J+J J3-35, J3-20, J3-85, J3-140, J3-300 Quick Manual

...
J3 Status light functions:
The LED flashes on/ off
When the valve actuator senses an impending valve jam, the electronic torque limiter is
activated and on activation,
Constantly lit LED
If the electric actuator is operat­ing correctly with no faults, the
LED shows a constantly lit
light.
The LED flashes with 2 blinks
If the actuator has been left in
‘manual’ mode, the actuator’s motor runs but doesn’t drive
the output shaft. After a pre-set time, the actuator knows that as the torque limiter has not activated and that the motor is
running, it must be in manual.
Aug 2010
Doc: J3-H85/07 KW
the manual override to be se­lected to assist in clearing the
jam. The effect of condensation in
the J3 electric actuator is eliminated by an internal ther­mostatic anti-condensation heater that does not require a separate independent power
supply.
Standard function for the
J3-H85 electric valve actuator
is power open, power close, stays put on power
failure.
New to the J3 electrical actu­ators are plug and play accesso­ries –the function can be changed to either failsafe or modulating by fitting the new
plug and play conversion kits. The modulating kit has the new
digital positioner that offers auto-calibrating and self reset­ting functionality. These conver­sion kits are available as option-
al extras.
The J3 is a very smart red box!
Feature rich J+J multi-voltage electric actuator with LED status light and plug & play accessories.
New in 2008, the J3 range of electric actuators takes its high­ly successful predecessor, the J2
range, to the next level.
With an all new, rugged weath­erproof and anti-corrosive
Polyamide housing, the J3 valve actuator offers more user
-friendly features than the J2, and introduces a highly visible
LED status light.
This visual indicator shows whether the actuator is operat­ing correctly, or has tripped out either by its electronic torque limiter, or has been left in
‘manual’ mode.
Site operators are no longer
left with the ‘valve or actuator?’
question when an actuator doesn’t respond to a signal.
The J3 rotary electric actua­tor is quick and easy to install,
with IS0:5211 multi­flange mounting and a double
square drive, allowing fast mounting to ISO:5211 valves. There is no need to remove the cover to connect the J3 electri­cally, saving installation time.
Using the external DIN plugs and external wiring diagrams supplied with the actuator, installations
can be pre-wired. Protection against valve jams is
provided by an electronic torque limiter, which auto-relaxes the gearbox when activated, allowing
Quick guide to the
J3 electric actuator:
Standard Features
Multi-voltage electric actuator with auto-voltage sensing. 110 ~ 24V0 AC or DC .
LED Status light to indicate operational status of actuator
Electronic over-torque protec­tion against valve jams
Thermostatic anti-condensation heater
Manual override for emergency hand operation
2 Volt free end of travel confir­mation switches
IP65 weatherproof anti­corrosive and UV protected Polyamide housing
Local visual position indicator
ISO5211 multi-flange mounting with double square drive
All external electrical connec­tions via supplied DIN plugs
CE marked
IS0 9000 manufacturer
Failsafe and digital positioner plug & play kits available.
Model J3 - H85
Electric Actuator
Specifications: J3 H85
Materials of construction:
The J3 - H85 electric rotary actuator
Model J3 – H85 Electric Actuator
Visual indication of the
actuator’s operating
status is constantly shown by a highly visible LED light.
J3
Voltage range - automatically sensed by actuator 85-240 AC (1ph) or DC
Operating time (0-90° no load) 30 seconds
Maximum break torque 93.5 Nm / 827 lb.ins
Maximum operating torque (run/ reseat) 85 Nm / 752 lb.ins
Duty rating 75%
IP Rating (IEC 60529) IP65
Working angle Standard (on request) 90° (180° or 270° options)
Mounting ISO:5211 x DIN 3337 F05 & F07 x 17
Motor switches 2 x SPDT micro switches
End of travel confirmation (volt free) 2 x SPDT micro switches
Heater 4 W
Ambient temperature range -20° to +70°C -4 to +158°F
Electrical connecting plugs DIN 43650/ ISO4400 & C192
Consumption:
240V/1ph At maximum torque 0.09A
240V DC At maximum torque 0.10A
110V/ 1ph At maximum torque 0.22A
110V DC At maximum torque 0.17A
Weight 3.0 kg
Housing Anti-corrosive Polyamide
Fasteners Stainless steel
Gears Polyamide (speed reducing) & steel
Shaft Stainless steel
Output drive Zammac
Position indicator Glass filled Polyamide
Method of operation:
On receipt of a continuous power signal within the voltage range shown above, the motor in the J3 electric actuator runs and, via a flat gear system, rotates the output shaft. The motor is stopped by internal cams striking micro switches. On receipt of a reversing continuous signal, the motor turns in
the opposite direction reversing the output drive. Note: The power signal needs to remain on at all times to activate the thermostatic anti-condensation
heater. The volt free end of travel confirmation switches must NOT be used to cut the power. As they are set ahead of the final motor stop position, cutting the power on receipt of the end of travel signal will result in the J3 electric actuator stopping short of the full open or full closed position determined
by the motor switch settings.
The standard on-off version can have plug and play failsafe or modulating kits retro­fitted to convert the function.
The modulating kit contains a self calibrating digital positioner.
Dimensions: J3 - H85
Change of function retro-fit kits:
Failsafe option
This kit converts the electric actuator to a failsafe unit
using a BSR (Battery ‘Spring Return’) system that pro-
vides an alternative (battery) power supply to set the actuator in the failsafe position should the main power
supply fail.
It can be configured normally open, or normally closed.
Modulating Option
Using the new self calibrating and self adjusting digital positioning system, this kit converts the actuator to a modulating electric actuator using either a 4-20mA or
0-10VDC control signal.
An output signal is provided as standard.
Model J3 - H85 Electric Actuator
J3
LED status light
55mm
2.17”
73mm
2.88”
177mm
6.97”
196mm 7.72”
128mm 5.04”
Mounting F05 F07
ISO: 5211 50mm 70mm
Drive 17mm
Optional 14mm
Failsafe modulating option
Install both kits
J3 Electric rotary actuator
J+J’s BSR system simply provides an alternative
power supply to drive the electric actuator to a pre­set failsafe position in the event of a mains power failure. It has no mechanical springs, it uses internal
battery power.
During normal operation the J3-BSR operates as a power open - power closed electric actuator, simulta­neously maintaining the industrial re-chargeable battery
at full strength from an internal trickle charging system.
The main advantage of J+J’s BSR system is that it is more competitively priced compared to mechanical
spring return electric actuators, as the J+J failsafe actuator has no mechanical springs to compress, or solenoids to release them - the actuator is the same size as that for an on-off version. This offers massive savings compared to true mechanical spring return
electric actuators.
What it does and how it works
Aug 2010
Doc: J3/BSR/03/KW
Quick guide to the
J3 electric actuator
standard features :
Highly visible LED light gives
continuous actuator status
indication.
J3 L - 12-24V AC/DC
J3 H - 80-240V AC/DC
Multi-voltage electric actuator with auto-voltage sensing:
Torque output: range: 25~95Nm Break 20~80Nm Reseat
Electronic torque limiter Protects against valve jams
Anti-condensation heater
Manual override
All connections via external DIN plugs ~ no need to remove cover to connect
Volt free end of travel
confirmation switches
IP65 weatherproof housing
CE marked
Traceable sequential serial num­bering system
Optional failsafe kit (Battery Back-up) - actuator fails to safe position on power failure
Optional modulating kit with digital positioning system, either
0-10V or 4-20mA
Failsafe version ‘BSR’
Battery ‘Spring Return’
J3
The industrial battery is deliberately oversized and whilst not necessary, can provide many cycles at full load. This offers a degree of pro­tection in the unlikely event that the battery
degrades and loses some charge.
In the event of a mains failure, if not already in that position, an internal switch changes to immediately draw battery power to drive the
actuator to the failsafe position.
Following a battery driven cycle the actuator will need to charge for a short period to re-
place the energy used in the battery cycle. This is particularly relevant if you intend to
use the J3 -BSR like a solenoid, eg: energise open, fail close.
The BSR fits inside the J3 electric actuator housing eliminating extra piggy-backed hous­ings, making the J3 failsafe actuator very compact and lightweight. It can be supplied as a retro-fittable kit containing all the parts needed to convert a standard on-off electric
actuator.
Charging data
Aug 2010
Doc: J3/BSR/03/KW
Quick guide to the
J3 electric actuator
standard features :
Highly visible LED light gives
continuous actuator status
indication.
J3 L - 12-24V AC/DC
J3 H - 80-240V AC/DC
Multi-voltage electric actuator with auto-voltage sensing:
Torque output: range: 25~95Nm Break 20~80Nm Reseat
Electronic torque limiter Protects against valve jams
Anti-condensation heater
Manual override
All connections via external DIN plugs ~ no need to remove cover to connect
Volt free end of travel
confirmation switches
IP65 weatherproof housing
CE marked
Traceable sequential serial num­bering system
Optional failsafe kit (Battery Back-up) - actuator fails to safe position on power failure
Optional modulating kit with digital positioning system, either
0-10V or 4-20mA
Failsafe version ‘BSR’
Battery ‘Spring Return’
J3
J3-20 J3-35 J3-55 J3-85 J3-140 J3-300
Initial minimum charge time
BEFORE being put into service 36 hrs 36 hrs 36 hrs 36 hrs
Not in
production
Not in
production
Nominal capacity ± 5% 800mA 800mA 800mA 800mA
Battery consumption per
Movement (W)
0.1
0.18
0.23
Minimum recharge time after movement by battery
26 mins 26 mins 50 mins 65 mins
Configuration
The J3-BSR is factory supplied to fail closed on mains failure (normally closed) but can be configured to fail open (normally open) simply by removing a jumper from the actuator PCB - see below.
A few seconds after a power cut, the J3’s LED will slowly flash and the actuator will be driven to the fail safe position, the LED will continue to flash on-off for 3 minutes - during this time the battery pro-
vides power to the J3’s internal circuitry and anti-condensation heater. At the end of these 3 minutes, if mains power has not been restored, the J3 completely shuts down and the LED goes out.
On resumption of mains power, conditional that the control signal has not changed during the power outage, the actuator will reset to the position it saw at the moment of the power failure.
‘NC’ Normally closed jumper position
(factory standard)
‘NO’ Normally open jumper position
(jumper removed)