Johnson S1-TTSCC01 Installation Manual

Page 1
Johnson Controls Unitary Products 542933-UIM-C-0112
INSTALLATION MANUAL
TOUCH SCREEN COMMUNICATING CONTROL
MODELS: S1-TTSCC01
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MOUNTING THE TOUCH SCREEN COMMUNICATING CONTROL . . . . . . . . . . . . . . . . . . . 4
REMOVING CONTROL MOUNTING BACK PLATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
WIRING COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
WIRING REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SYSTEM WIRING OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
HUMIDIFIER CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
INITIAL POWER-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
POWER-UP SEQUENCE (SYSTEM MASTER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SYSTEM CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ENTERING SERVICE MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SERVICE MODE ON MASTER CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NAVIGATING SERVICE MODE: MASTER CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
FORCED OPERATION: MASTER CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
SERVICE TOOL SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Page 2
542933-UIM-C-0112
2 Johnson Controls Unitary Products
SECTION I: GENERAL
The Touch Screen Communicating Control is designed to manage communicating system compo­nents (including: heat pumps, air conditioners, air handlers and furnaces). In general, these compo­nents are the variable speed modulating furnace and variable speed air handler, premium 15 and 18 SEER air conditioners or premium 13, 15 and 18 SEER heat pumps.
While the communicating system has been designed for easy installation, this document will pro­vide the installer with a more detailed explanation of installation process.
SECTION II: SAFETY CONSIDERATIONS
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to
the potential for personal injury and equipment damage. Understand and pay particular attention to the signal words DANGER, WARNING, and CAUTION.
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not avoided, could result i n death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only prop-
erty damage.
INSPECTION
The following list details the parts included in this kit. Examine the kit to insure that all parts are included.
LIMITATIONS
The Touch Screen Communicating Control’s primary function is to command a system containing communicating product.
Exceptions to this rule are:
Installing a communicating variable speed modulating furnace with a non-communicating air conditioner. In this case the variable speed modulating furnace relays 24 VAC outputs to the non-communicating air conditioner (per communicated commands by the Touch Screen Communicating Control).
Installing communicating controls in non-communicating UPG products.
Installing Communicating Interface Control (which converts communicating commands into 24VAC outputs).
Item QTY. Description
1 1 Touch Screen Communicating Control 2 1 Communicating Plug Harness 3 1 Screw and Anchor Hardware bag 4 1 USB Adapter 5 1 Installation Instructions 6 1 Owner's Manual 7 1 Quick Help Document 8 1 Warranty Certificate 9 1 Warranty Regist ration Card
Page 3
542933-UIM-C-0112
Johnson Controls Unitary Products 3
SECTION III: INSTALLA TION
The intention of this document is to ensure proper connection/setup of the various communicating system components. These instructions should be used in conjunction with the instructions pro­vided with indoor, outdoor and accessory equipment of which the Touch Screen Communicating Control will command.
This installation instruction cont ains (in part) setup, operation, and t roubleshootin g of the UPG Com­municating System.
The Touch Screen Communicating Control will engage the inst aller with sp ecial screen prompt s and introduce settings to simplify and provide a path through the initial start up of the system.
When Installing this Product...
1. Read all instructions carefully before beginning installation. Failure to follow these instructions can create hazardous situations or damage the product.
2. Make certain the product is suitable for your application by checking all ratings on the product and in the instruction provided.
3. Installer must be a trained, experienced service technician.
LOCATION
Install the Touch Screen Communica ting Control at or around 5 ft. (1.5m) above the floor in an area with good circulation of room temperature. See Figure 1.
Do not install the Touch Screen Communicating Control wher e it can be affected by:
Drafts or dead spots behind doors and in corners
Hot or cold air from ducts
Radiant heat from sun or appliances
Concealed pipes and chimneys
Unconditioned areas such as an outside wall
FIGURE 1:
Control Location
NO
NO
NO
YES
5 FEET
(1.5 METERS)
Page 4
542933-UIM-C-0112
4 Johnson Controls Unitary Products
MOUNTING THE TOUCH SCREEN COMMUNICATING CONTROL
For most installations, mounting Touch Screen Communicating Control can be done following some very basic installation steps outlined below. However, there may be some cases where the installer is not able to penetrate t he wall wh ere mount ing t he To uch Screen Communicat ing Control , or the re may be an application where the thermostat/control being replaced has left a larger hole than needed for installation of this control. For these and other applications, (including installation with a vertical j-box) an installer can obtain a Decorative/Mounting Kit (S1-02815909000).
1. If an existing thermostat or control is being replaced: a. Remove existing control from wall.
b. Disconnect wires from existing control. c. Properly discard or recycle old control.
2. Mark on the wall where the Touch Screen Communicating Control will be mounted (standard
height is 5 feet from the floor).
3. Cut a 2” x 2” square hole with the bottom of the square at the mark.
4. Using the mounting back plate as a template, mark the screw holes on the surface where
mounting the Touch Screen Communicating Control. Use a level to insure proper installation.
Voltage Hazard: Live wires can cause electrical shock or equipment damage. Disconnect power before beginning installation.
Mercury is a hazardous substance, if existing thermostat or control contains any mercury, it MUST be disposed of properly. The Touch Screen Communicating Control does not contain mer­cury.
If an existing thermostat was in place, it may be ideal to use the same location for the Touch Screen Communicating Control.
Make sure that th e hole is cut so that the Touch Screen Communicatin g Control can be leveled when mounted. See Figure 2 for more detailed mounting information.
NOTICE
NOTICE
NOTICE
Page 5
542933-UIM-C-0112
Johnson Controls Unitary Products 5
5. Remove mounting back plate.
6. Drill holes (3/16” in diameter) in the marked area to accommodate the anchors (provided in the
kit).
7. Place anchors in the pre-drilled holes. Be sure that the anchors are fully inserted.
8. Pull low voltage wires through the mounting back plate as shown in Figure 3.
9. Connect low voltage wires as instructed in the wiring secti on of this document.
10.Screw the wired mounting back plate to the wall using the screws provided in the kit.
11. Align the terminal screw block with the pins on the back of the Touch Screen Communicating
Control and snap it to the mounting back plate.
REMOVING CONTROL MOUNTING BACK PLATE
Gently remove by tilting up to release the bottom of the Touch Screen Communicating Control and then pull out/down to completely remove.
FIGURE 2:
Mounting Back Plate Dimensions
FIGURE 3: Wires Pulled Through Mounting Back Plate
Fastening the wires in the terminal block before attaching the back plate to the wall will ultimately ease the installation of the wire. Once on the wall, the terminal block has limited accessibility.
3-1/4”
2”
2”
5/8”
3/16”
1”
5/8”
Page 6
542933-UIM-C-0112
6 Johnson Controls Unitary Products
SECTION IV: WIRING COMMUNICATION
All wiring must comply with local electrical codes and ordinances. Refer to Table 1 for terminal des­ignations.
WIRING REQUIREMENTS
Standard 18 awg thermostat wires can be used to connect the communicating system. Special (shielded) cable is not typically required. As with all communicating devices, it is a good
idea to keep wiring at least one foot away from large inductive loads. Examples of large inductive loads include: electronic air cleaners, motors, etc. If these wiring practices are ignored, it may intro­duce electrical interference (noise) which can cause erratic system operation.
SYSTEM WIRING OVERVIEW
The system is connected by four wires. Two of the wires are used to bring power into the individual controls (R and C) and two of the wires are used for serial communication (A+ and B-). The plug/ harness that is provided in the kit should be used on the outdoor control.
Each Touch Screen Communicating Control Kit is equipped with a Communicating Plug Harness (Fig. 5). This wire harness should be used for the wiring of the outdoor unit.
TABLE 1:
Terminal Designations
Signal Definition Label
Data Non-inverted signal A (+) Low voltage power hot 24 VAC (Hot) R Low voltage power common and data
ground
24 VAC (Common) C
Data Inverted signal B (-)
There may be installation applications where large inductive loads cannot be avoided. In these cases shielded wire would be desired to ensure proper system functionality.
The communicating system requires 4 wires to operate. If installing a communicating system, be sure to supply at least 4 wires to each unit/control. Below is a simple diagram showing the ideal wiring path.
NOTICE
Page 7
542933-UIM-C-0112
Johnson Controls Unitary Products 7
FIGURE 4:
High Level Wiring Path
FIGURE 5: Communicating Plug Harness
FIGURE 6: Wiring Diagram (Fully communicating system components)
ARCB
COMM.COMM.
A - GREEN WIRE R - RED WIRE C - BLACK WIRE B - BLUE (WHITE WIRE)
ARCB
ARCB
ARCB
WHITE (B) BLACK (C) RED (R) GREEN (A)
1 2 3 4
Touch Screen
Communicating Control
VS Air Handler/Furnace Communicating Control
Air Conditioner/Heat Pump
Communicating Control
A+
R
C
B-
A+
R
GND
B-
A+
R
C
B-
Page 8
542933-UIM-C-0112
8 Johnson Controls Unitary Products
Touch Screen Communicating Control Wiring
1. Turn off all power to equipment.
2. Loosen the screws in the terminal block of the mounting back plate.
3. Match and connect thermostat wires to proper terminals on Touch Screen Communicating Con-
trol mounting back plate.
4. Push any excess wire back into the wall.
5. Once wires are secured, the mounting back plate can be placed on the wall as previously out-
lined.
FIGURE 7:
Wiring Diagram Communicating Furnace, Non-Communicating AC
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury, death, or equipment damage. Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
Plugging the hole in the wall wi th nonflammable insulation can help prevent draf ts from adversely affecting temperature control.
A+
R
C
B-
A+
R
GND
B-
LO
COMP
HI
COMP
O
DHUM
Y1
Y/Y2
W
R
G
C
Y
Y2
R
C
Touch Screen
Communicating Control
Modulating Furnace
Communicating Control
Non-Communicating
Air Conditioner
NOTICE
Page 9
542933-UIM-C-0112
Johnson Controls Unitary Products 9
Outdoor Control Wiring
A new communicating heat pump or air conditioner (denoted by a “-C” in the model number) will have two communicating plug terminals (as shown in Figure 8).
1. Disconnect all power from system (including high and low voltage).
2. Remove factory installed low voltage harness.
3. Plug the communication harness provided in the Touch Screen Communicating Control Kit (S1-
TTSCC01) into the communication port on the outdoor control.
4. Wire nut thermostat wire (from the indoor control) to the communication harness wires.
FIGURE 8:
Outdoor Communicating Terminals
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury, death, or equipment damage. Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
COMMUNICATING TERMINALS
COMMUNICATING AC CONTROL
COMMUNICATING HEAT PUMP CONTROL
Page 10
542933-UIM-C-0112
10 Johnson Controls Unitary Products
5. Set the wires which are now connected (with wire nuts) into the Junction Box of the control
housing (pictured below).
6. Set the appropriate jumper settings to insure proper control functionality (See table below).
When connecting the loose ends of the wire harness, be sure to note color for each of the four wires (A+, R, C, B-).
FIGURE 9:
Outdoor Control Housing
Unit Control
Jumpers which must be set
Heat Pump
Fossil Fuel
Hot Heat Pump
Air Conditioner No Jumpers to set
Jumpers listed here are required and if set incorrectl y will f lag an er ror upon install ation. While the other jumpers can be set from the Touch Screen Communicating Control, it is goo d practi ce t o ini­tially set all jumpers at the respective control. This will avoid any confusion that may occur with future service at the units.
For installation of a non-co mmunicating outdoor unit with the Touch Screen Communicating Con­trol, the installer should reference the indoor and outdoor unit installation instructions. If informa­tion is not provided, there may be a need for a Communicating Interface Control Field Kit (S1-
33102953000).
NOTICE
COMMUNICATIONS PORT
CONTROL BOARD
COMMUNICATIONS HARNESS
JUNCTION BOX
NOTICE
NOTICE
Page 11
542933-UIM-C-0112
Johnson Controls Unitary Products 11
Indoor Control Wiring
A communicating furnace or air handler (denoted by a “-C” in the model number) will arrive with a control outfitted for communication. The communicating indoor controls will have two communicat­ing terminals. One will be a communicating plug input and the other will be a screw terminal (as shown below in Figure 10).
1. Disconnect all power from system (including high and low voltage).
2. Screw the 4 wires from the Touch Screen Communicating Control and outdoor control to the
communicating screw terminal (8 wires in all). Be sure that all wires are connected respectively (A+ = A+, R = R, C = C, B- = B-).
FIGURE 10:
Communicating Indoor Controls
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury, death, or equipment damage. Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
If the installer finds that the indoor control screw terminals are presenting a challenge, wire nuts can be used to connect the controls on the outside of the indoor unit.
COMMUNICATING
FURNACE CONTROL
COMMUNICATING
AIR HANDLER (AV/MV)
CONTROL
COMMUNICATING TERMINALS
COMMUNICATING
AIR HANDLER (AHV)
CONTROL
NOTICE
Page 12
542933-UIM-C-0112
12 Johnson Controls Unitary Products
3. Set the appropriate jumper settings to insure proper control functionality (See table below).
The furnace control may be labeled so that C = GND.
FIGURE 11:
Indoor Screw Terminal Location
Unit Control Jumpers which must be set
Furnace
Heat Pump
Humidistat
Zone Control
Air Handler (AHV) No Jumpers Required
Air Handler (AV/MV)
Heat/No Heat
AC/HP
Hum Stat
Jumpers listed here are required and if set incorrectl y will f lag an er ror upon install ation. While the other jumpers can be set from the Touch Screen Communicating Control, it is goo d practi ce t o ini­tially set all jumpers at the respective control. This will avoid any confusion that may occur with future service at the units. The Hum Stat jumper on the air handler must be set to “YES”.
NOTICE
FURNACE COMMUNICATING PORT
AIR HANDLER COMMUNICATING PORT (AV/MV)
SCREW
TERMINAL
B-
GND
R
A+
NOTICE
Page 13
542933-UIM-C-0112
Johnson Controls Unitary Products 13
HUMIDIFIER CONNECTION
A bypass or fan powered humidifier may be installed with the communicating system. The installer should physically install the humidifiers according to the instructions that are included with the humidifier being installed. For information on the wiring of the humidifier, see below diagrams.
Bypass Humidifiers
Communicating Furnace
For installation of a non-communicating indoor unit with the Touch Screen Communicating Con­trol, the installer should reference the indoor and outdoor unit installation instructions. If informa­tion is not provided, there may be a need for use of an Communicating Interface Control Field Kit(S1-33102953000).
Do Not Use a traditional humidistat to control humidifier operation. If a humidifier is installed, the Touch Screen Communicating Control will operate humidifier.
FIGURE 12:
Furnace Bypass
NOTICE
NOTICE
B-
C
B-
R
W1
W2
O
HUM
X/L
R
G
Y/Y2
Y1
COM
Touch Screen
Communicating Control
Air Handler
Communicating Control
Air Conditioner/Heat Pump
Communicating Control
A+
C
B-
R
A+
C
B-
R
A+
HUM OUT
HOT
NEUTRAL
HUM OUT
Bypass Humidifier
120 VAC
24 VAC
Transformer
(120 VAC to 24 VAC)
Page 14
542933-UIM-C-0112
14 Johnson Controls Unitary Products
Communicating Air Handler
Fan Powered Humidifiers
Communicating Furnace
FIGURE 13:
Air Handler Bypass
FIGURE 14: Furnace Fan Powered
B-
C
B-
R
W1
W2
O
HUM
X/L
R
G
Y/Y2
Y1
COM
Touch Screen
Communicating Control
Air Handler
Communicating Control
Air Conditioner/Heat Pump
Communicating Control
A+
C
B-
R
A+
C
B-
R
A+
HUM OUT
HOT
NEUTRAL
C
R
Bypass Humidifier
B-
C
B-
R
W1
W2
O
HUM
X/L
R
G
Y/Y2
Y1
COM
Touch Screen
Communicating Control
Air Handler
Communicating Control
Air Conditioner/Heat Pump
Communicating Control
A+
C
B-
R
A+
C
B-
R
A+
HUM OUT
HOT
NEUTRAL
Fan Powered Humidifier
120 VAC Plug
Wall outlet
Jumper
Page 15
542933-UIM-C-0112
Johnson Controls Unitary Products 15
Communicating Air Handler
SECTION V: INITIAL PO WER-UP
Before applying power, check to make sure that all wiring has been complet ed as instr ucted throu gh the installation instructions of the equipment on the system.
Once power is applied, the installer should return to the thermostat to complete the installation pro­cess.
FIGURE 15:
Air Handler Fan Powered
Failure to follow this caution may result in equipment damage. Do not power the system until you have confirmed that the wiring has been completed correctly (per this document).
B-
C
B-
R
W1
W2
O
HUM
X/L
R
G
Y/Y2
Y1
COM
Touch Screen
Communicating Control
Air Handler
Communicating Control
Air Conditioner/Heat Pump
Communicating Control
A+
C
B-
R
A+
C
B-
R
A+
HUM OUT
HOT
NEUTRAL
Wall outlet
Contactor
HUM OUT
gul PCA
V021
Fan Powered
Humidifier
Page 16
542933-UIM-C-0112
16 Johnson Controls Unitary Products
POWER-UP SEQUENCE (SYSTEM MASTER)
The Touch Screen Communicating Control will guide the installer through the set up process. The following screens will load upon initial power up:
SCREEN 1 - Set date and time
SCREEN 2 - The control will Display Software Revision on the screen to insure that you are install-
ing a control with the most up to date software.
SCREEN 3 - The control will “listen” for network traffic for a random int erval between 1-10 seconds. SCREEN 4 - The control “gathers” system information (including indoor and outdoor system com-
ponents).
SCREEN 5 - Set Control “Mode”
SYSTEM CONFIGURATION
After selecting the “System Master Mode” button, the Touch Screen Communicating Control will begin a routine to “discover” system components. The installer will be directed through screens (Auto Setup) that are dependen t upon the system being conf igured. Th e below screens will appear dependent on equipment being installed.
If daylight savings is selected, on the second Sunday of March the clock will change from 1:59 am to 3:00 am. Likewise, on the first Sunday in November the clock will change from 1:59 am to 1:00 am
System Master
is for installation of a residential
system press. Demo mode
is for use of the Touch Screen Com­municating C ontrol as a sales o r trainin g tool an d will not control a system.
Service Tool Mode
is for use of the control to view operation of a system already being controlled by a Touch Screen Communicating Control in sys­tem master mode.
Done
Date/Time
12 hr 24 hr
Yes No
Date
Clock
Clock Format
Observe Daylight
Savings Time
08
12
May
00 AM
2009
:
Press the box to highlight and modify using the up/down arrows
The up/down arrows control the “Date” and “Clock”
Press the “12 hr” or “24 hr” to display standard or Military Time
Press “Yes” or “No” to observe Daylight savings
NOTICE
System Master
Mode
Service Tool
Mode
Demo
Mode
Select the desired mode of operation for this device.
11:07AM Thu 21 Jul
Page 17
542933-UIM-C-0112
Johnson Controls Unitary Products 17
Heat kit configuration screens will appear in a communication system that includes a communicat­ing variable speed air handler (indicated by a “-C” in t he model numbe r). For the AV/MV Air Handler, the heat jumper must be located in the "On" position. For more information on the function of these screens refer to the Service Mode section of this document.
Heat Pump Configuration screens are only available in systems which contain communicating heat pumps (denoted by a "-C" in the model number. For more information on the function of these screens refer to the Service Mode section of this document.
The screen shown above is representative only. Actual heat kit models may vary.
If you have a system which has a heat kit installed, but did not see the heat kit configuration screens, be sure to check the air handler control to insure that the heat kit jumper is on "Heat". This only applies to the AV/MV Air Handler.
System ID screen will appear in every communi­cating system install. This screen displays the sys­tem ID that is used to identify system operation. For more information about the system ID and how the system will operate refer to Communicat­ing Wiring Diagrams located on UPGnet.com.
Heat Kit Config
Back
11:07AM Thu 21 Jul
4HK*6500506 4HK*6500806 4HK*6501006
4HK*65020064HK*6501806
4HK*6501506
4HK*6502506
Selected Heat Kit: 4HK16501506
Heat Kit Config
11:07AM Thu 21 Jul
To select desired heat staging, select desired 1st stage KW:
1st stage heat:
9.6 KW
2nd stage heat:
14.4 KW
AcceptBack
NOTICE
Current System ID Configuration is: AC15
11:07AM Thu 21 Jul
Accept
Re-configure
Heat Pump Config
NextBack
1
Defrost Curve:
ON
Y2 Lock:
35
Switch Point:
ON
Compressor Delay:
11:07AM Thu 21 Jul
Heat Pump Config
Next
Furnace Only
Furnace/ Heat Pump
Heat Pump Only
Back
Low Temp Cutout= 10° Balance Point = 35°
Outdoor Temp F°
10 35
11:07AM Thu 21 Jul
Page 18
542933-UIM-C-0112
18 Johnson Controls Unitary Products
The Airflow Configuration screen is only available on a system that contains a variable speed com­municating indoor unit (denoted by "-C" in the model number). For more information on the function of this screen refer to the Service Mode section of this document.
The Airflow summary screen is only available on a system that contains a variable speed commu­nicating indoor unit (denoted by "-C" in the model number). The screen will be populated depending on the system being installed. For more informa­tion on the function of this screen refer to the Ser­vice Mode section of this document.
The modulating furnace airflow during heating is still controlled by the ignition control not the Touch Screen Communicating Control.
The Edit/Add Devices screen is shown for every system install. For the system to properly control accessories, they must be “ADDED” using this screen. The information displayed will depend on the system being installed. Accessories such as humidifiers, EAC, and UV lights are not commun i­cating, and model and serial numbers can be manually entered. For more information on the function of this screen refer to the Service Mode section of this document.
Maintenance Reminder screen is shown for every system install. Annual Maintenance Reminder can be entered by enabling the reminder and selecting the desired day and month. These are set up as you choose based on your business plan (i.e., do you want the homeowner to call for maintenance or not?). Two maintenance reminder events may be established (fall and spring).
Airflow Config
Next
Dry
Temperate
Humid
Normal
Delay Profile: Dry
Best in dry regions such as the southwest US. Increases the blower ramp-down times to help retain humidity.
Back
11:07AM Thu 21 Jul
NextBack
Heat Pump
Model YZH036
AH Model AV060 Heat Kit Model 4HKx6501506
530Set CFM 1950
Air Handler
High Heat
Low Heat
High Cool
Low Cool
809
1245
809
1245
4.3 KW
9.6 KW
4.8 KW
14.4 KW
Airflow Summary 11:07AM Thu 21 Jul
1860
730
NOTICE
Next
Back
Edit/Add Devices
Add
Device
Select a device to edit/add information:
11:07AM Thu 21 Jul
Other:
System ID = HP14
Other:
Furnace
Heat Pump
Humidifier
Maint Reminder
1st Maintenance Reminder
recurring every:
2nd Maintenance Reminder
recurring every:
Warning Alert:
Enabled
2 Weeks in Adv
Disabled
NextBack
08 May
/
11:07AM Thu 21 Jul
Page 19
542933-UIM-C-0112
Johnson Controls Unitary Products 19
SECTION VI: ENTERING SERVICE MODE
SERVICE MODE ON MASTER CONTROL
Once in the service mode, the thermostat background will be gray (as pictured below) and the con­trol can access system settings/information. The mast er has access to all areas of the co mmunicat­ing system.
NAVIGATING SERVICE MODE: MASTER CONTROL
Equipment details:
The equipment details screen d isplays fixed inf ormation which may includ e: System I D, Model n um­ber, Serial number and other details that pertain to the selected communicating equipment.
The Dealer Information screen is shown for every system install. This screen is for dealer informa­tion entry. Text can be entered with the keyboard or imported. For more information on the function of this screen refer to the Service Mode section of this document. This is the final setup screen. Once completed you can exit service mode for normal operation.
NOTE: For more information see “Navigating Service Mode: Master control” under SECTION VI of this document.
The master contr ol is a Touch Screen Communi­cating Control that has been configured to assume full control of a communicating system. To enter the service portion of the control press and hold (for 5 seconds) on the brand symbol located in the upper right hand side of a given screen (see picture).
From the system map (as shown) the controller provides access to view all communicating com­ponents and settings. Press the icon that relates to the part of the system that you would like to access and the controller will view each commu­nicating component’s: Equipment Details, Equip­ment Status, and Inputs/Outputs. Below is a description of each of these screens.
Next
Logo
Dealer Name Dealer Phone Number(s)
Dealer Address 1 Dealer Address 2 Dealer Email Dealer Website
Dealer Info
11:07AM Thu 21 Jul
Back
Edit
72°
Menu
Auto
ON
71
°
30%Humidity
3
0
%
%
dity
72°
11:07AM Thu 21 Jul
55°
Alert: Change Filter
Touch ICON for a detailed view
Log MenuRefresh Accessories
Exit Service Mode
Humidifier ON
UV Lamps ON
EAC Not Installed
Heat Pump OFF
Thermostat ON
Furnace ON
11:07AM Thu 7/21
UV La
ON
EAC
N
ot I
n
F
urn
a
O
N
Page 20
542933-UIM-C-0112
20 Johnson Controls Unitary Products
Equipment status:
The equipment status screen displays more dynamic information which may include: equipment state, timers, temperatures, fault code s, and o ther sta tuses that perta in to the selected communicat­ing equipment.
Equipment inputs/outputs:
Accessories Button:
The inputs/outputs screen displays system com­mands which may include: thermostat input sig­nals, control output signals and other input/ outputs that pertain to the selected communicat­ing equipment.
On each of the described screens there is a “Refresh” button. This button can be used to update the information on the screen to make sure all of the information being displayed is current.
From the system map the accessories button can be pressed. Here any additional accessories that have been added to the system can be viewed. This would include IAQ products such as ERV/ HRV, dehumidifiers, etc.
The details of the accessories are viewed by pressing the respective accessory icon.
Furnace
Back
Equipment
Details
Equipment
Status
Inputs / Outputs
11:07AM Thu 21 Jul
NOTICE
Touch ICON for a detailed view
Log MenuRefresh Accessories
Exit Service Mode
Humidifier ON
UV Lamps ON
EAC Not Installed
Heat Pump OFF
Thermostat ON
Furnace ON
11:07AM Thu 7/21
UV La
ON
EAC
N
ot I
n
F
urn
a
O
N
Touch ICON for a detailed view
NextBackRefresh
Accessories
BackRefresh
Touch ICON for a detailed view
Ventilator ON
Dehumidifier ON
11:07AM Thu 21 Jul
Page 21
542933-UIM-C-0112
Johnson Controls Unitary Products 21
Log Button: Master Control
Viewing Details of a Log Entry
Viewing/Filtering Displayed Log Content
All: Will display the full list of entries available on the system. Faults: Will display all faults that have occurred on the communicating system. Events: Will display all maintenance reminders and alerts that are not categorized as a fault. Custom: Will display custom entries that have been manually input. TSTAT: Will display all faults, alerts, and events that pertain to the Touch Screen Communicating
Control.
Inside: Will display all faults, alert s, and even ts that pe rtai n to the indoor communica ting equipme nt. Outside: Will display all faults, alerts, and events that pertain to the outdoor communicating equip-
ment.
From the system map, the “Log” button can be pressed. Here the event and fault log screen can be viewed. This screen displays maintenance reminders, custom log entries, and faults.
Pressing an entry displayed on the “Log” screen will prompt a screen that contains a more det ail ed description of the fault, event, alert , etc.
Press the filter button to narrow down the entries being displayed. The log entries displayed ca n be sorted by: All, Faults, Events, Custom, TSTAT, Inside, and Outside. See list below for more infor­mation.
Touch ICON for a detailed view
Log MenuRefresh Accessories
Exit Service Mode
Humidifier ON
UV Lamps ON
EAC Not Installed
Heat Pump OFF
Thermostat ON
Furnace ON
11:07AM Thu 7/21
UV La
ON
EAC
N
ot I
n
F
urn
a
O
N
Select Entry Detail
Log
11:07AM Thu 21 Jul
Thermostat Fault Thu 21 Jul 10:13AM Outdoor Equipment Fault Wed 10 Jul 1:26PM
BackClearNewExport
Filter
Select Entry Detail
Log
11:07AM Thu 21 Jul
Thermostat Fault Thu 21 Jul 10:13AM Outdoor Equipment Fault Wed 10 Jul 1:26PM
BackClearNewExport
Filter
Page 22
542933-UIM-C-0112
22 Johnson Controls Unitary Products
Exporting Log File
Clearing a Log Entry
New Event Entry
Press the Export button to export the displayed log information. Using this function gives the user the ability to save the log of a Touch Screen Com­municating Control for future reference.
If the export function is selected the user will be prompted to insert a USB device. Once the device is inserted, the Touch Screen Communi­cating Control will export the log information.
Do not remove the USB device until prompted.
Press the Clear button to delete all of the dis­played log entries. When the clear button is pressed, the Touch Screen Communicating Con­trol will delete the log entries per the sort selec­tion. For example, if “All” is selected in the sort screen, all of the log entries that have been saved on Touch Screen Communicating Control will be cleared (deleted).
Press the “New” button to create a new log entry. When the “Edit” button has been pre ssed the key­board will pop up to allow the user to manually input a log entry. This can be used to keep track of home service, visits, maintenance, etc. For example, the user can check to see when the last A-Coil cleaning had taken place (if ent ered at time of cleaning).
Select Entry Detail
Log
11:07AM Thu 21 Jul
Thermostat Fault Thu 21 Jul 10:13AM Outdoor Equipment Fault Wed 10 Jul 1:26PM
BackClearNewExport
Filter
NOTICE
Select Entry Detail
Log
11:07AM Thu 21 Jul
Thermostat Fault Thu 21 Jul 10:13AM Outdoor Equipment Fault Wed 10 Jul 1:26PM
BackClearNewExport
Filter
Select Entry Detail
Log
11:07AM Thu 21 Jul
Thermostat Fault Thu 21 Jul 10:13AM Outdoor Equipment Fault Wed 10 Jul 1:26PM
BackClearNewExport
Filter
Page 23
542933-UIM-C-0112
Johnson Controls Unitary Products 23
Service-Menu Button: Master Control
From the system map, the “menu” button can be pressed. Here the main system menu is displayed (shown below).
Import/Export:
The import/export screen allows the user to import and export thr ough the mini USB port locat ed on the bottom side of the thermostat (pictured). To access the port, use the mini USB to USB adapter (S1-03102965000) provided in the Touch Screen Communicating Control kit attached to a USB memory drive.
The USB can be used to import and export:
Program Schedule
If the “Program Schedule” is selected, the control will import/export the setting of the program schedule (including: Schedule name, day, part times, and temperatures).
Dealer information
If the “Dealer Information” is selected, the control will import/export the dealer information (Includ­ing: address, number, name, etc.)
Dealer logo
If the “Dealer Logo” is selected the control will import/export the dealer logo (or picture).
Homeowner configuration File
Most USB drives are compatible with the Touch Screen Communicating Control. However, if you have questions as to which USB me mory drive s are appro ved for the Touch Screen Communicat- ing Control, see UPGnet.com for more information.
Touch ICON for a detailed view
Log MenuRefresh Accessories
Exit Service Mode
Humidifier ON
UV Lamps ON
EAC Not Installed
Heat Pump OFF
Thermostat ON
Furnace ON
11:07AM Thu 7/21
UV La
ON
EAC
N
ot I
n
F
urn
a
O
N
Menu
Close
Forced
Operation
Auto
Setup
Import/
Export
Tools/
Settings
Edit/Add
Devices
11:07AM Thu 21 Jul
NOTICE
Page 24
542933-UIM-C-0112
24 Johnson Controls Unitary Products
If the “Homeowner Configuration” is selected, the control will import/export the sound, display, schedule, security, View/Mode, etc. In short, it will be all homeowner sett ings including the personal­ized schedules.
Installer configuration file
If the “Installer Configuration” is selected, the control will import/export every file available on the Touch Screen Communicating Control. Including the Homeowner settings, programmed schedules, dealer information, etc.
Auto Setup
Auto setup is used to view the installer system configuration screens that the installer was originally directed through. These screens will vary dependi ng on the installed components.
Edit/Add Devices
Edit/Add devices screen is used to add accessories/upgrades to the communicating system. These accessories/upgrades may include: heat pump, air conditioner, filters, humidifiers, UV lights, etc. Adding equipment through this screen will allow the control to provide maintenance updates and track any changes to the system. It will also ensure proper system functionality. Accessories must be added using this screen to enable the functionality of the Touch Screen Communicating Control for each accessory.
To add a device:
Auto setup screens are described in more detail in other sections of this document.
Follow the installation instructions provided with the equipment being installed. For wiring instruc­tions of Humidifier, see the wiring section of this document.
1. Select from one of the options on the main,
edit/add devices screen (see picture).
NOTICE
NOTICE
Next
Back
Edit/Add Devices
Add
Device
Select a device to edit/add information:
11:07AM Thu 21 Jul
Other:
System ID = HP14
Other:
Furnace
Heat Pump
Page 25
542933-UIM-C-0112
Johnson Controls Unitary Products 25
4. When all desired information has been entered, press the “Done” button in the lower right hand corner of the screen.
5. The user will be prompted as to whether or not to save the settings. Press Yes if all information is entered as desired, or No if there is editing needed.
2. Once “Add Device” is selected the possible devices to add will be loaded for selection. Select the icon that represents the device being added (In this case humidifier).
Some of the device icons that are shown may not be used unless the communicating accessory board has been installed.
3. The next screen allows the user to add a model and serial number to the device details for future reference. Simply press the space that indicates “Model Number” or “Serial Num­ber”. This will activate the keyboard for input.
This information is not required for SYSTEM OPERATION.
6. Once saved, the device will display on the main edit/add devices screen.
Cancel
Add Devices
Clean Air:
11:07AM Thu 21 Jul
UV LampElectronic Air Cleaner
Ventilation:
Humidifier
Heat Recovery Ventilator
Energy Recovery Ventilator
Generic Ventilator
NOTICE
Done
Add Devices
Please Enter Accessory Model/Serial Number
11:07AM Thu 21 Jul
Humidifier:
Cancel
Model/Serial Number:
Model Number
Serial Number
NOTICE
Next
Back
Edit/Add Devices
Add
Device
Select a device to edit/add information:
11:07AM Thu 21 Jul
Other:
System ID = HP14
Other:
Furnace
Heat Pump
Humidifier
Page 26
542933-UIM-C-0112
26 Johnson Controls Unitary Products
To remove a d e vice:
1. Select a device that is available on the main “Edit/Add Devices” screen. This will display the model and serial number of the device that has been enter ed.
2. At the bottom of the screen there is a button that says “Remove Device”.
3. Another screen will confirm that the device is to be removed. Press “Yes” to remove the device or “No” to view the model and serial number screen.
Tools and Settings
The tools and settings screen displays all of the available system settings (including settings on the individual communicating controls).
System Settings
Depending on the equipment that has been installed, the system settings screen will display differ­ent user options. These settings will determine how the Touch Screen Communicating Control will command the installed equipment. The settings pertain to installed equipment as well as general thermostat control settings. The Touch Screen Communicating Control is highly adaptable; the installer should consider all the available settings to maximize usability and comfort provided by the communicating controls (the settings are described in the follo wing sections).
Heat Kit Configuration
This screen is available if there is a variable speed air handle r wit h the a ddit ion of an ap proved heat kit. Here the heat kits approved for the installed air handler will be displayed (and the current selected heat kit will be highlighted). If there has been a change in the originally installed heat kit, the installer MUST use this screen so that the appropriate air flows will be applied during heat kit operation.
Heat Pump Configuration
These screens are available if there is a communicating heat pump control inst all ed. These screens allow heat pump “jumpers” to be changed from the Touch Screen Communicating Control.
In some cases, the Touch Screen Communicating Control will need to be reset for the chan ges to take place.
The options explained in this document may or may not be available on your communicat i ng sys­tem. They depend on installed components.
If the heat kit selected does not match the heat kit installed, the Touch Screen Communicating Control may apply air flow values that can cause nuisance limit trips or cold blow.
NOTICE
Page 27
542933-UIM-C-0112
Johnson Controls Unitary Products 27
If the outdoor temperature is above the balance point temperature setting, the auxiliary heat will not be used to satisfy the heating demand *.
If the outdoor temperature is below the LTCO, the heat pump wil l not be used to satisfy the heating demand.
If the outdoor tem perature i s between both the balance point and the LTCO temperature settings, the thermostat will stage both heat pump and auxiliary heat as demand increases.
*If after 4 hours the heating demand is not satisfied, auxiliary heat will be supplied. Reference communicating heat pump literature for more detail on heat pump operation.
Airflow Configuration
The airflow configuration screens are available on systems that contain a communicating ID unit. Here the user can change delay profiles and airflow settings. CFM settings and ranges are defined by factory programmed values in the outdoor and indoor controls.
Delay profile:
The delay profile is an airflow profile that the system will run in COOL mode. These profiles are not implemented in heating. Each profile is designed to accommodate the original environment where the equipment is installed.
Compressor Delay: (ON, OFF) Compressor Delay will turn the compressor off for 30 seconds immediately after energizing the reversing valve (in defrost). The purpose is to reduce noise in defrost.
Defrost Curve: (1-6) Defrost Curve is set in the factory and should only be changed in a repair part installation
Switch Point: (35, 40, 45) Switch Point is the temperatu re of the liquid line se nsor (in Fahrenheit) at which the heat pump will force 2
nd
stage operation.
Y2 Lock: (ON, OFF) Y2 Lock allows the Heat pump control to anticipate 2
nd
stage operation.
Balance Point and Low Temperature Cut Out (LTCO): Balance Point and LTCO settings deter­mine how heating calls will be satisfied by the system.
Changing airflow settings can effect system efficiency. Reference outdoor equipment tech guide for more information on system efficiencies.
To change the delay profiles press the box next to the profile that is desired (as pictured). Each of the profiles, (when selected) will provide a brief description of the profile design intent.
Heat Pump Config
Next
Furnace Only
Furnace/ Heat Pump
Heat Pump Only
Back
Low Temp Cutout= 10° Balance Point = 35°
Outdoor Temp F°
10 35
11:07AM Thu 21 Jul
Airflow Config
Next
Dry
Temperate
Humid
Normal
Delay Profile: Dry
Best in dry regions such as the southwest US. Increases the blower ramp-down times to help retain humidity.
Back
11:07AM Thu 21 Jul
Page 28
542933-UIM-C-0112
28 Johnson Controls Unitary Products
Airflow Summary
Airflow Configuration
The “View/Edit Dehum” check box, when selected, will display the option to reduce the airflow by a selectable percentag e wh en there is a call to dehumidify.
Comfort Settings
This tool is available in all communicating systems. This screen is used to control comfort settings. These settings effect how the Touch Screen Communicating Control will satisfy calls for condition­ing.
Humidity Settings: The humidity settings screen is used to change the humidify/dehumidify set­tings to fit the equipment installed.
Humidification settings (Available only with humidifier installed) Humidification with a heat demand: If this option is selected the control will only activate the
humidifier if there is a demand for both heat ing and humidity. Humidification with or without a heat demand: If this option is selected the control will activate
the humidifier any time there is a humidity demand.
The airflow summary screen displays all current airflow settings at a glance. To edit the airflow set­tings press the indoor or outdoor button (heat pump or air handler shown).
The airflow configuration screen shows the avail­able airflow adjustments at the top of the screen (High Cool, Low Cool, High Heat, etc.). Simply press the desired adjustment to edit airflow.
Once in the desired airflow adjustment screen t he user can adjust the airflow by CFM (in 10 CFM increments) by sliding the “homeplate” icon or pressing the “+” or “-“ symbol s.
The “Restore Defaults” button will return the air­flow to the factory setting.
When changing airflow settings on electric heating components, the user should reference mini­mum CFM values required for operation (provided in the communicating air handler installation instructions).
NextBack
Heat Pump
Model YZH036
AH Model AV060 Heat Kit Model 4HKx6501506
530Set CFM 1950
Air Handler
High Heat
Low Heat
High Cool
Low Cool
809
1245
809
1245
4.3 KW
9.6 KW
4.8 KW
14.4 KW
Airflow Summary 11:07AM Thu 21 Jul
1860
730
AH Airflow Config
11:07AM Thu 21 Jul
Low Cool High Heat Low HeatHigh Cool
Back
Max 1800Min 400
View/Edit Dehumidification
High Cool CFM: 1245
1245
Restore Defaults
Airflow Config
Page 29
542933-UIM-C-0112
Johnson Controls Unitary Products 29
No Humidification: The control will never activate the humidifier. Dehumidification settings De-Humidification with equipment: If this option is selected the control will only dehumidify by
running a reduced airflow on the indoor equipment
(Available only with communicating indoor
equipment).
De-Humidification by overcooling: If this option is selected the control will continue to run cooling up to 3 degrees below set point to meet humidity setting of the home (selectable from 1-3 degrees).
De-Humidification with external equipme nt: If this o pti on is sele cted, ther e shoul d be an e xtern al (whole home) de-humidifier.
No De-Humidification: If this option is selected the control will not send a command to de-humid­ify.
Smart Recovery : (ON, OFF) Smart recovery is used in programmable or advanced programmable mode. The controller initiates equipment operation, if required, before the start time of the program schedule day part. This is done to re ach the progr am schedul e event’ s d esired te mperature set point at the time the event occurs, rather than after.
T emperat ure Control Settings: Temperature Control Settings screen is used to customize h ow the Touch Screen Communicating Control will satisfy temperature set point. As well as, how the control will stage the installed equipment. The Touch Screen Communicating Control can be set up to sat­isfy demand differently depending on whether there is a heat demand or a cool demand.
Below is a table of explaining each of the available settings.
This is for use with hot water or steam humidifiers.
This option may require a communication accessory control.
NOTICE
Page 30
542933-UIM-C-0112
30 Johnson Controls Unitary Products
Auto Mode Deadband: (4, 6, 8, 10) Auto mode deadband dictates th e minimum tempera ture dif fer­ence between the cooling and heating set point.
Offset Settings: (-5° – 5°) Offset setting allows the user to calibrate the displayed temperature and humidity from the measured temperature and humidity (i ndoor and outdoor) in the control.
Control Settings: Control settings screen is used to set “soft jumpers” on the inst alled communicat ­ing controls. Soft jumpers are settings that are conventionally set using a jumper on the control board, but are available to be set from the Touch Screen Communicating Control as well.
Equipment Temp Limits
This screen allows the user to limit equipment functionality based on outdoor temperature. The Heating Temperature Limit, when enabled, will not allow heating operation when the outdoor
temperature rises above the setting. The Cooling Temperature Limit, when enabled, will not allow cooling operation when the outdoor
temperature drops below the setting.
Variable Default Settings Explanation
1
st
Stage
Differential
0.5
0.3, 0.5, 0.7, 1.0,
1.5, 2.0, 2.5, 3.0,
4.0, 5.0, 6.0, 7.0, 8.0
This is the difference between current tem­perature and set point for which the thermo-
stat will command 1
st
stage operation.
2
nd
Stage
Differential
0.5
0.3, 0.5, 0.7, 1.0,
1.5, 2.0, 2.5, 3.0,
4.0, 5.0, 6.0, 7.0, 8.0
This value Plus the 1
st
stage differential is
the value for which the thermostat will com­mand 2
nd
stage operation.
3
rd
Stage
Differential
0.5
0.3, 0.5, 0.7, 1.0,
1.5, 2.0, 2.5, 3.0,
4.0, 5.0, 6.0, 7.0, 8.0
This value Plus the sum of 1
st
stage differ-
ential and the 2
nd
stage differential is the
value for which the thermostat will command 3
rd
stage operation.
Minimum on timer
5 min.
1-5 min in 1 min
intervals
Once a demand is present the thermostat will run for the selected Min on time.
Minimum off timer
5 min. N/A
Once a demand is satisfied the thermostat will remain off for the Min off time.
Force stage up
90 min.
Off, 10 min, 20 min,
30 min, 60 min,
90 min, 120 min
If the forced stage up timer has been satis­fied the control will stage up regardless of stage differential settings.
Stage Up Inhibit Timer
5 min.
5-60 min in
5 min intervals
If the stage inhibit timer has not been satis­fied the control will not stage the equipment UP regardless of stage differential settings.
Allow Equipment to stage down?
Yes Yes or No
This will give the thermostat the ability to stage down per temperature differentials.
Stage Down Inhibit Timer
5 min.
5-60 min in
5 min intervals
If the stage down inhibit timer has not been satisfied the control will not stage the equip­ment DOWN regardless of the stage differ­ential settings.
Page 31
542933-UIM-C-0112
Johnson Controls Unitary Products 31
Ventilation Settings
The Vent ilation Settings screens are used to view/edit settings associated with a whole home venti­lator (ERV/HRV) devices. These screens are only accessible in system which have an ERV/HRV Accessory control installed. The settings availabl e are explained in the table below.
The installer must also add the ventilation device through the Edit/Add device screen (as described previously)
Variable Default Settings Explanation
Ventilation Mode Timed
Continuous, Timed or Off
This will determine how often the ventilation device will be opened
Ventilation Runtime per Cycle
20 min.
5-55 min in 5 min intervals
If ventilation mode is set to “Timed”, the control will allow ventilation per this setting per Ventila­tion Cycle Time
Ventilation Cycle Time
1 hour 1 -4 hours
If ventilation mode is set to “Timed”, the control will allow Ventilation Runtime per this setting
Ventilation Limits
Disabled
Disabled, Default, and Manual
If there is a damper installed for venti l ation pur­poses
No Ventilation Above
100 F
The touch screen will not allow ventilation if the outdoor temperature exceeds this setting
No Ventilation Below
0 F
The touch screen will not allow ventilation if the outdoor temperatures is below this setting
There are additional settings for ventilation that are covered with a temperature slider. These set­tings will determine if the ventilat or is opened dur­ing a call for conditioning. The Touch Screen Communicating Control will open ventilation any time there is a call for conditioning if the outdoor temperature falls in the “Ventilation with a heat­ing/cooling call”. Otherwise ventilation will run with the indoor blower per the previously described settings.
Finally the ventilation can be controlled per indoor humidity. If the outdoor temperature is above 50 degrees the touch screen can be set so that it will disable ventilation if the indoor humidity rises above the desired setting.
NOTICE
Ventilation Settings
Back
Ventilation with a
heating call
Ventilation per
Installer settings
100
11:07AM Thu 21 Jul
Ventilation with a
cooling call
0
10 85
5101520 2530 3540 85 90 95
Back
6540
50%
No ventilation is the outdoor
temperature is above 50F and
above the selected indoor humidity
Ventilation Settings
11:07AM Thu 21 Jul
45 50 55 60
Page 32
542933-UIM-C-0112
32 Johnson Controls Unitary Products
Float Switch Settings
This screen allows the user to activate the optional condensate float switch (S1-6-JMP) and to determine how the outdoor equipment will shut down.
Dealer Information
This tool is available in all communicating systems. This screen is used to view, import and edit the dealer information.
3. The keyboard will “pop up” which is used to type name, address, e-mail, phone, and any other dealer information which will fit in the provided space.
To add a logo, simply press the “Add Logo” button and follow the instructions on the screen.
In addition to manually entering dealer information at the thermostat, the dealer information can be added using the configuration tool. From the “Dealer Information” screen select the “Edit” button. Then select the “Import” button and plug the USB drive into the Touch Screen Communicating Con­trol (as described in the “Import/Export” section of these instruct ions).
Variable Default
Settings
Float switch installed? No Yes, No
Shut down outdoor equip­ment when float switch is:
Open Open, Closed
Once the “Dealer Information” button has been pressed in the “Tools and Settings” screen, the dealer information is displayed as previously input. To edit the information:
1. Press the “edit” button.
2. Press the field that you would like to edit .
The logo must be saved on a USB drive and plugged into the Touch Screen Communicating Con­trol as described in the “Import/Export” section of these instructions.
The logo must be saved in the appropriate format using the configurat ion tool.
Float Switch Installed?
Yes
Float Switch Settings
11:07AM Thu 21 Jul
Shut down outdoor equipment when float switch is
Open
Back
Next
Logo
Dealer Name Dealer Phone Number(s)
Dealer Address 1 Dealer Address 2 Dealer Email Dealer Website
Dealer Info
11:07AM Thu 21 Jul
Back
Edit
NOTICE
NOTICE
Page 33
542933-UIM-C-0112
Johnson Controls Unitary Products 33
Maintenance Reminder
This “tool” is available in all communicating systems. This screen gives the user access to view, edit, enable, and disable maintenance reminders.
The maintenance reminder was designed to give an installer the opportunity to display a “mainte­nance needed pop up” to the homeowner on a specified date displaying the dealer information entered.
Administrator Tools
This screen is used to access firmware update, firmware restart, and restore defaults.
Firmware:
The firmware button is used wh en th ere is a need to updat e the cont roller to a more re cent program. To update the firmware:
1. Load the new firmware onto a USB drive.
2. Plug the drive into the Touch Screen Communicating Control as described in the “Import /Export ” section of these instructions.
3. Press the “Firmware” button (on the Administrator tools screen).
4. The thermostat will locate the firmware file.
Restart Firmware:
Restarting the firmware will simulate a power loss to the Touch Screen Communicating Control. This will restart the Touch Screen Communicating Control, which will validate all of the system set­tings and resume normal operation.
Restore Defa u lts:
Restoring defaults on the Touch Screen Communicating Control will return the control to its original factory settings. Upon re-boot, the control will run through auto setup screens as described earlier in this document. Restore defaults may be used when there is a System Miconfiguration that could be caused by a change in hard jumper settings or a change in equipment (which may include when an installer installs a furnace in the winter and then comes back in the spring to install an AC or heat pump).
This reminder could be used for seasonal system checkups or any other preventable mainte­nance that the dealer sees fit.
Flashing new firmware will restore the Touch Screen Communicating Control to defaults. To pre­vent losing system settings: export “Installer Configuration” file before installing the new firmware. The installer configuration file can be impor ted after the firmware update to return the t her most ats settings, schedule, dealer information, etc.
Do not remove the USB drive until the thermostat instructs you to do so. Failure to follow these instructions can cause your controller to perform erratically.
NOTICE
Page 34
542933-UIM-C-0112
34 Johnson Controls Unitary Products
User Interface Settings
This screen is used to customize homeowner access. There are several options to limit what the “homeowner” sees and how the touch screen will display.
To change a setting, simply press the desired box and a check mark will fill the selected setting (as pictured). To understand how these settings affect the functionality of the Touch Screen Communi­cating Control, reference the table below.
When selecting “No” on this screen the installer is restricting what can be viewed/edited by the “Homeowner”.
Available Setting If checked “Yes”
Indoor Fan Icon and Status
The fan icon and animation will be disp layed on the touch screen dash.
Indoor Humidity Icon and Status
The humidity icon and animation will be displayed on the touch screen dash.
Outdoor Temperature
The outdoor temperature will be displayed on the touch screen dash.
Upgrade Firmware
The “homeowner” will have the ability to upgrade firmware.
Import Configuration File
The “homeowner” will have the ability import configuration settings.
Export Configuration File
The “homeowner” will have the ability export configuration settings.
Create a New Event in Log
The “homeowner” will have the ability to create a custom log entry.
View Details of Events in Log
The “homeowner” will have the ability to view fault and event details in the log.
Enable Security
The “homeowner” will have the ability to set and change pin settings to limit access to the touch screen
Change Sleep Screen
The “homeowner” will have the ability to select whether the touch screen displays the sleep screen aft er ti me out.
Select Advanced Programmable Mode
The “homeowner” will have the ability to select Advanced Programmable as a view mode from the menu screen.
Select Programmable Mode
The “homeowner” will have the ability to select Programmable as a view mode from the menu screen.
Import/Export Program Schedule
The “homeowner” will have the ability to import/export a saved schedule.
Back
UI Settings
Indoor Humidity Icon and Status
11:07AM Thu 21 Jul
Indoor Fan Icon and Status
Display Items to User?
Upgrade Firmware?
Import Configuration File?
Outdoor Temperature
Allow User to:
Yes No
NOTICE
Page 35
542933-UIM-C-0112
Johnson Controls Unitary Products 35
Brand Selection
This screen is used to select the desired brand to be displayed on the Touch Screen Communicat­ing Control. There are three brands to choose from: York, Coleman, and Luxaire. The touch screen is set by default to York. The brand selected will be displayed in the “sleep” screen as well as in the top right corner in several screens (as the service mode short cut).
FORCED OPERATION: MASTER CONTROL
Giving the homeowner the ability to “Upgrade Fir mware” may require that the Touch Screen Com­municating Control re-enter the auto-setup process. The installer should be sure that the home-
owner is capable of this task before allowing this option. If the auto-setup is not executed properly, the system may not operate as desired.
Forced operation is available in all communicat­ing systems. The options and functions available depend on system ID. Forced operation (Located in the service mode menu screen) is a very pow­erful trouble shooting tool. This function allows the controller to command indoor and outdoor operation. Forced operation is separated into three different modes: Cool Mode, Heat Mode, IAQ Mode.
When entering forced operation, n ormal ope ration of the system will be discontinu ed. This means that the controller will not control equipment to maintain a set point, schedule, mode of operation, etc. Forced operation is a deviation from normal operation and the system will only run when commanded through the forced operation menus. Normal operation is restored when forced operation is exited.
Please Select Brand
OK
Please Select Brand
OKCancel
Menu
Close
Forced
Operation
Auto
Setup
Import/
Export
Tools/
Settings
Edit/Add
Devices
11:07AM Thu 21 Jul
NOTICE
Page 36
542933-UIM-C-0112
36 Johnson Controls Unitary Products
To force operation of the system:
1. Select the mode to test.
2. Select the length of time to test.
Cool Mode: Will test compressor cooling opera­tion. This may include: 1
st
stage, 2nd stage cool-
ing, and continuous fan operation. Heat Mode: Will test compressor heating opera-
tion (if communicating heat pu mp is presen t), Fur­nace/Gas heating operation, and Electric/Air handler heating operation
IAQ Mode: Will test IAQ accessories that have been added to the system using the "Edit/Add Device" tool.
To force operation of IAQ equipment, an ERV/HRV interface control may be necessary.
Forced operation allows for abnormal operating conditions. This includes: bypassing anti-short cycle timers, forcing into and out of defrost, running air conditioner in low ambient temperatures, etc. The user should be aware of these conditions and proceed with caut ion.
The time selected can be bypassed anytime by pressing the “Stop” button.
Forced Operation
Exit
Cool Mode
Heat Mode
IAQ Mode
Time remaining for current forced operation:
15:37
Stop
11:07AM Thu 21 Jul
NOTICE
NOTICE
Page 37
542933-UIM-C-0112
Johnson Controls Unitary Products 37
6. Once the system is running as “forced”, the user can press “System Map”.
From the system map the user can access the equipment details, equipment status, and inputs/out­puts screens along with the faults and log screen.
7. To return to the Forced operation menu from system map, press “Menu”
8. To leave forced operation, navigate by pressing the “back” button to the forced operation main menu screen and press “Exit”.
When leaving forced operation, the system will discontinue the “forced” operation and resume “nor­mal” operation.
Exiting Service Mode
3. Select the “Operation” to be forced (and press "Apply" to start the oper ation).
Operations are on the left side of the screen. Operations available depend upon the f orce oper­ation mode (Cool, Heat, or IAQ) and the system ID. For the most part, the operations include indoor and outdoor eq uipment stagin g and conti n­uous fan.
4. Once the operation is selected, the timer will start to count down, and the modifiers will appear.
5. Select a modifier (if desired).
On the right side of the screen are the "mod ifiers". Modifiers are dependent upon the mode of opera­tion selected (and will not appear until a mode has been selected and applied). Modifiers are additional “commands” that the controller can append to the current operation. In general, the modifiers will augment the operation to make more specific functionality.
Remember, on screens that contain information which varies dynamically, a “Refresh” button is available. Pressing the refresh button will insure that all information being displayed is current.
To exit service mode, press the button in the upper, right hand corner of the system map screen. When the exit button is pressed, the Touch Screen Communicating Control will re-vali­date and return to normal operation.
Apply
StopBack System Map
Forced Cooling Operation Menu
Stage 1 Stage 2
Select Mode of Operation and Press Apply
20 min
Set:
Apply
StopBack System Map
Forced Cooling Operation Menu
Stage 1 Stage 2
Bypass
ASCD
De-
humidify
Set
Airflow
Modifiers
Select Mode of Operation and Press Apply
20 min
Set: Remaining:
18:56
NOTICE
Touch ICON for a detailed view
Log MenuRefresh Accessories
Exit Service Mode
Humidifier ON
UV Lamps ON
EAC Not Installed
Heat Pump OFF
Thermostat ON
Furnace ON
11:07AM Thu 7/21
UV La
ON
EAC
N
ot I
n
F
urn
a
O
N
Page 38
542933-UIM-C-0112
38 Johnson Controls Unitary Products
SERVICE TOOL SETUP
The service tool application is defined as a Touch Screen Communicating Control that is being used to trouble shoot/view details of a system. The Touch Screen Communicating Control can access the system from the indoor and the outdoor controls via the communication ports outlined earlier in this document.
To set up the service tool for operation:
1. Extend wire harness.
Extending the Communication Harness
Each Touch Screen Communicating Control is supplied with a communicating plug harness. This harness is 18” long and can be extended with thermostat wire to allow more convenient and safe use of the service tool.
To extend the harness:
a. Use 5-6 feet of thermostat wire (enough to maintain a safe/comfortable distance from
the high voltage in the control panels) and 4 wire nuts.
b. Use the wire nuts to connect the stripped ends of the communicating plug harness to
the loose/stripped ends of the thermostat wire.
c. Wire the non-plug end of the extended harness to the terminal block of the mounting
back plate of the Touch Screen Communicating Control.
d. Snap the Touch Screen Communicating Control on the back plate.
2. Disconnect power to the entire system that you wish to access a communications port (commu­nication ports are outlined in the wiring section of this document).
3. Once power is disconnected, plug the harness into one of the communicating. terminals. Rout­ing the harness so that the power can be re-applied (allowing for the door switches etc. where applicable)
While the service tool is highly useful device mode, the Touch Screen Communicating Control that has been configured as the “master” of the communicating system contains all the informa­tion available for trouble shooting purposes while the service tool function may have some limita­tions.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury, death, or equipment damage. Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
The control housings contain areas of high voltage. Always assure, when trouble shooting the system, that a safe distance is maintained from high voltage. Below are illustrations that show some of the high voltage areas.
NOTICE
Page 39
542933-UIM-C-0112
Johnson Controls Unitary Products 39
4. Place touch screen down in a safe/dry space (away from fan blades, condensation, etc.).
5. Return power to the entire system.
6. The Touch Screen Communicating Control will commence the start up sequence (as outlined previously).
FIGURE 16:
Outdoor Unit Communicating Terminals
FIGURE 17: High Voltage Locations
Failure to ensure the Touch Screen Communicating Control is safely placed may cause damage to the device.
COMMUNICATIONS PORT
CONTROL BOARD
COMMUNICATIONS HARNESS
JUNCTION BOX
HEAT KIT LOCATION
Page 40
542933-UIM-C-0112
40 Johnson Controls Unitary Products
Navigating Service Mode: Service Tool
Service mode screens on the service tool are the same as described before. However, there is some functionality of service mode that is not available on the service tool. The following outlines what is available from the service tool.
Log Button: Service Tool
7. Select the service tool option when prompted.
The system map displayed on the service tool has all of the information that the master disp lays. This includes pressing the equipment icons and viewing: Equipment Details, Status, and Inputs/ Outputs screens.
The log button is available in service mode. The user will not be able to enter a new log event or clear log entries. The other functions of log are available and are outlined in t he Log But ton: Mas­ter Control section of this document.
System Master
Mode
Service Tool
Mode
Demo
Mode
Select the desired mode of operation for this device.
11:07AM Thu 21 Jul
Touch ICON for a detailed view
Log MenuRefresh Accessories
Exit Service Mode
Humidifier ON
UV Lamps ON
EAC Not Installed
Heat Pump OFF
Thermostat ON
Furnace ON
11:07AM Thu 7/21
UV La
ON
EAC
N
ot I
n
F
urn
a
O
N
Touch ICON for a detailed view
Log MenuRefresh Accessories
Exit Service Mode
Humidifier ON
UV Lamps ON
EAC Not Installed
Heat Pump OFF
Thermostat ON
Furnace ON
11:07AM Thu 7/21
UV La
ON
EAC
N
ot I
n
F
urn
a
O
N
Page 41
542933-UIM-C-0112
Johnson Controls Unitary Products 41
Menu Button: Service Tool
When using the service tool, the installer only has access to the force operation feature.
Forced Operation: Service Tool
Exiting Service Tool
To exit service mode, simply remove power from the device. This will reset the software and return the Touch Screen Communicating Control to original settings.
Demo Mode Setup
The Demo Mode application is defined as a Touch Screen Communicating Control that is being used to simulate connection to a communicating system. While in demo mode, the control will allow the user to choose the type of equipment to be displayed and the Touch Screen Communicating Control will present as though the system components are connected.
Forced operation on the service tool is fully func­tional. However, when viewing the system map while forcing operation, the same limitations of the log and system map exist.
To view more information about forcing system operation, view the “Forced Operation: Master Control” section.
Demo mode will simulate a fault every 5 minutes. Demo mode only requires 24 VAC on the R and C terminals. While the Touch Screen Communicating Control is configured in Demo Mode, other communicat­ing controls will not receive commands. Demo Mode will not control a communicating sys- tem.
Menu
Close
Forced
Operation
11:07AM Thu 21 Jul
NOTICE
Page 42
Subject to change without notice. Published in U.S.A. 542933-UIM-C-0112 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 542933-UIM-B-0311
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
NOTES
Loading...