Do Žlábku 733, 514 01 Jilemnice
Subject: MTP Technical documentation Page No./No. of pages: 5/20
TECHNICAL CONDITIONS
INSTRUCTIONS FOR INSTALLATION, OPERATION
AND MAINTENANCE OF AIR HEATER MTP,
MTPAL, MTP-V
1. Use:
Air heaters using gaseous fuels are used to heat the air for purposes of heating or
ventilation with heating and are designed for separate operation or for installation in airconditioning systems, air-conditioning units and other applications.
2. Function description
The basis of the heaters MTP, MTPAL, MTP-V is a closed air-flue gas exchanger which
consists of a combustion chamber and a tube heat exchanger. The air-conditioning and
combustion circuit of the air heater are therefore separated. The heater heats the air
conveyed by the fan that is or is not part of the heater (depending on the type). The air is
sucked directly from the heated space or via the air-conditioning piping. The air is heated
while circling around the combustion chamber and the tube heat exchanger and being
heated it flows through the heater to its discharge section.
The burners are always pressure burners and only separately certified highquality burners are used. The burner is designed according to the fuel used, its inlet
pressure and the regulation requirement. Flue gases are drawn from the combustion
chamber by a chimney (the chimney is not a part of the heater).
3. Type designation:
Produced heaters are marked with a type designation, the meaning of which is as
follows:
MTP 50
MTPAL 50
MTP-V 50
designation of the heater
type size (according to the table of basic parameters)
MTP 25, 37, 50, 65, 85, 100, 125, 150, 175, 225, 300, 350, 400, 525, 650,
850, 1000, 1500, 2000, 2500
MTPAL 50, 80, 150, 200, 300, 500, 700, 900, 1200
MTP-V P1, P2, 25, 37, 50, 65, 85, 100, 125, 150, 175, 225, 300, 350, 400, 525,
650, 850, 1000, 1500, 2000, 2500
4. Design description: