Jetmaster 550, 700, 850 De Luxe, 850 Installation & Operating Instructions Manual

INSTALLATION
& OPERATING
INSTRUCTIONS
550, 700 & 850 De Luxe
Gas Convector
1
CONTENTS
INDEX
PLEASE READ THESE CAREFULLY BEFORE STARTING WORK
The fitter must read ALL parts below. Customers are strongly recommended to read Parts 1 - 5, 8, 11 and 13 - 23 of these instructions.
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
Technical Data 2 Installation Instructions
1 General 3 2 Gas Specifications 4 3 Regulations 4 4 Deviation from Instructions 4 5 Ventilation 5 6 Chimney 5 7 Preparatory Building Work 6 8 Fitting the Jetmaster Convector Box 6 9 Gas Cylinders, Pipe Runs and Sizes 7 10 Fitting the Gas Burner 8 11 Positioning the Coals: 550, 700 & 850 Gas Convector 11 12 Commissioning the Fire 14
Users Instructions
13 General 15 14 Lighting the Fire: 550 & 700 Gas Convector 16 15 Lighting the Fire: 850 Gas Convector 17 16 Cleaning Instructions 18
Servicing Instructions
17 General 19 18 Servicing Procedure 19 19 Registering the Warranty 19 20 Repairs under Warranty 20 21 Maintaining the Gas Grate 20 22 Gas Fumes
Warranty 21
Technical Data
Gas Inlet Connection: 5/16" (8 mm) O.D. tube with olive fittings into a test
point on the right-hand side of the Gas Convector.
Regular LPG: 2,75 Kpa inlet pressure.
Gas Control: BM 733 model for both the 550 and 700 burner.
Baby Sit Manual Control Valve fitted to the 850 burner. These gas controls are located centrally underneath the burner.
Pilot Markings: Oxygen depletion system fitted.
LPG 9221 O.P. Controls.
Pilot Turnoff Valve: Integral with BM valve fitted to 550 and 700 burner.
Integral with Baby Sit Manual Control Valve fitted to 850 burner.
Pressure Test Point: 5/16" (8mm) diameter nipple located on the inlet gas
supply on the 550 and 700 burner. Test point on the Baby Sit Manual Control Valve on the 850 burner.
Gas Cylinder Size: 1 x 48kg bottle for 550-700 De Luxe Gas Convector.
2 x 48kg bottle for 850 De Luxe Gas Convector.
2
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
Note: The total width measurement including gather is A + 50
H
50 50
A + 50
A
D
B
C
J
I
G
F
E
MODEL
& SIZE
NOMINAL
FLUE SIZE
mm
ABCDEFGJHI Ø 550 316 650 200 105 625 420 90 200 200 200 700 316 650 200 105 625 420 90 200 200 200 850 316 650 200 105 625 420 90 300 200 250
ROUND
EQUIVALENT
1. General
This fire is intended for decorative purposes. Jetmaster Gas Grates are a fuel effect appliance intended for use in a fireplace for the burning of solid fuel.
This fire should be installed by a qualified person. All relevant Codes and Regulations laid down by the Gas Supply Authorities, Uniform Building Regulations and requirements of local Municipal Authorities must be observed.
Installation and use of this fire must be in accordance with these instructions.
Prior to installation, ensure that the local distribution conditions, (identification of the type of gas and pressure) and the adjustment of the appliance are compatible.
The builders opening or fireplace opening must be constructed of a non-combustible material and must conform to any current National Building Regulations.
Combustible material should not be placed within 0.5m radius of the fire.
3
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
In some countries a non-combustible hearth must be fitted in front of the fire in accordance with National Regulations.
The flue and/or chimney should be swept and tested in accordance with National Regulations to prove it has an adequate updraught which is sufficient to remove all waste products of combustion before the appliance is installed.
The Gas connection must be in accordance with National Regulations and be carried out by a qualified person.
The pilot light and flame sensing device fitted to this fire is also an atmosphere sensing device. If for any reason any part of the pilot assembly is to be replaced ALL the assembly including the Pilot Burner, Thermocouple, Electrode and Injector must be exchanged complete for an original Manufacturers Pilot Assembly only. This Atmosphere Sensing Device is not adjustable and must not be put out of action.
2. Gas Specifications
Jetmaster Gas Convector fireplaces are designed to burn LP Gas only. For proper performance, LP Gas fires are set either for use on the Highveld or coastal regions. Check the markings on the outside of the box in which the burner is delivered to make sure you have the correct burner for where you stay. Do not take a Highveld burner to the coast or vice versa. Do not burn LP Gas on a Towns Gas burner or vice versa.
3. Regulations
The installation of this Gas Convector must be carried out fully in accordance with these Installation Instructions, which comply with the current regulations of the Liquid Petroleum Gas Association of Southern Africa (LPGAS Association). The gas fitting connection and testing part of the installation must be carried out by a fitter registered with the SAQCCI.
The following documents have references which apply to the installation of this gas fireplace, and the relevant clauses must be applied:
SABS 1539: 2001:
Appliances operating on LP Gas portable and mobile appliances; safety aspects.
SABS 087 Part 1: March 1999:
Consumer LP Gas cylinder installation.
SABS 087 Part 2: 1975:
Installation in mobile units and small non-permanent dwellings.
SABS 087 Part V11: 1997:
Retail outlets and similar gas filling sites for small cylinders.
SABS 0400:
Building Regulations.
SABS 1237: March 1990:
Single stage low pressure regulators for LP Gas.
Fire Department:
Safety guidelines.
Building Inspectors for the planning of the installation. Occupational Health and Safety Act 1993.
4. Deviations from Instructions
Consult with Jetmaster PRIOR to commencing installation, if any deviation from these guidelines is being considered. Failure to do so may result in an illegal, dangerous and uninsured fitting and will invalidate your Jetmaster Warranty.
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
4
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
6. Chimney
The fireplace must be flued with the recommended size flue (see specifications in front of this book on page 2) to the outside atmosphere not less than 4,6 metres high, and must be cowled. The flue must be swept with a brush before installation, and annually thereafter. DO NOT attach the gas fire to a flue pipe of less than 200 mm internal dimension.
5. Ventilation
Two ventilators to the outside must be provided, one at just below ceiling level and one at floor level. The existing regulation states that : an air supply must be provided up to 150 cm2 for 50 MJ input. This must be provided in the form of two ventilators, one at ceiling height and one at floor level. Most properties have a ventilator at ceiling height. The lower vent can be made quickly and cleanly using a core drill and fitting a sleeve and grids at each end and is best placed on the same wall as the fireplace, and close to the sides of the fire.
NB: Larger vents are required if venting to well ventilated adjacent room (300 cm
2
).
5
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
Roof pitch 10˚ or more
At least 1 m
An opening or an adjacent structure
If within 1,5 m
Chimney (excl. cowl)
Roof pitch less than 10˚
At least 1 m
Chimney (excl. cowl)
Uppermost roof level
Chimney (excl. cowl)
Roof pitch less than 10˚
1 m
At least 600 mm
If 600 mm or less
If more than 600 mm
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
6
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
and minimise heat loss to the building.
8 Where offset in the flue is required,
do not bend more than 45 degrees. Jetmaster fabricated bends are available.
8. Fitting the Jetmaster Convector Box
(This work can be carried out by a person who is not registered LPGAS Association installer.)
1 Slide the convector box into the recess.
Ensure that no insulation or other material can fall and obstruct the fume outlets. Ensure that a seal is formed behind the frame of the convector box such that the only air which can reach the flue must travel in through the front of the convector box and up through the fume outlets.
2 Check that the flue outlets on top of
the convector box will not be obstructed. Where the convector box is to be installed beneath a particularly deep lintel supporting the chimney breast and the flue outlets might be partially obscured, steps must be taken to chamfer the underside of the lintel to 45 degrees to provide a smooth, unrestricted path for gases.
3 Check that the convection inlet channel
at the base of the front of the convector box is not restricted.
4 If a gather has not been fitted, for
instance when the convector box has been installed in an existing fireplace opening, mark and drill two securing holes in the base of the convector box and the hearth below, and secure the convector box to prevent it from moving forward.
7. Preparatory Building Work
(This can be carried out by a person who is not a registered LPGAS Association installer.)
1 When building the Jetmaster Gas
Convector into an existing fireplace, first remove all loose materials from the recess and measure the opening and recess to ensure that the Jetmaster Gas Convector will fit.
2 The recess must be large enough to
provide a clearance of 15 to 20 mm around the sides of the convector box and be in accordance with the dimensions given on page 2. Cut away or build up to achieve the desired dimensions.
3 Where the recess is to be newly built,
form the recess to give a clearance around the sides and back of the convector box of 15 to 20 mm to accommodate the fibreglass insulation.
4 Where the sides or back of the recess
have to be built up, and the masonry flue gather of the chimney is to be used, build up to the height of the convector box only and then top with a sloping fillet or mortar.
5 If a metal flue gather with flue liners
is to be used, they are available from Jetmaster or any authorised Jetmaster dealer.
6 Check that the hearth, or new plinth
where this is constructed, is level.
7 Wrap the faces and sides of the fire
with insulating material. This insulation is not essential but it is recommended, particularly when fitting to and outside wall, since it will maximise heat retention in the convection chamber,
9. Gas Cylinder, Pipe Runs and Sizes
(This work must only be carried out by a person who is a registered LPGAS Association installer.)
1 Jetmaster LP Gas Convectors must
be operated off one or more 48 kg cylinders, depending on size of unit. The cylinder(s) must be positioned outside, as close as possible to the appliance, and in any case not further than 30 metres, the cylinders must be away from heat sources, electrical devices, drains, windows and combustible materials, in accordance with SABS 087 Part 1: March 1999. Cylinders must always stand in the VERTICAL position and must be fixed so they cannot fall or be knocked over. For best performance, avoid cold areas and shade. Where the regulator or pipework is in a position which is liable to be very cold in winter, it is advisable to lag them to prevent freezing up. It is always advisable to fix the regulator vertically rather than horizontally. This will prevent any condensation settling in the bottom of the regulator which will freeze up in the cold weather causing the Gas Convector to shut down.
2 Check the Jetmaster Pipe Sizing Chart
below to choose the correct size of pipe for the Gas Convector size and length of run. Although Jetmaster supplies 4 metres of 8 mm copper tube with LP Gas Convectors, it is not necessarily of sufficient size if larger fire or longer than 4 metre run are to be fitted. Be sure to fit the right size pipe. Do not run more than one gas fire off each supply, without first checking the fitter’s supply chart. Any queries please contact Jetmaster Technical Department.
LP pipe size: From cylinder and low pressure regulator (28 Mbar) to gas appliance:
Copper tubing 8mm 15mm LP Gas up to to 30 m
Convector 4 m
It is recommended by the LPGAS Association that any pipe run greater than 9 metres is supplied under high pressure and a low pressure regulator is fitted within 4 metres of the fire.
3 Having positioned the 48 kg gas
cylinder in a fixed position, connect the regulator supplied to the flexible hose, and the male hose connector to the end of the copper tubing using the compression fitting. These fittings are supplied and should be used. If a larger pipe is to be used then the correct size of fittings will have to be obtained.
4 Tighten the hose clamps and connect
the regulator to the cylinder. The regulator should be protected from rain and fixed in the vertical position if possible alternatively angle the regulator so that liquids cannot collect on the top causing rusting of internal components and subsequent malfunctioning, i.e. the plastic cap should not face upwards. The air vent in the regulator must be pointing downwards.
5 Cover the end of the gas pipe to
prevent dirt getting into it and damaging the valve, which will invalidate the Warranty.
7
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
8
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
6 If the pipe is to be laid in concrete,
or comes through a wall or chased into a wall then the pipework must be sleeved. This sleeve can be electrical conduct or plastic pipe of a size larger than the outside diameter of the gas supply line. Place the gas pipe within the sleeve for protection.
7 Run the gas pipe from the cylinder
to the area of the fireplace allowing a full metre of free pipe at the fireplace end; pipe may be brought in through either side or the rear of the gas fire.
8 All bends should be made with a pipe
bender to prevent a restrictive kink forming.
10. Fitting the Gas Burner
(To ensure that the burner and coals are not damaged, this work must be done after all building work has been completed. This work can only be carried out by a person who is a registered LPGAS Association installer.)
1 Drill the side or the back of the
Jetmaster with a 10 or 12 mm drill for the gas pipe entry point. Sleeve the gas pipe with metal/plastic tubing where it is to pass through the wall of the convector box to protect it. If the pipe run from the gas cylinder
has been made with larger than 8 mm pipe, reduce it as close as possible to the fire but not more than 4 metres away, by using a reduction fitting. Now that the pipe work is within the convector box, secure the convector box by screwing it to the floor. (See
7.4 above)
2 Purge the pipe for dust and debris by
running the gas for a few moments; failure to clear the dust or debris from the pipe will invalidate the Warranty.
3 Remove the burner from its packing
and examine the connections, checking that none are loose.
4 With the burner immediately in front
of the convector box, place the unit in the frame supplied, run the gas pipe to the test point nipple, which for the LP burner is positioned on the right­hand side of the control valve when viewed from the front. Place the burner and frame in the convector box and connect the pipe with the 8 mm compression nut and olive making sure that the connection is gas tight. Do not strip it. Use of PTFE tape will invalidate the Warranty as small pieces can enter the pipe and damage the valve.
9
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
5 Having placed the burner tray in the
frame supplied, push to the back of the convector box, making sure that there is enough space between the front edge of the burner tray and gas front to allow the ceramics to sit in the correct position. Adjustment on the support legs on the burner may be required.
6 Open the gas supply and test for leaks
as far as the valve, attaching a
manometer or U gauge to the test nipple, making sure that the little screw on the test nipple is screwed tightly back in place when testing has finished. The dynamic pressure should read 28 MBar. If the pressure is lower, check the regulator on the cylinder and test all joints on the pipe-work and burner with an electronic gas leak detector or leak test fluid. Rectify and test again.
7 Fit the gas front.
Inlet test point
OUT IN
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
10
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
Front Options
11
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
11. Positioning the coals: 550, 700 & 850 Gas Convector
Warning
The fire must only be fitted with the ceramics supplied. Do not add any extra coals or logs.
1 Position the front coal pieces as shown. The left hand front coal piece has a cut
on its rear edge to clear the pilot hole. Ensure that the pilot hole and flame strip are not obstructed.
2 Position the back board centrally into the burner tray ensuring it is correctly
seated and that the flame strip is not obstructed.
3 Fit the left hand and right hand coal pieces either side of the back board into
the burner tray. They should be fully fitted into the burner tray and touch the rear of the front coal pieces.
Pilot hole
Left hand
front coal
piece
Right hand
front coal
piece
Flame strip
Back Board
Flame strip
Left hand coal piece
Right hand coal piece
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
12
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
4 Position a first row of coals at the front (5 on the 550GC, 6 on the 700GC
and 9 on the 850GC). They should bridge the gap between the front coal pieces and the front row of pyramids on the back board. Leave a gap of approximately 5 - 10mm between each coal. Do not attempt to force any coals down into the gap between the front coal pieces and the back board.
6 Position a third and final row of coals (5 on the 550GC, 6 on the 700GC and
8 on the 850GC). These should rest between the second row of coals and the top of the back board. Leave a gap of approximately 5 - 10mm between these coals. Do not attempt to force these coals down between the second row of coals and the top of the back board.
5 Position a second row of coals (4 on the 550GC, 5 on the 700GC and 7 on the
850GC). These should rest on the pyramids on the back board and touch the front row of coals. Leave a gap of approximately 5 - 10mm between these coals. Do not attempt to force the coals down between the pyramids.
First row of coals
Second row of coals
Second row of coals
13
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
EXTRA NOTE
BURNER STRIP
FRONT CERAMIC PIECES
BACK ELEVATION FRONT ELEVATION
CERAMIC SIDE CHEECK
CARE SHOULD BE TAKEN
WHEN HANDLING THE
CERAMICS
When assembling the ceramics on the
Deluxe Burner it is important to make
sure that pieces of ceramic are fitted
properly. The 2 pieces of ceramic that
go onto the front ceramic support tray
should be behind the stop lugs, not on
top or pushed down onto the lugs. If
these ceramics do not fit then a fine file
should be used across the whole of the
front edge of the ceramic pieces until
enough has been filed away so that they
lay flat on the base of the front ceramic
support tray and behind the stop lugs.
The same process should take place with
the two side cheeks. If they do not fit
then the outside edge of both ceramic
side cheeks should be filed down until
they fit correctly.
DELUXE GAS BURNERS
STOP LUGSPILOT BURNER
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
14
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
12. Commissioning the Fire
Connect a suitable pressure gauge to the pressure test point. Light the fire on maximum as described in the “User’s Instructions”. Check that the setting pressure is in accordance with that given on the Chart in the “Technical Data” Section or on the Data Label found in the appliance. Adjust the Natural Gas or Propane Regulator as necessary. After this has been checked shut down the gas fire.
Temporarily isolate the fire from the mains supply. Then disconnect the pressure gauge, replace the pressure test point sealing screw, reinstate the mains supply and test for gas soundness.
Turn the control knob and light the pilot as described in the “User Instructions”. Turn the control knob to the maximum position and fit the ash pan cover. Check that after ten minutes all the products of combustion are entering the flue by traversing the perimeter of the fireplace opening or canopy by using a smoke generator e.g. smoke match.
Once the fire is installed and opperational the installer must check for spillage. Carry out the lighting procedure and turn the fire to high.
Allow to warm up for 5 minutes and then using a smoke match or joss stick set 25mm down and 25mm inside of the fire opening run the match across the width of the opening to check that all of the smoke is drawn away. Some small whiffs of smoke may be expelled from the extreme ends of the fire opening and this is quite normal.
Repeat the test with doors and windows to the premises open and closed, and with any extractor fans in the same room or adjacent rooms running on high. The fire should continue to clear its combustion products. Also operate any other flued appliances in the same or neighbouring rooms and ensure they continue to function satisfactorily as multiple flues can work against one another.
If spillage is detected during this procedure it could indicate a faulty flue or lack of ventilation. If the problem cannot be rectified immediately, disconnect the appliance, and advise the customer not to use the appliance until the problem has been resolved.
The customer should always be advised of the need for regular servicing and checks to ensure the continued clearance of combustion products.
15
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
User’s Instructions
13. General
This fire is intended for decorative purposes. Any purpose provided ventilation should be checked regularly to ensure that it is free from obstruction. This fire should be serviced regularly by a qualified person.
It is recommended that a guard be used for the protection of young children, the elderly or infirm. A vacuum cleaner may be used to clean the appliance.
DO NOT throw rubbish etc. upon the coals or otherwise disturb the fuel bed. Debris from any source or soot formed should be removed from time to time. See “Cleaning Instructions”.
The pilot light and flame sensing device fitted to this fire is also an atmospheric sensing device which shuts off both the main burner and pilot if evacuation of the combustion products is interrupted. If
the fire shuts itself off, do not use the fire and have the flue and fire checked by a qualified person.
Due to the newness of materials the fire may give off a slight smell for a period of time after commissioning. This is quite normal and any odour should disperse after a few hours operation.
Warning Notes
Properly installed and operated this appliance will not leak gases. Persistent fume emission must not be tolerated. If fume emission does exist, then the following steps should be taken:
1 Open doors and windows to ventilate
room.
2 Turn the fire off.
3 Check for flue blockage and clear if
necessary.
4 Do not attempt to re-light the gas
grate until the cause of the emission has been identified and rectified. Should assistance or advice be required contact your nearest agent.
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
16
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
14. Lighting the Fire: 550 & 700 Gas Convector
The positions of the control valve are depicted on the control panel fitted around the control knob.
If the main burner or pilot light are extinguished for any reason do not attempt to re-light the pilot within three minutes.
The off position is self explanatory ­preventing any gas from passing through the control valve to either the pilot burner or to the main burner.
By pressing the control knob in it is possible to turn it anti-clockwise. The first function is to turn on the gas to the pilot, this occurs just before reaching the pilot position. (If the fire has not been lit for some time it may be necessary to hold the knob in this position for some seconds to clear the air from the pipe and allow gas to reach the pilot burner). Once gas is available at the pilot, continual rotation anti-clockwise will cause the piezo ignitor to spark. This is accompanied by a click at the valve, and should result in the pilot burner igniting. This should be verified by looking at the left-hand side of the fire tray, behind the front coal piece.
Once the pilot is lit the control knob should continue to be pressed in for 10
- 20 seconds. In this time the pilot flame will have heated the flame supervision thermocouple sufficiently to operate a hold on magnet within the valve. The knob should then be turned so that the pointer is approximately horizontal. This allows gas at a low rate to enter the burner and be ignited by the pilot flame. Once the fire has fully cross lit, allow approximately 15 seconds at this setting to allow the flame to fully establish before setting to any level between Maximum and Minimum by adjusting the control knob accordingly.
To turn off the main burner, turn the control to MIN - press the knob gently until it will turn clockwise to the pilot position. To turn off the pilot press knob and turn to off.
If burnback occurs underneath the burner, turn knob to the off position. Then re-light the fire. If this problem re­occurs switch off unit and call your gas installer.
Thus the sequence is:
A. To Light the Fire
1 From off press the control knob in
and turn slowly anti-clockwise.
2 When the ignition click occurs,
check that the pilot is lit (if not repeat 1 & 2).
3 Hold knob in for 10 - 20 seconds.
4 Release knob and check pilot
remains alight.
5 Turn knob until pointer is horizontal.
The fire should then ignite.
6 Let fire fully cross ignite and allow
approximately 15 seconds.
7 Adjust flames to required level
without pressing knob.
B. To Extinguish the Fire
1 Turn control knob clockwise to
minimum position.
2 Press knob gently until able to
continue turning clockwise to pilot.
3 To extinguish the pilot, press knob
and turn to off, although it is in order to leave the pilot permanently lit.
17
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
15. Lighting the Fire: 850 Gas Convector
A. Commissioning the Fire
The gas control knob is marked with positions of OFF • PILOT º MINIMUM ¢ MAXIMUM Æ gas rate. The position selected should be placed opposite the indicating arrow. The gas control valve is fitted with a piezo spark ignition. WARNING: If the main burner or pilot are extinguished for any reason, you will not be able to re-light the pilot for three minutes. As there is a further safety feature into the control valve do not force the control knob on the valve.
B. To Light the Pilot
1 Ensure that the gas is turned on. 2 Ensure that the gas control knob is
in the OFF POSITION (Fig. 2A).
3 Slightly depress the gas control knob
and turn anti-clockwise until the PILOT POSITION
(Fig. 2B) is opposite the indicating
arrow.
4 Push the control knob fully in, and
with it held in position, fully depress and push the end button on the piezo spark ignitor and the pilot should light. If the pilot has not lit, repeat the operation.
5 Once the pilot is lit, continue and hold
in the gas control knob for a further 10 -15 seconds to establish the pilot. If the pilot fails to remain alight repeat the procedure, but hold the gas control knob in for longer to allow the pilot to establish.
C. To Light the Fire
1 If the pilot is not already alight, light
the pilot as described in B.
2 Slightly depress the gas control knob
and turn anti-clockwise until the
MINIMUM FLAME POSITION (Fig. 2C) is opposite the indicating arrow. The burner will then ignite.
3 Turn the control knob to MAXIMUM
FLAME POSITION (Fig. 2D).
4 Check setting pressure on the inlet
pressure test point at the maximum rate (LPG 2.75 kPa).
5 Depress and turn the gas control
knob clockwise until the PILOT POSITION (Fig. 2B) is opposite the indicating arrow. The fire will go out and the pilot will remain lit. Remove the gauge from the pressure test point and refit the pressure test point sealing screw.
6 Turn the fire on and check for gas
soundness.
7 Refit the air inlet grill.
D. To Turn the Fire Off
1 Remove the air inlet grill. 2 Turn the gas control knob clockwise
to the MINIMUM GAS RATE (Fig, 2C) position, slightly depress the knob and continue turning to the PILOT POSITION. The fire will go out and the pilot will remain lit and may be left on permanently.
3 Replace air inlet grill.
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
18
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
E. To Turn the Fire and Pilot Off
1 Remove the air inlet grill. 2 Turn the fire off as described in No.
3 Depress the control knob.
3 Turn to the OFF POSITION and the
pilot will go out.
4 Replace the air inlet grill.
Safety Feature: If the pilot is turned off you will not be able to re-ignite the pilot for a minimum of 30 seconds.
16. Cleaning Instructions
NOTE: Due to the ceramic fibre material used in the fuel bed it is inevitable that cleaning/replacement can be a dirty and dusty operation. Suitable precautions should be taken. Due to the intense temperatures reached in the fire some surface cracks may appear on the ceramic components. This is quite normal and will not affect the safe operation of the appliance.
1 Turn off the fire and allow it to go
cold.
2 Carefully remove all the coals one
at a time by hand and remove any soot deposits with a soft brush.
3 Remove any debris etc., from the back
board. A vacuum cleaner may be used with care.
4 Carefully reposition or renew the
coals as described in “Positioning the coals”.
5 Do not add any additional logs or
coals.
Figure1: A: Outlet pressure test point
B: Inlet pressure test point
Switch indicator point
Figure 2A
OFF
Figure 2B
PILOT
Figure 2C
MINIMUM
Figure 2D
MAXIMUM
19
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
17. General
The following servicing procedure should be carried out regularly and only by a qualified person.
NOTE: Due to the materials used in the fuel bed, it is inevitable that servicing can be a dirty and dusty operation. Suitable precautions should be taken.
Important: The pilot and flue sensing device fitted to this fire is also an atmospheric sensing device. If for any reason any part of the pilot assembly is to be replaced the entire assembly including the pilot burner, thermocouple electrode and injector must be exchanged complete for a pilot assembly from the original manufacturer only. This atmosphere sensing device is not adjustable and must not be put out of action.
18. Servicing Procedure
1 Turn off fire and allow it to go cold. 2 Turn off gas supply at the isolation
tap.
3 Carefully remove all the coals and
ceramics one at a time by hand and remove any soot deposits by hand with a soft brush i.e. paint brush.
NOTE: Due to the intense temperatures reached in the fire some surface cracks may appear on the ceramic components. This is quite normal and will not affect the safe operation of the appliance.
4 Disconnect the gas pipe from the
valve and lift the gas grate out of the fire box.
5 Remove the injectors then clean
and visually inspect for damage before replacing.
6 Clean the burner tray and flame
strip.
7 Visually inspect the gas grate for
any defects before replacing.
8 Re-assemble in reverse order,
reconnect to gas supply and check for gas soundness.
9 Replace all ceramics and coals as
described in “Positioning the Coals”.
10 Check that any purpose provided
ventilation is free from obstruction.
11 Re-commission the fire as described
in “Commissioning the Fire”.
19. Registering the Warranty
Jetmaster warrants the Gas Grate for one year, providing it is fitted and used correctly, and has been fitted by a registered LPGAS Association fitter accredited by Jetmaster, and the Warranty Card is returned to Jetmaster fully completed, including the fitter’s details and telephone contact number, within 30 days of purchase.
SERVICING INSTRUCTIONS
20. Repairs under Warranty
(This work can only be carried out by a person who is a registered LPGAS Association installer.)
Most problems are minor and can be solved by the fitter, and it is a condition of the Warranty that in the first instance the customer contacts the Distributor from whom the fire was purchased and arranges for the same fitter to return to try to remedy the problem. If necessary, the fitter can telephone the Jetmaster Technical Help Telephone Line on (011) 474-2100 from site and get advice. In the unlikely event that this fails to cure the problem, Jetmaster will organise for technical assistance on site. In this case Jetmaster requires that the original fitter also attends. The Jetmaster Warranty is only effective if the Gas Grate is installed fully in accordance with these instructions and the Warranty Card is returned fully completed within 30 days of purchase. The fitter must fill in his details of the Warranty Card.
21. Maintaining the Gas Grate
Gas fires need checking annually. This involves cleaning and relaying the coals, checking the pilot light and all joints, checking ventilators and fume clearance, and repainting the exposed parts. It should take an hour to an hour and a half. We are a seasonal business - so please do not leave calling us for a maintenance visit until the first day of winter! Book ahead! Keep a service book on until.
22. Gas Fumes
Occasional fumes from cross-draughts may occur but persistent fume emission must not be tolerated. If this occurs, if you smell gas, or if you feel drowsy or have a head-ache when the Gas Grate is burning, the following immediate actions must be taken:
1 Turn off the Gas Grate and extinguish
all naked flames.
2 Open doors and windows to ventilate
room. 3 Turn the gas off at the gas cylinder. 4 Check for flue and ventilator blockage
and clean if required. 5 Do not attempt to re-light the Gas
Grate until the cause of fume emission
has been identified and rectified. If
necessary seek professional advice
from Jetmaster (Pty) Ltd telephone
(011) 474-2100 or a registered LPGAS
Association installer.
550, 700 & 850 GAS CONVECTOR INSTALLATION & OPERATING INSTRUCTIONS
20
INSTALLATION AND OPERATING INSTRUCTIONS:
550, 700 & 850 DE LUXE
We would like to thank you for purchasing one of our gas fireplaces
1 Jetmaster warrants that the burner and controls of this Gas Grate or Gas Convector
will be free from defects in workmanship or materials under normal use and service for a period of one year from the invoiced date of purchase.
2 Jetmaster warrants that the Gas Convector firebox will be free from defects in
workmanship or materials under normal use and service for a period of ten years from the invoiced date of purchase. This Warranty does not cover rust as all units are made of mild steel.
3 This warranty is only effective if:
3.1 At the time of the claim the then owner of the Gas Grate/Gas Convector burner and/or firebox produces documentary evidence to prove the date of purchase, e.g. the original or true copy of the invoice.
3.2 The Warranty Card (supplied separately) was fully completed and returned to Jetmaster by main or by fax within 30 days of purchase.
3.3 The Gas Grate/Gas Convector burner and/or firebox was installed by a registered LPGAS Association fitter and was purchased from an appointed Jetmaster Agent.
3.4 The installation, operation and maintenance of the Gas Grate/Gas Convector burner and/or firebox was, in the opinion of Jetmaster, carried out in accordance with the Installation and Operating Instructions current at the time of purchase and no modifications have been made to the product without written authority.
4 When a valid claim arises under this Warranty, Jetmaster will, as its sole option,
either repair or replace the Gas Grate/Gas Convector burner and/or firebox, having firstly been investigated by the appointed Distributor of Jetmaster.
5 Under no circumstances will Jetmaster be liable for any consequential loss or
damage or injury arising out of, or in connection with, the use or operation of the Gas Grate/Gas Convector burner and/or firebox resulting from the failure to follow the Installation and Operating Instructions, or from a breach of the Warranty conditions.
Jetmaster (Pty) Ltd.
PO BOX 43178, Industria 2042
SOUTH AFRICA
0800005858 (Toll-free no.)
Gauteng (Johannesburg): Cape Town:
1316 Clubhouse Street Cnr. Koeberg Road and School Street Maraisburg, Johannesburg Milnerton Tel: (011) 661 5900 Tel: (021) 552 0808 Fax: (011) 474 2144 Fax: (021) 552 0810
www.jetmaster.co.za
Mpumalanga:
10 Milli Street Middelburg Mpumalanga Tel: (013) 246 2600 Fax: (013) 246 2951
Richards Bay:
63 Kabel Kring Road Alton, Richardsbay Tel: (035) 797 5800 Fax: (035) 797 5818
Durban:
Cnr. Meridian & Solstice roads Umhlanga Ridge Tel: (031) 566 2252 Fax: (031) 566 2632
Gauteng (Pretoria):
Menlyn Shopping Centre. Shop LF 8/9 Pretoria Tel : (012) 348 7741 Fax: (012) 348 7972
Port Elizabeth:
130 Burman Road Deal Party Tel: (041) 486 1471 Fax: (041) 486 1409
East London:
3 Nottingham Road Gately East London Tel: (043) 731 1246 Fax: (043) 731 1268
Loading...