JinkoSolar Photovoltaic Module Installation Manual

JinkoSolar
Photovoltaic Module
Installation Manual
Contents
1 General Information
1.1 Overview
1.2 Warnings
2. Installation
2.1 Installation Safety
2.2 Installation Condition
2.2.1 Climate Condition
2.2.2 Site Selection
2.2.3 Tilt Angle Selection
2.3 Mechanical Installation Introduction
2.3.1 Mounting with Bolts
2.3.2 Mounting with Clamps
1 1
1
3
3
4
4
4
5 5
6
3 Wiring and Connections
4 Maintenance and Care
4.1 Visual Inspection
4.2 Cleaning
4.3 Inspection of Connector and Cable
5 Electrical Specification
6 Disclaimer of Liability
Appendix1: Applicable Products
Appendix2Electrical Specifications
22
24 24
25
25
25
26
26
34
Edition 10/2020
-1-
1. General Information
1.1 Overview
Thanks for choosing Jinko Solar PV modules. In order to ensure the PV modules are installed correctly, please read the following installation instructions carefully before modules are installed and used. Please remember that these products generate electricity and certain safety measures need to be taken to avoid danger. Make sure the module array is designed in such a way not to exceed the maximum system voltage of any system component such as connectors or inverters. The assembly is to be mounted over a fire resistant roof covering rated for the application. Before mounting the module, please consult your local building department to determine approved roofing materials. The modules are qualified for application class A: Hazardous voltage (IEC 61730: higher than 50V DC; EN 61730: higher than 120V), hazardous power applications (higher than 240W) where general contact access is anticipated. Modules qualified for safety through EN IEC 61730 -1 and - 2 within this application class are considered to meet the requirements for Safety Class II.
1.2 Warnings
PV modules generate DC electrical energy when exposed to sunlight or other light sources. Active
parts of module such as terminals can result in burns, sparks, and lethal shock.
Artificially concentrated sunlight shall not be directed on
the module or panel.
Front protective glass is utilized on the module. Broken
solar module glass is an electrical safety hazard (may cause electric shock or fire). These modules cannot be repaired and should be replaced immediately.
To reduce the risk of electrical shocks or burns, modules
may be covered with an opaque material during installation to avoid injury.
The installation work of the PV array can only be done under the protection of sun-sheltering covers
or sunshades and only qualified person can install or perform maintenance work on this module.
Follow the battery manufacture’s recommendations if batteries are used with modules.
Do not use this module to replace or partly replace roofs and walls of living buildings. Do not install modules where flammable gas may be present. Do not remove any part installed by Jinko Solar or disassemble the module.
-2-
All instructions should be read and understood before attempting to install, wire, operate and
maintain the module.
Don’t lift up PV modules using the attached cables or the junction box.  Do not touch live terminals with bare hands. Use insulated tools for electrical connections.
All PV systems must be grounded to earth. If there is no special regulation, please follow the National
Electrical Code or other national code.
Under normal conditions, a photovoltaic module is likely to experience conditions that produce more
current and/or voltage than reported at standard test conditions. Accordingly, the value of Isc and Voc marked on the module should be multiplied by 1.25 when determining PV system component voltage ratings, conductor current ratings, fuse sizes, and size of controls connected to the PV output.
Once the PV module has been shipped to the installation site, all of the parts should be unpacked
properly with care.
Do not stand or step on the PV module like below pictures show. This is prohibited and there is a
risk of damage to the module and cause injury for you.
Only PV modules with the same cell size should be connected in series. During transporting modules, please attempt to minimize shock or vibration to the module, as this
may damage the module or lead to cell micro cracks.
During all transportation situations, never drop the module from a vehicle, house or hands. This will
damage module.
Do not clean the glass with chemicals. Only use tap water. Make sure the module surface
temperature is cool to the touch. Cleaning modules with cool water when module surface temp is high may result in glass breakage.
-3-
Do not disconnect any of the modules when under load. When looking at PV modules with anti-reflection (AR) coating technology, it will be normal to see
some cells with a slight color difference at different angles. Modules with LRF(light reflective film) and without LRF should not be built in the same array or roof.
Connector of junction box can not be contacted with oily substances, for example, lubricant, rust
inhibitor etc.
 The maximum altitude the PV module is designed for ≤ 2000m.  The maximum irradiance is 1300W/m2 for module with transparent rear.  Meaning of crossed –out wheeled dustbin:
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities. Contact your local government for information regarding the collection systems available. If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into the groundwater and get into the food chain, damaging your health and well-being. When replacing old appliances with new ones, the retailer is legally obligated to take back your old appliance for disposals at least free of charge.
2. Installation
2.1 Installation Safety
Always wear protective head gear, insulating gloves and safety shoes (with rubber soles). Keep the PV module packed in the carton until installation. Do not touch the PV module unnecessarily during installation. The glass surface and the frame may
be hot. There is a risk of burns and electric shock.
Do not work in rain, snow or windy conditions. Due to the risk of electrical shock, do not perform any work if the terminals of the PV module are wet. Use insulated tools and do not use wet tools. When installing PV modules, do not drop any objects (e.g., PV modules or tools). Make sure flammable gasses are not generated or present near the installation site. Insert module connectors fully and correctly. An audible "click" sound should be heard. This sounds
confirms the connectors are fully seated. Check all connections.
The module leads should be securely fastened to the module frame, Wire Management should be
-4-
done in a way to avoid the connector from scratching or impacting the back sheet of the module.
Do not touch the junction box and the end of the interconnect cables (connectors) with bare hands
during installation or under sunlight, regardless if the PV module is connected to or disconnected from the system.
Do not expose the PV module to excessive loads on the surface of the PV module or twist the frame. Do not hit or put excessive load on the glass or back sheet, this may break the cells or cause micro
cracks.
During the installation or operation, don’t use sharp tools to wipe the back sheet and glass. Scratches
can appear on the module.
Do not drill holes in the frame. It may cause corrosion of the frame. When installing modules on roof mounted structures, please try to follow the “from top to bottom”
and/or “from left to right” principle, and don’t step on the module. This will damage the module and would be dangerous for personal safety.
2.2 Installation Condition
2.2.1 Climate Condition
Please install the modules in the following conditions: a) Operating temperature: within –40°C(-40) to 85°C (185) b) Humidity: < 85RH% Note: The mechanical load bearing (include wind and snow loads) of the module is based on the approved mounting methods. The professional system installer must be responsible for mechanical load calculation according to the system design.
2.2.2 Site Selection
In most applications, Jinko solar PV modules should be installed in a location where they will receive maximum sunlight throughout the year. In the Northern Hemisphere, the module should typically face south, and in the Southern Hemisphere, the modules should typically face north. Modules facing 30 degrees away from true South (or North) will lose approximately10 to 15 percent of their power output. If the module faces 60 degrees away from true South (or North), the power loss will be 20 to 30 percent. When choosing a site, avoid trees, buildings or obstructions, which could cast shadows on the solar photovoltaic modules especially during the winter months when the arc of the sun is lowest over the horizon. Shading causes loss of output, even though the factory fitted bypass diodes of the PV module will minimize any such loss. Do not install the PV module near open flame or flammable materials. When solar modules are used to charge batteries, the battery must be installed in a manner, which will
protect the performance of the system and the safety of its users. Follow the battery manufacturer’s
-5-
guidelines concerning installation, operation and maintenance recommendations. In general, the battery (or battery bank) should be away from the main flow of people and animal traffic. Select a battery site that is protected from sunlight, rain, snow, debris, and is well ventilated. Most batteries generate hydrogen gas when charging, which can be explosive. Do not light matches or create sparks near the battery bank. When a battery is installed outdoors, it should be placed in an insulated and ventilated battery case specifically designed for the purpose. Do not install the PV module in a location where it would be immersed in water or continually exposed to water from a sprinkler or fountain etc.
2.2.3 Tilt Angle Selection
The tilt angle of the PV module is measured between the surface of the PV module and a horizontal ground surface (Figure 1). The PV module generates maximum output power when it faces the sun directly. For standalone systems with batteries where the PV modules are attached to a permanent structure, the tilt angle of the PV modules should be selected to optimize the performance based on seasonal load and sunlight. In general, if the PV output is adequate when irradiance is low (e.g., winter), then the angle chosen should be adequate during the rest of the year. For grid-connected installations where the PV modules are attached to a permanent structure, PV modules should be tilted so that the energy production from the PV modules will be maximized on an annual basis.
Figure1: PV module tilt angle
2.3 Mechanical Installation Introduction
Solar PV modules usually can be mounted by using the following methods: bolts and clamps. Note:
1) All installation methods herein are only for reference, and Jinko solar will not provide related mounting components, the system installer or trained professional personnel must be responsible for the PV system’s design, installation, and mechanical load calculation and security of the system.
2) Before installation, the following items should be addressed:
a) Visually check the module for any damage. Clean the module if any dirt or residue remains from
shipping .
b) Check if module serial number stickers match.
3) Jinko modules are designed to meet a maximum positive (or downward) pressure of 3600Pa (Only
-6-
refer to the mentioned module type in this manual) and negative (or upward) pressure of 1600Pa. This design load was then tested with a safety factor of 1.5 times. So Jinko modules are tested under a maximum downward pressure of 5400Pa and upward pressure of 2400Pa. When mounting modules in snow-prone or high-wind environments, special care should be taken to mount the modules in a manner that provides sufficient design strength while meeting local code requirements.
2.3.1 Mounting with Bolts
For mounting with bolts, the following modules in tables 1 are applicable. The frame of each module has 8 mounting holes (Length* Width: 14mm*9mm) used to secure the modules to support structure. Always use all the eight mounting holes to secure the modules. The module frame must be attached to a mounting rail using M8 corrosion-proof bolts together with spring washers and flat washers in eight symmetrical locations on the PV module. The applied torque value should be big enough to fix the modules steadily. The reference value for M8 bolt is 16~20N*m. As to special support system or special installation requirement, please reconfirm with the support’s supplier for the torque value. Please find detailed mounting information in the below illustration as Figure 2&3&4.
2.3.1.1 Mounting with Boltseight mounting holes
Figure 2: PV module installed with bolt fitting methodeight mounting holes
-7-
Module type
Max. Design Pressure: 3600Pa
(positive ) &1600Pa (negative)
mechanical load
Max. Design Pressure: 3600Pa
(positive ) &1600Pa (negative)
mechanical load
Module dimensions(mm)
A*B
54P
Height of the framemm
/
30
Group 65
1719*1134*30
Group 66
1687*1134*30
60P
Height of the framemm
35
/
Group 1
1650*992 & 1665*1002
Group 2
1665*992 & 1684*1002
Group 3
1650*992 & 1665*1002
Group 4
1665*992 & 1684*1002
Group 5
1650*992 & 1665*1002
Group 6
1665*992 & 1684*1002
Group 7
1650*992 & 1665*1002
Group 8
1665*992 & 1684*1002
Group 9
1665*992 & 1684*1002 1672*992 & 1704*1008
Group 20
1704*1008
Group 22
1684*1002
Group 30
1704*1008
Group 46
1684*1002
Group 57
1693*1029
Group 58
1693*1029
Group 59
1716*1032
Group 60
1716*1032
Group 56
1684*1002
Group 64
1750*1039 & 1750*1038
Group 61
1716*1032
Group 62
1716*1032
Group 68
1868*1134
72P
Height of the framemm
40
/
Group 10
1956*992 & 1979*1002
Group 11
1987*992 & 2008*1002
Group 12
1956*992 & 1979*1002
Group 13
1987*992 & 2008*1002
Group 14
1956*992 & 1979*1002
Group 15
1987*992 & 2008*1002
Group 16
1956*992 & 1979*1002
Group 17
1987*992 & 2008*1002
Group 18
1987*992 & 2008*1002 & 2031*1008
-8-
Group 19
2031*1008
Group 21
2008*1002
Group 29
2031*1008
Group 45
2008*1002
Group 55
2008*1002
Height of the framemm
35
/
Group 63
2090*1039 & 2090*1038
Group 71
2274*1134
Group 72
2230*1134
66P
Height of the framemm
35
/
Group 24
1796*995 & 1796*998
Group 26
1822*1008
Group 28
1822*1008
Group 32
1840*998 & 1841*1002
Group 34
1868*1008 & 1865*1005
Group 36
1868*1008 & 1865*1005
Group 38
1840*998 & 1841*1002
Group 40
1842*1021 & 1842*1024 1855*1029 & 1855*1032
Group 42
1868*1034 & 1878*1032
Group 44
1868*1034 & 1878*1032
Group 48
1842*1021 & 1842*1024 1855*1029 & 1855*1032
Group 50
1842*1021 & 1842*1024
& 1855*1029 & 1855*1032
Group 52
1842*1021 & 1842*1024
& 1855*1029 & 1855*1032
Group 54
1840*998*35(铭牌)
1841*1002*30CDF
Group 69
2089*1134
Group 70
2049*1134
78P
Height of the framemm
40
/
Group 23
2113*995 & 2113*998
Group 25
2130*1002 & 2139*1008
Group 27
2130*1002 & 2139*1008
Group 31
2163*995 & 2167*997 & 2167*998 & 2166*1002
Group 33
2194*1008 & 2190*1005
Group 35
2194*1008 & 2190*1005
Group 37
2163*995 & 2167*997 & 2167*998 & 2166*1002
Group 39
2168*1021 & 2168*1024 2182*1029 & 2182*1032
Group 41
2194*1034 & 2205*1032
-9-
Group 43
2194*1034 & 2205*1032
Group 47
2168*1021 & 2168*1024 2182*1029 & 2182*1032
Group 41
2168*1021 & 2168*1024
& 2182*1029 & 2182*1032
Group 43
2168*1021 & 2168*1024
& 2182*1029 & 2182*1032
Group 45
2166*1002
Group 73
2411*1134
Table 1: Mechanical dimensions for bolt fitting methodeight mounting holes NotesGroup 1~73 refer to appendix 1 for details. According to IEC 61215 for a maximum positive design loading of below 3600Pa, and negative design loading 1600Pa, with 1.5 times safety factor.
2.3.1.2 Mounting with Boltsfour mounting holes
Figure 3: PV module installed with bolt fitting methodfour mounting holes
Module type
Max. Design Pressure: 3600Pa (positive )
&1600Pa (negative) mechanical load
Module dimensions(mm)
A*B
60P
Height of the framemm
30
Group 1
1650*992 & 1665*1002
Group 2
1665*992 & 1684*1002
Group 3
1650*992 & 1665*1002
Group 4
1665*992 & 1684*1002
Group 5
1650*992 & 1665*1002
Group 6
1665*992 & 1684*1002
Group 7
1650*992 & 1665*1002
Group 8
1665*992 & 1684*1002
-10-
Group 9
1665*992 & 1684*1002 1672*992 & 1704*1008
Group 20
1704*1008
Group 22
1684*1002
Group 30
1704*1008
Group 46
1684*1002
72P
Height of the framemm
30
Group 10
1956*992 & 1979*1002
Group 11
1987*992 & 2008*1002
Group 12
1956*992 & 1979*1002
Group 13
1987*992 & 2008*1002
Group 14
1956*992 & 1979*1002
Group 15
1987*992 & 2008*1002
Group 16
1956*992 & 1979*1002
Group 17
1987*992 & 2008*1002
Group 18
1987*992 & 2008*1002 & 2031*1008
Group 19
2031*1008
Group 21
2008*1002
Group 29
2031*1008
Group 45
2008*1002
66P
Height of the framemm
30
Group 24
1796*995 & 1796*998
Group 26
1822*1008
Group 28
1822*1008
Group 32
1840*998 & 1841*1002
Group 34
1868*1008 & 1865*1005
Group 36
1868*1008 & 1865*1005
Group 38
1840*998 & 1841*1002
Group 40
1842*1021 & 1842*1024 1855*1029 & 1855*1032
Group 42
1868*1034 & 1878*1032
Group 44
1868*1034 & 1878*1032
Group 48
1842*1021 & 1842*1024 1855*1029 & 1855*1032
78P
Height of the framemm
35
Group 23
2113*995 & 2113*998
Group 25
2130*1002 & 2139*1008
Group 27
2130*1002 & 2139*1008
Group 31
2163*995 & 2167*997
2167*998 & 2166*1002
Group 33
2194*1008 & 2190*1005
-11-
Group 35
2194*1008 & 2190*1005
Group 37
2163*995 & 2167*997
2167*998 & 2166*1002
Group 39
2168*1021 & 2168*1024
2182*1029 & 2182*1032
Group 41
2194*1034 & 2205*1032
Group 43
2194*1034 & 2205*1032
Group 47
2168*1021 & 2168*1024 2182*1029 & 2182*1032
Table 2: Mechanical dimensions for bolt fitting methodfour mounting holes Note:The installation method of bolt fitting(four mounting holes)is based on the internal results in Jinko. According to IEC 61215 for a maximum positive design loading of below 3600Pa, and negative design loading 1600Pa, with 1.5 times safety factor.
2.3.1.3 Mounting with BoltsNextracker four mounting holes
Figure 4: PV module installed with bolt fitting method (NEX)
Module type
Max. Design Pressure: 1067Pa (positive ) &1067Pa
(negative) mechanical load
Module dimensions(mm)
A*B
72P
Height of the framemm
40
30
Group 10
1956*992 & 1979*1002
Group 11
1987*992 & 2008*1002
Group 12
1956*992 & 1979*1002
Group 13
1987*992 & 2008*1002
Group 14
1956*992 & 1979*1002
Group 15
1987*992 & 2008*1002
Group 16
1956*992 & 1979*1002
-12-
Group 17
1987*992 & 2008*1002
Group 18
1987*992 & 2008*1002 2031*1008
Group 19
2031*1008
Group 21
2008*1002
Group 29
2031*1008
Group 45
2008*1002
78P
Height of the framemm
/
35
Group 23
2113*995 & 2113*998
Group 25
2130*1002 & 2139*1008
Group 27
2130*1002 & 2139*1008
Group 31
2163*995 & 2167*997 & 2167*998 & 2166*1002
Group 33
2194*1008 & 2190*1005
Group 35
2194*1008 & 2190*1005
Group 37
2163*995 & 2167*997 & 2167*998 & 2166*1002
Group 39
2168*1021 & 2168*1024 & 2182*1029 & 2182*1032
Group 41
2194*1034 & 2205*1032
Group 43
2194*1034 & 2205*1032
Group 47
2168*1021 & 2168*1024 & 2182*1029 & 2182*1032
Table 3: Mechanical dimensions for bolt fitting method (NEX) NoteThe installation method of bolt fitting (NEX) is based on the experimental results in Jinko. According to IEC 61215 for a maximum positive design loading of below 1067Pa, and negative design loading 1067Pa, with 1.5 times safety factor.
2.3.2 Mounting with clamps
The module clamps should not come into contact with the front glass and must not deform the frame. Be sure to avoid shadowing effects from the module clamps. The module frame is not to be modified under any circumstances. When choosing this type of clamp-mounting method, please be sure to use at least four clamps on each module, two clamps should be attached on each long sides of the module. Depending on the local wind and snow loads, if excessive pressure load is expected, additional clamps or support would be required to ensure the module can bear the load. The applied torque value should be big enough to fix the modules steadily (Please consult with the
clamp or support’s supplier for the specific torque value). Please find
detailed mounting information in the below illustration, the mounting place distance is suggested bigger than J and less than K. The installation diagram of clamp is shown in figure 5. Note: The Movement of the mounting rail and the clamps center line are recommended to be within the black arrow area. As shown in the figure on the right, the minimum length L of the
-13-
clamps is 50mm.
Figure 5: PV module installed at the side with Clamp fitting method
Clamp type
Dimension(mm)
Composition
material
End Clamp
(40 mm thickness)
39 x 50 x 42
39 x 60 x 42(For 1.5mm thickness frame)
Aluminum-alloy
End Clamp
(35 mm thickness)
41.5 x 50 x 40
End Clamp
(30 mm thickness)
41.5 x 50 x 35
Middle Clamp
(40 mm & 35 mm
thickness)
42 x 50 x 28
42 x 60 x 28(For 1.5mm thickness frame)
Q R P
13.5
15
2.5
Middle Clamp
(30 mm thickness)
42 x 50 x 29.5
Q R P
14
14
3
Table 4: Mechanical dimensions, specification and material when modules installed with mid Clamp
When installing modules using clamps on the long side of the frame, the applicable product types and installation locations are shown in figure 6 and table 5. When installing modules using clamps on the short side of the frame, the applicable product types and installation locations are shown in figure 7 and table 6. When installing modules using clamps on the long side & short side of the frame, the applicable product
Middle modules installation
Fringe modules installation
Module type
Module dimensions(mm)
A*B
J K J
K
54P
Height of the framemm
35
30
Group 65
1719*1134*30
/
L/4±50mm( L is the
length of the long side
of the module)
Group 66
1687*1134*30
/
60P
Height of the framemm
35
30
Group 1
1650*992 & 1665*1002
280
420
L/4±50mm( L is the
length of the long side
of the module)
Group 2
1665*992 & 1684*1002
280
420
Group 3
1650*992 & 1665*1002
280
420
Group 4
1665*992 & 1684*1002
280
420
Group 5
1650*992 & 1665*1002
280
420
Group 6
1665*992 & 1684*1002
280
420
Group 7
1650*992 & 1665*1002
280
420
Group 8
1665*992 & 1684*1002
280
420
Group 9
1665*992 & 1684*1002 1672*992 & 1704*1008
280
420
Group 20
1704*1008
280
420
Group 22
1684*1002
280
420
Group 30
1704*1008
280
420
Group 46
1684*1002
280
420
Group 57
1693*1029
/
/
types and installation locations are shown in figure 8 and table 7. When installing modules using clamps on the long side of the frame, the applicable product types and installation locations (The without C transparent backsheet series module) are shown in figure 9 and table 8.
2.3.2.1 Clamp Mounting on Long Sides of the Frames
Figure 6: Installation of clamps on long side of frames
-14-
Loading...
+ 37 hidden pages