Jenbacher DIANE.XT User Manual

1 of 87
CHECK WITH LOCAL UTILITIES
FOR RELAY AND
SYNCHRONIZER APPROVALS
Jenbacher DIA.NE XT Control
Description of Document Page Number
DIA.NE XT (General Description) --------------------- 3 Table of Contents ------------------------ 4
Mains Monitoring Relay (SEG – MRN3) ------------- 17
Table of Contents ----------------------- 18
Synchronizing Module (MMU) ------------------------- 57
DIA.NE WIN (General Description) ------------------ 77
Table of Contents ----------------------- 78
TI-2300-0006 Internet Security Note ------------------ 89
Up-Dated October 2010
2 of 87
Blank Page for Notes
3 of 87
4 of 87
5 of 87
6 of 87
7 of 87
8 of 87
9 of 87
10 of 87
11 of 87
12 of 87
13 of 87
14 of 87
15 of 87
16 of 87
Blank Page for Notes
17 of 87
MRN3
Mains decoupling relay
-
Contents
18 of 87
1 Introduction and application
2 Features and characteristics
3 Design
3.1 Connections
3.1.1 Analog input circuits
3.1.2 Blocking input
3.1.3 Reset input
3.1.4 Output relays
3.1.5 Fault recorder
3.2 Parameter settings
3.3 LEDs
3.4 Front plate
4 Working principle
4.1 Analog circuits
4.2 Digital circuits
4.3 Voltage supervision
4.3.1 Selection of star or delta connection
4.4 Principle of frequency supervision
4.5 Measuring of frequency gradient (MRN3-2)
4.6 Vector surge supervision (MRN3-1)
4.6.1 Measuring principle of vector surge supervision
4.7 Voltage threshold value for frequency measuring
4.8 Blocking function
5 Operation and setting
5.1 Display
5.2 Setting procedure
5.3 Systemparameter
5.3.1 Display of residual voltage U quantity (U
prim/Usec
)
as primary
E
5.3.2 /Y – Switch over
5.3.3 Setting of nominal frequency
5.3.4 Display of the activation storage (FLSH/NOFL)
5.3.5 Parameterswitch/external trigger for the fault recorder
5.4 Protection parameters
5.4.1 Parameter setting of over- and under­ voltage supervision
5.4.2 Number of measuring repetitions (T) for frequency functions
5.4.3 Threshold of frequency supervision
5.4.4 Tripping delays for the frequency elements
5.4.5 Parameter setting of vector surge supervision (MRN3-1)
5.4.6 Parameter setting of frequency gradient (MRN3-2)
5.4.7 Voltage threshold value for frequency and vector surge measuring (df/dt at MRN3-2)
5.4.8 Adjustment of the slave address
5.4.9 Setting of Baud-rate (applies for Modbus Protocol only)
5.4.10 Setting of parity (applies for Modbus Protocol only)
5.5 Adjustment of the fault recorder
5.5.1 Number of the fault recordings
5.5.2 Adjustment of trigger occurences
5.5.3 Pre-trigger time (T
)
pre
5.6 Adjustment of the clock
5.7 Additional functions
5.7.1 Setting procedure for blocking the protection functions
5.8 Indication of measuring values
5.8.1 Measuring indication
5.8.2 Min./Max.- values
5.8.3 Unit of the measuring values displayed
5.8.4 Indication of fault data
5.9 Fault memory
5.9.1 Reset
5.9.2 Erasure of fault storage
2 TD_MRN3_08.03_GB
19 of 87
6 Relay testing and commissioning
6.1 Power-On
6.2 Testing the output relays
6.3 Checking the set values
6.4 Secondary injection test
6.4.1 Test equipment
6.5 Example of test circuit
6.5.1 Checking the input circuits and measuring functions
6.5.2 Checking the operating and resetting values of the over/undervoltage functions
6.5.3 Checking the relay operating time of the over/undervoltage functions
6.5.4 Checking the operating and resetting values of the over/underfrequency functions
6.5.5 Checking the relay operating time of the over/underfrequency functions
6.5.6 Checking the vector surge function
6.5.7 Checking the external blocking and reset functions
6.6 Primary injection test
6.7 Maintenance
7 Technical data
7.1 Measuring input circuits
7.2 Common data
7.3 Setting ranges and steps
7.3.1 Interface parameter
7.3.2 Parameters for the fault recorder
7.4 Output relays
8 Order form
TD_MRN3_08.03_GB 3
1 Introduction and application
20 of 87
The MRN3 is a universal mains decoupling device and covers the protection requirements from VDEW and most other utilities for the mains parallel operation of power stations.
Over/ and undervoltage protection,
over/ and underfrequency protection,
extremely fast decoupling of generator in case of
mains failure (MRN3-1) or
rate of change of frequency df/dt (MRN3-2)
Because of combination of three protectional functions in one device the MRN3 is a very compact mains de- coupling device. Compared to the standardly used single devices it has a very good price/performance ratio.
For applications where the single protection functions are required SEG can offer the single MR-relays as fol­lows:
MRU3-1 four step independent over-/ and under-
voltage protection (also used for gene­ rator earth fault protection).
MRU3-2 two step independent over-/ and under-
voltage protection with evaluation of the symmetrical voltage components.
MRF3 four step independent over/ and under-
frequency protection and two step frequency gradient supervision df/dt.
MRG2 generator mains monitor / vector surge
detection.
Important: For additional common data of all MR-relays please refer to technical description "MR - Digital Multifunc­tional Relays".
2 Features and characteristics
Microprocessor technology with watchdog,
effective analog low pass filter for suppressing har-
monics when measuring frequency and vector surge,
digital filtering of the measured values by using dis-
crete Fourier analysis to suppress higher harmonics and d.c. components induced by faults or system operations,
integrated functions for voltage, frequency and vec-
tor surge in one device as well as single voltage, frequency and vector surge devices,
two parameter sets,
voltage supervision each with two step under-/and
overvoltage detection,
frequency supervision with three step under-/or
overfrequency (user setting),
completely independent time settings for voltage and
frequency supervision,
adjustable voltage threshold value for blocking fre-
quency and vector surge measuring,
display of all measuring values and setting parame-
ters for normal operation as well as tripping via a alphanumerical display and LEDs,
display of measuring values as primary quantities
Storage of trip values and switching-off time (t
5 fault occurences (fail-safe of voltage),
recording of up to eight fault occurences with time
stamp
for blocking the individual functions by the external
blocking input, parameters can be set according to requirement,
user configurable vector surge measurement 1-of-3
or 3-of-3,
reliable vector surge measuring by exact calculation
algorithm,
suppression of indication after an activation
(LED flash),
free assignment for output relays,
display of date and time,
in complience with VDE 0435, part 303 and IEC
255,
serial data exchange via RS485 interface possible;
alternatively with SEG RS485 Pro-Open Data Proto­col or Modbus Protocol.
CBFP
) of
4 TD_MRN3_08.03_GB
3 Design
21 of 87
3.1 Connections
Figure 3.1: Connection diagram MRN3-1 and MRN3-2
3.1.1 Analog input circuits
The analog input voltages are galvanically decoupled by the input transformers of the device, then filtered and finally fed to the analog digital converter. The measuring circuits can be applied in star or delta con­nection (refer to chapter 4.3.1).
3.1.2 Blocking input
The blocking function can be set according to re­quirement. By applying the auxiliary voltage to D8/E8, the previously set relay functions are blocked (refer to 4.8 and 5.7.1).
3.1.3 Reset input
Please refer to chapter 5.9.1.
3.1.4 Output relays
The MRN3 is equipped with 5 output relays. Apart from the relay for self-supervision, all protective func­tions can be optionally assigned:
Relay 1: C1, D1, E1 and C2, D2, E2
Relay 2: C3, D3, E3 and C4, D4, E4
Relay 3: C5, D5, E5
Relay 4: C6, D6, E6
Relay 5: Signal self-supervision (internal failure of the
unit ) C7, D7, E7
All trip and alarm relays are working current relays, the relay for self supervision is an idle current relay.
TD_MRN3_08.03_GB 5
3.1.5 Fault recorder
22 of 87
The MRN3 has a fault value recorder which records the measured analog values as instantaneous values. The instantaneous values
U or U
; UL2; UL3 for star connection
L1
; U23; U21 for delta connection
12
are scanned at a raster of 1.25 ms (at 50 Hz) and
1.041 ms (at 60 Hz) and saved in a cyclic buffer. It is possible to store 1 - 8 fault occurences with a total re­cording time of 16 s (with 50 Hz) and 13.33 s (with 60 Hz) per channel.
Storage division
Independent of the recording time, the entire storage capacity can be divided into several cases of distur­bance with a shorter recording time each. In addition, the deletion behaviour of the fault recorder can be in­fluenced.
No writing over
If 2, 4 or 8 recordings are chosen, the complete memory is divided into the relevant number of partial segments. If this max. number of fault event has been exceeded, the fault recorder block any further re­cordings in order to prevent that the stored data are written over. After the data have been read and de­leted, the recorder to ready again for further action.
Writing over
If 1, 3 or 7 recordings are chosen, the relevant num­ber of partial segments is reserved in the complete memory. If the memory is full, a new recording will always write over the oldest one.
The memory part of the fault recorder is designed as circulating storage. In this example 7 fault records can be stored (written over).
Figure 3.2: Division of the memory into 8 segments, for example
Memory space 6 to 4 is occupied. Memory space 5 is currently being written in
Since memory spaces 6, 7 and 8 are occupied, this example shows that the memory has been assigned more than eight recordings. This means that No. 6 is the oldest fault recording and No. 4 the most recent one.
trigger occurence
recording duration
Tpre
[s]
Figure 3.3: Basic set-up of the fault recorder
Each memory segment has a specified storage time which permits setting of a time prior to the trigger event.
Via the interface RS485 the data can be read and processed by means of a PC (HTL/PL-Soft4). The data is graphically edited and displayed. Binary tracks are recorded as well, e.g. activation and trip.
6 TD_MRN3_08.03_GB
3.2 Parameter settings
23 of 87
System parameters
Parameter settings MRN3-1 MRN3-2
U /Y
X X
prim/Usek
X X fN X X P2/FR X X LED-Flash X X
Table 3.1: System parameters
Protection parameters
Setting
MRN3-1 MRN3-2
parameter
U< X X tU< X X U<< X X t
X X
U<<
U> X X tU> X X U>> X X t
X X
U>>
T X X f1 X X tf1 X X f2 X X tf2 X X f3 X X tf3 X X df X dt X 1/3 X ∆Θ
X UB< X X RS485/Slave X X Baud-Rate* X X Parity-Check* X X
Blocking functions
Parameter settings MRN3-1 MRN3-2
U< X X U<< X X U> X X U>> X X f1 X X f2 X X f3 X X
θ
df/dt X
Table 3.3: Blocking functions
Parameters for the fault recorder
Parameter setting MRN3-1 MRN3-2
Number of fault events Trigger events X X Pre-Triggerzeit T
Table 3.4: Parameters for the fault recorder
Additional functions
Parameter settings MRN3-1 MRN3-2
Ralay assignment X X Fault recorder X X
Table 3.5: Additional functions
Date and time
Parameter settings MRN3-1 MRN3-2
Year Y = 99 Month M = 03
Table 3.2: Protection parameters
*only Modbus
Day D = 16 hour h = 07 minute m = 29 second s = 56
X
X X
X X
pre
X X X X X X
X X X X X X
Table 3.6: Date and time
The window for parameter setting is located behind the measured value display. The parameter window can be accessed via the <SELECT/RESET> key.
TD_MRN3_08.03_GB 7
3.3 LEDs
24 of 87
All LEDs (except LED RS, min. and max.) are two­coloured. The LEDs on the left side, next to the alpha­numerical display light up green during measuring and red after tripping.
The LEDs below the push button <SELECT/RESET> are lit green during setting and inquiry procedure of the setting values which are printed on the left side next to the LEDs. The LEDs will light up red after parameteriz­ing of the setting values next to their right side.
The LED marked with letters RS lights up during setting of the slave address of the device for serial data communication.
The LED marked with the letters FR is alight while the fault recorder is being adjusted.
3.4 Front plate
Figure 3.4: Front plate MRN3-1
Figure 3.5: Front plate MRN3-2
8 TD_MRN3_08.03_GB
4 Working principle
25 of 87
4.1 Analog circuits
The input voltages are galvanically insulated by the input transformers. The noise signals caused by induc­tive and capacitive coupling are supressed by an ana­log R-C filter circuit.
The analog voltage signals are fed to the A/D­converter of the microprocessor and transformed to digital signals through Sample- and Hold- circuits. The analog signals are sampled with a sampling fre­quency of 16 x f ms for every measuring quantity, at 50 Hz.
4.2 Digital circuits
The essential part of the MRN3 relay is a powerful mi- crocontroller. All of the operations, from the analog digital conversion to the relay trip decision, are carried out by the microcontroller digitally. The relay program is located in an EPROM (Electrically-Programmable­Read-Only-Memory). With this program the CPU of the microcontroller calculates the three phase voltage in order to detect a possible fault situation in the pro­tected object.
For the calculation of the voltage value an efficient digital filter based on the Fourier Transformation (DFFT
- Discrete Fast Fourier Transformation) is applied to suppress high frequency harmonics and d.c. compo­nents caused by fault-induced transients or other system disturbances. The microprocessor continuously com­pares the measured values with the preset thresholds stored in the parameter memory (EEPROM). If a fault occures an alarm is given and after the set tripping de­lay has elapsed, the corresponding trip relay is acti­vated.
The relay setting values for all parameters are stored in a parameter memory (EEPROM - Electrically Erasable Programmable Read Only Memory), so that the actual relay settings cannot be lost, even if the power supply is interrupted. The microprocessor is supervised by a built-in "watch­dog" timer. In case of a failure the watchdog timer re­sets the microprocessor and gives an alarm signal via the output relay "self supervision".
, namely, a sampling rate of 1.25
N
4.3 Voltage supervision
The voltage element of MRN3 has the application in protection of generators, consumers and other electri­cal equipment against over-/and undervoltage. The relay is equipped with a two step independent three-phase overvoltage (U>, U>>) and undervoltage (U<, U<<) function with completely separate time and voltage settings. In delta connection the phase-to-phase voltages and in star connection the phase-to-neutral voltages are con­tinuously compared with the preset thresholds.
For the overvoltage supervision the highest, for the un­dervoltage supervision of the lowest voltage of the three phases are decisive for energizing.
TD_MRN3_08.03_GB 9
4.3.1 Selection of star or delta
26 of 87
connection
All connections of the input voltage transformers are led to screw terminals. The nominal voltage of the de­vice is equal to the nominal voltage of the input trans­formers. Dependent on the application the input trans­formers can be connected in either delta or star. The connection for the phase-to-phase voltage is the delta connection. In star connection the measuring voltage is
reduced by 1/
3
. During parameter setting the con-
nection configuration either Y or has to be adjusted.
Sec. winding of mains V.T.
a
b
c
A3
A4
A5
A6
A7
U12
U23
4.4 Principle of frequency supervision
The frequency element of MRN3 protects electrical generators, consumers or electrical operating equip­ment in general against over- or underfrequency. The relay has independent three frequency elements f
- f3 with a free choice of parameters, with separate
1
adjustable pickup values and delay times.
The measuring principle of the frequency supervision is based in general on the time measurement of com­plete cycles, whereby a new measurement is started at each voltage zero passage. The influence of harmon­ics on the measuring result is thus minimized.
u(t)
T
t
A8
Figure 4.1: Input v.t.s in delta connection (∆)
Sec. winding of mains V.T.
a
b
c
Figure 4.2: Input v.t.s in star connection (Y)
A3
A4
A5
A6
A7
A8
U31
U1
U2
U3
T
Figure 4.3: Determination of cycle duration by means of zero passages.
In order to avoid false tripping during occurence of in­terference voltages and phase shifts the relay works with an adjustable measuring repetition. (refer to chap­ter 5.4.2)
Frequency tripping is sometimes not desired by low measured voltages which for instance occur during al­ternator acceleration. All frequency supervision func­tions can be blocked with the aid of an adjustable voltage threshold U value is below this value.
4.5 Measuring of frequency gradient (MRN3-2)
Electrical generators running in parallel with the mains, e.g. industrial internal power supply plants, should be separated from the mains when failure in the intrasys­tem occurs for the following reasons:
It must be prevented that the electrical generators
are damaged when mains voltage recovering asynchrone, e.g. after a short interruption.
The industrial internal power supply must be main-
tained.
in case the measured voltages
B
10 TD_MRN3_08.03_GB
A reliable criterion of detecting mains failure is the
27 of 87
measurement of the rate of change of frequency df/dt. Precondition for this is a load flow via the mains cou­pling point. At mains failure the load flow changing then spontaneously leads to an increasing or decreas­ing frequency. At active power deficit of the internal power station a linear drop of the frequency occurs and a linear increase occurs at power excess. Typical frequency gradients during application of "mains de­coupling" are in the range of 0.5 Hz/s up to over 2 Hz/s. The MRN3 detects the instantaneous frequency gradient df/dt of each mains voltage period in an in­terval of one half period each. Through multiple evaluation of the frequency gradient in sequence the continuity of the directional change (sign of the fre­quency gradient) is determined. Because of this spe­cial measuring procedure a high safety in tripping and thus a high stabilty against transient processes, e.g. switching procedure are reached. The total switching off time at mains failure is between 60 ms and 80 ms depending on the setting.
4.6 Vector surge supervision (MRN3-1)
The vector surge supervision protects synchronous gen­erators in mains parallel operation due to very fast de­coupling in case of mains failure. Very dangerous are mains auto reclosings for synchronous generators. The mains voltage returning after 300 ms can hit the generator in asynchronous position. A very fast de­coupling is also necessary in case of long time mains failures. Generally there are two different applications:
a) Only mains parallel operation no single opera- tion: In this application the vector surge supervi­ sion protects the generator by tripping the gen­era- tor circuit breaker in case of mains failure.
b) Mains parallel operation and single operation: For this application the vector surge supervision trips the mains circuit breaker. Here it is insured that the gen.-set is not blocked when it is required as the emergency set.
A very fast decoupling in case of mains failures for synchronous generators is known as very difficult. Volt­age supervision units cannot be used because the syn­chronous alternator as well as the consumer imped­ance support the decreasing voltage.
For this the mains voltage drops only after some 100 ms below the pickup threshold of voltage supervi­sion relays and therefore a safe detection of mains auto reclosings is not possible with this kind of relay.
Frequency relays are partial unsuitable because only a highly loaded generator decreases its speed within 100 ms. Current relays detect a fault only when short­circuit type currents exist, but cannot avoid their devel­opment. Power relays are able to pickup within 200 ms, but they cannot prevent power to rise to short-circuit values too. Since power changes are also caused by sudden loaded alternators, the use of power relays can be problematic.
Whereas the MRN3-1 detects mains failures within 60 ms without the restrictions described above be­cause they are specially designed for applications where very fast decoupling from the mains is required.
Adding the operating time of a circuit breaker or con­tactor, the total disconnection time remains below 150 ms. Basic requirement for tripping of the genera­tor/mains monitor is a change in load of more than 15 - 20% of the rated load. Slow changes of the sys­tem frequency, for instance at regulating processes (adjustment of speed regulator) do not cause the relay to trip.
Trippings can also be caused by short-circuits within the grid, because a voltage vector surge higher than the preset value can occur. The magnitude of the volt­age vector surge depends on the distance between the short-circuit and the generator. This function is also of advantage to the Power Utility Company because the mains short-circuit capacity and consequently the energy feeding the short-circuit is limited.
To prevent a possible false tripping the vector surge measuring can be blocked at a set low input voltage (refer to 5.4.7). The undervoltage lockout acts faster then the vector surge measurement.
Vector surge tripping is blocked by a phase loss so that a VT fault (e.g. faulty VTs fuse) does not cause false tripping. When switching on the aux. voltage or measuring voltage , the vector surge supervision is blocked for 5 s (refer to chapter 4.8).
TD_MRN3_08.03_GB 11
Loading...
+ 60 hidden pages