IMPROPER INSTALLATION MAY CREATE A
CONDITION WHERE THE OPERATION OF THE
PRODUCT COULD CAUSE PERSONAL INJURY
OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE INJURY OR PROPERTY DAMAGE.
REFER TO THIS MANUAL FOR ASSISTANCE
OR ADDITIONAL INFORMATION, CONSULT A
QUALIFIED INST ALLER, SER VICE AGENCY OR
THE GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED IN
STRICT COMPLIANCE WITH THE ENCLOSED
INSTALLATION INSTRUCTIONS AND ANY
APPLICABLE LOCAL, STATE, AND NATIONAL
CODES INCLUDING BUT NOT LIMITED TO,
BUILDING, ELECTRICAL AND MECHANICAL
CODES.
The furnace area must not be used as a broom
closet or f or any ot her sto rage pu rposes , as a fir e
hazard bay be cr eat ed. N ever stor e it ems s uch as
the following on, near or in contact with the furnace.
1.Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners or other cleaning tools.
2.Soap powders, bleaches, waxes or other cleaning
compounds; plastic items or containers; gasoline,
kerosene, cigarette lighter fluid, dry cleaning fluids
or other volatile fluid.
3.Paint thin ners and other painting compounds.
4.Paper bags, boxes or other paper products
Never operate the furnace with the blower door
removed. To do so could result in serious personal
injury and/or equipment damage.
This Category I furnace is designed for installation in a residential or commercial application. A Cate
a fan assist ed combustion s
mechanical means to draw products of combustion throu
the combustion chamber and heat exchan
installed in a basement,
attic or an
ances to combustibles and other restrictions are met. It is
designed for natural gas-fired operation, but may be converted to propane (LP) usin
other indoor location where all required clear-
stem equi pped with an i ntegral
arage, equipment room, alcove,
the INP0349 kit.
1 furnace has
er. It may be
Each furnace in this series is a Categ ory I furnace ,
suitable for common venting with other gas-fired
appliances as allowed by the National Fuel Gas
Code, NFPA 54/ANSI Z223.1-latest edition.
h
This appliance is not to be used for temporary
heating of buildings or structures under construction.
Do not install this furnace in a corrosive or contaminated atmosphere.
High altitude and propane (LP) changes or conversions
required in order for the appliance to satisfactoril
application must be made b
Canada, a certified conversion station or other qualified
ency, using factory specified and/or approved parts.
a
This furnace may be used only as a Category 1 unit.
The furnace must be installed so that all electrical compo-
nents are protected from water.
an authorized distributor: in
meet the
INSPECTION
As soon as a unit is receiv ed, it s hould be ins pecte d for po ssible dama
extent of t he dam a
bill.
A separate request for inspection b
should be made in writin
should be checked for belt, screws or bolts which ma
loosened in transit.
e during transit. If the damage is evident, the
e should be noted on t he c arri er’s freight
the carrier's agent
. Also, before installation, the unit
have
NOTES, CAUTIONS & WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION and WARNING. NOTES are intended to
clarify or make the installation easier. CAUTIONS are given
to prevent equipment dama
the installer that personal injur
damage may occur if installation procedures are not handled
properl
.
e. WARNINGS are given to alert
and/or equipment or propert
LIMITATIONS AND LOCATION
Do not install this furnace in a mobile home or recreational vehicle.
Furnaces shall not be installed directly on carpeting, tile or other combustible material other than
wood flooring.
Continuous return air temperature must not be
below 55 °F (13 °C).
Use onl
the furnace ratin
the type of gas approved for this furnace; refer to
plate.
Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces
that have bee n pr ope rly co nver te d to us e pr opa ne
(LP) gas. Do not use this furnace with butane.
Using wrong gas could create a hazard, resulting
in damage, injury or death.
For install ations ab ove 2,00 0 feet, re duce inpu t 4% for ea ch
1,000 feet above sea level. Canadian installations must be
derated 10% for elevations from 2,000 ft. to 4,500 ft. Use
1PS0301 kit to properl
The furnace shall not be connected to a chimney flue servin
a separate appliance designed to burn solid fuel.
Check the rating plate and power supply to be sure that electrical cha racteristics matc h. All models are factor
208 / 230 VAC, 1 phase, 60 Hertz power suppl
derate this furnace.
wired for
.
This furnace should be installed in accordance with all
national / local buildin
the absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1 - (latest edition) or, in Canada, CAN/CGA
B149.1 or.2 - (latest edition), and other applicable codes.
Unitar
Products Group3
/ safety codes and requirements, or in
A furnace installed in a residential
that all burners and burner i
less than 18" above the
tected to prevent dama
arage floor, and located or pro-
e by vehicles.
arage must be located so
nition devices are located no
Page 4
035-17443-000 Rev. A (800)
y
y
g
g
g
y
g
g
g
g
g
g
g
g
g
g
g
g
g
g
y
y
g
g
g
g
The size of the unit should be based on an acceptable heat
loss calculation for the structure. ACCA, Manual J or other
approved methods ma
The furnace should be located usin
1.Where a minimum amount of vent pipin
be required.
2.As centralized with the air distribution as possible.
3.Where adequate combustion air will be available.
4.In an area where ventila tio n fa ci lities provide for sa fe lim its of ambient temperature under normal operatin
ditions.
5.Where it will not interfere with proper air circulation in the
confined space.
6.Where the vent will not be blocked or restricted.
7.Where sufficient space is provided to allow proper service access. Mi nimum re commen ded servi ce clearanc es
are as follows:
-four (24) inches between the fron t of th e furnace
Twent
and an adjacent wall or an oth er ap pliance, when access
is required for servicing and cleaning.
Eighteen (18) inches at the side where access is
required for passa
or replacement of flue / vent connections.
8.Where it will not interfere with the cleanin
removal of other appliances.
be used. (See Table 3 on page 6).
these guidelines:
and elbows wi ll
con-
e to the front for servicing, inspection
, servicing or
Rooms communicati n
appliances are considered part of the unconfined space, if
openin
A confined space
1000 Btu/hr input ratin
area.
The followin
combustion and ventilation in confined spaces.
Air Source from Inside the Building
Two permanent openin
the confined space and one within 12 inches of the bottom,
shall each have a free area of not less than one square inch
per 1,000 Btuh of total input ratin
the space. The openin
rior areas havin
NOTE:
s are not furnished with doors.
must be considered to obtain proper air for
At least 100 square inch es free area sh all be used f or
directly with the space containing the
is an area with less than 50 cubic feet per
for all appliances installed in that
s, one within 12 inches of the top of
of all appliances located in
s shall communicate freely with inte-
adequate infiltration from the outside.
each opening.
Air Source from Outdoors
1.Two permanent openin
top of the confine d space and one with in 12 inc hes of th e
bottom, shall commun ica te dire ctl
ducts, with the outdoors or to such cr a wl or atti c spa ce s
that freel
a.
communicate with the outdoors.
Vertical Ducts
area of not less th an one square inch per 4,00 0 Btuh
of total input of all appliances located in the space.
s, one within 12 inches of the
, or by means of
- Each openin
must have a free
9.Wh ere the follow in
combustibles can be maintained: Table 1 on pa
minimum clearances (in inches) to
e5.
UNIT INSTALLATION.
Remove blower shipping support, located under
blower assembly, only after unit has been positioned for installation or damage may occur.
COMBUSTION AIR
All installations must comply with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI
Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or.2
Installation Code - latest editions.
An unconfined space
Btu/hr input ratin
is not less than 50 cubic feet per 100 0
for all appliances install ed in that area.
EXAMPLE:
Total Input of All Appliances
4000
Horizontal Ducts
b.
area of not less th an one square inch per 2,00 0 Btuh
of total input of all appliances located in the space.
Ducts must have the same cross-sectional area as
NOTE:
- Each openin
= Square Inches Free Area
must have a f ree
the free area in the opening to whic h they are conn ected. The
minimum dimension of rectangular ducts shall be three
inches.
2.One permanent opening, commencing within 12 inches
of the top of the enclosure shall be permitted where the
equipment has clearances of at least 1 inch from the
sides and back and 6 inches from the front of the appliance. The openin
or horizontal duct to the outdoors, or spaces (crawl or
attic) that freely communicate with th e outdoors and shall
have a minimum free area of:
a.1 sq. in. per 3000 Btu per hr of the total input ratin
of all equipment located in the enclosure.
shall communicate through a vertical
4Unitar
Products Group
Page 5
035-17443-000 Rev. A (800)
y
g
g
y
g
y
g
g
y
y
y
y
g
g ty
g
g
g
g
g
g
y
TABLE 1: UNIT CLEARANCES TO COMBUSTIBLES (ALL DIMENSIONS ARE IN INCHES)
ALL SURFACES IDENTIFIED WITH THE UNIT IN AN UPRIGHT CONFIGURATION
APPLICATIONTOPFRONTREAR
UPFLOW / HORIZONT AL MODELS - UPFLOW APPLICATION
UPFLOW160036COMBUSTIBLEYESYESYESNO
UPFLOW B-VENT130001COMB USTIBLEYESYESYESNO
UPFLOW / HORIZONT AL MODELS - HORIZONTAL APPLICATION
HORIZONTAL160036COMBUSTIBLENOYESYES
HORIZONTAL
B-VENT
1.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of
the furnace jacket and building joists, studs or framing.
130001COMBUSTIBLENOYESYESYES1
LEFT
SIDE
b.Not less than the sum of the areas of all vent con-
nectors in the confined space.
3.Louvers, Grilles and Screens
a.In calculatin
to the blockin
free area, conside r ati on m ust b e given
effects of louvers, grilles and
screens.
If the free area of a specific louver or grille is not known, refer
to Table 2 to estimate free area.
TABLE 2: ESTIMATED FREE AREA
Wood or Metal
Louvers or Grilles
2
Screens
1.
Do not use less than 1/4 in. mesh
2.
Free area of louvers and grilles varies widely; installer
should follow louver or grille manufacturer’s instructions.
Wood 20-25%
Metal 60% - 70%
1/4 in. mesh or larger 100%
RIGHT
SIDE
1
FLUE
FLOOR /
BOTTOM
CLOSET ALCOVE ATTIC
CONTACT
Combustion Air Quality
The recommended sourc e of comb ustion air is to us e the outdoor air suppl
bustion air will result in safet
. Excessive exposure to contaminated com-
and performance related
problems. However, the use of indoor air in most applications
is acceptable, except as follows:
1.If the furnace is installed in a confined space it is recom-
mended that the necessar
the outdoors b
direct openin
way of attic, crawl space, air duct or
.
combustion air come from
2.If outdoor combustion ai r is used, ther e mus t be no e xpo-
sure to the installations or substances listed in #3 below.
3.The followin
pes of installations may require OUT-
DOOR AIR for combustion, due to chemical exposure.
a.Commercial buildings
b.Buildin
s with indo or pools
c.Furnaces installed in laundry rooms
d.Furnaces installed in hobby or craft rooms
If mechanically operated louvers are used, a means
NOTE:
to prevent main burner ignition and operation must be
provided should louvers close during startup or operation.
Special Combustion and Ventilation Considerations
Operation of a mechanical exhaust, such as an exhaust fan,
kitchen ventilation s
ate conditions requirin
tor
operation of gas appliances.
stem, clothes dryer or fireplace may cre-
special att ention to av oid un satisf ac-
Specially Engineered Installations
The above requirements shall be permitted to be waived
where special engineering, approved by the authority havin
jurisdiction, provides an adequate supply of air for combustion, ventilation and dilution of flue
ases.
e.Furnaces installed near chemical stora
f.Permanent wave solutions
.Chlorinated waxes and cleaners
h.Chlorine based swimmin
pool chemicals
i.Water softening chemicals
j.De-icing salts or chemicals
k.Carbon tetrachloride
l.Halo
en type refrigerants
m. Cleaning solvents (such as perchloroethylene)
n.Printin
inks, paint removers, varnishe s, etc .
o.Hydrochloric acids
p.Cements and glues
q.Antistatic fabric softeners for clothes dr
r.Masonry acid washing chemicals
e areas
ers
LINE
YES
1
Unitar
Products Group5
Page 6
y
FIGURE 1: DIMENSIONS
(
035-17443-000 Rev. A (800)
Note: Vent must be increased to 5” using adaptor provided (7” tall).
All dimensions are in inches and are approximate.
TABLE 3: RATINGS & PHYSICAL/ELECTRICAL DATA
B
LOWER
MAX.
OVERCURRENT
PROTECT
MODEL
INPUT
MBH
OUTPUT
MBH
AFUE
1
AIR T
EMP
RISE °F
M
OUTLET
TEMP. °F
AX
.
MOTOR
HP
N
OMINAL
M
OTOR
A
MPS
T
SIZE
OTAL
UNIT
AMPS
@230V
P4HUE30N130061601307825 - 551501-1/21012 x 15250
208/230 VAC (ONLY )152012
115 and 208/230 VAC (SPLIT)6 & 111512
115 VAC (ONLY)
1.
AFUE numbers are determined in accordance with DOE test procedures.
2.
Wire size and overcurrent protection must comply with the National Electrical Code (ANSI / NFPA-70-latest edition)
3.
Motor must be converted for 115 VAC operation.
• For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V.
• Wire size based on copper conductors, 60° C, 3% voltage drop.
• See Replacem ent Parts list for LP gas and High Altitude conversion kits. External filter kits (bottom & side) are also available for
models above.
• Continuous return air temperatures must not be below 55
3
F (13° C)
°
273010
IN
.
M
IRE
W
SIZE
AWG)
@ 75 FT.
ONE
2
WAY
OPER
WGT.
(LBS)
.
6Unitar
Products Group
Page 7
035-17443-000 Rev. A (800)
y
y
g
g
g
g
g
y
y
y
g sy
y
y
g sy
g
g
g
g sy
g
y
g sy
y
y
g
y
g
g
g sy
y
y
g
VENTING
It is the responsibility of the installer to verify
proper vent system operation.
CATEGORY 1 - VERTICAL VENTING
Category 1 venting consists of vertically venting one or more
appliances in B-vent or masonr
single wall metal pi p e or B -ve nt co nn ec to r s. Type B vent system extends in a
tain offsets exceedin
not more than one 60-degree offset is permitted.
havin
This appliance may be common vented with another
NOTE:
eneral vertical direction and does not con-
45 degrees, except that a vent system
gas appliance as allowed by the following codes and standards.
The furnace rating plate lists t he ma xi mum v ent gas temperature. This temperature must be used to select appropriate
materials and cle ara nce s. A typical example is show n
ventin
below.
CATEGORY 1 - 450 F. MAX. VENT TEMP.
All installations must be vented in accordance with the
National Fuel Gas Code, NFPA 54 / ANSI Z223.1 - latest edition. For reference, the National Fuel Gas Code Handbook,
available from NFPA (item JP-54HB96) is recommended.
The appliance must also be vented in compliance with all
local utilit
must be vented in accordance with the National Standard of
Canada, CAN / CGA-B149.1 and.2 - latest editions.
and code requirements. In Canada, the furnace
A furnace shall not be connected to a chimney flu e
serving a separate appliance designed to burn
solid fuel.
This furnace requires the use of a special 4" to 5"
vent adapter. It is provided with the furnace and
must be installed.
HORIZONTAL SIDEWALL VENTING
For applications where vertical venting is not possible, the
onl
approved method of horizontal venting is through the
use of an auxiliar
Fields Controls Mod el SW G-4 Y or Tjernlund Model GPAK-JT.
Follow all application and installation details provided by the
manufacturer of the power venter.
power venter. Approved p ow er ve nters a re
chimney (as allowed), usin
VENT SAFETY CHECK PROCEDURE
If this furnace is replacing a common-vented furnace, it may be necessary to resize the existing
vent line and chimney to prevent oversizing problems for the new combination of units. Refer to the
National Fuel Gas Code, ANSI Z223.1 or CAN/
CGA B149.1 or .2 Installation Code - latest editions.
The following steps shall be followed with each appliance
connected to the ventin
other applia nces con nected to the comm on venti ng sys-
an
tem are not in operation.
1.Seal an
tem.
2.Inspect ventin
pitch, as required in the National Fuel Gas Code ANSI
Z223.1 or the CAN / CGA B149 Installation Codes and
these instructions. Determine that there is no blocka
or restriction, leaka
which could cause an unsafe condition.
3.Insofar as is practical, close all buildin
dows and all doors betwe en the s pace in whic h the a ppliance(s) connecte d to the v entin
other spaces of the buildin
an
in
Turn on an
bathroom exhausts so the
speed. Do not operate a summer exh aust fan. Close fireplace dampers.
4.Follow the lighting instructions. Place the appliance
bein
ance will operate continuousl
5.Test for draft hood equipped appliance spillage at the
draft hood relief openin
operation. Use the flame of a match or candle.
6.After it has been determined that each appliance connected to the venting system properly vents when tested
as outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas-burning appliance
to its previous condition of use.
7.If improper ventin
tests, the ventin
8.Any corrections or resizing of the common venting system must be in accordance with the National Fuel Gas
Code, ANSI Z223.1 or Section 7, Venting Systems and
Air Suppl
lation Code - latest editions. If the common vent s
must be resized, it should be resized to approach the
minimum size as determ ine d usi n
tables in Appendix G of the above codes.
unused openings in the common venting sys-
other appliances not conne cted to the commo n vent-
stem.
exhaust fans, such as range hoods and
operated in operation. Adjust thermostat so appli-
for Appliances, CAN/CGA B149.1 or.2 Instal-
stem placed in operation, while
stem for proper size and horizontal
e
e, corrosion or other deficiencies
doors and win-
stem are located and
. Turn on clothes dryers and
will operate at maximum
at full input rate.
after 5 minutes of main burner
is observed during any of the above
stem must be corrected.
stem
the appropriate
Unitar
Products Group7
Page 8
035-17443-000 Rev. A (800)
y
g
y
y
g
y
g
g
y
y
g
g
y
g
g
y
g
y
g
g
y
g
g
g
y
g
y
y
g
y
g
y
DUCTWORK
The duct system design and installation must:
1.Handle an air volume appropriate for the served sp ace
and within the operatin
ifications.
2.Be installed in accordance with standards of NFPA
(National Fire Protection Association) as outlined in
NFPA pamphlets 90A and 90B (- latest editions).
3.Create a closed duct s
be connected to the furnace outlet and the return duct
system must be conn ected to the furna ce inle t. Both su p-
and return duct systems must terminate outside the
pl
space containin
4.Generall
culate throu
ment and to and from the conditioned space.
complete a path for heated or cooled air to cir-
h the air conditioning and heating equip-
The cooling coil must be installed in the supply air
duct downstream of the furnace.
parameters of the furnace spec-
stem. The supply system must
the furnace.
On all installations without a coil, a removable access panel
is recommended in the outlet duct such that smoke or
reflected li
cate the presence of leaks in the heat exchan
access cover shall be attached in such a manner as to prevent leaks.
Return Duct Connection
Return air must enter the cabinet throu
a bottom and one side. Single or Dual side return only is not
allowed.
panel of the unit.
tion for details. Be sure to see the “Filters” section of this
instruction and side-return detail (See Fi
FILTER INSTALLATION
All applications require the use of a filter. All filters must be
field supplied and located outside the furnace cabinet in
either a filter rack, duct s
NOTE:
ht would be observable inside the casing to indi-
er. This
h the bottom only, or
Return air may not be connected into the rear
See the sp ecific t
stem or filter grille.
pe application installa-
ure 2 ).
All air velocities over 300 feet per mi nute, requ ire the
use of high velocity filters.
The return air return requirements for this furnace consist of:
1.Bottom Onl
Return = 536 Ft./Min.
When the furnace is used in conjunction with a coolin
the coil must be installed parallel with, or in the suppl
side of the furnace to avoid condensation in the primar
exchan
When a parallel flow arran
other means used to control air flow must be a dequat e to p revent chilled air from entering the furnace, and if manuall
operated, must be equipped with means to prevent operatin
of either unit unl es s the dam pe r is i n the full heat or coo l p os ition.
er.
ement is used, the dampers or
coil,
air
heat
UPFLOW APPLICATIONS
SUPPLY PLENUM CONNECTION
Attach the supply plenum to the furnace
outlet duct connection flan
t
pically through the use of S cleat material when a metal plenum is used. The
use of an approved flexible duct connector is recommended on all installations.
This connec tion sh ould be sealed to prevent air leaka
If a matching cooling coil is used, it ma
be placed directly on the furnace outlet
and sealed to prev ent lea ka
coil instructions for installin
plenum.
e.
es. This is
e. Follow the
the suppl
2.Bottom & Sin
3.Bottom & Two-Sides = 300 Ft./Min.
le Side = 390 Ft./Min.
All installations must have a filter installed.
The return duct ma
bend tabs or other approved methods. Be sure to seal the
duct to the furnace to prevent air leaka
Where the return duct system is not complete , th e re turn co nnection must ru n ful l s ize to a location o uts ide th e utilit
basement or space where furnace is installed. For further
details, consult Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1, or CAN /
CGA B149.1 or.2, Installation Code - latest editions.
An external mounted (1SR0302) upflow side-return
NOTE:
be attached to the furnace by “S-cleat,”
e.
room,
accessory kit , which includes an aluminized mesh filter, is
available and is size d to fit the si de kno ckou ts on th e cab ine t.
8Unitar
Products Group
Page 9
035-17443-000 Rev. A (800)
y
y
g
g
g
g
g
g
g
g
g
g
g
y
g
y
y
y
g
g
g
.
FIGURE 2:SIDE RETURN CUTOUT MARKINGS
Bottom Return
Bottom return applications normall
base platform or return air plenum. Be sure the return platform structure is suitab le to support the wei
Refer to Fi
wei
num connection to prevent air leaka
NOTE
ure 1 on page 6, and Table 3 on page6 for unit
hts and dimensions. Be sure to seal the furnace to ple-
:A bottom filter frame accessory kit (1BR0332) is avail-
pull return air through a
ht of the furnace.
e.
able (less filters) for this model. If the external mounted filter
rack is being used, see the instructions provided with that
accessory for installation.
Upflow attic in stallations must meet all minimum clearanc es
to combustibles and have floor support with required service
accessibility.
HORIZONTAL APPLICATION
The appropriate electrical knock-outs for power wirin
trol wirin
Return air may enter the furnace through either one side and
a bottom or throu
application. Return air may not be connected into the rearpanel of the unit. See the specifi c t
tion for details. Be sure to see the Filters section of this
instruction.
ATTIC INSTALLATION
This appliance is desi
installed horizontall
sides form a line.
This line ma
ever, refer to the “VENTING, and “CLEARANCES” sections
in this manual for additional information.
Secure a platform constructed of pl
material to the floor joists. Sheet metal, 12" in front of the furnace combustion air openi n
ure 3 on pa
and gas piping should be removed at this time.
h bottom on ly, depending on the type of
pe application installa-
n certified f or lin e cont act for f urn aces
. The intersection of the furnace top and
be in contact with combustible material. How-
wood or other buildin
s is recommended. Refer to Fig-
e 9 for details.
, con-
When a furnace is installed in an attic or other
insulated space, keep all insulating materials at
least 12" away from furnace and burner combustion air openings.
NOTE:
See crawl s pace inst allation f or suspendi ng the fur-
nace in attic installations.
SUPPLY PLENUM CONNECTION
The furnace may be installe d ho riz onta lly with the supply airflow toward the left or ri
ht side panel.
ri
Do not install the unit on the rear panel.
After determinin
the shippin
Unitar
Products Group9
the best orientation, lay the unit on top of
carton to protect the finish.
ht by laying the unit on the left or
FIGURE 3: TYPICAL ATTIC INSTALLATION
Page 10
035-17443-000 Rev. A (800)
y
g
g
g
g
g
g
g
y
g
g
g
g
y
g
g
g
g
y
y
g
g
g
g
CRAWL SPACE INSTALLATION
The furnace can be hu n
able blocks or pad. Blocks or pad installations shall provide
adequate hei
dama
When suspending the furnace from rafters or floor joists
rod, pipe or straps, refer to Figure 1 on page6 and
usin
Table 3 on pa
determine suitable means of suspension.
le supports should be located as shown in Figure 5 to
An
permit service of blower and burner compartments. All six
suspension points must be level to ensure proper door fit-up
and quiet furnace operation. Isolators shoul d be use d to m in imize noise bein
be securel
vent movement and vibration.
ht to ensure the unit will not be subject to wa ter
e.
e 6, for furnace weight and dimensions to
transferred to the structure. Furnace should
fastened to the bottom angle iron bracket to pre-
from floor hoists or i ns tal led on su it-
GAS PIPING
An overpressure protection device, such as a
pressure regulator, which conforms to the National
Fuel Gas Code, ANSI Z22 3.1 (U S) or CAN -B1 49. 1
or .2 (Canada) and acts to limit the downstream
pressure to value that does not exceed 0.5 PSI
(14” w.c.), must be installed in the gas piping system upstream of the furnace. Failure to do so may
result in a fire or ex plo si on or c au se dam ag e t o th e
furnace or some of its components.
An accessible manual shutoff valve must be installed
NOTE:
upstream of the furnace gas controls and within 6 feet of the
furnace.
The furnace and its individual shutoff valve must be disconnected fr om the
sure testin
(3.48 kPa).
psi
The furnace must be isolated from the
closing its individual external manual shutoff valve
tem b
any pressure te sting of the gas supply piping system
durin
at test pressures equal to or less than 1/2 psi
as supply piping system duri ng any pres-
of that system at test pressures in excess of 1/2
as supply piping sys-
(3.48 kPa).
FIGURE 4 : TYPICAL FURNACE INSTALLATION
USING SUSPENSION MATERIALS
FIGURE 5 : TYPICAL FURNACE INSTALLATION
USING SUSPENSION MATERIALS
Never apply a pipe wrench to the body of the combination automatic gas valve. A wrench must be
placed on the projection or wrench boss of the
valve when installing pip ing to it.
Gas pipin
Sizin
with the local utility requirements.
The gas supply should be a separate line, installed in accordance with the National Fuel Gas Code, ANSI Z223.1, or
CAN / CGA B149.1 or.2 Installation Codes - (latest editions).
Some utilit
lar
wrou
connections to the unit. Installation of a drop le
union is required (refer to Fi
may be connected from either side of the furnace.
and installation of the supply gas line should compl
companies, or local codes, require pipe sizes
er than the minimum sizes listed. Use properly sized
ht iron, approved flexible or steel pipe, to make gas
and ground
ure 6 )
10Unitar
Products Group
Page 11
035-17443-000 Rev. A (800)
y
g
y
y
g
g
y
y
y
y
y
g
g
g
g
g
Drop Leg
FIGURE 6 : GAS PIPING
.
Compounds used on t hreaded joints of gas pip ing
must be resistant to the action of liquefied petroleum gases.
Provide a power suppl
(s) separate from all other circuits.
Install overcurrent protection and disconnect switch per
local / national el ec tric al codes. The switc h s hou ld be reason-
close to the unit for convenience in servicing. With the
abl
disconnect switch(s) in the OFF position, check all wirin
against the unit wiring label. Also, see the wiring diagram in
this instruction. .
Use copper conductors only.
NOTE:
The furnace control system depends on correct
polarity of the power supply and a proper ground connection.
Refer to the Furnace Control Diagnostics section for symptoms of reversed power supply polarity.
Connect th e power supply as shown on the unit wiring label
on the inside of the blow er compartment door and as deta ile d
in (Refer to Fi
ure 7 on page12).
FURNACE CONTROL CIRCUIT
The control circuit requires 115 volt power suppl
. The black
and blue leads must be c onn ec ted to the hot conductor of the
power suppl
. Refer to Figure 7 on page 12.
After all gas piping connections are completed,
leak test all joints, fittings and furnace connections with rich soap and water solution, commercial available bubble type leak detection fluid, or
other approved means.
Do not use an open flame or other source of ignition for leak testing.
:
NOTE
A 1/8” NPT plug is includ ed in the in let s ide of the gas
valve for measuring incoming gas pressure. Refer to Table 4
for inlet pressure information.
TABLE 4: INLET GAS PRESSURE RANGE
INLET GAS PRESSURE RANGE
Natural GasPropane (LP)
Minimum4.5 In. W.C.11 In. W.C.
Maximum13.9 In W.C.13.9 In. W.C.
ELECTRICAL POWER CONNECTION
Field wiring to the unit must conform to and be grounded in
accordance with the provisions of the National Electrical
Code ANSI/NFPA No. 70 -latest edition, Canadian Electric
Code C22.2 Part 2 - (latest edition) and / or local codes.
Electrical wires which are field instal led sh all con form with th e
temperature limitatio n fo r 63°F / 35°C rise wire when installed
in accordance with instructions. Specific electrical data is
iven on the furnace rating plate.
BLOWER MOTOR CIRCUIT
The motor circuit requires 230 volt power suppl
This circuit ma
motor onl
to wirin
diagram on the motor.
be changed to 115 volts (standard 1-1/2 HP
) by revising the internal motor connections. Refer
as shipped.
All field power wiring connections are shown in Figure 7 A,
B, & C on pa
e 12.
Remove the 4 x 4 junction box cover plate. Route the power
through the unit side panel with a conduit connector or
wirin
other proper connection. Make wirin
in Fi
ures 7 A, B, or C. Replace the wiring box cover pl ate
connections as shown
and secure with screws.
Unitar
Products Group11
Page 12
035-17443-000 Rev. A (800)
y
g
g
g
g
g
g
y
y
y
y
FIGURE 7A
FIGURE 7B
ELECTRICAL CONTROL CONNECTIONS
Install th e field-supplie d thermostat. Th e thermostat inst ructions for wirin
mostat set in the OFF position and the main electrical source
disconnected, complete the low-volta
mostat to the terminal board on the low-volta
Connect Class 2 control wirin
“WIRING DIAGRAM”.
strain relief to the therm os tat wi res pas sing through the
Appl
cabinet.
FIGURE 8 : TYPICAL HEATING AND COOLING
Set the heat ant icip at or in the ro om t herm ost at to .45
amps. Setting it lower will cause short cy cle s. Setti ng
it higher will cause the room temperature to exceed
the setpoint.
are packed with the thermostat. With the ther-
e wiring from the ther-
e transformer.
as shown in F igures 8 and 14
CONTROL CONNECTIONS
FIGURE 7C
7C
FIGURE 7 : ELECTRICAL WIRING
An alternate wiring method is to use a field prov ided 4 x 4 bo x
and cover on the outside of the furnace. Route the furnace
leads into the box usin
pass throu
NOTE:
h the furnace panel.
The power connection leads and wiring box on
upflow units may be relocated to the left side of the furnace.
Remove the screws and cut wire tie holding excess wiring.
Reposition on the left side of the furnace and fasten using
holes provided. Resecure loose wires to prevent contact with
moving parts / hot surfaces and sheet metal edges.
a protective bushing where the wires
Some electronic ther mostats do not have adjustable
NOTE:
heat anticipators. They may have other types cycle rate
adjustment. Follow the thermostat manufacturer's instructions.
The 24-Volt, 40 VA transformer is sized for the furnace components onl
devices such as humidifiers, air cleaners, etc. The
transformer ma
contactor.
, and should not be connected to auxiliar
provide power for an air conditioning unit
If the furnace is installed with a condensing unit
equipped with its own transformer, the condensing unit control circuit must be isolated from the
furnace transformer. Refer to Figure 9 for connection details.
12Unitar
Products Group
Page 13
035-17443-000 Rev. A (800)
y
y
g
y
g
y
y
g
y
y
g
g
g
g sy
g
g
g
g
g
g
y
g
To separate control circuits, use one of the fo llo wng methods:
1.Install an isolation rela
condensin
2.Use a thermostat equipped with separate “R-H” and “R-
C” contacts.
Remove the jumper between these contacts of the
NOTE:
unit transformer.
between the thermostat and the
thermostat, if so equipped. .
The blower motor pow er supply will not be deenergized when the blower door is removed. Turn main
power disconnect switch to OFF to remove power
to motor.
Blower and burner must never be operated withou t
the blower panel in place.
Electrical suppl
covers the blower compartment bein
positioned.
to the unit is dependent upon the panel that
in place and properl
Main power supply(s) to the unit must still be interrupted at the main power disconnect switch(s)
before any service or repair work is to be done to
the unit.
Do not rely upon the interlock switch
as a main power disconnect.
Rollout Switch Controls:
the burner assembl
partment exceeds its set point, the i
valve are de-ener
must be reset before operation can continue.
These controls are mounted on
. If the temperature in the burner com-
niter control and the gas
ized. This is a manual reset control and
FIGURE 9 : TYPICAL THERMOSTAT WRIING
WITH COMMERCIAL CONDENSING
UNIT
This furnace is equipped with a “Time-On” Delay Relay to
protect the belt-drive motor and start rela
ates, (1) under continuous fan mode, or (2) when installin
twinning kit 2TC03700124. Application of twinning kit also
requires use of “Accessor
Sensor Kit 2TS03700106.
if furnace oper-
SAFETY CONTROLS
Blower Door Safety Switch:
electrical interlock switch mounted in the blower compartment. This switch interrupts the 115 volt control power at the
unit when the blower door panel is removed..
This unit is equipped with an
The operation of this control indicates a malfunction in the
combustion air blower or a blocked vent pipe condition.
Pressure Switch:
pressure switch which monitors the flow throu
and ventin
control module and the
tions are present:
1.Blocka
2.Blocka
3.Failure of combustion air blower / motor.
Limit Controls:
located on the furnace ve stibul e panel ju st to the left and ri
of the heat exchan
provides over temperature protection due to reduced airflow,
such as a dirty filter or a blower motor malfunction.
Control Circuit Fuse:
the 24 volt transformer from overload caused b
cuit wirin
is located on the furnace control.
errors. This is an ATO-3, automotive type fuse and
This furnace is supplied with a differential
h the furnace
stem. This switch de-energizes the ignition
as valve if any of the following condi-
e of internal flue gas passageways.
e of vent piping.
Two hi
h temperature limit controls are
er. This is an automatic reset control and
A 3-amp fuse is provided to protect
control cir-
ht
Unitar
Products Group13
Page 14
035-17443-000 Rev. A (800)
y
g
g
g
g
y
y g
g
y
g
y
y
g
y
g
g
g
y
g
g
g
g
g
g
g
g
g
g
g
g
y
g by
y
g
y
y
y
g
g
y
g
g
g
g
g
g
START-UP AND ADJUSTMENTS
The initia l start-up of the fu rnace re quires the follo wing additional procedures.
1.When the
the
it is recommended that the
ened until the odor of
detected, immediatel
leaks. Allow five minutes for an
continuin
2.All electrical connections made in the field and in the factor
IGNITION SYSTEM CHECKOUT / ADJUSTMENT
1.Turn the gas supply ON at external m anual shutoff va lv e
and main
2.Set the thermostat above room temperature to call for
heat.
stem start-up will occur as follows:
3.S
a.The venter motor will start and come up to speed.
b.After this warm-up c
Burner ignition may not be satisfactory on first start-
NOTE:
up due to residual air in gas line, or until gas pressure (manifold) is adjusted. The control will make three (3) attempts to
light before locking out.
4.With the furnace in operation, paint the pipe joints and
valve
Bubbles indicate a
stop the leaks. If the leak persists, replace the component.
as supply is initially connected to the furnace,
as piping may be full of air . In order to purge this air ,
round joint union be loos-
as is detected. When gas is
retighten the union and check for
as to dissipate before
with the start-up procedure.
should be checked for proper tightness.
as valve.
after venter start-up, the hot surface igniter
Shortl
low for about 17 seconds.
will
cle, the ignition module will
ener
ize (open) the main gas valve for seven sec-
onds.
asket lines with a rich soap and water solution.
as leak. Take appropriate steps to
The accuracy of the gas meter is affected by both the
temperature and barometric pressure. Gas meter readin
should be ac curate at 60º F and 30.0”h.
sure. However, temperatures hi
meter to speed up resultin
readin
while lower temperatures will result in lower con-
sumption readin
reater than 30” h.g. will slow the meter while a value less
than 30” h.
tions, an error of
If weather conditions si
the time when the
meter correct ion factor can be easil
more accurate input rate adjustment. To calculate a meter
correction factor, use the following formula:
(Barometric Pressure) x 520
(Temperature + 460) x 30
Using the information from above, calculate the gas input
ratin
consumed per hour b
Btu conten t (heatin
localit
calculated.
NOTE:
multiplying the number of cubic feet of gas
. Use 1 for a meter correction factor if it was not
Contact your gas company for the actual heating
s. For the barometric pressure, a value
. speeds up the meter. Depending on the condi-
±
5% is not uncommon.
nificantly differ from these values at
as input rate is being determined, a gas
the meter correction factor and by the
value) of the gas in your particular
her than 60º F will cause the
in a higher gas consumption
= Meter Correction Factor
. barometric pres-
calculated to provide for
value of the gas in your locality as it varies widely from city to
city.
Example - Checking Gas Input
It is found b
on the 1 cubic foot dial to make a revolution with onl
120,000 Btuh furnace runnin
26 seconds in the first column of Table 5 on pa
across to the colum n he ad ed
that 138 cubic feet of
nace at that rate.
measure that it takes 26 seconds for the hand
a
. Using this information, locate
e15. Read
1 cubic foot
as per hour are consumed by the fur-
where
ou will see
s
DO NOT
omit this test! NEVER use a flame to
check for gas leaks.
CHECKING GAS INPUT
1.Turn off all other gas appliances con nec ted to gas meter.
2.With the furnace turned on, meas ure the time needed for
one revolution of the hand on the smallest dial on the
meter. A t
1 cubic foot test dial.
3.Usin
size of the test dial increment, find the cubic feet of
consumed per hour from Table 5.
14Unitar
pical domestic gas meter usually has a 1/2 or
the number of seconds fo r each revol ution and t he
With the barometer at 28.9” and a 70º F temperature, the
correction factor will be .945. If the local
935 BTU per cubic foot the calculations will be as follows:
(Gas Rate) x (MCF) x (Heatin
(138ft3/hr)(0.945)(935 Btuh/ft3) = 121,933 Btuh
The calculated firin
the
+2%
tolerance of our nominal 120,000 furnace.
If the actual input is not within
allowance bein
ulator setting (0.3 inches W.C.), replace the orifice spuds
re
with spud of the proper size.
as
rate of 121,933 BTU per hour is within
made for the permissible range of the
Value) = Hourly Input Rate
+2%
as heating value is
of the furnace rating, with
Products Group
Page 15
035-17443-000 Rev. A (800)
y
g
g
g
g
g
g
y
g
y
g
g
Be sure to relight any gas appliances that were
turned off at the start of this input check.
ADJUSTMENT OF MANIFOLD GAS PRESSURE
1.Turn gas off at main gas valve. Remove 1/8" plug/outlet
pressure tap in the main
proper manometer tu be adapter fitt in
as valve tap to manometer.
as valve body and install
. Connect line from
FIGURE 10 : GAS VALVES
TOP - WHITE-RODGERS 36F52-252
BOTTOM - HONEYWELL VR8205
The screw-off cap for the pressure regulator must be
NOTE
ure 10 on page 15 for location of outlet pres -
ulator adjustment cap and screw
as valve.
removed entirely to gain access to the adjustment screw.
The cap must be replaced in order for the furnace
to operate properly.
3.Turn gas and electrical supplies ON. Turn gas valve
switch to “ON” position. Start furnace and observe manifold pressure on manifold.
4.If necessar
valve re
, adjust manifold pressure by adjusting gas
ulator screw to agree with Table 6 values.
TABLE 6: MANIFOLD PRESSURE
Natural Gas3.5" W.C.
Propane (LP)10.0" W.C.
be necessary to re-adjust the gas valve inl et press ure
It ma
(see Table 4 for values) usin
the inlet pressure tap on valve - adjust line regulator.
If gas valve regulator is turned in, or clockwise, manifold
pressure is increased. If screw is turned out, or counterclockwise, manifold pressure will decrease.
The manifold pressure must be checked with the
screw-off cap in place on the pressure regulator.
If manifold pressure is too high, an over-fire condition exists which could cause heat exchanger failure. If the manifold pressure is too low, sooting
and eventual clogging of the heat exchanger could
occur.
a similar proced ure but usin
Unitar
Products Group15
Page 16
035-17443-000 Rev. A (800)
y
g
y
g
g
g
g
g
g
g
y
g
y
y
y
g
g
y
g
g
y
g
g
y
y
y
y
g
g
g
g
g
g
y
g
y
g
g
5.Once the correct gas pressure to the burners has been
established, turn the
the electrical suppl
sure tap at the
compound (on the threads) resistant to the action of LP
ases.
6.Turn the electrical and
the burners in operation, check for
the plu
with a soap and water solution.
as valve switch to OFF and turn
switch OFF; then, remove the pres-
as valve and re-install the plug using a
as supplies back on, and, with
as leakage around
Be sure that the gas valve pressure regulator cap
is replaced.
ADJUSTMENT OF TEMPERATURE RISE
The temperature rise, or temperature difference between the
return air and the heated air from the furnace, must be within
the range shown on the furnace rating plate and within the
application limitat ions s hown in Table 3. After the temperature
rise has been determined, the airflow (cfm) can be calculated. Refer to Blower Performance Matrix, Table 7 on pa
22.
6.Repeat the pulle
desired temperature rise is obtained.
adjustment procedure until the
ADJUSTMENT OF FAN-OFF CONTROL SETTINGS
This furnace is equipped with a time-on / time-off heating fan
control. The fan on dela
is field adjustable from 60 to 180 seconds. The fan off
dela
dela
is factory set to 120 seconds.
The “fan-off” settin
the furnace, but not so lon
heated space. The “fan-off” timin
the jumper (refer to Figure 11 ) located on the con-
tionin
trol board.
e
is fixed at 30 seconds. the fan off
must be long enough to adequately cool
that cold air is blown into the
may be adjusted by posi-
After about 20 minutes of operation, determine the furnace
temperature rise. Take readin
heated air in the ducts, about six feet from the furnace where
will not be affected by radiant heat.
the
Increase the blower speed to decrease the temperature rise;
decrease the blower speed to increase the rise. Blower
speed adjustment is made as follows:
1.Remove the belt and loosen the set screw in the adjustable flan
2.Close the pulle
the pulle
3.Position the set screw with one of the flats on the pulle
hub and ti
4.Ali
pulle
e of the motor pulley.
to decrease the temperature rise; open
to increase the rise.
hten it.
n the fixed flange of the motor pulley with the blower
.
s of both the return air and the
Improper alignment will cause excessive noise,
belt wear and bearing failure.
5.Adjust the belt tensio n wi th the motor adjustin
the belt can be depressed 1" with a fin
between the two pulleys. Loosen the (4) motor
wa
mount bolts to permit adjustment. Reti
adjustin
.
hten bolts after
bolt until
er at a point half-
FIGURE 11 : FAN-OFF TIME ADJUSTMENT
ACCESSORY CONNECTIONS
The furnace control will allow power switching control of various accessories. Refer to Fi
Electronic Air Cleaner Connection:
nals (EAC and EAC N) for electronic air cleaner connections
are located on the control board. The terminals provide 115
VAC (1.0 amp maxi mum) durin
Humidifier Connection:
and HUM N) for humidifier connections are located on the
control board. The terminals provide 115 VAC (1.0 amp maximum) during heating system operation
Twinning:
duct s
latin
before the second blower, the duct s
surized wit h air and the se cond blower wi ll be made to t urn
backwards. During heating operation, this will cause overheatin
condition and dama
When two furnaces are installed using the same
stem, it is very important that the two furnaces circu-
air blowers operate simultaneously. If one blower starts
of the second furnace, possibly causing an unsafe
e to the furnace. If twinning of two fur-
ure 12 for connection details.
Two 1/4" spade termi-
circulating blower operation.
Two 1/4" spade terminals (HUM
stem will become pres-
16Unitar
Products Group
Page 17
035-17443-000 Rev. A (800)
y
g
g
g
y
naces is desired, it is necessary to use the accessory twinin
kit that is designed for use with these furnaces.
This furnace is equipped with a “Time-On” Delay Relay which
is required to protect the belt-drive motor/starter if operated
(1) under continuous fan mode, or (2) when installin
kit 2TC03700124. Application of twinning kit also
nin
requires use of “Accessor
Sensor Kit 2TS03700106.
twin-
FIGURE 12 : ACCESSORY CONNECTIONS
Unitar
Products Group17
Page 18
035-17443-000 Rev. A (800)
y
g
g
g
g
g
y
g
g
g
g
g
g
g
g
g
g
g
g
y
g cy
g cy
g
y
g
g
g
g
y
g
g
y
g
g
y
g
g
g
g
g
g
g
y
y
y
y
OPERATION AND MAINTENANCE
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. See “WIRING DIAGRAM” Fi
location. Refer to Fi
ure 13 for event schedule.
CONTINUOUS BLOWER
On cooling / heating thermostats with fan switch, when the
fan switch is set in the ON position, a circuit is completed
between terminals R and G of the thermostat. The blower
motor is ener
selected speed.
ized through the contactor and runs at the
INTERMITTENT BLOWER - COOLING
On cooling / heating thermostats with fan switch, when the
fan switch is set in the auto position and the thermostat calls
for coolin
minals. The motor is ener
runs at the selected speed. The No “On-Dela
tin
, a circuit is compl ete d b etwe en the R , Y an d G ter-
ized through the contactor and
is fixed at 60 seconds for SEER enhancement.
HEATING CYCLE
When the system switch is set on HEAT, the fan is set on
AUTO, and the room thermostat calls for heat, a circuit is
completed between the terminals R and W of the thermostat.
When the proper amount of combustion air is bein
a pressure switch activates the i
ure 14, for component
”“Fan-Off” set-
provided,
nition control.
After the 60-second wait, the i
with an additional 10 seconds of i
i
nition attempt is unsuccessful, one more re-try will be
made before lockout.
A momentar
or open condition in the flame probe circuit will be sensed
within 0.8 seconds.
as valve will de-energize and the control will restart the
The
nition sequence immediately. Recycles will begin and the
i
burner will operate normall
fault condition is corrected prior to the last i
Otherwise, the control will lockout.
The control will repeat the i
cles if flame is lost within the first 10 seconds of
rec
establishment.
If flame is esta bli sh ed fo r m ore t han 1 0 seconds after i
the control will clear the i
flame is lost after 10 seconds, it will restart the i
sequence. This can occur a maximum of five times.
Durin
millseconds or lon
the power is restored, the
and a restart of the i
loss of gas supply, flame blowout, or a shorted
burner operation, a momentary loss of power of 50
er will drop out the main gas valve. W h en
nition sequence will begin immediately.
nition sequence is restarted
niter warm-up time. If this
if the gas supply returns, or the
nition attempt.
nition sequence for a total of two
nition,
nition attempt (retry) counter. If
nition
as valve will remain de-energized
HOT SURFACE IGNITION SYSTEM
The ignition control provides a 17-second warm-up period.
as valve then opens for seven seconds.
The
As gas starts to flow and ignition occurs, the flame sensor
ins its sensing function. If a flame is detect ed withi n seve n
be
seconds after i
until the thermostat circuit between R and W is opened. After
flamme is present for 30 seconds, the circulatin
ener
ized.
When the thermostat circuit opens, the i
ener
ized. With the ignition control de-energized, the gas
flow stops and the burner flames are extin
ventor continues to operate for 15 seconds after the
stops.
The blower motor contin ue s to o pera te fo r the a mo unt o f tim e
set b
the fan-off del ay switches located o n th e c ontrol board.
The heatin
the start of the next heatin
If the flame is not detected within the seven second sensin
period, the gas valve is de-energized. The control is
equipped with a re-tr
followin
detected).
an unsuccessful ignition attempt (flame not
nition, normal furnace operation continues
blower is
nition control is de-
uished. The
as flow
cle is then complete and the unit is ready for
cle.
option. This provides a 60-second wait
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a
potential shock ha zar d from the com ponent s of th e
hot surface ignition system. The furnace can only
be lit automatically by its hot surface ignition system.
MAINTENANCE
AIR FILTERS
The filters should be checked periodically for dirt accumulation. Dirt
the s
Clean (or rep lace) th e filter s at least ev er
new construction, check the filters ever
filters greatly restrict the flow of air and overburden
stem.
three months. On
week for the first
18Unitar
Products Group
Page 19
035-17443-000 Rev. A (800)
y
y
y
g
y
y
y
g
y
g
g
g
y
y
g
g
g
g
y
g ig
g
g
g
y
g
y
y
g
y
g
y
g
g
y
g
y
y
g
g
y
g
four weeks. Inspect the filters every three weeks after that,
especiall
if the system is running constantly.
When replacing filters,
DO NOT
use a type with
excessively high pressure drop. Some high efficiency filters available will cause the furnace to
operate improperly and could result in a safety
hazard.
LUBRICATION
Blower and venter motors in these furnaces are permanentl
lubricated and do not require periodic oiling.
BLOWER CARE
Even with good filters properly in place, blower wheels and
motors will become dust laden after lon
tion. The entire blower assembl
all
. If the motor an d w h eel ar e he a vi ly coated with dust, the
can be brushed and cleaned with a vacuum cleaner.
The procedure for removing the blower assembly for cleanin
is as follows:
should be inspected annu-
months of opera-
BURNER REMOVAL / CLEANING
The main burners should be checked periodically for dirt
accumulation.
If cleanin
1.Turn off the electrical power to the unit and turn off
2.Remove the blower and burner compartment access
3.Unplu
4.Note the location and then disconnect the senser and
5.Remo ve the two screws securin
6.To re-assemble - reverse the procedure. Restore power
is required, follow this procedure:
at the shutoff valve.
suppl
doors.
niter from the wire harness and remove the
niter / bracket assembly from the burner air shield.
i
Handle the i
ken.
rollout switch wires located on the top of the air shield
and remove the shield.
burner assembl
ed side down) before removing. Burners may be
(flan
cleaned b
cleaner.
and verif
niter carefully as it is fragile and easily bro-
each burner to the
. Note the orientation of the burner
rinsing in hot water or by using a vacuum
operation.
as
1.Turn off electrical power suppl
nect switch(s). Remove access doors. Remove motor
harness usin
2.Remove the screws holdin
blower. Swin
removal of the blower.
3.Remove blower/motor assembl
and deck screws; Stop and slide the blower assembl
out of the slots in the deck.
4.When cleanin
NOT remove or chan
wheel.
3 wires on panel.
the control box out of the way to allow
or servicing the blower assembly, DO
e the balance clips on the blower
to the furnace at discon-
the control box to the
, shipping screws (2),
This blower motor assembly weighs 90 lbs. Have
adequate support to prevent injury.
5.To reassemble, reverse the procedure, restore power to
the furnace and verify operation.
6.To re-assemble, reverse the procedure, restore power
and verify operation.
CLEANING THE HEAT EXCHANGER
If heat exchanger is sooted, it is recommended that
NOTE:
the heat exchanger be replaced due to difficulty in cleaning.
Lower Heat Exchanger Access
1.Turn off the electrical power to the unit and turn off
at the shutoff valve.
suppl
2.Remove the blower and burner compartment access
doors. Disconnect the gas supply piping at the union to
permit removal of the entire burner and
assembl
on the
3.Unplu
senser and rollout switch wires located on top of the air
shield. Identify and note the loc atio n o f al l l ead s for ease
of reinstallation. Also disconnect the wires at the side
rollout switches (upflow onl
4.Remove the screws holdin
vestibule panel and remove this assembl
assembl
fra
exchan
assembl
as outlined in burner cleanin
from the vestibule panel. Use the wren ch boss
as valve when removing or installing this piping.
the igniter from the wire harness. Disconnect
) and the gas valve wires.
the burner assembly to the
carefully since it cont ains the igniter which is
ile and easily broken. The lower portion of the heat
er will now be exposed. To clean the burner
, use a vacuum cle aner, or remove the burners
, and clean in hot water.
as control
. Handle the
as
Unitar
Products Group19
Page 20
035-17443-000 Rev. A (800)
y
g
g
g
g
g
y
y
g
g
g
g
g
y
g
y
y
g
g
g
g
g
g
g
g
g
y
y
g
y
y
y
g
g
y
y
y
g
y
g
g
y
y
y
y
y
y
g
y
y
g
Upper Heat Exchanger Access
1.Perform steps 1-4 above.
2.Disconnect vent pipin
the top panel on the furnace.
3.Unplu
NOTE:
the venter motor wires and ground wire. Remove
the pressure switch tubin
housin
.
It is recommended that replacement gaskets be
from the vent motor assembly at
at the tap on the venter motor
available before removing venter motor.
4.Remove six mounting screws that hold the venter motor
to the restr ictor plate. The surface is
ket can be reused if it is carefull
to remove this assembly to gain access to the
sar
restrictor plate mountin
vacuumed if cleanin
parts are dama
(except for
5.Remove the perimeter screws attachin
plate assembl
asketed. The assembly, including the flue baffle
also
plate (rear) ma
if necessar
6.The upper portion of the heat exchan
ble. With a lon
tube at both the top and bottom. The brush must pass
around the rear heat exchanger tubes. Vacuum loose
scale and dirt from each tube.
7.Clean - Replace all components in reverse orde r. Re
ket all surfaces which required a
. Reattach vent pipe and gas supply lines before
wirin
restorin
check
operation.
as supply piping for leaks, then verify furnace
ed, replace with an entire new assembly
askets).
to the vestibule panel. The surface is
be vacuumed or cleaned with hot water
.
flexible wire brush, clean inside each
service to furnace. Restore electrical power,
holes. The assembly may be
is necessary. If any vent assembly
asketed and gas-
removed. It is neces-
the restrictor
er is now accessi-
as-
asket. Reconnect all
TROUBLESHOOTING
The following visual checks should be made before troubleshootin
1.Check to see that the power to the furnace and the igni-
2.The manual shutoff valves in the gas line to the furnace
3.Make sure all wirin
4.Review the sequence of operation.
Start the s
temperature. Observe the s
troubleshootin
operation.
:
tion control module is ON.
must be open.
connections are secure.
stem by setting the thermostat above the room
stem's response. Then use the
section in this manual to check the system's
FURNACE CONTROL DIAGNOSTICS
The furnace has a built-in, self diagnostic capability. If a system problem occurs, a fault code is shown b
It is loca ted behind a clear view port in t he blower c ompartment door. DO NOT remove the furnace blower compartment
panel OR turn off furnace power as either action will clear the
control's memory of the fault.
The control continuousl
operation of the s
cate the failure code. If the fa ilure i s inte rnal to the co ntrol, th e
ht will stay on continuously. In this case, the entire control
li
should be replaced as the control is not field repairable.
Flash sequence codes 1 thou
turn “on” for one second and “off” for one second. This pattern will be repeated the number of times equal to the code.
For example, six “on” flashes equals a number 6 fault code.
All flash code sequences are broken b
period.
IGNITION CONTROL (P/N 031-01267-001)
Normal flame sense current is approximately
Low flame signal and control lockout point is
CONTINUOUS FLASH: This indicates the flame was sensed
when there was not a call for heat. With this fault code the
control will turn on both the inducer motor and suppl
blower. This fault would t
that leaks throu
2 FLASH: This indicates that the normally open pressure
switch contacts are stuck in the closed position. The control
confirms these contacts are open at the beginning of each
cle. This would indicate a faulty pressure switch or m
heat c
is-wirin
3 FLASH: This indicates the normally open pressure switch
contact did not close at the be
could be caused b
blocked vent pipe, broken pressure switch hose or fault
pressure swit ch.
4 FLASH: This indicates that a primary or auxiliary limit
switch has opened its normall
fault code the control will operate the suppl
inducer. This condition m a
erl
incorrect firin
5 FLASH: This fault is indicated if the normall
tacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air,
proper inducer operation, primar
burner problem. Be sure to reset the switch after correctin
the failure condition.
6 FLASH: This indicates that after the unit was opening, the
pressure switch open ed 4 time s d urin
main blower is in a “Dela
subsequent delay off period. The ventor continues to
an
operate until the pressusre switch re-closes or a call for heat
is removed.
7 FLASH: This fault code in dicates that t he flame could not
be established. This no-li
retries) durin
be caused by low gas pressure, faulty gas valve, fau lty hot
surface i
8 FLASH: This fault in indicated if the flame is lost 5 times (4
rec
cles) durin the heating cycle. This could be caused b
low gas pressure or faulty gas valve.
9 FLASH: Indicates reversed line volta
and cooling operations will be affected. Check polarity at
in
furnace and branch.
11 FLASH: This fault will be indicated if the rollout jumper
wire connection soldered into the board is broken. If this fault
occurs the control will have to be replaced. This fault ma
also occur in installations when an improper ground is
present. Prior to replacin
erl
rounded.
STEADY ON: This fault occurs if the
when there is no call for heat. If this happens the ventor is
energized and will remain energized for 5 seconds or until the
fault clears itself at which point the ventor de-ener
the call for heat before locking out. This ma
nitor or burner problem.
On” mode, it will co mplete it and
ht condition occurred 3 times (2
control, verify that the unit is prop-
the call for heat. If the
e polarity. Both heat-
as valve is energized
izes. This
failure is counted as a rec
for proper operation.
60 MINUTE AUTOMATIC RESET FROM LOCKOUT: This
control includes a “wat chdo
lockout condition after 60 minutes. Operational faults 1,6,7,8
and Stead
unoccupied structure if a temporar
a furnace malfunction. An example would be a low incomin
as supply pressure preventing unit operation. When the gas
pressure is restored, at some point the “watchdo
restart the unit and provide heat for the house.
NOTE:
On will be reset. This provides protection to an
If a flame is detected, the control flashes the LED for
cle. Check the valve and control
” type circuit that will reset from a
condition exists causin
” would
1/8 of a second and then enters a flame stabilization period.
jumper the pressure switch to allow furnace
Never
operation. To do so will allow furnace to operate
under potentially hazardous conditions.
Do not try to repair controls. Replace defective
controls with UPG Source 1 Part s.
Never adjust pressure switch setpoint to allow
furnace operation.
Operation at these conditions will cause motor overload.
Operation in the shaded area ma
NOTES:
Airflow is expressed in standard cubic feet per minute.
EXTERNAL STATIC PRESSURE, INCHES W.C.
3467331831632950
1307----
EXTERNAL STATIC PRESSURE, INCHES W.C.
3383324231002890
1724----
cause excessive furnace temperature rise.
1.00
2049
18601026
1.00
1804
1889--
22Unitar
Products Group
Page 23
035-17443-000 Rev. A (800)
y
y
y
g
y
y
g
y
y
y
y
y
y
y
g
g
g
y
g
g
y
y
g
y
FILTER PERFORMANCE
The airflow capacit
data published in Table 7 represents
blower performance WITHOUT filters. To determine the
approximate blower performance of the s
ter drop value for the filter bein
used or select an appropri-
stem, apply the fil-
The filter drop valu es in Table 8 are t
of filter listed and should onl
pressure drop ratin
s for each filter type vary between filter
be used as a gu ideline. Actual
manufacturer.
pical values for the type
ate value from Table 8.
TABLE 8: FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.
Note: Data includes pressure drop of bottom filter rack.
APPLYING FILTER PRESSURE DROP TO DETERMINE
SYSTEM AIRFLOW
To determi ne t he a pproximate airflow of the un it w i th a fil ter i n
place, follow the steps below:
1.Select the filter t
2.Determine the External S
pe.
stem Static Pressure (ESP)
without the filter.
3.Select a filter pressure drop from the table and add to the
ESP from Step 3 to determine the total s
stem static.
High VelocityDisposableHigh Velocity
3.Subtract the total s
difference b
0.60”-0.50”, to obtain a percenta
stem static from 0.50” and divide this
the difference in ESP values in the table,
e.
(0.58-0.50) / (0.60-0.50) = 0.8
4.Multipl
percentage by airflow differenc e to obtain airflow
reduction.
(0.8) x -144) = -115
Subtract airflow reduction value to airflow @0.50” to obtain
actual airflow @0.58” ESP.
3550 - 115 = 3435
4.If total s
flow table (i.e., 0.20, 0.60, etc.) the s
stem static measures an ESP value in the air-
stem airflow corresponds to the intersection of the ESP c olumn and Blower
Speed row.
5.If the total s
in the table (i.e., 0.58, 0.75, etc.) the stati c pressure ma
be rounded to the nearest value in the table determinin
the airflow usin
the followin
Example: It is fouond that the total s
1-turn pulley. To determine the system airflow, com-
usin
plete the f ollowin
stem static falls between ESP ESP values
Step 5 or calculate the airflow by using
example.
stem stati c is 0 .58” w.c.
steps:
1.Ob tain the airflow v alues at 0.50” and 0.60” ESP.
Airflow @ 0.50”: 3550 CFM
Airflow@0.60”: 3406 CFM
2.Subtract the airflow @0.50” from the airflow @0.60” to
obtain airflow difference.
3406 - 3550 = -144
Unitar
Products Group23
Page 24
FIGURE 14 : WIRING DIAGRAM
y
NOTE:
The furnace’s control s
stem depends on correct polarity of the power supply.