Range
Models SVE47600, SVE47500,
SVE47100, SCE30600, SCE30500
INSTRUCTIONSTO INSTALLER:"Important: Savefor localelectricalinspector'suse".
_'JENN-AIR
403WESTFOURTHSTREET,NORTH• NEWTON,IA50208
I WARNING
_'_ II_I1' ALL RANGES CAN TIP AND
Range Overall Dimensions:
Width - 29-15/16" (76.04 cm)
Depth - 26-3/8" (70.00 cm)
Height - 35-1/2" (90.17 cm)
*Add 2" (5.08 cm) for door handle
ELECTRICAL SPECIFICATIONS: 120/240 VAC OR 120/208 VAC 60 Hz 50 amp circuit protection recommended,
40 amp minimum required. Wire size: For 50 amp service use #6 60°C or #8 75°C (copper only) three or four
conductor, for 40 amp service use #8 (copper only) three or four conductor.
ELECTRICAL CONNECTION: Unitto beproperlycircuitprotected andwired according to localelectrical code and
national electric code. Unit power requirements located on serial plate on front of range.
I AUSEINJURIESTOPERSONS.
I" INSTALL ANTI-TIP DEVICES
I PACKED WITH RANGE.
i
'!" FOLLOW ALL INSTALLATION
I INSTRUCTIONS.
8101P265-60
(06-99-01)
,1.
Unpack Range (Figure 1)
• Cut and remove shipping carton.
• Remove lower range panel or drawer, and place out of work area.
• Remove blower package (if you have not already done so.) (Downdraft
Models Only.)
• Locate Ducting Instructionsheet. (Downdraft Models Only.)
NOTE:Please read through entire installation instructions and ducting
instructionsprior to beginning installation.
=
Select Range Location (Figure 2)
• Carefully select the range location, keeping in mind the following:
A. Over-range cabinets are not recommended. However, ifnecessary, see
#8.
B. Make sure electrical power can be provided. (See #13.)
C. For downdraft ranges plan the range ducting system. (Per #'s 9-12 and
ducting instructions.)
D. Make sure there is adequate space. (See #'s 4, 5, 6, and 7.)
E. Island or peninsular installationswith 24" deep base cabinet must use
flush back (no rear toe space) cabinets to avoid range interference. If a
rear toe space isdesired, use 27" or deeper base cabinets.
NOTE: This range complies with UL requirements for"1 "clearance from the
range to adjacent vertical side walls and 7/8" from rear vertical wall.
Abnormal surface unit operation (high heat and no utensils) could
result inpossible scorching ofvertical walls and pose a potential fire
hazard. Therefore, a 6" (15.24 cm) minimum spacing is
recommended. On Downdraft models 6" spacing is required for
proper ventilation. (See illustration.)
,
Type of Installation (Free-Standing/Slide-in) (Figure 3)
• Will range be free-standing? (Range setting on floor.) If so, go to #7.
• Will range be slide-in? (Range top rests on countertop.) If so, go to #4.
• These appliances have been designed in accordance with the requirements
of various safety agencies and comply with the maximum allowable wood
cabinet temperatures of 194°E If these appliances are installed with
cabinets that have a lower working temperature than 194°1, discoloration,
delamination or melting may occur.
NOTE:Slide-in cutout does not allow for use of backsplash or side panels.
If either are desired, use the free-standing cutout and instruction.
(Figure 1)
[r lrl !r 1-qin--
k:,.-I o.....°.c..,.,.
I(lS.24cm)l
2S'* MIN.
(63.50 cm)
,,,____, g ]
(Figure2)
FREE
STANDING
(Figure 3)
NOT RECOMMENDED
t
(See #8)
|_.
SLIOE-IN
.
Measure for Slide-In Cutout (Figure 4)
• Most standard counters are 25" (63.50 cm) deep, 36" (91.44 cm) high, and
extend 1" (2.54 cm) over the cabinet front.
• Measure the countertop and overhange.
0
(Figure 4)
OVERHANG
OIMENSIOll
5. Slide-In Cutout (Figure 5)
• Use the overhang measurement to figure the "A"dimension:
Overhang 1t2" (1.27 cm) to 1" (2,54 cm) .... "A" =22-5t8" (57.47 crn)
Overhang 1" (2.54 cm) to 1-3/4" (4.45 cm) .... "A" = 23" (5-5.42 cm)
• Carefully mark the countertop and recheck you dimensions.
• Before you cut, check the rear countertop dimensions. (See #6.)
NOTE: The minimum clearance between the cutoutand cabinet doors and
drawer edge is 7/8".
6. Slide-In Cutout (Figure 6)
• Check your marked up dimensions carefully. The rear dimensions shown
in the illustration must be maintained.
NOTE: Where this isnotdone, itwill be necessary to relieve a portionof the
underside of the countertop and/or support members to clear the
range rear panel.
• Cutting tolerance is = 1/6 (16 cm)
• Carefully make the cutout
7. Free-Standing Cutout (Figure 7)
• 30-1/8" (76.52 cm) minimum clearance is required.
• Carefully mark the countertop, recheck your dimensions and make the
cutout.
NOTE: Range side panels may be desirable if the cutout is too large or
cabinets are on one side of the range only.
• Proceed to step 8.
(Figure 5)
cm)
(Figure 6)
8. Over-Range Cabinets (Figure 8)
• To eliminate the hazard of reaching over a heated surface unit, cabinet
storage space above the range should be avoided. If cabinet storage is to
be provided, the riskcan be reduced by installingarange hoed that projects
horizontally a minimum of 5 inches beyond the bottom of the cabinets.
However, if over-range cabinets are necessary, observe the following:
B = 30" (76.2 cm) minimum clearance between the top of the cooking
platform and the bottom of an unprotected wood or metal cabinet.
B = 24" (60.96 cm) minimum when bottom of wood or metal cabinet is
protected by not less than 1/4" (0.635 cm) FLAME RETARDANT
millboard covered with not less than No. 28MSG sheet steel, 0.015"
(0.038 cm) stainless steel, 0.024" (0.061 cm) aluminum or copper.
NOTE: If you are NOT installing a downdraft unit, skip to step 13.
9. Measure For Floor Vent
If unit will be vented through the wall, go to #11.
If floor will be concrete slab, see enclosed ducting instructions.
For let and right hand venting through cabinet toe space, see special
instructions on pages 7 & 8.
NOTE: Optimum center line vent location is11" to 17" from edge of cabinet.
Vents located less than this distance wUlrequirethe unit tobe raised
over blower for installation.
(Figure 7)
o oo
(Figure 8)
10, Floor Vent Cutout (Figure 10)
• Check the direction of the floorjoists (see illustration.)
• Locate 6" square cutout anywhere within shaded area.
The cutout must miss the floor joist!!
• Recheck your dimensions and make the cutout.
• Skip to Step #12.
(Figure 10)