Jenn-Air SVE47600B, SVE47600W Installation Guide

Range
Models SVE47600, SVE47500,
SVE47100, SCE30600, SCE30500
INSTRUCTIONSTO INSTALLER:"Important: Savefor localelectricalinspector'suse".
_'JENN-AIR
403WESTFOURTHSTREET,NORTH NEWTON,IA50208
I WARNING
_'_ II_I1' ALL RANGES CAN TIP AND
Range Overall Dimensions:
Width - 29-15/16" (76.04 cm) Depth - 26-3/8" (70.00 cm)
ELECTRICAL SPECIFICATIONS: 120/240 VAC OR 120/208 VAC 60 Hz 50 amp circuit protection recommended, 40 amp minimum required. Wire size: For 50 amp service use #6 60°C or #8 75°C (copper only) three or four
conductor, for 40 amp service use #8 (copper only) three or four conductor.
ELECTRICAL CONNECTION: Unitto beproperlycircuitprotected andwired according to localelectrical code and national electric code. Unit power requirements located on serial plate on front of range.
I AUSEINJURIESTOPERSONS. I" INSTALL ANTI-TIP DEVICES
I PACKED WITH RANGE.
i
'!" FOLLOW ALL INSTALLATION
I INSTRUCTIONS.
8101P265-60
(06-99-01)
,1.
Unpack Range (Figure 1)
Cut and remove shipping carton.
Remove lower range panel or drawer, and place out of work area.
Remove blower package (if you have not already done so.) (Downdraft
Models Only.)
Locate Ducting Instructionsheet. (Downdraft Models Only.) NOTE:Please read through entire installation instructions and ducting
instructionsprior to beginning installation.
=
Select Range Location (Figure 2)
Carefully select the range location, keeping in mind the following:
A. Over-range cabinets are not recommended. However, ifnecessary, see
#8.
B. Make sure electrical power can be provided. (See #13.) C. For downdraft ranges plan the range ducting system. (Per #'s 9-12 and
ducting instructions.)
D. Make sure there is adequate space. (See #'s 4, 5, 6, and 7.) E. Island or peninsular installationswith 24" deep base cabinet must use
flush back (no rear toe space) cabinets to avoid range interference. If a
rear toe space isdesired, use 27" or deeper base cabinets.
NOTE: This range complies with UL requirements for"1 "clearance from the
range to adjacent vertical side walls and 7/8" from rear vertical wall.
Abnormal surface unit operation (high heat and no utensils) could
result inpossible scorching ofvertical walls and pose a potential fire hazard. Therefore, a 6" (15.24 cm) minimum spacing is recommended. On Downdraft models 6" spacing is required for
proper ventilation. (See illustration.)
,
Type of Installation (Free-Standing/Slide-in) (Figure 3)
Will range be free-standing? (Range setting on floor.) If so, go to #7.
Will range be slide-in? (Range top rests on countertop.) If so, go to #4.
These appliances have been designed in accordance with the requirements
of various safety agencies and comply with the maximum allowable wood cabinet temperatures of 194°E If these appliances are installed with
cabinets that have a lower working temperature than 194°1, discoloration, delamination or melting may occur.
NOTE:Slide-in cutout does not allow for use of backsplash or side panels.
If either are desired, use the free-standing cutout and instruction.
(Figure 1)
[r lrl !r 1-qin--
k:,.-I o.....°.c..,.,.
I(lS.24cm)l
2S'* MIN.
(63.50 cm)
,,,____, g ]
(Figure2)
FREE
STANDING
(Figure 3)
NOT RECOMMENDED
t
(See #8)
|_.
SLIOE-IN
.
Measure for Slide-In Cutout (Figure 4)
Most standard counters are 25" (63.50 cm) deep, 36" (91.44 cm) high, and extend 1" (2.54 cm) over the cabinet front.
Measure the countertop and overhange.
0
(Figure 4)
OVERHANG
OIMENSIOll
5. Slide-In Cutout (Figure 5)
Use the overhang measurement to figure the "A"dimension:
Overhang 1t2" (1.27 cm) to 1" (2,54 cm) .... "A" =22-5t8" (57.47 crn)
Overhang 1" (2.54 cm) to 1-3/4" (4.45 cm) .... "A" = 23" (5-5.42 cm)
Carefully mark the countertop and recheck you dimensions.
Before you cut, check the rear countertop dimensions. (See #6.) NOTE: The minimum clearance between the cutoutand cabinet doors and
drawer edge is 7/8".
6. Slide-In Cutout (Figure 6)
Check your marked up dimensions carefully. The rear dimensions shown in the illustration must be maintained.
NOTE: Where this isnotdone, itwill be necessary to relieve a portionof the
underside of the countertop and/or support members to clear the range rear panel.
Cutting tolerance is = 1/6 (16 cm)
Carefully make the cutout
7. Free-Standing Cutout (Figure 7)
30-1/8" (76.52 cm) minimum clearance is required.
Carefully mark the countertop, recheck your dimensions and make the
cutout.
NOTE: Range side panels may be desirable if the cutout is too large or
cabinets are on one side of the range only.
Proceed to step 8.
(Figure 5)
cm)
(Figure 6)
8. Over-Range Cabinets (Figure 8)
To eliminate the hazard of reaching over a heated surface unit, cabinet storage space above the range should be avoided. If cabinet storage is to
be provided, the riskcan be reduced by installingarange hoed that projects horizontally a minimum of 5 inches beyond the bottom of the cabinets.
However, if over-range cabinets are necessary, observe the following: B = 30" (76.2 cm) minimum clearance between the top of the cooking
platform and the bottom of an unprotected wood or metal cabinet.
B = 24" (60.96 cm) minimum when bottom of wood or metal cabinet is
protected by not less than 1/4" (0.635 cm) FLAME RETARDANT
millboard covered with not less than No. 28MSG sheet steel, 0.015" (0.038 cm) stainless steel, 0.024" (0.061 cm) aluminum or copper.
NOTE: If you are NOT installing a downdraft unit, skip to step 13.
9. Measure For Floor Vent
If unit will be vented through the wall, go to #11.
If floor will be concrete slab, see enclosed ducting instructions.
For let and right hand venting through cabinet toe space, see special
instructions on pages 7 & 8. NOTE: Optimum center line vent location is11" to 17" from edge of cabinet.
Vents located less than this distance wUlrequirethe unit tobe raised over blower for installation.
(Figure 7)
o oo
(Figure 8)
10, Floor Vent Cutout (Figure 10)
Check the direction of the floorjoists (see illustration.)
Locate 6" square cutout anywhere within shaded area.
The cutout must miss the floor joist!!
Recheck your dimensions and make the cutout.
Skip to Step #12.
(Figure 10)
Loading...
+ 5 hidden pages