbol
and
E Ht
(emergency heat) are displayed, the thermostat
will control using the emergency heat with the
compressor locked out. (T500HPN-1/Heat Pump
only.)
•
When the
symbols and word
Snowflake
AUTO
and the
are displayed, the
Flame
thermostat will automatically change over
between heating and cooling.
Note:The thermostat never allows less than a 1°C
(2°F) difference between cooling and heating
setpoints.
•
When
OFF
is displayed, the equipment will not
operate.
Note:Use caution when using the
OFF
mode in
extremely cold weather.
75
Outdoor
Day/Night
Press to
select
continuous
fan operation
Mode
Fan
Figure 17: Selecting Continuous Fan Operation
Outdoor Button
When an outdoor temperature sensor (order
separately) is connected to the T500 thermostat, you
can display the current outdoor temperature by
pressing the
Outdoor
button. If the sensor option is
not connected, the thermostat will display “— —”.
See the
Ordering Information
section.
Day/Night Button
When the T500 thermostat is first installed or after a
power loss, the display will show the
the temperature, and the mode. To select an
alternate or
Night
temperature:
Day
symbol
,
•
Celsius/Fahrenheit
and
∧∧∧∧
buttons simultaneously to
Press the
∨∨∨∨
alternate between Celsius and Fahrenheit display.
Press the
•
Install a time clock using the CLK1 and CLK2
terminals, to activate the thermostat’s night
mode. (The T500 Thermostat will remember the
Fan
If continuous fan is not selected, the fan will operate
night mode setpoint.) See
Terminals CLK1 - CLK2.
automatically and the fan symbol will be off. To
select continuous fan operation, press the
button. The Fan symbol
will be displayed.
Fan
(See Figure 17.)
14
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Day/Night
button,
Options: Clock
or
Page 15
etting the Thermostat
S
O
ptions
1. Press the
2. Set the mode to cooling
3. Select the desired temperature for equipment to
maintain while in the cooling mode using the
∨∨∨∨
or
16 to 40°C (60 to 108°F).
4. Set the mode to heat
5. Select the desired temperature for equipment to
maintain while in the heating mode using the
or
∨∨∨∨
5 to 30°C (38 to 88°F).
6. Press the
and repeat Steps 2 through 5.
Day/Night
∧∧∧∧
buttons. The cooling setpoint range is
∧∧∧∧
buttons. The heating setpoint range is
Day/Night
button until is displayed.
.
.
button until is displayed
Changing Settings While the Keyboard
is Locked
To change settings while the DIP switch is set to lock
the keyboard:
1. Open the thermostat and switch the DIP switch
to unlock the keyboard. (See Table 1, Table 2
and Table 3). Close the thermostat.
2. Make the necessary changes.
3. Open the thermostat and switch the DIP switch
to lock the keyboard again. Close the
thermostat.
,
Temporary Override While the Keyboard
is Locked
Clock Terminals CLK1 - CLK2
The T500 thermostat has a contact closure for a
clock/timer to allow the use of alternate heating and
cooling setpoints.
When the contact is open, the day symbol
displayed and the thermostat controls to the day
setpoint. When the contact is closed, the
symbol
the night setpoint.
Pressing the
is in night mode will switch the thermostat to the day
mode, even if a clock/timer is used. The CLK
contacts on the thermostat are parallel with the
thermostat contacts and will change to the next
command given by the clock. Therefore, if the
thermostat is in night mode (contacts closed) and the
thermostat is switched to the day mode (contacts
open), then at the next clock control time the
thermostat will stay in the day mode.
is displayed and the thermostat controls to
Day/Night
button when the thermostat
is
Night
Remote Sensor
The indoor remote sensor allows the T500 to be
mounted away from the controlled space, and allows
use of multiple sensors for temperature averaging.
Order separately. See
Accessories
.
Table 10: Optional
Outdoor Sensor
Order separately. See
Accessories
.
Table 10: Optional
To alter the setpoint while the DIP switch is set to
or
lock the keyboard, press the
the setpoint ± 3°C or ± 6°F. This will temporarily
change the setting for 1 hour. If the setpoint is
altered while in night mode, the thermostat will
change to the day mode setting.
ensor Calibration (Fan/10 Seconds)
S
The internal and remote sensors can be calibrated to
eliminate wire resistance errors or to match another
reference.
1. Press and hold the
2. Adjust the temperature with the
The temperature is shown on the lower display
to the hundredths place. For example, 72°F on
the large display is shown as 72 13.
∨∨∨∨
Fan
button for 10 seconds.
ower Failures
∧∧∧∧
buttons to alter
or
∨∨∨∨
∧∧∧∧
buttons.
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
P
In the event of a power failure, the thermostat will
retain setpoints. When power is restored, it will
continue normal operation and will not require
resetting unless power was lost when the thermostat
was in the night mode, in which case it will return to
the day mode.
15
Page 16
uzzy Logic Control
F
Over time, the T500 learns how long it takes the
system to meet the load. If the system can change
the room temperature quickly, the T500 allows the
thermostat to drift further from setpoint before
starting the equipment. If the system takes a longer
period of time to change the room temperature, it will
not allow the temperature to drift as far from setpoint.
The T500 also takes into account the minimum
On/Off times.
The 2-minute On/Off time allows the equipment to
cycle more frequently at smaller differentials than the
4-minute On/Off time.
For multi-stage applications, the T500 does not bring
on the next stage of cooling or heating if it knows
that the system can change the temperature by
6 degrees in 1 hour, or 1 degree in 10 minutes. To
verify thermostat operation, force the next stage on
by changing the setpoint by more than 2 degrees.
erification
V
To verify proper functioning of the thermostat:
1. Press the
mode. (See Figure 18.)
Mode
button to select the heat or cool
If the equipment does not come on, proceed to the
Troubleshooting
Note:If you are using the T500HPN-1 and DIP
switch number 5 is in the “on” position, the
auxiliary heat will not come on when the
setpoint is raised more than two degrees
above room temperature (See Table 2.)
Move the switch to the “off” position to force
on the auxiliary heat when the setpoint is
raised.
section.
75
Press to
select
mode (heat
or cool).
Mode
Fan
Outdoor
Day/Night
or
∨∨∨∨
2. Press the
above or below the current ambient temperature.
The thermostat should call for either heating or
cooling, and should activate the fan.
∧∧∧∧
buttons to raise the setpoint
Npiface3
Figure 18: Verifying Proper Operation
16
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Page 17
roubleshooting
T
Table 8: Troubleshooting
SymptomPossible CauseCorrective Action
No display/faint display ...
Keyboard inoperative ...
Thermostat will not call for
heat ...
Thermostat will not call for
cooling ...
Fan does not turn on with
the system ...
“AC” is displayed on the
LCD ...
LCD shows missing or
extra segments ...
Supply voltage incorrectUse a voltmeter to check the voltage between the 24V and
24V(c) terminals. Voltage should be between 20-30 VAC. If
voltage is less than 20 VAC, disconnect the thermostat and
check the voltage between 24V and the other system wires;
see possible causes below. If voltage is greater than
30 VAC, troubleshoot the power source and replace the
thermostat.
System transformer weak
or overloaded
Thermostat damaged
because system voltage
was greater than 30 VAC
Keyboard lockedSwitch the keyboard DIP switch to the unlocked position.
Short cycle delay still in
progress
Thermostat setpoint is
satisfied
T500HPN-1 ONLY: If DIP
switch number 5 is in the
“on” position, the auxiliary
heat will not come on when
the setpoint is raised more
than two degrees above
room temperature.
(See Table 2.)
Short cycle delay still in
progress
Thermostat setpoint is
satisfied
Fan failurePlace a jumper between Terminals R and G. Fan should
20-30 VAC absent from
R and C terminals
LCD failureReplace the unit.
Check and/or replace with a suitable 24V transformer.
Replace with new thermostat, and ensure new thermostat is
isolated from the system using suitable relays and a
transformer of the proper rating.
Wait 4 minutes, equipment short cycle protection in
progress.
Raise the heating setpoint using the
Move the switch to the “off” position to force on the auxiliary
heat when the setpoint is raised.
Wait 4 minutes, equipment short cycle protection in
progress.
Lower the cooling setpoint using the
come on. If it does not, troubleshoot the fan system. If fan
does come on, replace the thermostat.
Using a voltmeter, measure voltage between the 24V and
24V(c) terminals. If the reading is less than 20 VAC, check
system transformer. If the voltage is between 20-30 VAC,
replace the thermostat.
* The Non-Programmable T500 Thermostats do not have a
supercap back up. The “AC” on the LCD will therefore
never flash.
button.
∧∧∧∧
button.
∨∨∨∨
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Remote Indoor Air Temperature Communication Module with Integral Sensor
Outdoor Air Temperature Communication Module with Outdoor Air Sensor
Outdoor Air Temperature Communication Module with Duct Mount Sensor
eplacement and Repair Parts
R
The SEN-500 series of products allows for easy
replacement of the sensor. For a replacement
sensor, contact the nearest Johnson Controls
branch office or wholesale distributor and order using
the information from
Table 11: Replacement Parts
and
Table 10: Optional Accessories
SEN-500-1
SEN-500-2
SEN-500-3
.
Table 11: Replacement Parts
ItemProduct Code Number
Replacement Outdoor Air Temperature Communication Module
Replacement Outdoor Air Temperature Sensor (includes mounting hardware)
Replacement Duct Mount Temperature Sensor (includes mounting hardware)
SEN-500-603
SEN-500-604
SEN-500-605
Table 12: Repair Parts
ItemProduct Code Number
3 in. Sensor Probe (use with outdoor air sensor)
8 in. Sensor Probe (use with duct mount sensor)
18
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
SEN-500-601
SEN-500-602
Page 19
Notes
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
19
Page 20
pecifications
S
Product
Power Requirements
Relay Contact Rating
Recommended Wire Size
Thermostat Measurement
Range
Outdoor Air Temperature
Indication Range
Control Range
Display Resolution
Minimum Deadband
°C/°F Conversion
Ambient Operating
Conditions
Ambient Storage
Conditions
Dimensions (H x W x D)
Shipping Weight
FCC Compliance
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products
T500HCN-1, T500MSN-1, T500HPN-1
20-30 VAC, 50/60 Hz, 24 VAC nominal
Maximum Inductive:1 ampere with surges to 3 amperes, 24 VAC Class 2
Maximum Resistive:1 ampere, 24 VDC (2000 VA Maximum for all outputs)
Minimum:10 uA for 24 VAC circuit; 10 mA for 24 VDC circuit
24-18 gauge
0 to 48°C (28 to 124°F)
-48 to 48°C (-50 to 124°F)
Heating: 5 to 30°C in 1° steps; 38 to 88°F in 1° steps
Cooling: 16 to 40°C in 1° steps; 60 to 108°F in 1° steps
1C or 1F
1°C or 2°F between heating and cooling
20°C = 68°F, each Celsius degree above or below 20°C = 2°F
0 to 55°C (32 to 131°F), 5 to 90% RH non-condensing
-34 to 55°C (-30 to 131°F)
114.3 x 101.6 x 22.2 mm (4 1/2 x 4 x 7/8 in.)
0.171 kg (0.37 lb)
This equipment has been tested and found to comply with the limits for a Class A digital
device and verified to Class B pursuant to Part 15 of FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when this equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his/her own expense.
This device complies with Class A Part 15 of the FCC rules. It was also verified to Class B. Operation is subject to the following two
conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause undesired operation.
This Class A digital apparatus meets all of the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil
numerique de la Classe A respecte toutes les exigences du Reglement sur le materiel brouilleur du Canada.
Controls Group
507 E. Michigan Street
P.O. Box 423Printed in U.S.A.
Milwaukee, WI 53201www.johnsoncontrols.com
20
T500 Series Non-Programmable Thermostats Product/Technical Bulletin
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.